F100 (Globe) F1100 (Angle) Dimensions

ES-ACV-F100-F1100
Classic Series Basic Valves
LEAD FREE*
F100 / F1100
F1100 (Angle)
F100 (Globe)
Full Port Ductile Iron Single
Chamber Basic Valve
L
M
D
The Watts ACV Models F100 and F1100 are full port, single chamber basic valves that incorporate a one-piece disc and diaphragm
assembly. This assembly is the only moving part within the valve
allowing it to open, close, or modulate as commanded by the pilot
control system.
K
H
Watts ACV Main Valves are Lead Free. The Watts ACV piloting system contains Lead Free* components, ensuring all of our configurations are Lead Free compliant.
Model F100: Globe Pattern Single Chamber Basic Valve
Model F1100: Angle Pattern Single Chamber Basic Valve
A
E
B
C
F
G
I
J
Dimensions
Valve Globe Thread Globe 150#
Size
A
B
in.
in.
mm
in.
mm
184
11/4
71/4
184
216
11/2
71/4
81/2
2
238
238
93/8
93/8
11
279
11
279
21/2
3
12
305
101/2 267
4
15
381
6
20
508
8
253/8 645
10
293/4 756
12
34
864
14
39
991
16
413/8 1051
Globe 300#
Cover To Angle Thread
Center
C
D
E
in.
mm
in. mm in. mm
31/2 89 31/4 83
9
229 31/2 89 31/4 83
10
254 415/16 125 4
102
7 178 51/2 140
115/8 295
7 178 51/4 133
131/4 337
155/8 397 85/8 219
21
533 113/4 298
263/8 670 153/4 400
311/8 791 183/4 476
351/2 902 205/8 524
401/2 1029 221/4 565
431/2 1105 261/4 667
Angle 150#
Angle 300# Angle Thread
F
G
Angle 150#
H
in.
mm
in.
mm
4
4
51/2
53/4
63/4
81/2
11
147/8
17
102
102
140
146
171
216
279
378
432
41/4
513/16
61/8
71/8
87/8
111/2
155/8
173/4
108
148
156
181
225
292
397
451
in.
17/8
17/8
4
4
51/4
I
mm
48
48
102
102
133
in.
mm
4
4
4
53/4
63/4
81/2
11
147/8
17
102
102
102
146
171
216
279
378
432
Angle 300# Port Size Port Size Port Size Shipping
NPT
NPT
NPT
Weights*
J
K
L
M
in.
mm
in.
in.
in.
lbs. kgs.
15
7
1/4
1/2
1/8
15
7
1/4
1/2
1/8
108
35
16
41/4
1/2
1/2
1/4
65
30
45/16 110
1/2
1/2
3/8
156
95
43
61/8
1/2
1/2
3/8
181
190
86
71/8
1/2
1/2
3/8
225
320 145
87/8
1/2
1/2
1/2
1
650 295
111/2 292
1/2
1/2
1
1
1
940 426
155/8 397
1
1
1
1500 680
173/4 451
1
1
1
1675 760
1
1
1
3100 1406
Standard Materials
Operating Pressure
Body & Cover: Ductile Iron ASTM A536
Threaded = 400psi (27.6 bar)
150 Flanged = 250psi (17.2 bar)
Coating:
NSF Listed Fusion Bonded Epoxy Lined
and Coated
Trim:
316 Stainless Steel
Operating Temperature
Elastomers:
Buna-N (standard)
EPDM (optional)
Viton (optional)
Buna-N: 160°F (71°C) Maximum
Stem, Nut &
Spring:
Stainless Steel
NOTICE
The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer.
You are required to thoroughly read all installation instructions and product safety
information before beginning the installation of this product.
300 Flanged = 400psi (27.6 bar)
EPDM: 300°F (140°C) Maximum
Viton®: 250°F (121°C) Maximum
Epoxy Coating**: 140°F (60°F) Maximum
** Valves can be provided without internal epoxy coating consult factory
*The wetted surface of this product contacted by consumable
water contains less than 0.25% of lead by weight.
Viton® is a registered trademark of DuPont Dow Elastomers.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
F100 / F1100 — Full Port Ductile Iron Single Chamber Basic Valve
2
21/2
3
4
6
8
10
12
14
16
93
125
208
300
460
800
1800
3100
4900
7000
8500
11000
Maximum Intermittent
Flow Rate Gpm (Water)
115
158
260
370
570
1000
2300
3900
6000
8600
10500
14000
Minimum
Flow Rate Gpm (Water)
3
5
6
9
15
16
17
25
55
70
190
400
Factor GPM (Globe)
29
34
55
75
125
220
460
775
1200
1730
2100
2800
Factor GPM (Angle)
39
53
66
99
170
280
650
1100
1600
2500
3060
4210
10
12
14
12
14
16
8
10
16
6
8
Globe
6
11/4
11/2
2
Angle
4
•
The Cv factors stated are based upon a fully open valve.
Many factors should be considered in sizing control valves
including inlet pressure, outlet pressure and flow rates.
For sizing questions including cavitation analysis consult Watts
with system details.
3
•
•
Maximum continuous flow based on velocity of 20 ft. per second.
Maximum intermittent flow based on velocity of 25 ft. per seco
Minimum flow rates based on a 20-40 psi pressure drop.
The Cv Factor of a value is the flow rate in US GPM at 60°F that will
cause a 1psi drop in pressure.
Cv factor can be used in the following equations to determine Flow
(Q) and Pressure Drop (∆P):
Q (Flow) = Cv√∆P
∆P (Pressure Drop) = (Q/Cv)2
4
11/2
21/2
•
11/4
Maximum Continuous
Flow Rate Gpm (Water)
3
•
•
•
•
Valve Size - Inches
11/4
11/2
21/2 2
CV
Suggested
Flow Data - ACV F100 (Globe) / F1100 (Angle)
100
80
60
40
Pressure Drop (psi)
30
20
10
8
6
4
3
2
2
4
6
8 10
20
40
60
80 100
200
500
1000
2000
5000
10000
20000
100000
Flow Rate - Gallons per minute (Water)
Valve Cover Chamber Capacity
Valve Size - Inches
11/4
11/2
2
21/2
3
4
6
fl.oz.
U.S. Gal
4
4
4
10
10
22
70
8
10
12
14
16
1 1/4
2 1/2
4
6 1/2
9 1/2
Valve Travel
Valve Size - Inches
11/4
11/2
2
21/2
3
4
6
8
10
12
14
16
Travel - Inches
3/8
3/8
1/2
5/8
3/4
1
11/2
2
21/2
3
31/2
4
ES-ACV-F100-F1100
1442
© 2014 Watts
LEAD FREE*
F100
Full Port Ductile Iron Single Chamber Basic Valve
1
1
2
2
3
3
4
4
5
5
Item
Description
Material
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Pipe Plug
Cover
Cover Bearing
Stud with Cover Nut and Washer
Body
Spring
Stem Nut
Diaphragm Washer
Diaphragm*
Spacer
Quad Seal Retainer
Quad Seal*
O-Ring*
Quad Seal Plate
Shaft / Stem
Seat Ring
Seat Gasket*
Lead Free Brass
ASTM A536 65-45-12 Epoxy Coated Ductile Iron
ASTM A276 304 Stainless Steel
ASTM A570 Gr.33 Zinc Plated Steel
ASTM A536 65-45-12 Epoxy Coated Ductile Iron
ASTM A276 302 Stainless Steel
ASTM A276 304 Stainless Steel
ASTM A536 65-45-12 Epoxy Coated Ductile Iron
Buna-N (Nitrile)
ASTM A276 304 Stainless Steel
ASTM A536 65-45-12 Epoxy Coated Ductile Iron
Buna-N (Nitrile)
Buna-N (Nitrile)
ASTM A743 CF8M (316) Stainless Steel
ASTM A276 304 Stainless Steel
ASTM A743 CF8M (316) Stainless Steel
Buna-N (Nitrile)
6
6
7
7
8
8
9
9
8
8
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
* Contained in Main Valve Repair Kit
A Watts Water Technologies Company
ES-ACV-F100-F1100 1442
USA: Tel: (713) 943-0688 • Fax: (713) 944-9445 • Watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • Watts.ca
Latin America: Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • Watts.com
© 2014 Watts