vertex vt10 series pid operation manual microprocessor

1
VERTEX VT10 SERIES PID OPERATION MANUAL
MICROPROCESSOR BASED PID CONTROLLER
1. INTRODUCTION
This manual contains information for the installation and operation and tuning of our Vertex VT10 series auto-tuning
microprocessor based controllers. These controllers carry a one-year factory warranty.
The VERTEX microprocessor controllers are “proportional + integral + derivative” (PID) controllers that come in a variety of
standard DIN sizes. The input is configurable and allows selection or configuration of inputs between T/C, RTD, 4~20 and
other linear signals and outputs between relay, SSR, heat / cool, 4~20 mA or other linear signals. They have dual displays
that show the input (measured temperature) in the top digital display and the required set point in the lower. The controller
boasts a comprehensive range of other features that include auto/manual function, ramp feature, and comes standard with
two configurable alarms, (The VT4810 48 x 48 size only has one alarm). The controllers can be switched to manual and can
work as “time based ratio out-put controllers” in the event of thermocouple or input failures taking place.
2.
2.1
INSTALLATION
PANEL MOUNTING
Cut-out sizes are shown below. Panel width may be up to 10 mm thick. Do not tighten the mounting screws too tightly since
this can bow the controller housing.
Table 2-1 Panel cut-out
Model
Height
Width
VT4810
45mm
45mm
VT7210
67mm
67mm
VT9610
91mm
91mm
VT4910
91mm
45mm
VT9410
45mm
91mm
2.2
CONNECTION AND WIRING
1. Power supply (Mains Supply)
These controllers require 85~265 Vac 50/60 Hz. mains power supply. The mains should be fused by a fast blow
fuse of no more than 2 amps rating.
As with all electronic switch mode power supplies they are sensitive to overvoltage. If you work in an environment where surges are expected, then be sure to protect these devices with overvoltage relays. The low cost of the “over voltage device” will save you large amounts of down-time (money) by
preventing problems.
2. Sensor Input
Do not run sensor input cables adjacent to power carrying conductors. The correct type of thermocouple extension
lead wire or compensating cable must be used for thermocouples. Ensure that the polarity of the thermocouple /
4~20 input is correct. When using 4~20 mA inputs the loop has to be powered externally by a 24 Vdc switch mode
power supply. PT100 inputs require three copper core wires and can be run for up to 50 meters. You can simply
select any thermocouple types in the parameter setups. To select PT100 or analog (4~20) inputs requires simple
hardware changes such as de-soldering a link for PT100 etc. It is easier to simply order the controller with the
correct input type.
3. Control Output
Different types of outputs are available in the controller. Be sure that the correct output type is selected for your
application. Also ensure that the correct cycle time is used with the appropriate out-put type.
Available outputs are:

Relay 5A / 240 Vac maximum, resistive load

Pulsed voltage to drive SSR (24 Vdc)

4~20 mA or 0~20 mA, Maximum load 500 ohms

Various other linear outputs ( 1~5Vdc, 0~5Vdc, 0~10Vdc )
Changes of out-put types are relatively simple but must be done by the supplier.
2
4. Alarm Output
The alarm output is a relay contact. Maximum contact rating is 10 Amps resistive load. The VT4810 has only one
alarm, but all other models have two alarms.
Although the relay out-put is rated at 5 amps it is always necessary to switch an interposing
relay, SSR or Contactor that will switch the load. This avoids damage to the controller in the
event of a fault short developing on the power out-put circuit.
Always use a separate fused supply for the “power load circuit” and do not take this from the
live and neutral terminals supplying power to the controller.
STANDBY
On some versions of software fitted to the VT4910 controller a standby function is available.
Please check the software version of your controller to see whether this function is fitted.
When this function is part of the software, in order to operate fully, a link must be made
between terminals 6 & 7. This disables STANDBY mode.
Opening this link puts the controller into STANDBY mode. This disables the heat output
(including the setting of manual output power) and, on version 2.A, disables the alarms. This
feature is to enable the remote disabling of the controller by a switch or PLC.
TERMINAL LAYOUT DIAGRAMS
3.
FRONT PANEL DESCRIPTION
PV: Process Variable
a) Displays the actual measurement of the input sensor.
b) When in the configuration levels it displays the parameter name being accessed.
c) Displays Error messages.
SV: Setpoint Value
a) Displays the required set-point setting.
b) When in the configuration levels it displays the parameter value.
A1: Alarm 1 LED
a) LED lights when Alarm 1 is energised.
b) LED flashes if timer function is selected and activated in the alarm parameters.
A2: Alarm 2 LED
LED lights when Alarm 2 is energised.
3
C1: Control 1 LED
LED lights when Control Output 1 is on.
MA: Manual mode LED
LED flashes when manual control of out-put is selected.
AT: Autotuning LED
LED flashes while controller is auto tuning. (48 x 48 units have a dot on the left of the PV display that flashes).
C: Degree C LED
LED lights when programmed for degree C.
F: Degree F LED
LED lights when programmed for degree.
Scroll Key
When in one of the parameter levels, you can move from one parameter to the next by pressing the Scroll Key
once.
Also to activate an autotuning session, press and hold this key for 5 seconds.
Up Key
Increases the setpoint value and changes the parameter data when programming.
Down Key
Decreases the setpoint value and changes the parameter data when programming.
Return Key
When in one of the programming levels, press this key to return to the normal operating status.
Pressing and holding this key for 5 seconds puts the controller into manual operation.
Pressing the Return Key during normal operation, allows the user to view the controller output in percentage
(0~100%).
4. PARAMETER DEFINITIONS
There are 4 levels of parameters as follows
4.1
4.2
4.3
4.4
OPERATING LEVEL
CONTROL PARAMETER LEVEL
CONFIGURATION LEVEL
CALIBRATION LEVEL (not user adjustable, consult supplier)
ENTERING PROGRAMMING LEVELS
Press and hold these keys together for 5 seconds to enter the next level of parameters.
4.1 OPERATION LEVEL (LEVEL 1)
1.
SP
Set-Point Variable
This parameter is the desired target for control. It can be adjusted up and down using the up/down keys when
the controller is in its normal state, within the range defined by the “Low Limit” value and “High Limit” value.
4
2.
rRñP
Ramp Rate
0.0~100.0 °C/min
The controller can be configured to act either as a fixed set-point controller or as a single ramp on power up controller.
This function enables the user to set a predetermined ramp rate to allow the process to gradually reach set-point
temperature thus producing a “soft start” function. This parameter is activated by selecting the appropriate parameter
lock level that will allow access to the rAnP function, ie: 1, 3, 5, 7 etc. The ramp function is also automatically engaged
when making set-point changes. This means that the controller will ramp the temperature from the current value to the
new set-point value in accordance with the ramp setting. The ramp rate is determined by “rRñP” parameter, which can
be set in the range 0.0 to 100.0
C/minute. The ramp function is disabled when the rRñP parameter is set to zero.
Note that if the LoLt is set above 0ºC the output will be governed by the failure mode selected in
EroP and will not ramp or control at all until the measured variable has exceeded the LoLt.
3.
4.
Output offset Value for Manual Reset
0~100 % of full scale
oPoF
This is in essence a “manual reset” function. It can be used to alter the PV reading by introducing a fixed offset. This can be used to correct the relationship between the PV reading and the SV reading.
Under normal circumstances this should be set to “0”.
AISP
Alarm 1 Setpoint Value
full scale
This sets the value at which alarm 1 will operate if “A1Fu” 0 or 5, 1 or 5, 2 or 6, 3 or 7, 12 or 14 or 13 or 15 is
selected for alarm function. If the time based alarm functions 8, 9, 10 or 11 are chosen, this parameter will be
not be shown. You will use the tiñE setting instead. Time based functions are only available on alarm 1.
5.
A2SP
Alarm 2 Setpoint Value
full scale
This sets the value at which alarm 2 will operate if “A1Fu” 0 or 5, 1 or 5, 2 or 6, 3 or 7 is selected for alarm
function.
6.
tiñE
Dwell Time
0~9999 min’s
This parameter sets the “time value” to be used in the “A1Fu” time based alarm function. (“A1Fu” set to 8, 9, 10
or 11).
This parameter is available only in the case that the “A1Fu” is set to timer function.
The range available is from 0 to 9999 minutes.
4.2 OPERATION LEVEL (LEVEL 2)
1.
2.
Proportional Band Setting
0.0 to 100.0% of controller’s span
Setting range from 0.0 to 100.0% of controller’s span as set by LoLt and HiLt
This value can be automatically calculated by activating the Autotune Function.
Set to zero for ON/OFF control action.
Pb
C Pb
Cooling Prop Band Setting
multiplication factor 0.0 ~ 10.0
This value is the proportional band setting for the “cooling out-put” if that option is available on the controller.
It is set as a multiplication factor of the main out-put Pb value.
The default value is 1.0 which means that the C Pb value will equal the main Pb setting
C Pb = Pb x factor
3.
ti
Integral Time (Reset)
0~3600 sec
Setting range from 0 to 3600 seconds.
This value can be automatically calculated by activating the auto tune function.
4.
td
Derivative (Rate)
0~3600 sec’s
0 to 3600 seconds setting range.
This value can be automatically calculated by activating the auto tune function.
5.
db
Dead Band Value
-10.0%~ 10.0%
This function sets the dead-band between the heating and cooling out-puts.
Setting range from -10.0% to 10.0% of Pb.
5
4.3 CONFIGURATION LEVEL (LEVEL 3)
1.
rEño
Remote/Local Mode Selection
Set to 0 for local mode or 1 for RS485 remote mode.
In remote mode, all parameters can not be changed using the front panel keypad.
If not using remote comms, this is a way of locking all parameter settings from the operating staff.
2.
P-L
Parameter Lock
Permits the user to lock (prevent changes) for different levels as shown in the table below.
The levels can be adjusted wherever there is a 
Other parameters can be locked using other means (see Item 5 below)
P-L
rAñP
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

PyoF
















AISP
tiñE
A2SP
2nd Level
3rd
Level
4th
Level
























































Parameters can be adjusted
Note: No adjustments should be made in 4th stage under any circumstances
3.
A IFu
Alarm 1 Function.
See Table 1
Alarm one’s mode of operation is selected according to table.
4.
A 2Fu
Alarm 2 Function.
See Table 1
Alarm two’s mode of operation is selected according to table.
5.
A IHy
Alarm 1 Hysteresis
0.0 to 25% of controllers span
Setting range 0.0 to 25% of controllers span as defined by HiLt and LoLt. Used to eliminate relay “chatter”.
6.
A 2Hy
Alarm 2 Hysteresis
0.0 to 25% of controllers span
Setting range 0.0 to 25% of controllers span as defined by HiLt and LoLt. Used to eliminate relay “chatter”.
7.
Act
Control Output Action
Set to 1 for heating (reverse) action. 0 for cooling (direct) action.
8.
unit
Process Value unit of measure
Set to 1 for degrees C, 0 for degrees F, or 2 for other linear process.
9.
dP
Decimal Point Selection
This parameter defines the position of the decimal point on the process value and Set-point.
6
Can be set to 1 for PT100 or linear inputs (4~20 mA).
10.
Ct
Proportional Cycle Time of Output 1
15 sec’s
The value can be set from 0 to 100 seconds.
Set to 1 second for SSR output.
Set to 0 seconds for 4~20 mA output.
Set to 15 seconds or longer for relay out-put to prolong relay life.
11.
12.
C Ct
Proportional Cycle Time of Output 2
15 sec’s
HySt
Hysteresis (Dead Band) for ON/OFF control
User can set a range from 0.0 to 25.5% of SPAN.
When used in the on/off mode (i.e. Pb set to 0) this parameter will set the dead-band around the set-point.
The temperature will rise to the set-point then will have to cool down through the dead-band before switching
on again.
13.
EroP
Failure mode out-put status
See table 2
This setting defines the failure status of the out-puts in the event of a failure such as thermocouple break etc.
14.
Addr
Address for RS485 Communication
15.
PyoF
Process Value Offset
-100.0
C ~ 100.0
C.
This parameter allows for manual compensation of any process off-set that may exist between the
measurement of the probe and the reading on the controller.
16.
tYPE
Input Type Selection
Type Input Sensor Type
Range
J
-50
C ~ 1000
C
0
K
-50
C ~ 1370
C
1
T
-270
C
~
400
C
2
E
-500
C ~ 750
C
3
B
0
C ~ 1800
C
4
R
0
C ~ 1750
C
5
S
0
C
~
1750
C
6
N
-50
C ~ 1300
C
7
PT 100 DIN
-200
C ~ 500
C
8
For T/C G1 on PCB must be soldered
For PT100 it must be open
PT 100 JIS
-200
C ~ 500
C
9
LINEAR
(4~20)
-1999
~
9999
10
The change to linear input must be done by the supplier
17.
LoLt
Low Limit Range
This parameter sets a low limit that will restrict the operator from setting the set-point below this limit.
18.
HiLt
High Limit Range
This parameter sets a high limit above which the operator cannot set the set-point.
In addition to this function, it will ensure that if the process variable exceeds this limit the controller out-put will
be forced off preventing any further rise.
The PV display will flash while the value is out-side these parameters.
4.4 CONFIGURATION LEVEL (LEVEL 4)
These settings are only for factory adjustment
1.
LoCA
Low Calibration Value
2.
HiCA
High Calibration Value
7
3.
tunE
Auto-tuning Selection
5. OPERATIONAL FEATURES
5.1 AUTO / MANUAL CONTROL MODES
1. The manual function can be locked by pressing the
2. The function is unlocked by pressing the
and
and
keys together for 5 seconds.
keys together for 5 seconds.
3. Once this feature is unlocked, to change from auto to manual and back again, press the
key for five
seconds.
4. Automatic Control
In auto mode, the controller automatically adjusts the output variable in accordance with the PID algorithm to
reach and maintain the desired set-point. Auto mode is the normal mode of operation. It is normally PID control
(depending on the parameters you select for the P, I, + D parameters)
5. Manual Control
Manual control allows the operator to control the out-put by forcing it up or down using the keys.
With a 4~20 mA out-put controller the out-put can be increased or decreased by manually adjusting it using the
up and down keys.
With a relay out-put controller, when in manual you are able to vary the relationship between the on and off times,
thereby adjusting the power fed to the load. This is measured in % of cycle time in seconds. So 40 % would
cause the load to be on for 40 % of the cycle time and off for 60%. (Cycle time for a relay out-put controller is
usually set at 15 seconds). This is a useful feature that can be used in the event of a T/C break to keep
production running.
5.2 AUTOTUNE
The auto-tune feature will work when it should depending on the “tune” parameter selected below.
This is normally set at “1” which means the controller requires an instruction to perform an auto-tune operation.
This is best as in most cases once the controller has been set up one does not wish to keep changing the
parameters.
To affect an auto-tune operation you need to allow the controller to reach the set-point and then press and hold
the scroll key
for 5 seconds until the auto-tune dot in the right extreme of the PV display starts to flash.
The controller will then perform an auto-tune operation until the light stops flashing.
Normally this will be two or three cycles of control.
tunE
0
1
2
3
4
5
Auto-tune parameter selection.
Tune at set-point when instructed to do so manually.
Tune at 10% below set-point when instructed to do so manually.
This causes the controller to effect a once only auto-tune cycle on initial power up that
will be done at the PV. It will then reset itself to 0 (tune=0) on completion to prevent further
auto-tuning at consecutive power ups.
This causes the controller to effect a once only auto-tune cycle on initial power up that
will be done at 10% below the setpoint. It will then reset itself to 1 (tune=1) on completion to
prevent further auto-tuning at consecutive power ups.
This causes the controller to effect auto-tune at every power up that will be done at the
setpoint.
This causes the controller to effect auto-tune at every power up that will be done at 10%
below the setpoint.
5.3 RAMP
The controller can be configured to act either as a fixed set-point controller or as a single ramp controller on power up.
This function enables the user to set a predetermined ramp rate to allow the process to gradually reach set-point
temperature thus producing a “soft start” function. This parameter is activated by selecting the appropriate parameter
lock level that will allow access to the rAnP function, ie: 1, 3, 5, 7 etc
The ramp function is also automatically engaged when making set-point changes. This means that the controller will
ramp the temperature from the current value to the new set-point value in accordance with the ramp setting. The ramp
8
rate is determined by “rRñP” parameter, which can be set in the range 0.0 to 100.0
C/minute. The ramp function is
disabled when the rRñP parameter is set to zero.
5.4 RAMP AND DWELL
A dwell timer is incorporated within the controller when used with certain alarm functions. Alarm 1 can be configured by
setting “A 1Fu” = 9 to provide a dwell function or a soak function to be used in conjunction with the ramp function. To
achieve this you must wire the contactor output through the alarm contact. After setting the “A 1Fu” = 9 you will find the
tiñE function activated in the user level. This is where you will set the soak time in minutes. On turning the controller
on the alarm contact will be on, allowing the controller to control the temperature. Once the SV = SP the timer will be
started. The alarm light will flash to indicate that the soak timer is running. At the end of the pre-set time, the alarm
relay will switch off and the output will be disabled. This time alarm function can be used without the ramp, simply to set
a soak time for the controller and then switch iot off. To deactivate the timer function temporarily just set the time to –1
minutes or remove the function from the “A 1Fu” settings.
5.5
HEATING / COOLING CONTROL
There are two ways of doint this.
Using the Alarm for the cooling:
It is not always necessary to use proportional control for cooling as often cooling is done with some type of refrigeration
equipment or fan, that cannot be turned on and off on a frequent basis. In this case you use the standard off the shelf
controller that comes complete with an alarm. By configuring the alarm as a deviation alarm “A Ifu=0” it links the
alarm to the set-point by a fixed deviation, and the alarm out-put can then be used for cooling. The alarm setting in level
1 then dictates the gap between the heating setpoint and the “alarm” cooling setpoint. The alarm also has its own
hysteresis setting thereby allowing you to set a band on the cooling set point (alarm setting) that will dictate how far the
temperature must drop before cooling (alarm) switches off again. This is the “A Ihy” setting. In addition to this since
the alarm is linked to the main set point as you change the set point the cooling parameters follow and do not need to be
readjusted each time. This method is often used for “fan” cooling on extrusion barrel heaters
Purchasing a controller with a second proportional control output.
An option is available in these controllers is a second proportional control output that can be used for cooling. This
means you will have PID control on the heating output, and proportional control on the cooling. Note: A second
proportional cooling output is not available on the 48 x 48 size. This type of proportional control can be used when you
have liquid cooling on a barrel, where you are switching a solenoid valve to control the cooling.
5.6
AdEr
Open
AtEr
CSEr
ERROR MESSAGES
A/D converter damage
Sensor break error…faulty input
Incorrect operation of autotune procedure
Check sum error, value in memory may have changed accidentally
TABLE 2
EroP
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Alarm 2
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
Output 2
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
Alarm 1
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
Output 1
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
9
15
On
On
On
On
5.7 ALARM FUNCTIONS
The Alarm function can be locked by pressing the
The Alarm function can be unlocked by pressing the
and
keys for 5 seconds.
and
Select the type of alarm function required from the table below. Use
keys for 5 seconds.
AISP to set values as required.
TABLE 1
A Ifu
0 or 4
A 2Fu
0 or 4
1 or 5
1 or 5
2 or 6
2 or 6
ALARM OPTION SETTINGS
Deviation Alarm High
Alarm output on when PV >(SV+A1SP)
Deviation Alarm Low
Alarm output on when PV <(SV+A1SP)
High Alarm
3 or 7
3 or 7
Low Alarm
8
-
9
-
10
-
11
-
Timer Function
Timer on when PV=SV alarm on when timer off
Timer Function
Alarm on when power on, off when timer OFF
Timer Function
Alarm output ON when timer on
Timer Function
-
Alarm On when power on, off when timer ON
Band Alarm
Band Alarm
12 or 14
13 or 15
7. SPECIFICATIONS
1. INPUT
Thermocouple
 RTD
Linear Voltage (Current)
Range
Accuracy
Cold Junction Compensation
Input Impedance
Excitation Current for RTD
Sample Rate
Common Mode Rejection
Normal Mode Rejection
2. CONTROL
Proportional Band
Integral (Reset)
Derivative (Rate)
Anti Rest Windup
Ramp Rate
Dwell
On-Off
Cycle Time
J, K, T, E, B, R, S, N (IPTS68/DIN 43710)
Pt100 ohms RTD (DIN 43760/BS 1904 or JIS)
0~20 mA and 4~20 mA
User configurable (To best suit application)
± 0.1% + 1 LSD
0.1% (ambient typical)
10M ohms for T/C, 100K ohms for Linear Voltage,
2.7 ohms for 4~20mA
0.2mA Maximum
250 mS
120 dB
60dB
0.0 ~ 100.0% (of full scale)
0 ~ 3600 Seconds
0 ~ 3600 Seconds
Inhibits integral action outside Proportion Band
0.0 ~ 100.0 °C/ minute
0 ~ 9999 minutes
With adjustable hysteresis
0 ~ 99 Seconds
10
Control Action
Alarm functions
Configurable for Direct (Cooling) or Reverse (Heating)
16 configurable different functions available
3. OUTPUT
Relay
Pulsed Voltage SSR
Current 4~20 mA
Alarm
5A/240 VAC resistive
Isolated 24 VDC 100mA Maximum
Isolated 0 (4)~20mA Maximum load 500 ohms
Relay out. Form A contact (SPST) 10A/240 VAC resistive
4. POWER
Rating
Consumption
85 ~ 265 VAC 50/60 Hz
5 VA maximum
5. ENVIRONMENTAL
Operating Temperature
Humidity
Insulation
EMC Emission
EMC Immunity
Weight
-10 ~ 55°C
0 ~ 90%
20M ohms minimum @ 500 VDC
EN 50081-1:1992, EN 55022:1994
EN 50082-1:1992, IEC 801-2, IEC801-3, IEC 801-4:1988
VT4810 -180g, VT9410, VT4910 & - 240g,
VT7210 - 230g
Fast Heat UK Ltd
Unit 7, Alder Close
Eastbourne
East Sussex
BN23 6QF
TEL: 01323 647375
FAX: 01323 410355
EMAIL: [email protected] or [email protected]
WEB: www.fastheatuk.com
FHD0108-10-1105