North Eastern Regional Power Committee Agenda For 34th PCC Sub-Committee Meeting Time of meeting : 10:00 Hrs. Date of meeting : 16th June, 2015 (Tuesday) Venue : “Hotel Nandan”, Guwahati. A. CONFIRMATION OF MINUTES CONFIRMATION OF MINUTES OF 33rd MEETING OF PROTECTION SUBCOMMITTEE OF NERPC. The minutes of 33rd meeting of Protection Sub-committee held on 19th May, 2015 at Guwahati were circulated vide letter No. NERPC/SE (O)/PCC/2015/4520-4555 dated 04th June, 2015. No observations or comments were received from the constituents. The Subcommittee may discuss & confirm minutes of 33rd PCCM of NERPC. ITEMS A.1 FOR DISCUSSION Implementation of 3-phase Auto Reclosure Scheme in all lines connected to Khandong and Kopili HEP: For reliable operation of Power system it is required to implement 3-Phase Auto Reclosure Scheme in all the 132kV lines connected to Kopili and Khandong HEP of NEEPCO. The lists of such lines are: a) 132kV Khandong – Umrangso - Haflong b) 132kV Kopili – Khandong # 1 During 32nd PCC meeting, the sub-committee decided that at Khandong end it should be kept as check synchronization mode and at Khilehriat (PG) end it should be made as dead line charging mode. The Sub-committee requested NERTS and NEEPCO to co-ordinate amongst them and implement the 3-Phase Autoreclosure at the earliest. Agenda for 34th PCC Meeting held on 16.06.2015 During 33rd PCC meeting, the sub-committee requested Assam, NERTS & NEEPCO to co-ordinate amongst them and implement the 3-Phase Auto-reclosure by 15.06.15 and the status should be intimated in the next PCC meeting. Assam, NERTS and NEEPCO agreed. Assam/NEEPCO/NERTS may kindly intimate the status. A.2 Implementation of 3-Phase Auto Reclosure Scheme of Radially fed 132kV Lines connected to Ranganadi HEP: At present, the power flows to Nirjuli, Gohpur and Ziro radially from Ranganadi HEP and any transient fault in line causes undesirable outages. Hence, to avoid outages during transient fault it is essential to implement 3- Phase Dead Line charging of following 132kV Lines. a) 132kV Ranganadi – Nirjuli Line (Dead Line Charging at RHEP) b) 132kV Nirjuli – Gohpur Line (Dead Line Charging at Nirjuli) c) 132kV Ranganadi – Ziro Line (Dead Line Charging at RHEP) During 33rd PCC meeting, EE, SLDC, Ar. Pradesh requested NEEPCO to intimate their plan atleast one week in advance so that necessary action can be taken by them. The sub-committee requested NEEPCO to take up the matter with Ar. Pradesh so that SPAR on above lines could be completed. NEEPCO/Ar. Pradesh may kindly intimate the status. A.3 Implementation of the recommendations of the Protection Audit: As per Sl. no 9.1.1 & 9.1.4 of Report on Enquiry Committee on Grid Disturbance in Northern Region on 30th July 2012 and in Northern, Eastern & North-Eastern Region on 31st July 2012, thorough Third Party protection audit needs to be carried out periodically along with independent audit of Fault Recording Instruments. As decided in 32nd PCCM, all the constituents are requested to furnish the data as per check list of Task force in Annexure A.3(II) and the data as per format of NERPC in Annexure A.3(I) for future reference. AEGCL have furnished check list of protection objects. AEGCL are requested to confirm whether these protection objects are applicable for all transmission elements owned by them and also requested to furnish details as per format of NERPC. All the other constituents are requested to furnish the details as early as possible. 2 Agenda for 34th PCC Meeting held on 16.06.2015 During 32nd PCC meeting, the sub-committee had also requested NERPC to hold the special meeting to finalize the standard scheduling of O&M comprising of NERLDC, NERTS, NERPC, NEEPCO, Assam & Meghalaya etc., at the earliest so that the best O&M practices can be evolved in the region. During 33rd PCC meeting, SE(O) informed that since there were other issues to be discussed along with above agenda, the meeting could not be held in May, 2015. The above meeting as suggested by the Sub-committee will be conducted soon by NERPC. DGM (SO-II), NERLDC informed that information have been received from AEGCL (as per format II & Details of Protection Audit not received as per format-I), OTPC (as per format II), NEEPCO (Khandong & Kopili as per format-I). He requested the remaining constituents to submit at the earliest. The sub-committee requested NERPC to write a letter to remaining constituents (i.e. NERTS (POWERGRID), NTPC, NHPC, NEEPCO (except Khandong & Kopili), AEGCL (for Details of Protection Audit as per format II), APGCL, MePTCL, MePGCL, MSPCL, DOP, Mizoram, DOP, Nagaland, DOP, Arunachal Pradesh, TSECL) to furnish the data as per check list of Task Force in Annexure – A.3 (II) and well as the data as per format of NERPC in Annexure A.3 (I) at the earliest. NERPC has written to above constituents to furnish the data as per Annexure – A.3 (II) as well as Annexure – A.3 (I) and the reply is awaited. Constituents may kindly intimate the status. A.4 Standardization of Disturbance Recorder Channels: Disturbance Recorders on Transmission elements are necessary for post disturbance analysis, and identification & rectification of any protection maloperation. As per CBIP’s manual on Protection of Generators, GT, Transformers and Networks, it is recommended to have minimum 8(eight) analog signals and 16(sixteen) binary signals per bay or circuit. Also, it should have a minimum of 5 sec of total recording time, minimum pre-fault recording time of 100 msec and minimum post-fault recording time of 1000 msec. During 33rd PCC meeting, Manager (AM), NERTS informed that standardization for transformers & reactors are being finalized by their Corporate Centre for the whole country, the report would be circulated as soon as it is received from them. He also informed that suggestion by GM, NERLDC for NER States have already been communicated by them. He stated that as soon as the report is received they will intimate to NERPC/NERLDC accordingly. NERTS may kindly intimate the current status. 3 Agenda for 34th PCC Meeting held on 16.06.2015 A.5 Submission of formats for charging/first time synchronization of new elements: Information related to charging/first time synchronization of new elements/units is to be furnished to NERLDC (two month in advance). All the activities related to charging/first time synchronization of new elements are to be completed before charging/first time synchronization of new elements. The technical data of the elements are also necessary for preparation of Base Case for system study for NER system. During the 108th OCC meeting, SE(O) informed that nomination from NTPC was received only recently, the above meeting could not be conducted. Now since the complete list of nodal officers is received, NERPC will arrange the meeting at the earliest. NERPC may kindly intimate the current status about holding the special meeting comprising of nodal officers of constituents, NERLDC & NERPC as suggested by the Sub-committee. A.6 Reporting of failure of equipment/towers of transmission lines to Standing Committee of Experts: CEA vide letter dated 04.02.2015 has intimated that as per Section 73 of Electricity Act 2003, CEA is to carry out investigation of failure of substations/generating stations and failure of transmission line towers. Accordingly two Standing Committees have been constituted taking representation from academic institutes, Research Institutes like CPRI and utility to investigate the cause of failures: (a) Standing Committee of Experts to investigate the failure of Transmission line towers of 220 kV and above voltage level of Power utilities. (b) Standing Committee of Experts to investigate the failure of Equipments of 220 kV and above substations/Generating stations of power utilities. In view of above, it is requested that all utilities may please report the incidences of failure immediately after occurrence of such failure to Chief Engineer (SE&TD), CEA with copy to NERPC. The format for reporting the first hand information about the failure of equipment in substations/generating stations and failure of transmission line towers are attached at Annexure – A.6 During 32nd PCC meeting, Meghalaya representative stated that Recent failure of one 63 MVAR reactor at 400 kV S/S Byrnihat of Me.ECL would be sent to CEA for investigation as directed above as suggested by SE(O) to CEA within one week. 4 Agenda for 34th PCC Meeting held on 16.06.2015 During 33rd PCC meeting, Meghalaya representative requested NERPC to take up the matter with Director (Trans) regarding failure of above equipment at Byrnihat. The Sub-committee requested NERPC to write to Director (Transmission), Me. PTCL regarding above failure of important reactor at Byrnihat. NERPC has written to Director (T), Me. PTCL and the reply is awaited. Meghalaya may kindly intimate the status. A.7 Status of R&M Implementation of NER from PSDF: The Sub-committee requested all the constituents to intimate the status of progress to NERPC regularly so that the same could be intimated to CERC. Latest available status is enclosed at Annexure - A.7. Constituents may kindly intimate the status. A.8 Furnishing Protection Details of Transmission Lines, Transformers, Reactors and Bus Bars: a. Transmission Line As per section 43.4.c (Schedule V) of Technical Standards for construction of Electrical Plants and Electric Lines Regulation, 2010, Protection system of 400 kV lines consists of Main I, Main II, DEF, Two Stage Over Voltage, Auto Reclosing and Carrier Aided Inter Tripping. Protection system of 220 kV lines consists of Main I, Main II/Over Current & DEF, Auto Reclosing and Carrier Aided Inter Tripping. Protection system of 132 kV lines consists of Main I, Over Current & DEF, Auto Reclosing and Carrier Aided Inter Tripping. AEGCL, MSPCL, MePTCL, P&E, Mizoram, POWERGRID, NEEPCO (only AGBPP, Ranganadi HEP, Doyang HEP & AGTPP), NHPC & TSECL has furnished the information. DoP, Arunachal Pradesh, DoP, Nagaland, NEEPCO (for Khandong, Kopili & Kopili Stg II), OTPC (for 132 kV lines) are requested to furnish Protection Details of Transmission Lines as per enclosed format in Annexure - A.8 (I&II). b. Transformer As per section 43.4.c (Schedule V) of Technical Standards for construction of Electrical Plants and Electric Lines Regulation, 2010, Protection system of Transformer consists of Differential Protection, Over Flux Protection, REF Protection, Backup Directional Over Current and Earth Fault Protection (HV 5 Agenda for 34th PCC Meeting held on 16.06.2015 & LV side)/Impedance Protection, Buchholz, WTI, OTI, MOG, OSR for OLTC, PRD, SA, Tertiary Winding Protection, Over Load Alarm. AEGCL, MSPCL, MePTCL, P&E, Mizoram, POWERGRID, NEEPCO (only AGBPP, Ranganadi HEP & AGTPP), NHPC, OTPC & TSECL has furnished the information. DoP, Arunachal Pradesh, DoP, Nagaland, NEEPCO (for Khandong, Kopili & Kopili Stg II) are requested to furnish Protection Details of Transformer as per format in Annexure–A.8 (I&II). c. Reactor As per section 43.4.c (Schedule V) of Technical Standards for construction of Electrical Plants and Electric Lines Regulation, 2010, Protection system of Reactor consists of Differential Protection, REF Protection, Backup Definite Time Over Current and Earth Fault Protection/Impedance Protection, Buchholz, WTI, OTI, MOG, SA. AEGCL, MePTCL, NEEPCO (Rangaandi HEP), OTPC and POWERGRID have furnished the information. d. Bus Bar & LBB As per section 43.4.c (Schedule V) of Technical Standards for construction of Electrical Plants and Electric Lines Regulation, 2010, Bus Bar Protection and Local Breaker Backup Protection are to be provided in 220 kV and above voltage interconnecting sub-station and all generating station switchyards. MePTCL, POWERGRID, NEEPCO (AGTPP, AGBPP & Ranganadi HEP), NHPC & OTPC have furnished the information. DoP, Arunachal Pradesh (Deomali), AEGCL (BTPS, Agia, Boko, Sarusajai, Langpi, Samaguri, Jawaharnagar, Mariani, Tinsukia) & NEEPCO (Kopili) are requested to furnish Bus Bar Protection and Local Breaker Backup Protection as per enclosed format in Annexure-A.8 (I&II). e. Bus Coupler MSPCL, MePTCL, P&E, Mizoram, NEEPCO (only AGBPP, Ranganadi HEP & AGTPP) & NHPC have furnished the information. DoP, Arunachal Pradesh, AEGCL, DoP, Nagaland, POWERGRID, NEEPCO (for Doyang, Khandong, Kopili & Kopili Stg II) & OTPC are requested to furnish Bus Coupler Protection as per enclosed format in Annexure –A.8. Protection System Database prepared based on information furnished by power utilities of NER, which is attached at Annexure- A.8 (I&II). Power utilities of NER are requested to check & validate the same. After detailed deliberation in 32nd PCC meeting, the Sub-committee requested all the constituents to furnish the above information to NERLDC latest by 10.05.2015. 6 Agenda for 34th PCC Meeting held on 16.06.2015 Protection System Database prepared based on information furnished by power utilities of NER, which is attached at Annexure - A.8). Power utilities of NER were requested to check & validate the same. During 33rd PCC meeting, the sub-committee requested NERPC to write a letter to remaining constituents (i.e. AEGCL (for Bus Coupler (for all) & Bus Bar & LBB (for BTPS, Agia, Boko, Sarusajai, Langpi, Samaguri, Jawaharnagar, Mariani, Tinsukia)), DoP, Arunachal Pradesh (for Transmission Line, Transformer, Bus Coupler, Bus Bar (for Deomali) & LBB (for Deomali), DOP, Nagaland (for Transmission Line, Transformer, Bus Coupler), NEEPCO (Transmission line (for Khandong & Kopili Stg-II), Transformer (for Kopili, Khandong & Kopili Stg-II), Bus Bar & LBB (Kopili), Bus Coupler (Kopili, Khandong, Kopili St II), OTPC (for Transmission Line, Transformer, Reactor, Bus Copuler, Bus Bar & LBB), POWEERGRID (for Bus Coupler) to furnish the data as per enclosed format in Annexure – A.8 at the earliest. NERPC has written letter to constituents above and the reply is awaited. Concerned constituents may kindly intimate the current status. A.9 Major Oscillations in NER: NERLDC informed that during the month of May, 2015, there were persistent Low Frequency Oscillations (LFOs) in NER Grid which led to tripping of some generators in the Southern part of NER Grid around Khliehriat (Meghalaya) system. The oscillations occurred from 03:38:56.080 Hrs to 03:41:37.040 Hrs (around 3 minutes) and from around 03:42:33.440 Hrs to around 03:45:24.480 Hrs (around 3 minutes) on 29.05.15, & from around 22:56:30 Hrs to 22:58:15 Hrs on 31st May 2015. In both the incidents, Low Frequency Modes in the system around 1.2 Hz and it’s 2nd Harmonic mode around 2.4 Hz was observed in the system, and the modes have Poor / Negative damping. In the 29th May incident, the oscillations started after fault in Meghalaya system leading to tripping of 132 kV Khliehriat – Lumshnong line followed by oscillations in Leshka HEP of MePGCL and Khandong HEP of NEEPCO. There was tripping of Leshka units and Khandong units due to jerk in the system. The oscillations later continued between units of Kopili HEP and Kopili St-II HEP. In the 31st May incident, the oscillations started again after fault in Meghalaya system leading to tripping of 132 kV Khliehriat (PG) – Khliehriat (MePTCL) I & II lines followed by oscillations in Leshka HPP of MePGCL and Khandong HEP of NEEPCO. There was tripping of Leshka units, Umiam St IV units and Khandong unit due to jerk in the system. The oscillations later continued between units of Kopili HEP and Kopili St-II HEP. The Zone of oscillations in NER Grid is indicated below: 7 Agenda for 34th PCC Meeting held on 16.06.2015 Oscillations were more prominent in Active power/ Frequency than in Voltage. It thus suggests a lack of system stability as a whole. To address this issue, PSS (Power System Stabilizers) may be installed in Myndtu Leshka Power Station to enhance stability of the system. Members may like to discuss. A.9 Grid Incidences during May, 2015: The following numbers of Grid Disturbances (GD) occurred during the period w.e.f 1st May, 2015 to 31st May, 2015 :- Sl No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Control Area 1st Palatana AGBPP AGTPP Ranganadi Kopili Khandong Doyang Loktak Arunachal Pradesh Assam Manipur Meghalaya Mizoram Nagaland Tripura Grid Disturbance in nos. May, 2015 to 31st 1st January, 2015 to 31st May, 2015 May, 2015 1 5 0 1 1 4 2 3 0 1 0 1 0 2 0 4 2 22 4 25 6 34 6 9 2 5 1 13 1 3 8 Agenda for 34th PCC Meeting held on 16.06.2015 Grid Disturbance in nos. Sl No 1 2 3 4 5 Category of GD 1st May, 2015 to 31st May, 2015 1st January, 2015 to 31st May, 2015 GD 1 GD 2 GD 3 GD 4 GD 5 Total 18 2 0 0 0 20 83 4 0 0 1 88 This is for information to the members. Remedial actions are to taken by the concerned power utilities of NER A.10 Root cause analysis of Grid Disturbances: i. Disturbance in Meghalaya system – Repeated tripping of 132 kV Khliehriat (PG) – Khliehriat (Me. PTCL) – I & II lines: During the month of May, 2015, there were 6 nos. of grid disturbances in Khliehriat (including Lumshnong) area of Meghalaya. W.e.f 01.06.15 to 08.06.15, there were 10 nos. events involving tripping of 132 kV Khliehriat (PG) – Khliehriat (MePTCL) I & II lines, resulting in 9 nos. of grid disturbances. During the month of May15 a. At 1544 Hrs on 19.05.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines ( Line 1 : Khliehriat (PG) - DP, Z-III, R-B-E & Khliehriat (MePTCL)Not furnished and Line 2: Khliehriat (PG) - DP, Z-II, R-B-E & Khliehriat (MePTCL)- Not furnished), 132 kV Khliehriat – Lumshnong line (Khliehriat (MePTCL) - Earth Fault & Lumshnong - Not furnished) and 132 kV Khliehriat – NEIGRIHMS line (Khliehriat (MePTCL) – DP, Z1, R-Y-B & NEIGRIHMS – Not furnished) tripped. Due to tripping of these elements, there was loss of load in Khliehriat area (including Lumshnong) of Meghalaya System and loss of generation from Myndtu Leshka HPP. System was restored progressively by 15:48 Hrs. Load loss: 70 MW in Meghalaya Generation Loss: 35 MW in Meghalaya (Leshka) b. At 1043 Hrs on 23.05.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines tripped ( Line 1 : Khliehriat (PG) - DP, Z-III, R-E & Khliehriat (MePTCL)- Not furnished & Line II : Khliehriat (PG) - DP, Z-II, R-E & Khliehriat (MePTCL)- Not furnished), 132 kV Khliehriat (PG) – Khandong I line (Khliehriat (PG) - No tripping & Khandong (NEEPCO) - Earth Fault) 9 Agenda for 34th PCC Meeting held on 16.06.2015 line tripped. Due to tripping of these elements, there was loss of load in Khliehriat (including Lumshnong) area of Meghalaya. Load loss: 57 MW in Meghalaya c. At 1425 Hrs on 23.05.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines tripped (Line 1: Khliehriat (PG) - DP, Z-III, B-E & Khliehriat (MePTCL) - Not furnished) & Line 2: Khliehriat (PG) - DP, Z-II, Y-E & Khliehriat (MePTCL) - Not furnished). Due to tripping of these elements, there was loss of load in Khliehriat (including Lumshnong) area of Meghalaya. Load loss: 15 MW in Meghalaya d. At 0336 Hrs on 29.05.15, 132 kV Khliehriat (MePTCL) – Lumshong line (Khliehriat(MePTCL) - DP,Z-III,R-Y-B & Lumshong - Hand tripped) line tripped. This resulted tripping of Unit 3 of Myndtu Leshka HPP of Meghalaya and Units 1 and 2 of Khandong due to heavy jerk. There were Low Frequency Oscillations (LFOs) of 1.2 Hz and 2.4 Hz modes in the system having poor or negative damping. Oscillations were observed in Leshka, Khandong, Kopili and Kopili St-II units. Load loss: 24 MW in Meghalaya Generation Loss: 84 MW [44 MW in Leshka and 40 MW Khandong) e. At 0757 Hrs on 29.05.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines ( Line 1: Khliehriat (PG) - DP, Z-III, R-Y-B & Khliehriat (MePTCL)Not furnished & Line 2 : Khliehriat (PG) - DP, Z-II, R-Y-B & Khliehriat (MePTCL)- Not furnished) tripped. Due to tripping of these elements, there was loss of load in Khliehriat (including Lumshnong) area of Meghalaya and loss of entire generation of Leshka HPP on Under-voltage. Load loss: 73 MW in Meghalaya Generation Loss: 105 MW in Meghalaya (Leshka) f. At 2255 Hrs on 31.05.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines ( Line 1: Khliehriat (PG) - DP, Z-III, R-B-E & Khliehriat (MePTCL)Not furnished & Line 2 : Khliehriat (PG) - DP, Z-II, R-B-E & Khliehriat (MePTCL)- Not furnished) tripped. Due to tripping of these elements, there was loss of load in Khliehriat (including Lumshnong) area of Meghalaya, loss of entire generation of Leshka HPP on Undervoltage and loss of entire generation of Umiam StIV. There was Low Frequency Oscillations (LFOs) of poor/negative damped modes around 1.2 Hz and 2.4 Hz only. Oscillations were observed in Leshka, Khandong, Kopili and Kopili St-II units. Load loss: 73 MW in Meghalaya Generation Loss: 105 MW in Meghalaya (Leshka and Umiam St- IV) Category as per CEA Standards: GD-I 10 Agenda for 34th PCC Meeting held on 16.06.2015 W.e.f. 01.06.15 to 08.06.15 i. At 1857 Hrs on 01.06.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines tripped ( Line I: Khliehriat (PG) - DP, Z-II, R-Y-E & Khliehriat (MePTCL) - Not furnished and Line II: Khliehriat (PG) - DP, Z-III, R-Y-E & Khliehriat (MePTCL)- Not furnished). Due to tripping of these elements, there was loss of load in Khliehriat (including Lumshnong) area of Meghalaya and generation loss in Leshka HEP. Load loss: 88 MW in Meghalaya Generation Loss: 122 MW in Meghalaya (Leshka) ii. At 2356 Hrs on 01.06.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines tripped (Line 1: Khliehriat (PG) - Not furnished & Khliehriat (MePTCL) - Not furnished and Line 2: Khliehriat (PG) - Not furnished & Khliehriat (MePTCL) - Not furnished). Due to tripping of these elements, there was loss of load in Khliehriat (including Lumshnong) area of Meghalaya and generation loss in Leshka HEP. Load loss: 49 MW in Meghalaya Generation Loss: 122 MW in Meghalaya (Leshka) iii. At 2248 Hrs on 05.06.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines tripped ( Line 1: Khliehriat (PG) - DP, Z-III, R-Y-B & Khliehriat (MePTCL) - Not furnished and Line 2: Khliehriat (PG) - DP, Z-III, R-Y-B & Khliehriat (MePTCL) - Not furnished). Due to tripping of these elements, there was loss of load in Khliehriat (including Lumshnong) area of Meghalaya and generation loss in Leshka HEP. Load loss: 67 MW in Meghalaya Generation Loss: 114 MW in Meghalaya (Leshka) iv. At 1816 Hrs on 06.06.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines tripped ( Line 1 : Khliehriat (PG) - DP, Z-III, R-Y-B & Khliehriat (MePTCL) - Not furnished and Line 2 : Khliehriat (PG) - DP, Z-III, R-Y-B & Khliehriat (MePTCL)- Not furnished). Due to tripping of these elements, there was loss of load in Khliehriat (including Lumshnong) area of Meghalaya and generation loss in Leshka HEP. Load loss: 111 MW in Meghalaya Generation Loss: 67 MW in Meghalaya (Leshka) v. At 0056 Hrs on 08.06.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines tripped ( Line 1: Khliehriat (PG) - DP, Z-III, R-Y-B & Khliehriat (MePTCL)- Not furnished and Line 2: Khliehriat (PG) - DP, Z-III, R-Y-B & Khliehriat (MePTCL)- Not furnished) tripped. Due to tripping of these elements, there was loss of load in Khliehriat (including Lumshnong) area of Meghalaya and generation loss in Leshka HEP. 132 kV Khandong – Khliehriat (PG) I also tripped (Khandong – Not furnished & Khliehriat(PG) – Not furnished). 11 Agenda for 34th PCC Meeting held on 16.06.2015 Load loss: 39 MW in Meghalaya Generation Loss: 121 MW in Meghalaya (Leshka) vi. At 2222 Hrs on 08.06.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines tripped ( Line 1: Khliehriat (PG) - DP, Z-III, R-Y-B & Khliehriat (MePTCL)- Not furnished and Line 2: Khliehriat (PG) - DP, Z-II, R-Y-B & Khliehriat (MePTCL)- Not furnished). Due to tripping of these elements, there was loss of load in Khliehriat (including Lumshnong) area of Meghalaya and generation loss in Leshka HEP. Load loss: 58 MW in Meghalaya Generation Loss: 121 MW in Meghalaya (Leshka) vii. At 2317 Hrs on 08.06.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines tripped ( Line 1: Khliehriat (PG) - DP, Z-III, R-Y-B & Khliehriat (MePTCL)- Not furnished and Line 2: Khliehriat (PG) - DP, Z-III, R-Y-B & Khliehriat (MePTCL)- Not furnished) tripped. Due to tripping of these elements, there was loss of load in Khliehriat (including Lumshnong) area of Meghalaya and generation loss in Leshka HEP. 132 kV Khandong – Khliehriat (PG) I also tripped (Khandong – Not furnished & Khliehriat(PG) – Over-current). Load loss: 112 MW in Meghalaya Generation Loss: 67 MW in Meghalaya (Leshka) viii. At 0318 Hrs on 09.06.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines tripped ( Line 1: Khliehriat (PG) - DP, Z-III, R-Y-B & Khliehriat (MePTCL)- Not furnished and Line 2: Khliehriat (PG) - DP, Z-II, R-Y-B & Khliehriat (MePTCL)- Not furnished) tripped. Due to tripping of these elements, there was loss of load in Khliehriat (including Lumshnong) area of Meghalaya and generation loss in Leshka HEP. 132 kV Khandong – Khliehriat (PG) I also tripped (Khandong – Not furnished & Khliehriat(PG) – Earth Fault). Load loss: 77 MW in Meghalaya Generation Loss: 44 MW in Meghalaya (Leshka) ix. At 0508 Hrs on 09.06.15, 132 kV Khliehriat (PG) - Khliehriat (MePTCL) I & II lines tripped ( Line 1: Khliehriat (PG) - DP, Z-III, Y-B-E & Khliehriat (MePTCL)- Not furnished and Line 2: Khliehriat (PG) - DP, Z-II, Y-B-E & Khliehriat (MePTCL)- Not furnished) tripped. Due to tripping of these elements, there was loss of load in Khliehriat (including Lumshnong) area of Meghalaya and generation loss in Leshka HEP. 132 kV Khandong – Khliehriat (PG) I also tripped (Khandong – Not furnished & Khliehriat(PG) – Earth Fault). Load loss: 75 MW in Meghalaya Generation Loss: 38 MW in Meghalaya (Leshka) Category as per CEA Standards: GD-I (for events from Sl. No. a. to ix) 12 Agenda for 34th PCC Meeting held on 16.06.2015 x. At 0056 Hrs on 08.06.15, 132 kV Khandong – Khliehriat (PG) I tripped (Khandong – Not furnished & Khliehriat(PG) – Not furnished). Analysis of events: Due to tripping of these elements, power supply to Khliehriat (including Lumshnong) area of Meghalaya was interrupted repeatedly. It is suspected that there may be un-cleared fault in Meghalaya system or delayed fault clearance. As a result, several transmission lines tripped. In most of the cases, Leshka machines tripped and in some of the case, machines of Umiam St IV & Khandong tripped. The un-cleared faults may create oscillations in the system. It was observed that there was oscillation of machines of Leshka along with machines of Khandong. As a result, machines of Leshka and machines of Khandong tripped. Even after tripping of these machines, the oscillations in the system was continued and observed between machines of Kopili and machines of Kopili Stg-II until the mode damping improves. Oscillations were more prominent in Active power/Frequency rather than in Voltage. It thus suggests a lack of system stability as a whole. To address this issue, PSS (Power System Stabilizers) may be installed in Leshka Power Station to enhance stability of the system. DR output at both ends of all lines tripped required for proper analysis of the events. Me. PTCL, Me. PGCL, NEEPCO & NERTS, POWERGRID may elaborate. ii. Disturbance in AGTPP, Palatana and Tripura power system a. At 1526 Hrs on 29.05.15, due to tripping of 132 kV Agartala – Dhalabil line, 132 kVBaramura – Jirania line, 132 kV AGTPP - Agartala I line (AGTPP - DP, Z-III, R-E & Agartala - No tripping) & 132 kV AGTPP - Agartala II line (AGTPP- DP, Z-III, R-E & Agartala - No tripping), power supply to Tripura system was interrupted and all running units of AGTPP tripped (No information from AGTPP regarding unit tripping). 132 kV Palatana Surajmani Nagar line & 132 kV Palatana – Udaipur line also tripped, Due to tripping of 132 kV Palatana - Surajmani Nagar line & 132 kV Palatana – Udaipur line, Palatana Module II tripped (Due to tripping of Gas Booster Compressor). Tripping of Palatana machines triggered SPS I at Silchar with load relief of 70 MW at South Assam. Generation loss: 469 MW [Palatana = 335 MW, AGTPP = 76 MW] Load Loss: 70 MW in Tripura Category as per CEA Standards: GD-II Analysis of events: Due to tripping of all outgoing feeders of AGTPP, all the running units of AGTPP tripped. Due to tripping of 132 kV Palatana – Udaipur line and 132 kV Palatana – Surjamaninagar line, auxiliary system of Palatana Module II failed and subsequently Gas Booster Compressor (GBC) of Palatana Module II tripped. 13 Agenda for 34th PCC Meeting held on 16.06.2015 In this event on 29-May-2015, the 400/132 kV, 125 MVA ICT at Palatana was out of service. Since supply to Auxiliaries of Palatana units are taken from 132 kV Grid of Tripura, outage of 132 kV Palatana – Udaipur S/C and 132 kV Palatana – Surjamaninagar S/C led to failure of supply to Auxiliary system of Palatana units and hence tripping of Palatana units. If another 400/132 kV ICT at Palatana were in place, this type of incident could have been averted. This transformer would also ensure enhanced reliability of supply and also satisfied the N-1 contingency criteria as specified in CEA’s Manual on Transmission Planning Criteria, Jan’13. As an alternative arrangement, in such cases, if UATs at Palatana are of sufficient capacity, the Auxiliary supply failure would not have occurred. OTPC, Palatana may explore the provision of enhancement of UAT to sufficient capacity. DR output at both ends required for proper analysis of the events. NEEPCO, TSECL, OTPC & NERTS, POWERGRID may elaborate. iii. Disturbance in Manipur system a. At 1658 Hrs on 01.05.15, due to tripping of 132 kV Imphal(PG) - Imphal I & II lines (Line I: (Imphal (PG) - Earth fault & Imphal (MSPCL) - Not furnished & Line II : Imphal (PG) - Earth fault & Imphal (MSPCL) -Not furnished), power supply to Imphal (Capital) area of Manipur interrupted. Load loss: 63 MW in Manipur. b. At 0906 Hrs on 12.05.15, due to tripping of 132 kV Loktak- Ningthoukhong line (Loktak - Earth Fault & Ningthoukhong - Not furnished) & 132 kV Ningthoukhong - Imphal (PG) line (Ningthoukhong - Not furnished & Imphal (PG) - Earth Fault), power supply to Ningthoukong area of Manipur interrupted. Load loss: 28 MW in Manipur. c. At 1124 Hrs on 19.05.15, due to tripping of 132 kV Imphal (PG) - Imphal (MSPCL) I & II lines (Line I: Imphal (PG) - Earth fault & Imphal (MSPCL) Not furnished and Line II Imphal (PG) - Earth fault & Imphal (MSPCL) – Not furnished), power supply to Imphal (Capital) area of Manipur interrupted. Load loss: 76 MW in Manipur. d. At 0137 Hrs on 21.05.15, due to tripping of 132 kV Imphal (PG) - Imphal (MSPCL) I & II lines (Line I : Imphal (PG) - Earth fault & Imphal (MSPCL) Not furnished) & Line II: Imphal (PG)- Earth fault & Imphal (MSPCL)-Not furnished), power supply to Imphal (Capital) area of Manipur interrupted. Load loss: 30 MW in Manipur. 14 Agenda for 34th PCC Meeting held on 16.06.2015 e. At 1414 Hrs on 23.05.15, due to tripping of 132 kV Imphal (PG) - Imphal (MSPCL) I & II lines (Line1: Imphal (PG) - Earth fault & Imphal (MSPCL) Not furnished) & Line II: Imphal (PG) - Earth fault & Imphal (MSPCL) Not furnished), power supply to Imphal (Capital) area of Manipur interrupted. Load loss: 40 MW in Manipur. f. At 1714 Hrs on 23.05.15, due to tripping of 132 kV Imphal (PG) - Imphal (MSPCL) I & II lines (Line 1: Imphal (PG) - Earth fault & Imphal (MSPCL) Not furnished & Line 2: Imphal (PG) - Earth fault & Imphal (MSPCL) - Not furnished), power supply to Imphal (Capital) area of Manipur interrupted. Load loss: 44 MW in Manipur. Category as per CEA Standards: GD-I Analysis of events: It is suspected that there may be fault in MSPCL system in these cases. DR output at both ends of all lines tripped required for proper analysis of the events. NHPC, MSPCL, & NERTS, POWERGRID may elaborate. iv. Disturbance in Arunachal Pradesh and Gohpur area of Assam a. At 1138 Hrs on 18.05.15, due to tripping of 400 kV Balipara - Ranganadi I (Balipara (PG) – DP, Z-II, Y-B-E & Ranganadi (NEEPCO) – DP, Z-I, Y-B-E), power supply to Ziro & Capital area of Arunachal Pradesh and Gohpur area of Assam interrupted. There was also generation loss in Ranganadi HEP. Power was extended to these areas through 400 kV Balipara- Ranganadi II at 1210 Hrs on 18.05.15. 400 kV Balipara- Ranganadi II was kept open w.e.f 0006 Hrs on 18.05.15 due to control bus voltage at Ranganadi. Load loss: 60 MW in Arunachal Pradesh & Assam Generation Loss: 110 MW at Ranganadi (NEEPCO) Category as per CEA Standards: GD-II b. At 0008 Hrs on 25.05.15, due to tripping of 400 kV Balipara- Ranganadi I & II lines ( Line 1: Balipara(PG) – Overvoltage & Ranganadi (NEEPCO) – Overvoltage & Line 2 : Balipara (PG) – Overvoltage & Ranganadi (NEEPCO) – Overvoltage) lines, power supply to Ziro & Capital area of Arunachal Pradesh and Gohpur area of Assam interrupted. Load loss: 60 MW in Arunachal Pradesh & Assam Category as per CEA Standards: GD-I 15 Agenda for 34th PCC Meeting held on 16.06.2015 Analysis of Events: DR outputs have been received from Ranganadi of above events. DR output from Balipara (PG) has been received for the tripping of 400 kV Balipara – Ranganadi I on 18th May 2015. DR output from Balipara (PG) in respect of tripping of lines on 25-May-2015 was not received. Information from DR pertaining to 18th May 2015 tripping: From the DR of Main-I at Balipara pertaining to 18th May 2015 case, a maximum L-L voltage of 407 kV (RMS) can be observed while the extremism was at 575 kV. From the DR of Main-II at Balipara pertaining to 18th May 2015 incident, a maximum L-L voltage at around 407 kV (RMS) for duration of 287 milli-seconds could be observed and the maximum instantaneous extremism was 575 kV. From the DR of Main-I at Ranganadi pertaining to the 18th May 2015 incident, a maximum L-L voltage of around 417 kV (RMS) for duration of 888 milli-seconds could be observed and the maximum instantaneous extremism was 592 kV. Also, from the DR, Main-2 operated signal is high (Main-II DR was, however, not furnished to NERLDC). Information from DR pertaining to 25th May 2015 tripping: From the DR of Main-I at Ranganadi pertaining to the 25th May 2015 incident, a maximum L-L voltage of around 445 kV (RMS) for a prolonged duration could be observed and the maximum instantaneous extremism was 630 kV. However, from the DR there is no operation of Circuit Breaker / Line opening that could be observed. DR files before or after the incident would be required, and from both ends of the line for proper analysis. It is not clear when CB opening took place. Any other item: Date and Venue of next PCC It is proposed to hold the 35th PCC meeting of NERPC on second week of July, 2015. The exact venue will be intimated in due course. ******* 16 Annexure – A.6 Format for intimating the failure of Transmission line Towers 1. Name of Transmission line with voltage level: 2. Length of line (km): 3. Type of configuration: [(S/C, D/C, S/C strung on D/C towers, narrow base etc.)] 4. Number of Towers and Type of Towers failed: [suspension/ tension/ dead end/ special tower/ river crossing tower/ Powerline crossing/ Railway crossing etc., with/ without extension (indicate the type & length of extension)] 5. Tower location no. with reference to nearest substation (indicate name): 6. Name and size of conductor: 7. No. of sub-conductors per bundle and bundle spacing: 8. Number and size of Ground wire/ OPGW (if provided): 9. Type of insulators in use (Porcelain/ Glass/ Polymer): 10. Configuration of insulators (I/ V/ Y/ tension): 11. No. of insulators per string and No. of strings per phase: 12. Year of construction/ commissioning: 13. Executing Agency: 14. Weather condition on the date of failure: 15. Terrain Category 16. Wind Zone (1/2/3/4/5/6) and velocity of wind: 17. Details of earthing of tower (pipe type/ Counter poise): 18. Line designed as per IS: 802 (1977/1995/ any other code): 19. The agency who designed the line: 20. Any special consideration in design: 21. Date and time of occurrence/ discovery of failure: 22. Power flow in the line prior to failure: 23. Any missing member found before/ after failure of towers: 24. Condition of foundation after failure: 25. Brief description of failure: [alongwith photographs( if available), other related information like tower schedule, newspaper clipping for cyclone/ wind storm etc.] 26. Probable cause of failure: 27. Details of previous failure of the line/ tower: 28. Whether line will be restored on ERS or Space tower will be used: 29. Likely date of restoration: 30. Present Status: 31. Details of any Test carried out after failure: 32. Any other relevant information: Profoma for details of equipment failure (Information should be in detail and test reports should be furnished) 1. Name of Substation : 2. Utility/ Owner of substation : 3. Faulty Equipment : 4. Rating : 5. Make : 6. Sr. No. : 7. Year of manufacturing : 8. Year of commissioning : 9. Date and time of occurrence/ discovery of fault : 10. Fault discovered during (Operation/ maintenance) : 11. Present condition of equipment : 12. Details of previous maintenance : 13. Details of previous failure : 14. Sequence of events/ Description of fault : 15. Details of Tests done after failure : 16. Conclusion/ recommendation : Annexure – A.7 Rs. In Crore. Funding Sought by Entity Quantum of funding approved by Appraisal Committee (AC) Quantum of funding approved by Monitoring Committee (MC) DoP, AP DPR submitted to CEA/NLDCunder examination of CEA – now it will be taken up in next meeting of the techno-economic sub-group 33.45 - - Assam AEGCL Scheme already approved by Monitoring Committee – MoP sanctioned awaited 382.48 299.37 299.37 Manipur MSPCL DPR to be submitted - - - Me. PTCL Scheme already approved by Appraisal Committee & approval by Monitoring Committee is awaited 102.8 69.19 and recommended to MC - Me. PGCL DPR submitted to CEA/NLDCunder examination of CEA – now it will be taken up in next meeting of the techno-economic sub-group 48.16 - - Mizoram DoP, Mizoram Revised DPR submitted to CEA/NLDC- under examination of CEA – now it will be taken up in next meeting of the technoeconomic sub-group 31.38 - - Nagaland DoP, Nagaland Scheme already approved by Monitoring Committee – MoP sanctioned awaited 39.96 39.96 39.96 TSECL Revised DPR submitted to CEA/NLDC- under examination of CEA – now it will be taken up in next meeting of the technoeconomic sub-group - State Name of Entity Status Ar. Pradesh Meghalaya Tripura Annexure I 132 kV Transmission Line Protection Details Protection Details Sl. No. Name of Line Main I Charged End specified Protection Voltage for exists (Type in kV Protection of Relay and Make) (Yes/No) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) 1. Owner of Line : POWERGRID Note :1) Main-I Protection indicates Distance Protection 2) Type of Relay indicates it's operational mechanism - Numerical / Static / Electro-mechanical 3) List of inbuilt features of Numerical Relays are also to be furnished alongwith this format Fault Locator exists (Yes / No) Annexure I 220 kV Transmission Line Protection Details Protection Details Sl. No. Name of Line Data Recording System Details Directional Auto Main II Instantaneous Event End Main I Two stage Reclosing Carrier Power Charged Definite Number of Number of Logger / specified Protection Protection Over(Single aided Swing Pole Disturbance Fault Voltage exists Minimum Core used Core used Sequential for exists (Type Voltage Phase / InterBlocking Discrepancy Recorder Locator in kV (Type of Time(IDMT) for CT & for CT & Event Protection of Relay Protection Three tripping Feature Relay exists exists exists Relay and type Earth VT, used VT, used for Recorder and Make) exists Phase) exists exists (Yes/No) (Yes/No) (Yes/No) Make) Fault Relay for Main I Main II exists (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) 1. Owner of Line : Note :1) Main-I Protection indicates Distance Protection 2) Main-II Protection indicates one of Distance Protection / Directional Comparison Protection / Phase Segregated Line Differential protection 3) Type of Relay indicates it's operational mechanism - Numerical / Static / Electro-mechanical 4) List of inbuilt features of Numerical Relays are also to be furnished alongwith Annexure I 400 kV Transmission Line Protection Details Protection Details Sl. No. Name of Line Directional Auto Main II Main I Instantaneous Two stage Reclosing End Protection Carrier Charged Protection Definite Over(Single specified exists aided InterVoltage exists (Type Minimum Voltage Phase / for (Type of tripping in kV Three Protection of Relay and Relay and Time(IDMT) Protection exists Make) type Earth exists Phase) Make) (Yes/No) (Yes/No) Fault Relay (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) Data Recording System Details Power Number Swing Pole of Core Blocking Discrepancy used for Feature Relay exists CT & VT, exists (Yes / No) used for (Yes/No) Main I 1. Owner of Line : POWERGRID Note :1) Main-I Protection indicates Distance Protection 2) Main-II Protection indicates one of Distance Protection / Directional Comparison Protection / Phase Segregated Line Differential protection 3) Type of Relay indicates it's operational mechanism - Numerical / Static / Electro-mechanical 4) List of inbuilt features of Numerical Relays are also to be furnished alongwith Event Number of Logger / Core used Disturbance Fault Sequential for CT & Recorder Locator Event VT, used exists exists Recorder for Main (Yes/No) (Yes/No) exists II (Yes/No) Annexure I Transformer Protection Details Sl. No. Name of Transformer Directional MOG Over Tertiary Differential REF Over Impedance Buchholz WTI OTI with low OSR for Overload Fluxing PRD Winding LV side/ Protection Protection Current Protection Operation Protection Protection oil level OLTC SA exists Alarm Protection exists Protection HV side exits exists Protection exists exits exists exists alarm exists (Yes/No) exists exits (Yes/No) exists (Yes/No) (Yes/No) exits (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) 1. Owner of Transformer : 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side Note : 1. REF : Restricted Earth Fault, 2. WTI : Winding Temperature Indicator., 3. OTI : Oil Temperature Indicator) 4. MOG : Magnetic Oil Gauge, 5. OSR : Oil Surge Relay, 6. OLTC : On Load Tap Changer 7. PRD : Pressure Relieve Device, 8. SA : Surge Arrestor 9. List of inbuilt features of Numerical Relays are also to be furnished Annexure I Reactor Protection Details Sl. No. Name of Line Reactor/ Bus Reactor/ Tertiary Reactor Differential Protection exists (Yes/No) REF Definite Time Earth Fault Buchholz WTI OTI MOG with Protection Over Current Protection Operation Protection Protection low oil level SA exists exists Protection exists exists exists exists exists alarm exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) 1. Owner of Reactor : Note : 1. REF : Restricted Earth Fault, 2. WTI : Winding Temperature Indicator., 3. OTI : Oil Temperature Indicator) 4. MOG : Magnetic Oil Gauge, 5. SA : Surge Arrestor 6. List of inbuilt features of Numerical Relays are also to be furnished alongwith this format Annexure I Bus Bar & Local Breaker Backup(LBB) Protection Details Sl.No. Name of Bus Bar Bus Bar Protection LBB Protection exists exists (Yes/No) (Yes/No) 1. Owner of Bus Bar/LBB Note : 1. List of inbuilt features of Numerical Relays are also to be furnished alongwith this Annexure -A.9 (I) Bus Coupler Protection Details Sl.No. Name of Bus Coupler Non directional O/C Non directional E/F Protection exists Protection exists (Yes/No) (Yes/No) 1. Owner of Bus Coupler Note : 1. List of inbuilt features of Numerical Relays are also to be furnished alongwith this 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV End specified for Protection Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) 1. Owner of Line/End: Assam, AEGCL Balipara 1 Balipara-Depota 132 Depota Balipara 2 Balipara-Ghoramari 132 Ghoramari Depota 3 Depota-Ghoramari 132 Ghoramari Balipara 4 Balipara- Gohpur 132 Gohpur Barnagar 5 Barnagar-Dhaligaon 132 Dhaligaon Barnagar 6 Barnagar-Rangia 132 Rangia B.Chariali 7 B.Chariali-Depota 132 Depota B.Chariali 8 B.Chariali-Gohpur 132 Gohpur Yes (7SA SIEMENS) Yes (7SA SIEMENS) Yes (7SA SIEMENS) Yes (7SA61 SIEMENS) Yes (7SA52 SIEMENS) Yes (7SA61 SIEMENS) Yes (7SA SIEMENS) Yes (REL670 ABB) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(SEL321) Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV 1. Owner of Line/End: Assam, AEGCL 9 Depota-Rowta I End specified for Protection Depota 132 Rowta I Depota 10 Depota-Rowta II 132 Rowta II Dhaligaon 11 Dhaligaon-APM 132 APM 12 Dhaligaon-BRPL 132 Dhaligaon BRPL Dhaligaon 13 Dhaligaon-Gosaigaon 132 Gossaigaon Dhaligaon 14 Dhaligaon-Nailbari 132 Nalbari 15 16 17 BTPS (Salakati) BTPS (Salakati)Dhaligaon I 132 BTPS (Salakati)Dhaligaon II 132 Dhaligaon-Salakati I 132 Dhaligaon I BTPS (Salakati) Dhaligaon II Dhaligaon Salakati I Main I Protection exists (Type of Relay and Make) (Yes/No) Yes (7SA52 SIEMENS) Yes (7SA52 SIEMENS) Yes (7SA52 SIEMENS) Yes (7SA52 SIEMENS) Yes (7SA52 SIEMENS) Yes (7SA52 SIEMENS) Yes (7SA52 SIEMENS) NoT KNoWN Yes (7SA52 SIEMENS) Yes (7SA61 SIEMENS) Yes (7SA61 SIEMENS) Yes (REL 670 ABB) Yes (7SA52 SIEMENS) Yes (7SA52 SIEMENS) Yes (7SA52 SIEMENS) Yes (7SA52 SIEMENS) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV 1. Owner of Line/End: Assam, AEGCL 18 Dhaligaon-Salakati II 132 19 Dibrugarh-Moran 132 End specified for Protection Dibrugarh-Behiating 132 Behiating Moran 21 Moran-Behiating 132 Behiating Dibrugarh 22 Dibrugarh-Tinsukia 132 Tinsukia Garmur 23 Garmur-Bokakhat 132 Bokakhat 24 Gohpur-North Lakhimpur I 132 25 Gohpur-North Lakhimpur II 132 26 Dimapur (PG) - Bokajan 132 Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) Dhaligaon Salakati II Dibrugarh Moran Dibrugarh 20 Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details Yes (7SA52 SIEMENS) Yes (7SA61 SIEMENS) Yes (GRZ-100 TOSHIBA) Yes (7SA61 SIEMENS) Yes (7SA52 SIEMENS) Yes (7SA52 SIEMENS) Yes (7SA61 SIEMENS) Yes (GRZ-100 TOSHIBA) Yes (7SA52 SIEMENS) North Lakhimpur I Yes (D60 GE) Gohpur Yes (D60 GE) North Lakhimpur II Yes (D60 GE) Gohpur Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) Yes (IDMTL) Yes (IDMTL) No No No No No No Yes Yes Yes Yes Yes Yes 1 1 1 Yes Yes Yes Yes Yes Yes Yes Yes Yes Dimapur (PG) PGCIL Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Bokajan Yes (P442 MICOM) Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV End specified for Protection 1. Owner of Line/End: Assam, AEGCL 27 28 Golaghat-Mariani Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Mariani Yes (7SA52 SIEMENS) Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes 132 Golaghat Yes (GRZ-100 TOSHIBA) Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes 132 Bokajan Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) Yes (IDMTL) No No No No Yes Yes Yes Yes 1 1 Yes Yes Yes Yes Yes Yes Yes(D60 GE) Yes (7SA SIEMENS) Yes (7SA SIEMENS) NoT KNoWN Yes (7SA SIEMENS) Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes(D60 GE) Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes 132 132 Gauripur 30 Haflong - Lower Haflong 132 31 Kahilipara-Chandrapur 132 32 CTPS - Jagiroad (Bagjhap) 132 33 Jagiroad (Bagjhap) HPC, Jagiroad 132 Nazira - Jorhat 132 Haflong Lower Haflong Kahilipara Chandrapur CTPS Jagiroad (Bagjhap) Jagiroad (Bagjhap) HPC, Jagiroad Nazira 34 Jorhat Kahilipara 35 Kahilipara-Narengi Fault Locator exists (Yes / No) Yes (GRZ-100 TOSHIBA) Golaghat-Bokajan Gossaingaon-Gauripur Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Golaghat Gossaigaon 29 Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details 132 Narengi Yes (7SA52 SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(REL670 ABB) 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV 1. Owner of Line/End: Assam, AEGCL 36 Kahilipara-Rangia End specified for Protection Kahilipara 132 Rangia Kahilipara 37 Kahilipara-Sarusajai I 132 Sarusajai I Kahilipara 38 Kahilipara-Sarusajai II 132 Sarusajai II Kahilipara 39 Kahilipara-Sarusajai III 132 Sarusajai III Kahilipara 40 Kahilipara-Sarusajai IV 132 Sarusajai IV Kahilipara 41 Kahilipara-Sisugram 132 Sisugram 42 Dullavcherra Dharmanagar 132 Lakwa-Mariani 132 Dullavcherra Dharmanagar Lakwa 43 Mariani Main I Protection exists (Type of Relay and Make) (Yes/No) Yes (7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(RAZOA ABB) Yes (7SA SIEMENS) NoT KNoWN Yes(7SA SIEMENS) Yes(7SA SIEMENS) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV 1. Owner of Line/End: Assam, AEGCL 44 Lakwa-Moran End specified for Protection Lakwa 132 Moran 45 46 Srikona Srikona Panchgram(Old) 132 Panchgram Panchgram(Old) 132 NTPS - LTPS (Maidela) 132 Panchgram(Old) Panchgram Panchgram(Old) NTPS 47 LTPS (Maidela) NTPS 48 NTPS - Sonari 132 Sonari Sonari 49 Sonari- LTPS (Maidela) 132 LTPS (Maidela) Lakwa 50 Lakwa-Namrup I 132 Namrup I Lakwa 51 Lakwa-Namrup II 132 Namrup II Main I Protection exists (Type of Relay and Make) (Yes/No) Yes(7SA SIEMENS) Yes(GRZ-100 TOSHIBA) Yes(REL670 ABB) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV 1. Owner of Line/End: Assam, AEGCL 52 Lakwa-Nazira End specified for Protection Lakwa 132 Nazira Mariani 53 Mariani-Garmur I 132 Garmur I Mariani 54 Mariani-Garmur II 132 Garmur II Nalbari 55 Nalbari-Rangia 132 Rangia Namrup 56 Namrup-Tinsukia 132 Tinsukia Nazira 57 Nazira-Betbari 132 Betbari 58 North Lakhimpur North LakhimpurDhemaji 132 North Lakhimpur- Majuli 132 Dhemaji North Lakhimpur 59 Majuli Main I Protection exists (Type of Relay and Make) (Yes/No) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(REL670 ABB) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(GRZ-100 TOSHIBA) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV 1. Owner of Line/End: Assam, AEGCL 60 Narengi- Chandrapur 132 61 62 Pailapool-Srikona Panchgram-Dullavchera 132 132 63 Panchgram-HPL 132 64 Panchgram-Srikona 132 65 66 Rangia (Chirakhundi) Nalbari (Sariahatali) 132 Rangia-Rowta 132 End specified for Protection Main I Protection exists (Type of Relay and Make) (Yes/No) Yes(REL670 ABB) Chandrapur Yes(D60 GE) Yes(7SA Pailapool SIEMENS) Yes(REL670 Srikona ABB) Yes(7SA Panchgram SIEMENS) Yes(7SA Dullavcherra SIEMENS) Yes(7SA Panchgram SIEMENS) HPL NoT KNoWN Yes(7SA Panchgram SIEMENS) Yes(REL670 Srikona ABB) Rangia Yes(7SA (Chirakhundi) SIEMENS) Yes(REL670 Nalbari (Sariahatali) ABB) Yes(7SA Rangia SIEMENS) Yes(7SA Rowta SIEMENS) Narengi Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV 1. Owner of Line/End: Assam, AEGCL 67 Rangia-Sipajhar End specified for Protection Rangia 132 Sipajhar Rangia 68 Rangia-Sisugram 132 Sisugram Samaguri 69 Samaguri- B.Chariali 132 B.Chariali Samaguri 70 Samaguri- Khalaigaon 132 Khalaigaon Samaguri 71 Samaguri-S.Dev Nagar I 132 S.Dev Nagar I Diphu 72 Diphu-S.DevNagar 132 S.Dev Nagar Sipajahar 73 Sipajhar-Rowta 132 Rowta Tinsukia 74 Tinsukia-Margherita I 132 Margherita I Main I Protection exists (Type of Relay and Make) (Yes/No) Yes(7SA SIEMENS) Yes(REL670 ABB) Yes(7SA SIEMENS) Yes(RAZOA ABB) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(P442 MICOM) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(GRZ-100 TOSHIBA) Yes(P442 MICOM) Yes(REL670 ABB) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV 1. Owner of Line/End: Assam, AEGCL 75 Tinsukia-Margherita II End specified for Protection Tinsukia 132 Margherita II 76 Nalkata-Gohpur I 132 77 Nalkata-Gohpur II 132 Dispur-KHP 132 KHP 79 Dispur-Chandrapur 132 80 Bokajan-Dimapur 132 81 Chandrapur-Bagjap 132 82 LTPS (Maidela) - Nazira I 132 LTPS (Maidela) - Nazira II 132 83 84 85 Dispur Chandrapur Bokajan Dimapur Chandrapur Bagjap LTPS (Maidela) Nazira I LTPS (Maidela) Nazira II Sankardev Nagar (Lanka) - Diphu 132 Sankardev Nagar (Lanka) - TELCOM 132 Yes(7SA SIEMENS) Yes(7SA SIEMENS) Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Nalkata Gohpur I Nalkata Gohpur II Dispur 78 Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details Sankardev Nagar (Lanka) Yes(P442 MICOM) Yes(7SA SIEMENS) Yes(P442 MICOM) Yes(D60 GE) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes(P442 MICOM) Diphu Yes(GRZ-100 TOSHIBA) Sankardev Nagar (Lanka) TELCOM Yes(P442 MICOM) Not KNown 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV End specified for Protection Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) 1. Owner of Line/End: MSPCL Assam, AEGCL 2. (Manipur) 1 2 3 4 5 6 7 8 Ningthoukhong Churanchandpur I 132 Ningthoukhong Churanchandpur II 132 Rengpang - Jiribam 132 Imphal(Manipur) Karong Imphal(Manipur) Yaingangpokpi Yaingangpokpi - Kongba Kongba - Kakching Kakching Churanchandpur 132 132 132 132 132 Ningthoukhong Yes Yes Yes No No Yes 4&3 No No No Churanchandpur Yes Yes Yes No No Yes 4&3 No No No Ningthoukhong Yes Yes Yes No No Yes 4&3 No No No Churanchandpur Yes Yes Yes No No Yes 4&3 No No No Rengpang Yes Yes Yes No No Yes 4&3 No No No Jiribam(Manipur) Yes Yes Yes No No Yes 4&3 No No No Imphal(Manipur) Yes Yes Yes No No Yes 4&3 No No No Karong Yes Yes Yes No No Yes 4&3 No No No Imphal(Manipur) Yes Yes Yes No No Yes 4&3 No No No Yaingangpokpi Yes Yes Yes No No Yes 4&3 No No No Yaingangpokpi Yes Yes Yes No No Yes 4&3 No No No Kongba Yes Yes Yes No No Yes 4&3 No No No Kongba Yes Yes Yes No No Yes 4&3 No No No Kakching Yes Yes Yes No No Yes 4&3 No No No Kakching Yes Yes Yes No No Yes 4&3 No No No Churanchandpur Yes Yes Yes No No Yes 4&3 No No No 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV End specified for Protection Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) 1. Owner of Line/End: Meghalaya, Assam, AEGCL 3. MePTCL 1 Umiam St IV (Nongkhyllem) - Umtru I Umiam St IV (Nongkhyllem) 132 Umtru Umiam St IV (Nongkhyllem) 2 Umiam St IV (Nongkhyllem) - Umtru II Umiam St III (Kyrdemkulai) - Umtru I Umiam St III (Kyrdemkulai) 132 Umtru 4 Umiam St III (Kyrdemkulai) - Umtru II Umiam St III (Kyrdemkulai) 132 Umtru 5 Umiam St III (Kyrdemkulai) - Umiam St I (Sumer) I Yes, Yes, REL670 REL670 & & P127 Relay P127 Relay Yes, REL670 Relay No Yes, REL670 Relay Yes, REL670 Relay No 1 No Yes, P442 Relay Yes, P442 Relay No 1 Yes, ABB Yes, Directional make REL670, P127, Areva make Numerical No Yes, REL670 Relay Yes, REL670 Relay No 1 Yes, Yes, REL670 REL670 & & P127 Relay P127 Relay Yes, Toshiba make GRZ100, Numerical No Yes, GRZ100 Relay Yes, GRZ100 Relay No 1 Yes, GRZ100 Relay No Yes, REL670 Relay Yes, REL670 Relay No 1 Yes, Yes, REL670 REL670 & & P127 Relay P127 Relay Yes, Directional JNP096, JVS make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, Toshiba Yes, Directional make GRZ100, P127, Areva make Numerical No Yes, GRZ100 Relay Yes, GRZ100 Relay No 1 Yes, Directional JNP096, JVS make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, ABB Yes, Directional make REL670, P127, Areva make Numerical No Yes, REL670 Relay Yes, REL670 Relay No 1 Yes, Yes, REL670 REL670 & & P127 Relay P127 Relay No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P141Relay P141Relay Relay Yes, Areva make P442, Numerical Yes, Directional CDD, EE make Yes, P442 Relay Yes, P442 Relay Yes, P442 Relay Yes, REL670 Relay 132 Umtru 3 Yes, ABB Yes, Directional make REL670, P127, Areva make Numerical Umiam St III (Kyrdemkulai) 132 Umiam St I (Sumer) Yes, Directional CDD, EE make Yes, ABB Yes, Directional make REL670, P127, Areva make Numerical Yes, Areva make P442, Numerical Yes, Areva make P442, Numerical Yes, Areva make P442, Numerical Yes, Directional P141, Areva make Yes, P442 Relay Yes, GRZ100 Relay Yes, P442 Relay Yes, Yes, GRZ100 GRZ100 & & P127 Relay P127 Relay Yes, P442 Relay Yes, P442 Relay Yes, GRZ100 Relay Yes, REL670 Relay Yes, P442 Relay Yes, GRZ100 Relay Yes, P442 Relay Yes, REL670 Relay 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV End specified for Protection 1. Owner of Line/End: Assam, AEGCL 6 Umiam St III (Kyrdemkulai) - Umiam St I (Sumer) II Umiam St III (Kyrdemkulai) 132 8 EPIP II - Umtru I EPIP II - Umtru II 132 EPIP II - EPIP I (I) 132 10 EPIP II - EPIP I (II) 132 11 12 Khliehriat - Myntdu Leshka I Khliehriat - Myntdu Leshka II Yes, ABB Yes, Directional make REL670, P127, Areva make Numerical Fault Locator exists (Yes / No) No Yes, REL670 Relay Yes, REL670 Relay No 1 Yes, Yes, REL670 REL670 & & P127 Relay P127 Relay Yes, REL670 Relay No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P141Relay P141Relay Relay No No No No 0 No No No No No No No 0 No No No No No No No 0 No No No EPIP II Umtru No EPIP II No Umtru No Yes, Directional JNP060, JVS make No No No No 0 No No No EPIP II EPIP I EPIP II EPIP I No No No No No No No No No No No No No No No No No No No No No No No No 0 0 0 0 No No No No No No No No Khliehriat Yes, ABB make REL670, Numerical Yes, Directional REX521,ABB make No Yes, REL670 Relay Yes, REL670 Relay No 1 Yes, REL670 & REX521 Relay Myntdu Leshka Yes, ABB make REL670, Numerical Yes, Directional REX521,ABB make No Yes, REL670 Relay Yes, REL670 Relay No 1 Yes, REL670 & REX521 Relay Khliehriat Yes, ABB make REL670, Numerical Yes, Directional REX521,ABB make No Yes Yes No 1 Yes, REL670 & REX521 Relay Myntdu Leshka Yes, ABB make REL670, Numerical Yes, Directional REX521,ABB make No Yes, REL670 Relay Yes, REL670 Relay No 1 Yes, REL670 & REX521 Relay No No No No Yes, REL670 & REX521 Relay Yes, REL670 & REX521 Relay Yes, REL670 & REX521 Relay Yes, REL670 & REX521 Relay 132 9 Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Yes, Areva make P442, Numerical No Umiam St I (Sumer) 7 Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details Yes, Directional P141, Areva make No Yes, Directional IDMTL, ER make Yes, Directional CDD, ER make 132 132 Yes, REL670 Relay Yes, REL670 Relay Yes Yes, REL670 Relay 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV End specified for Protection 1. Owner of Line/End: Assam, AEGCL 13 14 Killing - EPIP II (I) Killing - EPIP II (II) Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) Killing Yes, ABB make REL670, Numerical Yes, Areva make P442, Numerical No Yes, REL670, P442 Relay Yes, REL670, P442 Relay No 1 Yes, REL670, P442 Relay EPIP II Yes, Areva make P442, Numerical Yes, Directional P127, Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P127 Relay P127 Relay Relay Killing Yes, ABB make REL670, Numerical Yes, Areva make P442, Numerical No Yes, REL670, P442 Relay Yes, REL670, P442 Relay No 1 Yes, REL670, P442 Relay EPIP II Yes, Areva make P442, Numerical Yes, Directional P127, Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P127 Relay P127 Relay Relay Yes, Alstom make P442, Numerical Yes, Directional P141, Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P141Relay P141Relay Relay Yes, Directional P141, Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P141Relay P141Relay Relay Yes, Directional P127 Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P127 Relay P127 Relay Relay Yes, Directional P141, Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P141Relay P141Relay Relay 132 132 Yes, Yes, REL670, REL670, P442 Relay P442 Relay Yes, Yes, REL670, REL670, P442 Relay P442 Relay Umiam St I (Sumer 15 Umiam St I (Sumer) Mawngap I 16 Umiam St I (Sumer) Mawngap II 132 Mawngap Umiam St I (Sumer 132 Mawngap Mawlai 17 Mawlai - Mawngap I 132 Mawngap Yes, Alstom make P442, Numerical Yes, Areva make P442, Numerical Yes, Alstom make P442, Numerical 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV 1. Owner of Line/End: Assam, AEGCL 18 Nongstoin - Mawngap 132 End specified for Protection Nongstoin Mawngap Nongstoin 19 Nongstoin - Nangalbibra 132 Nangalbibra Khliehriat 20 Khliehriat - NEHU 132 NEHU 21 22 Khliehriat NEIGRIHMS NEIGRIHMS - NEHU 23 No Yes, Alstom make P442, Numerical Yes, Areva make P442, Numerical Yes, Areva make P442, Numerical Yes, Areva make P442, Numerical Yes, Areva make P442, Numerical Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) No No No 0 No No No Yes, Directional P141, Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P141Relay P141Relay Relay Yes, Directional P127, Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P127 Relay P127 Relay Relay Yes, Directional P127, Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P127 Relay P127 Relay Relay Yes, Directional CDD, EE make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, Directional P127 Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P127 Relay P127 Relay Relay Yes, P442 Relay Yes, P442 Relay Yes, P442 Relay Khliehriat Yes, ABB make REL670, Numerical Yes, Directional CDD, EE make No Yes, REL670 Relay Yes, REL670 Relay No 1 Yes, REL670 Relay Yes, REL670 Relay Yes, REL670 Relay NEIGRIHMS Yes, Areva make P442, Numerical Yes, Directional CDD, EE make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 Relay Yes, P442 Relay Yes, P442 Relay NEIGRIHMS No No No No No 0 No No No No No No No 1 Yes, P127 Relay Yes, P127 Relay No Yes, Directional P127, Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, Directional P127, Areva make No No No No 0 132 132 NEHU Nangalbibra - Rongkhon (Tura) Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details Nangalbibra 132 Rongkhon (Tura) Yes, EE make RR3V, EM Yes, Areva make P442, Numerical No Yes, Directional CDD, EE make Yes, Directional P127 Areva make Yes, P442 & Yes, P442 & Yes, P442 P127 Relay P127 Relay Relay Yes, P127 Relay Yes, P127 Relay No 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV 1. Owner of Line/End: Assam, AEGCL 24 25 Lumshnong - Khliehriat Sohra (Cherrapunjee) Mawlai End specified for Protection Umiam St I (Sumer) Umiam Yes, Directional IDMTL, ER make No No No No 0 No No No Khliehriat Yes, Areva make P442, Numerical Yes, Directional CDD, EE make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 Relay Yes, P442 Relay Yes, P442 Relay Yes, Directional P127 Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P127 Relay P127 Relay Relay Yes, Directional P141, Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P141Relay P141Relay Relay Yes, Toshiba Yes, Directional make GRZ100, JNP066, JVS make numerical No Yes, GRZ100 Relay Yes, GRZ100 Relay No 1 Yes, Directional JNP066, JVS make No No No No 0 No No No Yes, Directional P127 Areva make No No No No 1 Yes, P127 Relay Yes, P127 Relay No Yes, Directional P141, Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P141Relay P141Relay Relay Yes, Directional P127 Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P127 Relay P127 Relay Relay Umiam St III (Kyrdemkulai) Yes, ABB Yes, Directional make REL670, P127, Areva make Numerical No Yes, REL670 Relay Yes, REL670 Relay No 1 Yes, Yes, REL670 REL670 & & P127 Relay P127 Relay Yes, REL670 Relay Umiam St IV (Nongkhyllem) Yes, ABB Yes, Directional make REL670, P127, Areva make Numerical No Yes, REL670 Relay Yes, REL670 Relay No 1 Yes, Yes, REL670 REL670 & & P127 Relay P127 Relay Yes, REL670 Relay 132 Sohra (Cherrapunjee) 132 Mawlai 132 Umiam Umiam - NEHU 29 Umiam St I (Sumer) Mawlai Umiam St III (Kyrdemkulai) - Umiam St IV - I (Nongkhyllem) Yes, Areva make P442, Numerical Yes, Areva make P442, Numerical No 132 Yes, EE make RR3V, EM Yes, Areva Umiam St I (Sumer) make P442, Numerical Yes, Areva Mawlai make P442, Numerical NEHU 28 Fault Locator exists (Yes / No) No Umiam 27 Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Lumshnong Umiam St I (Sumer) 26 Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details 132 Yes, GRZ 100 Yes, GRZ Relay 100 Relay Yes, GRZ100 Relay 132 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV End specified for Protection 1. Owner of Line/End: Assam, AEGCL 30 Umiam St III (Kyrdemkulai) - Umiam St IV - II (Nongkhyllem) Mawlai - NEHU 33 Umiam St I (Sumer) Umiam St II (Umsumer) EPIP II - Trishul Fault Locator exists (Yes / No) Yes, Toshiba Yes, Directional make GRZ100, JNP053, JVS make Numerical No Yes, GRZ100 Relay Yes, GRZ100 Relay No 1 Yes, Yes, GRZ100 GRZ100 & & P127 Relay P127 Relay Yes, GRZ100 Relay Umiam St IV (Nongkhyllem) Yes, ABB Yes, Directional make REL670, P127, Areva make Numerical No Yes, REL670 Relay Yes, REL670 Relay No 1 Yes, Yes, REL670 REL670 & & P127 Relay P127 Relay Yes, REL670 Relay No No No No 0 No No No No 1 Yes, Directional P141, Areva make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 & Yes, P442 & Yes, P442 P141Relay P141Relay Relay 132 132 No Yes, EE make RR3V, EM Yes, Areva Umiam St I (Sumer) make P442, Numerical NEHU 32 Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Umiam St III (Kyrdemkulai) Mawlai 31 Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details 132 132 Yes, Directional P127 Areva make Yes, Directional P127 Areva make Yes, P127 Relay Yes, P127 Relay Yes, P127 Relay Yes, P127 Relay No No Umiam St II (Umsumer) No Digital GRD 130, No No No No 0 Yes, Digital GRD 130 Relay Yes, Digital GRD 130 Relay No EPIP II No Yes, Directional CDD, ER make No No No No 0 No No No No Yes, Directional CDD, ER make No No No No 0 No No No No Yes, Directional CDD, ER make No No No No 0 No No No No Yes, Directional CDD, ER make No No No No 0 No No No No Yes, Directional CDD, ER make No No No No 0 No No No No Yes, Directional CDD, ER make No No No No 0 No No No Trishul 34 EPIP II - Nalari 132 EPIP II Nalari 35 EPIP I - Shyam Century 132 EPIP I Shyam Century 36 EPIP I - Maithan 132 EPIP I Maithan 37 EPIP I - Sai Prakash 132 EPIP I Sai Prakash 38 39 EPIP I Greystone/Nezone 132 EPIP I - Megha Carbides 132 EPIP I Greystone/Nezone EPIP I 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV 39 EPIP I - Megha Carbides 132 1. Owner of Line/End: Assam, AEGCL 40 Lumshnong - CMCL 132 End specified for Protection Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) Megha Carbides Lumshnong No Yes, Directional CDD, ER make No No No No 0 No No No No Yes, Directional JNC069, JVS make No No No No 0 No No No No Yes, Directional JNC069, JVS make No No No No 0 No No No No Yes, Directional JNC069, JVS make No No No No 0 No No No No Yes, Directional JNC069, JVS make No No No No 0 No No No No No No No 0 No No No No No No No 0 Yes, P127 Relay Yes, P127 Relay No No Yes, P442 Relay Yes, P442 Relay No 1 CMCL 41 Lumshnong - MCL 132 Lumshnong MCL 42 Lumshnong - Adhunik Cement 132 Lumshnong Adhunik Cement 43 Lumshnong - Hill Cement 132 Lumshnong Hill Cement 44 Lumshnong - JUD Cement 45 Lumshnong - GVIL Cement 132 46 MPL (Meghalaya Power Limited) - Lumnsnong 132 47 Sohra (Cherrapunjee) Mawngap 132 Lumshnong JUD Cement Lumshnong GVIL Cement MPL (Meghalaya Power Limited) Lumshnong No Sohra (Cherrapunjee) No Mawngap Yes, Alstom make P442, Numerical 132 Yes, Directional P127 Areva make Yes, Directional P127, Areva make Yes, Directional P141, Areva make Yes, P442 & Yes, P442 & Yes, P442 P141Relay P141Relay Relay 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV End specified for Protection Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) 1. AEGCL 4. Owner of Line/End: Assam, P&E, Mizoram 1 Bairabi - Kolasib 132 2 Zuangtui (Zemabawk) Bukpui (Serchhip) 132 3 Bukpui (Serchhip) Khawiva (Lunglei) 132 4 Zuangtui (Zemabawk) Saitual 132 Saitual - Khawzawl 132 5 Bairabi Micom P430A Kolasib No Zuangtui No (Zemabawk) Bukpui (Serchhip) No Bukpui (Serchhip) No Khawiva (Lunglei) No Zuangtui No (Zemabawk) Saitual No Saitual No Khawzawl No Yes No No No No No No No No No No No No No No No No No No No No No No Yes (EM) No Yes (EM) Yes (EM) No 4 No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes, O/C & EF Yes, O/C & EF Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes 5. Owner of Line/End: NEEPCO 1 2 Khandong - Kopili -I Khandong - Kopili - II 132 132 Khandong Kopili Khandong Kopili Yes, REL 670 Yes, REL 670 6. Owner of Line/End: POWERGRID 1 Badarpur- Jiribam 132 Badarpur (PG) Jiribam (PG) Aizawl (PG) 2 Aizawl-Kumarghat 132 Kumarghat (PG) Badarpur (PG) 3 Badarpur - Khliehriat 132 Khliehriat (PG) 4 Badarpur-Kumarghat 132 Badarpur (PG) Kumarghat (PG) Yes, MICOM P442 Yes, 7SA513 Yes, MICOM P442 Yes, MICOM P442 Yes, MICOM P442 Yes, MICOM P442 Yes, MICOM P442 Yes, 7SA513 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV 1. Owner of Line/End: Assam, AEGCL 5 Dimapur - Imphal 132 End specified for Protection Dimapur (PG) Imphal (PG) Jiribam (PG) 6 Jiribam - Aizawl 132 Aizawl (PG) Jiribam (PG) 7 Jiribam-Haflong 132 Haflong (PG) Silchar (PG) 8 Silchar- Badarpur-1 132 Badarpur (PG) Silchar (PG) 9 Silchar- Badarpur-2 132 Badarpur (PG) 10 Silchar- Imphal-1 132 Silchar (PG) Main I Protection exists (Type of Relay and Make) (Yes/No) Yes, MICOM P442 Yes, 7SA513 Yes, MICOM P442 Yes, MICOM P442 Yes, MICOM P442 Yes, MICOM P442 Yes, MICOM P442 Yes, MICOM P442 Yes, MICOM P442 Yes, MICOM P442 Yes, MICOM P442 Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, MICOM P442 Yes, O/C & EF Yes Yes Yes Yes Yes Yes, MICOM P442 Yes, O/C & EF Yes Yes Yes Yes Yes Yes, MICOM P442 Yes, O/C & EF Yes Yes Yes Yes Yes Imphal (PG) 11 Silchar- Imphal-2 132 Silchar (PG) Imphal (PG) 12 Silchar- Melriat-1 132 Silchar (PG) Melriat (PG) 13 Silchar- Melriat-2 132 Silchar (PG) Melriat (PG) Fault Locator exists (Yes / No) 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV End specified for Protection Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) 1. Owner of Line/End Line/End::Assam, 7. TSECLAEGCL 1 2 3 4 5 6 7 8 9 10 11 12 Grid-Rokhia-I Grid-Rokhia-II Grid-Dhalabil Dhalabil-Garodtilla Garodtilla-PKBari Garodtilla-Ambassa Grid-Bodhjungnagar Bodhjungnagar-Jirania Jirania-Baramura Baramura-Gamaitilla Gamaitilla-Ambassa Ambassa-PKBari 132 132 132 132 132 132 132 132 132 132 132 132 Grid No Yes No No No No No No No No Rokhia No Yes No No No No No No No No Grid No No No No No No No No No No Rokhia No No No No No No No No No No Grid No No No No No No No No No No Dhalabil No No No No No No No No No No Dhalabil No No No No No No No No No No Garodtilla No No No No No No No No No No Garodtilla No No No No No No No No No No PKBari No No No No No No No No No No Garodtilla No No No No No No No No No No Ambassa No No No No No No No No No No Grid No No No No No No No No No No Bodhjungnagar Yes Yes No No Yes No 3 & 2-Core No No No Bodhjungnagar Yes Yes No No Yes No 3 & 2-Core No No No Jirania Yes Yes No No Yes No 3 & 2-Core No No No Jirania Yes Yes No No Yes No 3 & 2-Core No No No Baramura No No No No No No No No No No Baramura No No No No No No No No No No Gamaitilla Yes Yes No No Yes No 3 & 2-Core No No No Gamaitilla No No No No No No No No No No Ambassa No No No No No No No No No No Ambassa No No No No No No No No No No PKBari No No No No No No No No No No 132 kV Transmission Line Protection Details Annexure-A.8 (II) Protection Details Sl. No. Name of Line Charged Voltage in kV 1. Owner of Line/End: Assam, AEGCL 13 Bodhjungnagar-SMNagar 132 14 15 16 SMNagar-Grid PKBari-Gournagar PKBari-Missiontilla 132 132 132 End specified for Protection Main I Protection exists (Type of Relay and Make) (Yes/No) Data Recording System Details Directional Auto Event Instantaneous Reclosing Number of Logger / Carrier aided Power Swing Pole Disturbance Definite Minimum (Single Core used Sequential Inter-tripping Blocking Discrepancy Recorder Time(IDMT) Over- Phase / for CT & Event exists Feature exists Relay exists exists Current & Earth Three Phase) VT, used Recorder (Yes / No) (Yes / No) (Yes / No) (Yes / No) Fault Relay exists exists for Main I exists (Yes/No) (Yes / No) (Yes / No) Fault Locator exists (Yes / No) Bodhjungnagar Yes Yes No No Yes No 3 & 2-Core No No No SMNagar Yes Yes No No Yes No 3 & 2-Core No No No SMNagar Yes Yes No No Yes No 3 & 2-Core No No No Grid No No No No No No No No No No PKBari No No No No No No No No No No Gournagar No No No No No No No No No No PKBari No No No No No No No No No No Missiontilla Yes Yes No No Yes No 3 & 2-Core No No No Note : 1) Main-I Protection indicates Distance Protection 2) Main-II Protection indicates one of Distance Protection / Directional Comparison Protection / Phase Segregated Line Differential protection 3) Type of Relay indicates it's operational mechanism - Numerical / Static / Electro-mechanical 4) List of inbuilt features of Numerical Relays are also to be furnished alongwith this format 132 kV Transmission Line Protection Details Annexure-II Protection Details Sl. No. Name of Line Data Recording System Details Directional Event Main I Auto Power Number Instantaneous Carrier Logger / Charged Protection Reclosing Swing Pole of Core Disturbance Fault Sequential Voltage End specified for Protection exists (Type Definite Minimum (Single Phase / aided Inter- Blocking Discrepancy used for Recorder Locator Time(IDMT) Overtripping Event in kV of Relay and Three Phase) Feature Relay exists CT & VT, exists exists Current & Earth exists Recorder Make) exists exists (Yes (Yes / No) used for (Yes / No) (Yes / No) Fault Relay exists (Yes / No) exists (Yes/No) (Yes / No) / No) Main I (Yes/No) (Yes / No) 1. Owner of End : Assam & Meghalaya Kahilipara 1 Kahilipara-Umtru I 132 Umtru Kahilipara 2 Kahilipara-Umtru II 132 Umtru Panchgram 3 Panchgram-Khliehriat 132 Khliehriat Panchgram 4 PanchgramLumshnong 132 Sarusajai-Umtru 132 Lumshnong Sarusajai 5 Umtru Sarusajai 6 Sarusajai-Umiam Stg IV 132 Agia - Nangalbibra 132 Umiam Stg IV Yes (7SA SIEMENS) Yes, Directional JNP096, JVS make Yes (7SA SIEMENS) Yes, Directional JNP096, JVS make Yes(7SA SIEMENS) NoT KNoWN Yes(7SA SIEMENS) Yes, Areva make P442, Numerical Yes(THR ER) Yes, Areva make P442, Numerical Yes(THR ER) Yes, Areva make P442, Numerical Yes (IDMTL) No No Yes Yes 1 Yes No Yes, GRZ100 Relay Yes, GRZ100 Relay No 1 Yes (IDMTL) No No Yes Yes No Yes, GRZ100 Relay Yes, GRZ100 Relay No 1 Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Non directional CDG, EE make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 Relay Yes (IDMTL) No No Yes Yes 1 Yes Yes, Directional CDD, EE make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 Relay Yes (IDMTL) No No Yes Yes 1 Yes Yes, Directional CDD, EE make No Yes, P442 Relay Yes, P442 Relay No 1 Yes, P442 Relay Yes, Directional P127, Areva make No No No No Yes, Yes, GRZ100 GRZ100 Relay Relay 1 Yes Yes, Yes, GRZ100 GRZ100 Relay Relay Yes Yes Yes, GRZ100 Relay Yes Yes Yes, GRZ100 Relay Yes, P442 Yes, P442 Relay Relay Yes Yes Yes, P442 Yes, P442 Relay Relay Yes Yes Yes, P442 Yes, P442 Relay Relay Agia 7 Nangalbibra No 0 Yes, P127 Relay Yes P127 Relay No 132 kV Transmission Line Protection Details Annexure-II Protection Details Sl. No. Name of Line Data Recording System Details Directional Event Main I Auto Power Number Instantaneous Carrier Logger / Charged Protection Reclosing Swing Pole of Core Disturbance Fault Sequential Voltage End specified for Protection exists (Type Definite Minimum (Single Phase / aided Inter- Blocking Discrepancy used for Recorder Locator Time(IDMT) Overtripping Event in kV of Relay and Three Phase) Feature Relay exists CT & VT, exists exists Current & Earth exists Recorder Make) exists exists (Yes (Yes / No) used for (Yes / No) (Yes / No) Fault Relay exists (Yes / No) exists (Yes/No) (Yes / No) / No) Main I (Yes/No) (Yes / No) 1. 2. Owner of End : Assam & Meghalaya POWERGRID Mokokchung (PG) 1 Mokokchung-Mariani 132 Mariani Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes (IDMTL) No No Yes Yes 1 Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes (IDMTL) No No Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, 7SA522 Yes, O/C & EF Yes Yes Yes Yes Yes Nirjuli (PG) Yes, MICOM Yes, O/C & EF Yes Yes Yes Yes Yes Haflong (PG)Haflong Haflong (PG) Yes, P442 Yes, P141 Yes Yes Yes Yes Yes Silchar (PG)Hailakandi I Silchar (PG) Yes, MICOM P442 Yes, O/C & EF Yes Yes Yes Yes Yes Yes, MICOM Yes, O/C & EF Yes Yes Yes Yes Yes Yes, MICOM P543 Yes, O/C & EF Yes Yes Yes Yes Yes Pailapool 2 Pailapool-Jiribam(PG) 132 Jiribam(PG) 3 Dimapur (PG) Bokajan Dimapur(PG) 132 Bokajan 4 Badarpur (PG) Badarpur Badarpur (PG) Badarpur 5 Not KNown Yes(7SA SIEMENS) Yes(7SA SIEMENS) Yes, MICOM P442 Yes, MICOM P442 Yes(THR ER) Yes, MICOM P442 Yes, MICOM Balipara (PG)Gohpur Balipara (PG) Yes Yes 1 Gohpur Gohpur 6 7 8 Gohpur - Nirjuli Haflong Hailakandi 9 10 Silchar (PG)Hailakandi II Silchar (PG) Silchar (PG)- Srikona I Silchar (PG) Hailakandi Yes 132 kV Transmission Line Protection Details Annexure-II Protection Details Sl. No. Name of Line Directional Event Main I Auto Power Number Instantaneous Carrier Logger / Charged Protection Reclosing Swing Pole of Core Disturbance Fault Sequential Voltage End specified for Protection exists (Type Definite Minimum (Single Phase / aided Inter- Blocking Discrepancy used for Recorder Locator Time(IDMT) Overtripping Event in kV of Relay and Three Phase) Feature Relay exists CT & VT, exists exists Current & Earth exists Recorder Make) exists exists (Yes (Yes / No) used for (Yes / No) (Yes / No) Fault Relay exists (Yes / No) exists (Yes/No) (Yes / No) / No) Main I (Yes/No) (Yes / No) 1. Owner of End : Assam & Meghalaya 11 Data Recording System Details Silchar (PG)- Srikona II Srikona Silchar (PG) Yes, MICOM P543 Yes, O/C & EF Yes Yes Yes Yes Yes Srikona 3. Owner of End : Manipur & POWERGRID 1 Imphal(Manipur) Imphal(PG) I 132 2 Imphal(Manipur) Imphal(PG) II 132 3 Imphal(PG) Ningthoukhong 132 4 5 Jiribam (PG) - Jiribam (Manipur) Jiribam (PG) Rengpang Imphal (Manipur) Yes Yes Yes No Imphal(PG) Yes, O/C Yes, O/C & EF Yes Yes Imphal (Manipur) Yes Yes, P543 (Differencial) Yes Yes No Yes, O/C & EF Yes Yes Yes Yes Yes No No Yes Jiribam (Manipur) Yes Yes Yes No No Yes Jiribam (PG) Yes, MICOM P442 Yes, O/C & EF Yes Yes Yes, Numerical MICOM P442 Yes, (EM relay in addition to Numerical Relay) Feature exists in SF6 breaker & Numerical Relay No Yes Yes Rengpang Yes Yes Yes No No Loktak Yes, Numerical MICOM P442 Yes, (EM relay in addition to Numerical Relay) Feature exists in SF6 breaker & Numerical Relay No Ningthoukhong Yes Yes Yes No Imphal(PG) 132 Yes 4&3 No No Yes Yes No No Yes Yes 4&3 No No No 4&3 No No No Yes Yes 1 core each Yes Yes Yes Yes 4&3 No No No Yes Yes 1 core each Yes Yes Yes No Yes 4&3 No No No Yes No Yes 4&3 Yes No No Imphal(PG) Ningthoukhong 132 No Jiribam (PG) Yes Rengpang 4. Owner of End : Manipur & NHPC 1 2 Loktak - Rengpang Loktak Ningthoukhong 132 132 Loktak 132 kV Transmission Line Protection Details Annexure-II Protection Details Sl. No. Name of Line Data Recording System Details Directional Event Main I Auto Power Number Instantaneous Carrier Logger / Charged Protection Reclosing Swing Pole of Core Disturbance Fault Sequential Voltage End specified for Protection exists (Type Definite Minimum (Single Phase / aided Inter- Blocking Discrepancy used for Recorder Locator Time(IDMT) Overtripping Event in kV of Relay and Three Phase) Feature Relay exists CT & VT, exists exists Current & Earth exists Recorder Make) exists exists (Yes (Yes / No) used for (Yes / No) (Yes / No) Fault Relay exists (Yes / No) exists (Yes/No) (Yes / No) / No) Main I (Yes/No) (Yes / No) 1. & Meghalaya 5. Owner of End : Assam MePTCL & POWERGRID 1 Khliehriat - Khliehriat (Meghalaya) I No Yes, P442 Relay Yes, O/C & EF Yes Yes No Yes, Directional P127 Areva make No No Badarpur (PG) Yes, MICOM P442 Yes, O/C & E/F Yes Yes Kolasib Yes, 7SA513 Yes, O/C & E/F Yes Kolasib Yes, 7SA513 Yes, O/C & E/F Aizwal (PG) Yes, 7SA513 Yes, O/C & E/F 132 Khliehriat (PG) 2 Khliehriat - Khliehriat (Meghalaya) II 132 Yes, Areva make P442, Numerical Yes, MICOM P442 Yes, Directional CDD, EE make Khliehriat (Meghalaya) Khliehriat (Meghalaya) Yes, P442 Relay No 1 Yes Yes, P442 Relay Yes, P442 Yes, P442 Relay Relay Yes Yes Yes, P127 Relay Yes, P127 Relay Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No 0 No Khliehriat (PG) 6. Owner of End: P&E, Mizoram & POWERGRID 1 2 Badarpur - Kolasib Kolasib - Aizwal 132 132 3 Aizwal - Luangmual 132 4 Zuangtui (Zemabawk) - Aizwal I 132 5 Zuangtui (Zemabawk) - Aizwal II 132 Aizwal (PG) Luangmual Zuangtui (Zemabawk) No No No No Aizwal (PG) Yes, 7SA513 Yes, O/C & E/F Yes Yes Zuangtui (Zemabawk) No Yes, REL 670 No No No Yes, O/C & E/F Yes Yes Aizwal (PG) No No No No No Yes Yes Yes No No No Yes Yes Yes No No 132 kV Transmission Line Protection Details Annexure-II Protection Details Sl. No. Name of Line Data Recording System Details Directional Event Main I Auto Power Number Instantaneous Carrier Logger / Charged Protection Reclosing Swing Pole of Core Disturbance Fault Sequential Voltage End specified for Protection exists (Type Definite Minimum (Single Phase / aided Inter- Blocking Discrepancy used for Recorder Locator Time(IDMT) Overtripping Event in kV of Relay and Three Phase) Feature Relay exists CT & VT, exists exists Current & Earth exists Recorder Make) exists exists (Yes (Yes / No) used for (Yes / No) (Yes / No) Fault Relay exists (Yes / No) exists (Yes/No) (Yes / No) / No) Main I (Yes/No) (Yes / No) 1. Owner of End: End :NEEPCO Assam & Meghalaya 7. & POWERGRID Rangandi 1 Ranganadi-Nirjuli 132 Nirjuli (PG) Rangandi 2 Ranganadi-Ziro 132 Ziro (PG) AGTPP 3 4 AGTPP- Kumarghat Balipara-Khupi 132 132 Semi Numerical, EPAC 3000, Yes MakeAlstom Yes, Yes, O/C & EF MICOM Semi Numerical, EPAC 3000, Yes MakeAlstom Yes, MICOM Yes, O/C & EF P442 OPTIMHO (LFZP111S1 No, Directional 0053E) Inverse type –CDD Make: GEC relay exists ALSTOM Yes (Three Phase) No Yes Yes Yes (Three Phase) No Yes Yes Facility exists but not in service Yes Yes No Core-1 of CT & CVT are used for Main-1 Yes Yes No Core-1 of CT & CVT are used for Main-1 Yes Yes Yes Core-1 of CT & CVT are used for Main-1 No No Yes Yes No No Yes Yes No No Kumarghat (PG) Yes, 7SA513 Yes, O/C & EF Yes Yes Yes Yes Yes Balipara (PG) Yes, SEL311C Yes, O/C & EF Yes Yes Yes Yes Yes Yes Yes Yes Yes Khupi Doyang 5 Doyang - Dimapur-I 132 Dimapur(PG) Static relayREL-100, ABB Make Yes, MICOM P442 Relay-2TJM-12 (Easun Reyrole) Yes, O/C & EF Yes Yes Yes No Yes No No No 132 kV Transmission Line Protection Details Annexure-II Protection Details Sl. No. Name of Line Directional Event Main I Auto Power Number Instantaneous Carrier Logger / Charged Protection Reclosing Swing Pole of Core Disturbance Fault Sequential Voltage End specified for Protection exists (Type Definite Minimum (Single Phase / aided Inter- Blocking Discrepancy used for Recorder Locator Time(IDMT) Overtripping Event in kV of Relay and Three Phase) Feature Relay exists CT & VT, exists exists Current & Earth exists Recorder Make) exists exists (Yes (Yes / No) used for (Yes / No) (Yes / No) Fault Relay exists (Yes / No) exists (Yes/No) (Yes / No) / No) Main I (Yes/No) (Yes / No) 1. Owner of End : Assam & Meghalaya Doyang 6 Doyang - Dimapur-II Data Recording System Details 132 Dimapur(PG) Static relayREL-100, ABB Make Yes, MICOM P442 Relay-2TJM-12 (Easun Reyrole) Yes No Yes Yes Yes, O/C & EF Yes Yes Yes Yes Yes Yes, MICOM P442 Yes, O/C & EF Yes Yes Yes Yes Yes Khliehriat (PG) Yes, MICOM P442 Yes, O/C & EF Yes Yes Yes Yes Yes Khandong Yes, 7SA513 Yes, O/C & EF Yes Yes Yes Yes Yes Khliehriat (PG) Yes, MICOM P442 Yes, O/C & EF Yes Yes Yes Yes Yes No No No No No No No No Khandong 7 Khandong - Haflong 8 Khandong - KhliehriatI 9 Khandong - KhliehriatII 132 Haflong (PG) Khandong 132 132 8. Owner of End: NEEPCO & TSECL 1 132 kV AGTPPAgartala I 132 kV AGTPP Agartala 2 132 kV AGTPPAgartala II 132 kV AGTPP Agartala OPTIMHO (LFZP111S1 No, Directional 0053E) Inverse type –CDD Make: GEC relay exists ALSTOM OPTIMHO OPTIMHO (LFZP111S1 No, Directional 0053E) Inverse type –CDD Make: GEC relay exists ALSTOM OPTIMHO Facility exists but not in service Yes Yes Yes Facility exists but not in service Yes Yes Yes Yes Yes Core-1 of CT & CVT are used for Main-1 Yes Yes Yes Core-1 of CT & CVT are used for Main-1 No No 132 kV Transmission Line Protection Details Annexure-II Protection Details Sl. No. Name of Line Data Recording System Details Directional Event Main I Auto Power Number Instantaneous Carrier Logger / Charged Protection Reclosing Swing Pole of Core Disturbance Fault Sequential Voltage End specified for Protection exists (Type Definite Minimum (Single Phase / aided Inter- Blocking Discrepancy used for Recorder Locator Time(IDMT) Overtripping Event in kV of Relay and Three Phase) Feature Relay exists CT & VT, exists exists Current & Earth exists Recorder Make) exists exists (Yes (Yes / No) used for (Yes / No) (Yes / No) Fault Relay exists (Yes / No) exists (Yes/No) (Yes / No) / No) Main I (Yes/No) (Yes / No) 1. Owner of End : POWERGRID Assam & Meghalaya 9. & NHPC 1 2 Loktak - Imphal II Loktak - Jiribam II Yes, (EM relay in addition to Numerical Relay) Feature exists in SF6 breaker & Numerical Relay will be implemented by Jan'15 Yes Yes, O/C & EF Yes Yes Loktak Yes, Numerical MICOM P442 Imphal (PG) Yes, MICOM P442 Loktak Yes, Numerical MICOM P442 Yes, (EM relay in addition to Numerical Relay) Jiribam (PG) Yes, MICOM P442 Yes, O/C & EF Yes Yes Yes, MICOM P442 Yes, O/C & EF Yes Yes, MICOM P442 Yes, O/C & EF Yes, MICOM P442 Yes, O/C & EF 132 132 Yes 1 core each Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Feature exists Feature in SF6 breaker exists and & Numerical can be Relay will be added when implemented required by Jan'15 Yes Yes Yes Yes 1 core each 10. Owner of End : POWERGRID & DoP, Nagaland 1 Dimapur (PG)Kohima 132 Dimapur(PG) Kohima 2 Dimapur (PG)Dimapur (State) 132 Dimapur(PG) Dimapur 11. Owner of End : POWERGRID & Gov. of Bhutan 1 Salakti-Gelephu 132 Salakati (PG) Gelephu Yes Yes 132 kV Transmission Line Protection Details Annexure-II Protection Details Sl. No. Name of Line Data Recording System Details Directional Event Main I Auto Power Number Instantaneous Carrier Logger / Charged Protection Reclosing Swing Pole of Core Disturbance Fault Sequential Voltage End specified for Protection exists (Type Definite Minimum (Single Phase / aided Inter- Blocking Discrepancy used for Recorder Locator Time(IDMT) Overtripping Event in kV of Relay and Three Phase) Feature Relay exists CT & VT, exists exists Current & Earth exists Recorder Make) exists exists (Yes (Yes / No) used for (Yes / No) (Yes / No) Fault Relay exists (Yes / No) exists (Yes/No) (Yes / No) / No) Main I (Yes/No) (Yes / No) 1. Owner & Meghalaya 12. OwnerofofEnd End: :Assam POWERGRID & TSECL 1 Silchar-P.K.Bari-1 132 Yes, MICOM P442 Yes, O/C & EF Yes Yes Yes Yes Yes Yes, MICOM P442 Yes, O/C & EF Yes Yes Yes Yes Yes Yes, SEL 311C Yes, O/C & EF Yes Yes Yes Yes Yes Static relayREL-100, ABB Make Relay-2TJM-12 (Easun Reyrole) Yes No Yes Yes Static relayREL-100, ABB Make Relay-2TJM-12 (Easun Reyrole) Yes No Yes Yes Missiontilla ASEB No No No No No No No No No No Banduar Yes Yes No No Yes No 3 & 2Core No No No Yes Yes No No Yes No 3 & 2Core No No No Yes Yes No No Yes No 3 & 2Core No No No Silchar (PG) P.K. Bari 2 Silchar- P.K.Bari-2 132 Silchar (PG) P.K. Bari 13. Owner of End : POWERGRID & DoP, Arunachal Pradesh 1 Ziro-Daporijo 132 Ziro (PG) Daporijo 14. Owner of End : NEEPCO & DoP, Nagaland 1 Doyang- Mokokchung 132 Doyang Mokokchung 2 Doyang- Kohima 132 Doyang Kohima 15. Owner of End : NEEPCO & TSECL 1 Missiontilla-ASEB 132 2 Banduar- Palatana 132 Palatana 3 Banduar- Monarchak 132 Banduar Monarchak 4 Rokhia-Monarchak 132 Rokhia Monarchak Note : 1) Main-I Protection indicates Distance Protection 2) Main-II Protection indicates one of Distance Protection / Directional Comparison Protection / Phase Segregated Line Differential protection 3) Type of Relay indicates it's operational mechanism - Numerical / Static / Electro-mechanical 4) List of inbuilt features of Numerical Relays are also to be furnished alongwith this format 220 kV Transmission Line Protection Details Annexure II Protection Details Sl. No. Name of Line Directional Main I Main II Instantaneous Two stage Charged End specified Protection Protection Definite OverVoltage in for Minimum Voltage kV Protection exists (Type of exists (Type Relay and of Relay and Time(IDMT) Protection Make) Make) type Earth exists (Yes/No) (Yes/No) Fault Relay (Yes/No) exists (Yes/No) Data Recording System Details Auto Reclosing (Single Phase / Three Phase) exists (Yes/No) Carrier aided Intertripping exists (Yes/No) Event Power Number of Number of Logger / Swing Pole Disturbance Core used Core used Sequential Blocking Discrepancy Recorder for CT & for CT & Event Feature Relay exists exists VT, used VT, used for Recorder exists (Yes/No) (Yes/No) for Main I Main II exists (Yes/No) (Yes/No) Fault Locator exists (Yes/No) 1. Owner of Line : Assam, AEGCL 1 Agia- BTPS I 220 Agia BTPS I 2 Agia- BTPS II 220 Agia BTPS II Azara 3 Azara-Sarusajai I 220 Sarusajai I Azara 4 Azara-Sarusajai II 220 Sarusajai II Boko 5 Boko-Azara 220 Azara Agia 6 Agia-Azara 220 Azara 7 Agia- Salakati I 220 8 Agia- Salakati II 220 9 Agia-Sarusajai 220 10 Boko-Agia 220 Agia Boko-Sarusajai 220 No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(REL650 ABB) Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes Yes(IDMT) Yes Yes(1-PH) Yes Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No Yes Yes Yes 1 1 Yes Yes Yes Yes(REL650 ABB) Yes(IDMT) Yes Yes(1-PH) Yes Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No Yes Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No Yes Yes Yes 1 1 Yes Yes Yes Yes(REL650 ABB) Yes(IDMT) Yes Yes(1-PH) Yes Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No Yes Yes Yes 1 1 Yes Yes Yes Yes(REL650 ABB) Yes(IDMT) Yes Yes(1-PH) Yes Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes Agia Salakati I Agia Salakati II Agia Sarusajai Boko 11 Yes(SEL321 SEL) Yes(D60 GE) Yes(7SA52 SIEMENS) Yes(D60 GE) Yes(REL670 ABB) Yes(7SA52 SIEMENS) Yes(REL670 ABB) Yes(7SA52 SIEMENS) Yes(7SA52 SIEMENS) Yes(REL670 ABB) Yes(7SA52 SIEMENS) Yes(REL670 ABB) Boko Sarusajai Yes(7SA52 SIEMENS) Yes(7SA52 SIEMENS) No No 220 kV Transmission Line Protection Details Annexure II Protection Details Sl. No. Name of Line Directional Main I Main II Instantaneous Two stage Charged End specified Protection Protection Definite OverVoltage in for Minimum Voltage kV Protection exists (Type of exists (Type Relay and of Relay and Time(IDMT) Protection Make) Make) type Earth exists (Yes/No) (Yes/No) Fault Relay (Yes/No) exists (Yes/No) 1. Owner of Line : Assam, AEGCL 12 Langpi- Sarusajai I Langpi 220 Sarusajai I Langpi Langpi- Sarusajai II 220 14 CMCL - Karbi Langpi 220 15 Sarusajai - CMCL 220 13 16 Mariani-Samaguri I Sarusajai II CMCL 220 Sarusajai CMCL Mariani Samaguri I Mariani Mariani-Samaguri II 220 18 Salakati-Harigaon I 220 17 Karbi Langpi Samaguri II Salakari Harigaon I 19 20 Salakati-Harigaon II 220 Samaguri-Balipara 220 Samaguri-Sarusajai 21 I 22 Samaguri Jawahar Nagar Salakari Harigaon II 220 Samaguri Balipara Samaguri Sarusajai I Samaguri 220 Jawahar Nagar Yes(7SA52 SIEMENS) Yes(7SA52 SIEMENS) Yes(7SA52 SIEMENS) Yes(7SA52 SIEMENS) Not KNown Yes(7SA52 SIEMENS) Yes(7SA52 SIEMENS) Not KNown Yes(7SA52 SIEMENS) Yes(7SA52 SIEMENS) Yes(7SA52 SIEMENS) Not KNown Yes(7SA52 SIEMENS) Not KNown Yes(7SA52 SIEMENS) PGCIL Yes(7SA52 SIEMENS) Yes(L-PRO ER) Data Recording System Details Auto Reclosing (Single Phase / Three Phase) exists (Yes/No) Carrier aided Intertripping exists (Yes/No) Event Power Number of Number of Logger / Swing Pole Disturbance Core used Core used Sequential Blocking Discrepancy Recorder for CT & for CT & Event Feature Relay exists exists VT, used VT, used for Recorder exists (Yes/No) (Yes/No) for Main I Main II exists (Yes/No) (Yes/No) Fault Locator exists (Yes/No) No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No Yes Yes Yes 1 1 Yes Yes Yes Yes(L-PRO ER) Yes(IDMT) No Yes(1-PH) Yes Yes Yes 1 1 Yes Yes Yes Yes(P442 MICOM) PGCIL 220 kV Transmission Line Protection Details Annexure II Protection Details Sl. No. Name of Line Directional Main I Main II Instantaneous Two stage Charged End specified Protection Protection Definite OverVoltage in for Minimum Voltage kV Protection exists (Type of exists (Type Relay and of Relay and Time(IDMT) Protection Make) Make) type Earth exists (Yes/No) (Yes/No) Fault Relay (Yes/No) exists (Yes/No) 1. Owner of Line : Assam, AEGCL Jawahar Nagar 23 220 Sarusajai 24 Jawahar Nagar Sarusajai Samaguri Samaguri-Sarusajai II 220 Tinsukia-AGBPP I 220 Sarusajai II Tinsukia 25 AGBPP I 26 Tinsukia Tinsukia-AGBPP II 220 Tinsukia-Namrup I 220 AGBPP II Tinsukia 27 Namrup I 28 Tinsukia-Namrup II Tinsukia 220 Namrup II Data Recording System Details Auto Reclosing (Single Phase / Three Phase) exists (Yes/No) Carrier aided Intertripping exists (Yes/No) Event Power Number of Number of Logger / Swing Pole Disturbance Core used Core used Sequential Blocking Discrepancy Recorder for CT & for CT & Event Feature Relay exists exists VT, used VT, used for Recorder exists (Yes/No) (Yes/No) for Main I Main II exists (Yes/No) (Yes/No) Fault Locator exists (Yes/No) Yes(L-PRO ER) Yes(7SA52 SIEMENS) Yes(7SA52 SIEMENS) Yes(7SA52 SIEMENS) Yes(7SA SIEMENS) Yes(SEL-321 SWITZER) Yes(SEL-321 SWITZER) Yes(SEL-321 SWITZER) Yes(7SA52 SIEMENS) Yes(7SA61 SIEMENS) Yes(7SA52 SIEMENS) Yes(7SA61 SIEMENS) Yes(L-PRO ER) Yes(IDMT) No Yes(1-PH) Yes Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No Yes Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes Yes(7SA SIEMENS) Yes(IDMT) No Yes(1-PH) No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes Yes(7SA SIEMENS) Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes, ABB make REL670, Numerical Yes, Areva make P442, Numerical Yes Yes Yes, Yes, Yes, REL670 & REL670 & REL670 & P442 P442 Relay P442 Relay Relay Yes 1 1 Yes, Yes, Yes, REL670 REL670 & REL670 & & P442 Relay P442 Relay P442 Relay Yes, ABB make REL670, Numerical Yes, Areva make P442, Numerical Yes Yes Yes, Yes, Yes, REL670 & REL670 & REL670 & P442 P442 Relay P442 Relay Relay Yes 1 1 Yes, Yes, Yes, REL670 REL670 & REL670 & & P442 Relay P442 Relay P442 Relay Yes 2. Owner of Line/End: Meghalaya, MePTCL Misa 1 Misa - Killing (Byrnihat) I 220 Killing (Byrnihat) Misa 2 Misa - Killing (Byrnihat) II 220 Killing (Byrnihat) 220 kV Transmission Line Protection Details Annexure II Protection Details Sl. No. Name of Line Directional Main I Main II Instantaneous Two stage Charged End specified Protection Protection Definite OverVoltage in for Minimum Voltage kV Protection exists (Type of exists (Type Relay and of Relay and Time(IDMT) Protection Make) Make) type Earth exists (Yes/No) (Yes/No) Fault Relay (Yes/No) exists (Yes/No) Data Recording System Details Auto Reclosing (Single Phase / Three Phase) exists (Yes/No) Carrier aided Intertripping exists (Yes/No) Yes, 7SA513 Yes Yes Yes Yes Yes Yes, 7SA513 Yes Yes Yes Yes Yes Yes, 7SA513 Yes Yes Yes Yes Yes Yes, 7SA513 Yes Yes Yes Yes Yes Yes, 7SA522 Yes Yes Yes Yes Yes Yes, 7SA522 Yes Yes Yes Yes Yes Yes, SIEMENS Yes, MICOM 7SA522 P442 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Event Power Number of Number of Logger / Swing Pole Disturbance Core used Core used Sequential Blocking Discrepancy Recorder for CT & for CT & Event Feature Relay exists exists VT, used VT, used for Recorder exists (Yes/No) (Yes/No) for Main I Main II exists (Yes/No) (Yes/No) 1. Owner of Line/End: Line : Assam, AEGCL 3. POWERGRID Yes, MICOM P442 Yes, MICOM Dimapur (PG) P442 Yes, MICOM Misa (PG) P442 Yes, MICOM Dimapur (PG) P442 Yes, MICOM Salakati (PG) P442 Birpara (PG) Yes, MICOM Salakati (PG) P442 Birpara (PG) Misa (PG) 1 2 Misa - Dimapur I Misa - Dimapur II 220 220 3 Salakti - Birpara I 220 4 Salakti - Birpara II 220 5 Misa - Mariani (PG) 220 Misa (PG) Mariani (PG) Yes, MICOM P444 Yes, REL 670 Note :1) Main-I Protection indicates Distance Protection 2) Main-II Protection indicates one of Distance Protection / Directional Comparison Protection / Phase Segregated Line Differential protection 3) Type of Relay indicates it's operational mechanism - Numerical / Static / Electro-mechanical 4) List of inbuilt features of Numerical Relays are also to be furnished alongwith this Fault Locator exists (Yes/No) 220 kV Transmission Line Protection Details Annexure II Protection Details Sl. No. Name of Line Directional Main II Instantaneous Two stage Charged End specified Main I Protection Protection Definite OverVoltage in for exists (Type of exists (Type Minimum Voltage kV Protection Relay and Make) of Relay and Time(IDMT) Protection (Yes/No) Make) type Earth exists (Yes/No) Fault Relay (Yes/No) exists (Yes/No) Data Recording System Details Auto Reclosing (Single Phase / Three Phase) exists (Yes/No) Carrier aided Intertripping exists (Yes/No) Event Power Number of Number of Logger / Swing Pole Disturbance Core used Core used Sequential Blocking Discrepancy Recorder for CT & for CT & Event Feature Relay exists exists VT, used VT, used for Recorder exists (Yes/No) (Yes/No) for Main I Main II exists (Yes/No) (Yes/No) Fault Locator exists (Yes/No) 1. Owner of End : Assam, AEGCL & POWERGRID Mariani (PG) 1 Mariani-Samaguri I 220 Samaguri 2 Mariani-Samaguri II Mariani (PG) No Yes (IDMT) No No No Yes Yes 1 1 Yes Yes Yes No Yes (IDMT) No No No Yes Yes 1 1 Yes Yes Yes Yes(P442 MICOM) Yes (IDMT) No No No Yes Yes 1 1 Yes Yes Yes Balipara (PG) Yes, MICOM P442 Yes, 7SA513 Yes Yes Yes Yes Yes Yes, SIMENS 7SA522 Yes Yes Yes Yes Yes 220 Samaguri Samaguri 3 4 5 6 Samaguri-Balipara Misa-Samaguri I Misa-Samaguri II Salakti - BTPS I 220 220 220 220 Yes (7SA52 SIEMENS) Yes (7SA52 SIEMENS) Yes (7SA52 SIEMENS) Misa (PG) Yes, MICOM Samaguri Yes, MICOM Yes, 7SA522 Yes Yes Yes Yes Yes Misa (PG) Yes, MICOM Yes, SIMENS 7SA522 Yes Yes Yes Yes Yes Samaguri Yes, MICOM Yes, 7SA522 Yes Yes Yes Yes Yes Salakati (PG) Yes, MICOM P442 Yes, 7SA522 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes BTPS 7 Salakti - BTPS II 220 Salakati (PG) Yes, MICOM P442 Yes, 7SA522 BTPS 8 Misa - Mariani 220 Misa (PG) Yes, SIEMENS 7SA522 Yes, MICOM P442 Mariani 2. Owner of End : Assam, AEGCL & NEEPCO Tinsukia 1 Tinsukia-AGBPP I 220 AGBPP I 2 3 Tinsukia-AGBPP II 220 kV AGBPP Mariani Tinsukia 220 AGBPP II 220 AGBPP Mariani Yes(7SA SIEMENS) No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes Yes(SEL-321 EASUN REY) Yes(SI PROTECH SIEMENS) Yes(IDMT) No Yes(1-PH) Yes Yes Yes 2 3 Yes Yes Yes No Yes(IDMT) No No No Yes Yes 1 1 Yes Yes Yes - Yes(IDMT) No Yes Yes Yes Yes 2 - Yes Yes Yes Yes (P443 ALSTOM) Yes No Yes Yes Yes Yes 1 2 Yes Yes Yes Yes(SEL-321 SWITZER) Yes(SEL-321 EASUN) Yes (P442 ALSTOM) 220 kV Transmission Line Protection Details Annexure II Protection Details Sl. No. Name of Line Directional Main II Instantaneous Two stage Charged End specified Main I Protection Protection Definite OverVoltage in for exists (Type of exists (Type Minimum Voltage kV Protection Relay and Make) of Relay and Time(IDMT) Protection (Yes/No) Make) type Earth exists (Yes/No) Fault Relay (Yes/No) exists (Yes/No) Auto Reclosing (Single Phase / Three Phase) exists (Yes/No) Data Recording System Details Carrier aided Intertripping exists (Yes/No) Event Power Number of Number of Logger / Swing Pole Disturbance Core used Core used Sequential Blocking Discrepancy Recorder for CT & for CT & Event Feature Relay exists exists VT, used VT, used for Recorder exists (Yes/No) (Yes/No) for Main I Main II exists (Yes/No) (Yes/No) Fault Locator exists (Yes/No) 1. Owner of End: End :Meghalaya, Assam, AEGCL & POWERGRID 3. MePTCL & POWERGRID Misa (PG) 1 Misa - Killing (Byrnihat) I 220 Killing (Byrnihat) Yes Yes, Yes, Yes, REL670 & REL670 & REL670 & P442 P442 Relay P442 Relay Relay Yes 1 1 Yes, Yes, Yes, REL670 REL670 & REL670 & & P442 Relay P442 Relay P442 Relay Yes Yes Yes, Yes, Yes, REL670 & REL670 & REL670 & P442 P442 Relay P442 Relay Relay Yes 1 1 Yes, Yes, Yes, REL670 REL670 & REL670 & & P442 Relay P442 Relay P442 Relay Yes Yes Yes Yes Yes 1 2 Yes Yes Yes No No No Yes, MICOM P442 Yes Yes Yes, MICOM P442 Yes Yes, MICOM P442 Yes Yes, ABB make REL670, Numerical Yes, Areva make P442, Numerical Yes, ABB make REL670, Numerical Yes, Areva make P442, Numerical Yes Misa (PG) 2 Misa - Killing (Byrnihat) II 220 Killing (Byrnihat) 4. Owner of End: POWERGRID & NEEPCO AGBPP Yes Yes 220 kV AGBPP 1 220 Mariani(PG) Mariani (PG) Yes, MICOM P444 Yes, REL 670 5. Owner of End: DoP,Arunachal Pradesh & NEEPCO EPAC 3000 220 kV AGBPP AGBPP 1 220 ALSTOM Deoamli Deomali 6. Owner of End: POWERGRID & NEEPCO Yes, SIMENS Misa (PG) 1 Misa - Kopili I 220 7SA522 Kopili Yes, SIMENS Misa (PG) 2 Misa - Kopili II 220 7SA522 Kopili 3 Misa - Kopili III 220 Misa (PG) Yes, 7SA513 SHPM 101 ALSTOM No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Kopili Note :1) Main-I Protection indicates Distance Protection 2) Main-II Protection indicates one of Distance Protection / Directional Comparison Protection / Phase Segregated Line Differential protection 3) Type of Relay indicates it's operational mechanism - Numerical / Static / Electro-mechanical 4) List of inbuilt features of Numerical Relays are also to be furnished alongwith this format Yes 1 2 Yes Yes 400 kV Transmission Line Protection Details Annexure II Protection Details Sl. No. Name of Line Directional Auto Main I Main II Instantaneous Two stage Reclosing End Carrier Charged Protection Definite Over(Single specified Protection aided InterVoltage exists (Type exists (Type Minimum Voltage Phase / for tripping in kV of Relay and of Relay and Time(IDMT) Protection Three Protection exists Make) Make) type Earth exists Phase) (Yes/No) (Yes/No) (Yes/No) Fault Relay (Yes/No) exists exists (Yes/No) (Yes/No) Data Recording System Details Power Number Swing Pole of Core Blocking Discrepancy used for Feature Relay exists CT & VT, exists (Yes / No) used for (Yes/No) Main I Event Number of Logger / Core used Disturbance Fault Sequential for CT & Recorder Locator Event VT, used exists exists Recorder for Main (Yes/No) (Yes/No) exists II (Yes/No) 1. Owner of Line : NETC Azara 1 Silchar - Azara 400 Silchar (PG) 2 Silchar - Killing (Byrnihat) 400 Palatana- Silchar I 400 Silchar (PG) Yes (REL670 Yes (REL670 ABB) ABB) Yes Yes Yes Yes, REL670 Yes Yes Yes Yes, REL670 Yes Yes Yes, MICOM P444 Yes, REL670 Yes Yes, MICOM P444 Yes, REL670 Yes, MICOM P444 Yes, MICOM P444 Yes, MICOM P444 Yes, MICOM P444 Yes Yes Yes 1 1 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes, REL670 Yes Yes Yes Yes Yes Yes Yes, REL670 Yes Yes Yes Yes Yes Yes Killing (Byrnihat) Palatana 3 Silchar (PG) Palatana 4 Palatana- Silchar II 400 Silchar (PG) Killing (Byrnihat) 5 Killing- Bongaigaon 400 Bongaigaon (PG) Azara 6 Azara- Bongaigaon 400 Bongaigaon (PG) Yes 400 kV Transmission Line Protection Details Annexure II Protection Details Sl. No. Name of Line Directional Auto Main I Main II Instantaneous Two stage Reclosing End Carrier Charged Protection Definite Over(Single specified Protection aided InterVoltage exists (Type exists (Type Minimum Voltage Phase / for tripping in kV of Relay and of Relay and Time(IDMT) Protection Three Protection exists Make) Make) type Earth exists Phase) (Yes/No) (Yes/No) (Yes/No) Fault Relay (Yes/No) exists exists (Yes/No) (Yes/No) Data Recording System Details Power Number Swing Pole of Core Blocking Discrepancy used for Feature Relay exists CT & VT, exists (Yes / No) used for (Yes/No) Main I Event Number of Logger / Core used Disturbance Fault Sequential for CT & Recorder Locator Event VT, used exists exists Recorder for Main (Yes/No) (Yes/No) exists II (Yes/No) 1. Owner of Line : POWERGRID NETC 2. 1 2 3 4 5 6 Bongaigaon- Binaguri I Bongaigaon- Binaguri II Bongaigaon- Binaguri III Bongaigaon- Binaguri IV Bongaigaon- Balipara I Bongaigaon- Balipara II 400 Bongaigaon (PG) Yes, MICOM P442 Yes, SIEMENS 7SA522 Yes Yes Yes Yes Yes Yes Yes, MICOM P442 Yes, SIEMENS 7SA522 Yes Yes Yes Yes Yes Yes Yes, MICOM P444 Yes, REL670 Yes Yes Yes Yes Yes Yes Yes, MICOM P444 Yes, REL670 Yes Yes Yes Yes Yes Yes Yes, 7SA513 Yes Yes Yes Yes Yes Yes Yes, SIEMENS 7SA522 Yes Yes Yes Yes Yes Yes Yes, 7SA513 Yes Yes Yes Yes Yes Yes Yes, SIEMENS 7SA522 Yes Yes Yes Yes Yes Yes Binaguri (PG) 400 Bongaigaon (PG) Binaguri (PG) 400 Bongaigaon (PG) Binaguri (PG) 400 Bongaigaon (PG) Binaguri (PG) Bongaigaon (PG) 400 Balipara (PG) Bongaigaon (PG) 400 Balipara (PG) Yes, MICOM P444 Yes, MICOM P442 Yes, MICOM P444 Yes, MICOM P442 400 kV Transmission Line Protection Details Annexure II Protection Details Sl. No. Name of Line 1. Owner of Line : NETC Directional Auto Main I Main II Instantaneous Two stage Reclosing End Carrier Charged Protection Definite Over(Single specified Protection aided InterVoltage exists (Type exists (Type Minimum Voltage Phase / for tripping in kV Three Protection of Relay and of Relay and Time(IDMT) Protection exists Make) Make) type Earth exists Phase) (Yes/No) (Yes/No) (Yes/No) Fault Relay (Yes/No) exists exists (Yes/No) (Yes/No) Data Recording System Details Power Number Swing Pole of Core Blocking Discrepancy used for Feature Relay exists CT & VT, exists (Yes / No) used for (Yes/No) Main I Yes, MICOM Yes, REL670 Yes Yes Yes Yes P444 Bongaigaon- Balipara 7 400 III Yes, Balipara MICOM Yes, REL670 Yes Yes Yes Yes (PG) P442 Yes, Bongaigaon MICOM Yes, REL670 Yes Yes Yes Yes (PG) P444 Bongaigaon- Balipara 8 400 IV Yes, Balipara MICOM Yes, REL670 Yes Yes Yes Yes (PG) P442 Yes, Balipara MICOM Yes, REL670 Yes Yes Yes Yes (PG) P444 9 Balipara- Ranganadi I 400 Yes, Yes MICOM Yes, PD571, Ranganadi No Yes (Single Yes Yes Yes P442, ALSTOM Phase) ALSTOM Yes, Balipara MICOM Yes, REL670 Yes Yes Yes Yes (PG) P444 10 Balipara- Ranganadi II 400 Yes, Yes MICOM Yes, PD571, Ranganadi No Yes (Single Yes Yes Yes P442, ALSTOM Phase) ALSTOM Yes, Balipara MICOM Yes, REL670 Yes Yes Yes Yes (PG) P444 11 Balipara- Misa I 400 Yes, Yes, MICOM Misa (PG) SIEMENS Yes Yes Yes Yes P442 7SA522 Yes, Balipara MICOM Yes, REL670 Yes Yes Yes Yes (PG) P444 12 Balipara- MIsa II 400 Yes, Yes, MICOM Misa (PG) SIEMENS Yes Yes Yes Yes P442 7SA522 Note :1) Main-I Protection indicates Distance Protection 2) Main-II Protection indicates one of Distance Protection / Directional Comparison Protection / Phase Segregated Line Differential protection 3) Type of Relay indicates it's operational mechanism - Numerical / Static / Electro-mechanical 4) List of inbuilt features of Numerical Relays are also to be furnished alongwith this Event Number of Logger / Core used Disturbance Fault Sequential for CT & Recorder Locator Event VT, used exists exists Recorder for Main (Yes/No) (Yes/No) exists II (Yes/No) Bongaigaon (PG) 1 1 1&2 1&2 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No Yes Yes No No Yes Yes Yes Yes Yes Yes Yes Yes No No Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side 1. Owner of Transformer : Assam, AEGCL 400/220 kV Azara (Mirza) LV side 1 2x315 MVA ICTs I & II HV side 220/132 kV 1x100 MVA LV side Agia ICT HV side 2 220/132 kV 1x50 MVA Agia LV side ICT HV side 220/132 kV 1x150 MVA LV side 3 Balipara ICT HV side 220/132 kV 1x50 MVA Boko LV side 4 ICT HV side 220/132 kV 2x80 MVA LV side BTPS ICTs HV side 5 220/132 kV 1x160 MVA LV side BTPS ICT HV side 220/132 kV 2x100 MVA LV side 6 Mariani ICTs HV side 220/132 kV 2x50 NTPS LV side 7 ICTs HV side 220/132 kV 3x50 MVA LV side 8 Samaguri ICTs HV side 220/132 kV 3x100 MVA LV side 9 Sarusajai ICTs HV side 220/132 kV 2x50 MVA LV side 10 Tinsukia ICT HV side 220/33 kV 2x50 MVA GIS LV side 11 (Jawaharnagar) ICT HV side 132/33 kV 1x40 MVA Agia LV side ICT HV side 12 132/33 kV 1X12.5 MVA Agia LV side ICT HV side 132/33 kV 1X12.5 MVA LV side APM (Ashok Paper Mill) HV side 13 132/33 kV 1X16 MVA APM LV side (Ashok Paper Mill) ICT HV side 132/33 kV 2X25 MVA LV side 14 Barnagar ICTs HV side 132/33 kV 2X16 MVA LV side 15 Biswanath Chariali ICTs HV side 132/33 kV 2X16 MVA LV side 16 Bokakhat ICTs HV side 132/33 kV 1X16 MVA LV side 17 Bokajan ICT HV side 132/33 kV 2X40 MVA Boko LV side 18 Differential Protection exits (Yes/No) Over Fluxing Protection exits (Yes/No) REF Protection exists (Yes/No) Directional Over Current Protection exits (Yes/No) Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes Yes No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side 18 1. Owner of Transformer : Assam, AEGCL ICTs HV side 132/33 kV 1X16 MVA BTPS LV side 19 ICT HV side 132/33 kV 1X16 MVA LV side Chandrapur (CTPS) ICT HV side 20 132/33 kV 1X30 MVA LV side Chandrapur (CTPS) ICT HV side 132/33 kV 2X31.5 MVA LV side 21 Depota ICTs HV side 132/33 kV 2X25 MVA LV side 22 Dhaligaon ICTs HV side 132/33 kV 2X16 MVA LV side 23 Dhemaji ICTs HV side 132/33 kV 2X31.5 MVA LV side 24 Dibrugarh ICTs HV side 132/33 kV 2X16 MVA Diphu LV side 25 ICTs HV side 132/33 kV 3X3.5 MVA LV side 26 Dullavcherra ICTs HV side 132/33 kV 1X25 MVA LV side 27 Garmur ICT HV side 132/33 kV 2X16 MVA LV side 28 Gauripur ICTs HV side 132/33 kV 1X16 MVA LV side 29 Ghoramari ICT HV side 132/33 kV 1X16 MVA LV side 30 Gohpur ICT HV side 132/33 kV 1X10 MVA LV side 31 Gohpur ICT HV side 132/33 kV 2X25 MVA LV side 32 Golaghat ICTs HV side 132/33 kV 2X16 MVA LV side 33 Gossaigaon (Joyma) ICTs HV side 132/33 kV 2X10 MVA LV side 34 Haflong ICTs HV side 132/33 kV 2X16 MVA LV side 35 Jagiroad (Baghjap) ICTs HV side 132/33 kV 2X25 MVA Jorhat LV side 36 (Garmur) ICTs HV side 132/33 kV 1X16 MVA Jorhat LV side 37 (Garmur) ICT HV side Differential Protection exits (Yes/No) Over Fluxing Protection exits (Yes/No) REF Protection exists (Yes/No) Directional Over Current Protection exits (Yes/No) Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side 1. Owner of Transformer : Assam, AEGCL 132/33 kV 1X31.5 MVA LV side 38 Kahilipara ICT HV side 132/33 kV 2X30 MVA LV side 39 Kahilipara ICTs HV side 132/33 kV 2X10 MVA Ledo LV side 40 (Margherita) ICTs HV side 132/33 kV 2X7.5 MVA LTPS LV side 41 ICTs HV side 132/33 kV 4X5.5 MVA LV side 42 Majuli (Single Phase) ICTs HV side 132/33 kV 2X16 MVA Moran LV side 43 ICTs HV side 132/33 kV 2X16 MVA LV side 44 Nalbari ICTs HV side 132/33 kV 2X25 MVA LV side 45 Narengi ICTs HV side 132/33 kV 2X25 MVA Nazira LV side 46 (Gargaon) ICTs HV side 132/33 kV 2X10 MVA North LV side 47 Lakhimpur (Nalkata) ICTs HV side 132/33 kV 1X31.5 MVA LV side 48 NTPS ICT HV side 132/33 kV 3X10 MVA LV side 49 Pailapool ICTs HV side 132/33 kV 2X25 MVA LV side 50 Panchgram New ICTs HV side 132/33 kV 2X10 MVA LV side 51 Panchgram Old ICTs HV side 132/33 kV 2X25 MVA LV side 52 Rangia ICTs HV side 132/33 kV 2X25 MVA Rowta LV side 53 ICTs HV side 132/33 kV 2X25 MVA LV side 54 Samaguri ICTs HV side 132/33 kV 1X16 MVA LV side 55 Sankar Dev Nagar (Lanka) HV side 132/33 kV 3X31.5 MVA LV side 56 Sarusajai ICTs HV side 132/33 kV 2X16 MVA LV side 57 Sibsagar ICTs HV side 132/33 kV 2X16 MVA LV side 58 Sipajhar ICTs HV side Differential Protection exits (Yes/No) Over Fluxing Protection exits (Yes/No) REF Protection exists (Yes/No) Directional Over Current Protection exits (Yes/No) Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes Yes No No No No Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side 1. Owner of Transformer : Assam, AEGCL 132/33 kV 2X31.5 MVA LV side 59 Sishugram (Amingaon) ICTs HV side 132/33 kV 1x40 MVA LV side 60 Sishugram (Amingaon) ICT HV side 132/33 kV 2X25 MVA LV side 61 Srikona ICTs HV side 132/33 kV 2X25 MVA LV side 62 Khaloigaon ICTs HV side 132/33 kV 2X25 MVA Sonari LV side 63 ICTs HV side 132/33 kV 2X40 MVA LV side 64 Behaiting ICTs HV side 132/66 kV 2X20 MVA LV side 65 Mariani ICTs HV side 132/66 kV 2X25 MVA NTPS LV side 66 ICTs HV side 132/66 kV 1X20 MVA NTPS LV side 67 ICT HV side 132/66 kV 3X20 MVA LV side 68 Tinsukia ICTs HV side 132/11 kV 2X16 MVA Dispur LV side 69 ICTs HV side 132/11 kV 2X10 MVA LV side 70 Kahilipara ICTs HV side 66/33 kV 3X5 MVA Bokajan LV side 71 ICTs HV side 66/33 kV 2X5 MVA Diphu LV side 72 ICTs HV side 66/33 kV 2X10 MVA LV side 73 Golaghat ICTs HV side 66/33 kV 1X6.3 MVA LV side 74 Golaghat ICT HV side 66/33 kV 2X16 MVA Mariani LV side 75 ICTs HV side 66/33 kV 2X16 MVA Nazira LV side 76 (Gargaon) ICTs HV side 66/33 kV 3X10 MVA NTPS LV side 77 ICTs HV side 66/33 kV 3X10 MVA Rupai LV side 78 (Doomdooma) ICTs HV side 66/33 kV 3x20 MVA LV side 79 Tinsukia ICTS HV side Differential Protection exits (Yes/No) Over Fluxing Protection exits (Yes/No) REF Protection exists (Yes/No) Directional Over Current Protection exits (Yes/No) Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side 1. Owner of Transformer : MSPCL, Assam, AEGCL 2. Manipur 132/33 kV Churachandpur LV side (Kheljang) 1x20 MVA HV side 1 132/33 kV Churachandpur LV side (Kheljang) 1x20 MVA HV side 132/33 kV Jiribam 1x20 LV side 2 MVA Transformer HV side 132/33 kV Kakching 1x20 LV side MVA Transformer I HV side 3 132/33 kV Kakching 1x20 LV side MVA Transformer II HV side 132/33 kV Karong 1x20 LV side MVA Transformer I HV side 4 132/33 kV Karong 1x20 LV side MVA Transformer II HV side 132/33 kV Ningthoukong LV side 1x20 MVA Transformer I HV side 5 132/33 kV Ningthoukong LV side 1x12.5 MVA Transformer II HV side 132/33 kV Rengpang 1x12.5 LV side 6 MVA Transformer HV side 132/33 kV LV side Yaingangpokpi1x20 MVA HV side 7 132/33 kV Yaingangpokpi LV side 1x20 MVA Transformer-II HV side 132/33 kV Yurembam 1x20 LV side MVA Transformer I HV side 132/33 kV Yurembam 1x20 LV side 8 MVA Transformer II HV side 132/33 kV Yurembam 1x20 LV side MVA Transformer III HV side 132/33 kV Kongba1x20 MVA LV side Transformer-I HV side 9 132/33 kV Kongba1x20 MVA LV side Transformer-II HV side Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) Differential Protection exits (Yes/No) Over Fluxing Protection exits (Yes/No) REF Protection exists (Yes/No) Directional Over Current Protection exits (Yes/No) Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA No No No No No No No No No No No No No No No No Yes Yes Yes No No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes NA NA NA NA NA NA No No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes NA NA NA NA NA NA NA NA NA Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side Differential Protection exits (Yes/No) Over Fluxing Protection exits (Yes/No) REF Protection exists (Yes/No) Yes Yes Directional Over Current Protection exits (Yes/No) Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) 1. Owner of Transformer : Meghalaya, Assam, AEGCL 3. MePTCL 400/220 kV Killing(Byrnihat) LV side 1x315 MVA Transformer I HV side 400/220 kV Killing(Byrnihat) LV side 1x315 MVA Transformer II HV side 1 220/132 kV Killing(Byrnihat) 1x160 MVA Transformer I 220/132 kV Killing(Byrnihat) 1x160 MVA Transformer II 2 132/33 kV Cherrapunjee (Sohra) 1x12.5 MVA Transformer 132/33 kV EPIP I 1x20 MVA Transformer I LV side HV side LV side HV side 132/33 kV EPIP II 1x50 MVA Transformer No 132/33 kV Khliehriat 1x20 MVA Transformer I LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side 5 132/33 kV Khliehriat 1x20 MVA Transformer II Yes No No HV side 4 132/33 kV EPIP II 1x20 MVA Transformer Yes LV side 3 132/33 kV EPIP I 1x20 MVA Transformer II Yes, ABB make, RET670, Numerical Yes, ABB make, RET670, Numerical LV side HV side Yes, ABB make, RET670, Numerical Yes, ABB make, RET670, Numerical Yes, Toshiba make, GRT100, Numerical Yes, ABB make, RET670, Numerical Yes, ABB make, RET670, Numerical Yes, ABB make, RET670, Numerical Yes Yes No Yes Yes Yes No No No No No No Non directional REX ABB make Non directional REX ABB make Non directional REX ABB make Non directional REX ABB make Non directional CDG, EE make Non directional CDG, EE make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional CDG, EE make Non directional P122 Areva make Non directional P122 Areva make No Yes Yes No Yes Yes Yes Yes No No Yes Yes Yes No No No Yes No Yes Yes Yes No No No Yes No Yes Yes Yes No Yes Yes Yes No Yes No Yes Yes No Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes No Yes Yes Yes No Yes Yes Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side 1. Owner of Transformer : Assam, AEGCL LV side 11 kV 132/33/11 kV Lumshnong LV side 33 6 1x10 MVA Transformer kV Differential Protection exits (Yes/No) No Over Fluxing Protection exits (Yes/No) No REF Protection exists (Yes/No) No HV side 132/33 kV Mawlai 1x20 MVA Transformer I 7 132/33 kV Mawlai 1x20 MVA Transformer II 132/33 kV Mawlai 1x20 MVA Transformer III 132/33 kV Nangalbibra 1x12.5 MVA Transformer I LV side HV side LV side HV side LV side HV side LV side HV side Yes, Areva make, P632, Numerical Yes Yes, Areva make, P632, Numerical Yes Yes, Areva make, P632, Numerical Yes Yes, EE make, Static type No Yes, Areva make, P632, Numerical Yes Yes, ABB make, RET670, Numerical Yes Yes, EE make, Static type Yes Yes, Areva make, P632, Numerical Yes No No No No 8 132/33 kV Nangalbibra 1x12.5 MVA Transformer II 132/33 kV NEHU 1x20 MVA Transformer I LV side HV side LV side HV side 9 132/33 kV NEHU 1x20 MVA Transformer II 10 132/33 kV Nongstoin 1x12.5 MVA Transformer LV side HV side LV side HV side No No No Yes Directional Over Current Protection exits (Yes/No) Non directional CDG, EE make Non directional JRC 059,JVS make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional CDG, EE make Non directional P122 Areva make Non directional P122 Areva make Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) No No Yes Yes No Yes Yes No No Yes Yes No No Yes No Yes No Yes No Yes No Yes No Yes No No No Yes No No No Yes No Yes Yes Yes No Yes Yes Yes No Yes No Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes No Yes Yes Yes Yes No Yes Yes Yes No Yes Yes Yes Yes No Yes Yes Yes No Yes Yes Yes Yes No Yes Yes Yes No Yes Yes Yes Yes No Yes Yes Yes No Yes Yes Yes Yes No Yes Yes Yes No Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes Yes No Yes Yes Yes Yes Yes Transformer Protection Details Over Fluxing Protection exits (Yes/No) LV side/ HV side Differential Protection exits (Yes/No) 1. Owner of Transformer : Assam, AEGCL LV side 132/33 kV Rongkhon (Tura) 1x20 MVA Transformer I HV side Yes, Areva make, P632, Numerical Yes Yes, Areva make, P632, Numerical Yes Yes, EE make, Static type Yes Yes, EE make, Static type Yes Yes, EE make, Static type Yes Yes, Toshiba make, GRT100, Numerical Yes Yes, Areva make, P632, Numerical Yes Yes, Areva make, P632, Numerical Yes Yes, Areva make, P632, Numerical Yes Sl. No. Name of Transformer 132/33 kV Rongkhon (Tura) 1x20 MVA Transformer II 11 132/33 kV Rongkhon (Tura) 1x5 MVA Transformer I 132/33 kV Rongkhon (Tura) 1x5 MVA Transformer II 132/33 kV Rongkhon (Tura) 1x5 MVA Transformer III 132/33 kV Umiam 1x20 MVA Transformer I LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side 12 132/33 kV Umiam 1x20 MVA Transformer II 132/33/11 kV NEIGRIHMS 1x10 MVA Transformer I LV side HV side LV side HV side REF Protection exists (Yes/No) No No No No No No No No 13 132/33/11 kV NEIGRIHMS 1x10 MVA Transformer II LV side HV side No Directional Over Current Protection exits (Yes/No) Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional CDG, EE make Non directional, CDG EE make Non directional JNC066, JVS make Non directional JNC066, JVS make Non directional P141 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) No Yes Yes No Yes Yes Yes Yes No No Yes Yes Yes No Yes Yes Yes No Yes Yes Yes No Np No Yes No Yes Yes Yes No Yes Yes Yes No Yes Yes Yes Yes No Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes No Yes Yes Yes Yes Yes Yes Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side 1. Owner of Transformer : Assam, AEGCL LV side 132/33 kV Mawngap 1x20 MVA Transformer I HV side 14 LV side 132/33 kV Mawngap 1x20 MVA Transformer II HV side 132/33 kV Umiam Stg I 1x10.6 MVA Transformer I 132/33 kV Umiam Stg I 1x10.6 MVA Transformer II LV side HV side LV side HV side Differential Protection exits (Yes/No) Over Fluxing Protection exits (Yes/No) Yes, Areva make, P632, Numerical Yes Yes, Areva make, P632, Numerical Yes Yes, Areva make, P632, Numerical Yes Yes, Areva make, P632, Numerical Yes Yes, Areva make, P632, Numerical Yes Yes, Areva make, P632, Numerical Yes REF Protection exists (Yes/No) No No No No 15 132/33 kV Umiam Stg I 1x10.6 MVA Transformer III 132/33 kV Umiam Stg I 1x10.6 MVA Transformer IV 132/33 kV Umiam Stg II 1x10.5 MVA Transformer I LV side HV side LV side HV side LV side HV side 16 132/33 kV Umiam Stg II 1x10.5 MVA Transformer II 132/33 kV Umiam Stg III 1x37.5 MVA Transformer I LV side HV side LV side HV side 17 132/33 kV Umiam Stg III 1x37.5 MVA Transformer II LV side HV side Digital M3311, Beckwith Electric Co. Digital M3311, Beckwith Electric Co. Yes, ABB make, RET670, Numerical Yes, ABB make, RET670, Numerical No No Directional Over Current Protection exits (Yes/No) Yes, Directional P141, Areva make Yes, Directional P141, Areva make Yes, Directional P141, Areva make Yes, Directional P141, Areva make Yes, Directional P141, Areva make Yes, Directional P141, Areva make Yes, Directional P141, Areva make Yes, Directional P141, Areva make Yes, Directional P141, Areva make Yes, Directional P141, Areva make Yes, Directional P141, Areva make Yes, Directional P141, Areva make Beckwith Electric Co. Yes Yes Yes No No No Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes No Yes No Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes No Yes Yes Yes No No Yes Yes Yes Yes Yes Yes No No Yes Yes Yes No Yes Yes Yes Yes No Yes Yes Yes No Yes Yes Yes No No Yes Yes Yes Yes Yes Yes No No Yes Yes Yes No Yes Yes Yes Yes No Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes Non directional CDG, EE make Non directional CDG, EE make Non directional CDG, EE make Non directional CDG, EE make Yes Yes No No Yes Yes Yes No No Yes Yes Yes Yes Beckwith Electric Co. Yes Yes No No Yes Yes Yes Beckwith Electric Co. Yes Yes Yes No No Yes Yes Yes No Beckwith Electric Co. Yes Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) Yes No Yes Yes Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side 1. Owner of Transformer : Assam, AEGCL LV side 132/33 kV Umiam Stg IV 1x37.5 MVA Transformer I HV side 18 LV side 132/33 kV Umiam Stg IV 1x37.5 MVA Transformer II HV side 132/33 kV Umtru 1x7.5 MVA Transformer I LV side HV side 19 132/33 kV Umtru 1x7.5 MVA Transformer II 132/33 kV Leshka 1x45 MVA Transformer I 132/33 kV Leshka 1x45 MVA Transformer II 20 132/33 kV Leshka 1x45 MVA Transformer III 132/33 kV Leshka 1x45 MVA Transformer I LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side 4. Owner of Transformer : P&E, Mizoram 132/33 kV Bairabi, 3.15 MVA LV side Transformer HV side 132/11 kV Bairabi, 15 MVA LV side 1 Transformer 1 HV side 132/11 kV Bairabi, 15 MVA LV side Transformer 2 HV side Differential Protection exits (Yes/No) Yes, ABB make, RET670, Numerical Yes, ABB make, RET670, Numerical Yes, ABB make, RET670, Numerical Yes, ABB make, RET670, Numerical Yes, ABB make, RET670, Numerical Yes, ABB make, RET670, Numerical Yes, ABB make, RET670, Numerical Yes, ABB make, RET670, Numerical Over Fluxing Protection exits (Yes/No) REF Protection exists (Yes/No) Yes Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Directional Over Current Protection exits (Yes/No) Non directional CDG, EE make Non directional CDG, EE make Non directional CDG, EE make Non directional CDG, EE make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional P122 Areva make Non directional REX ABB make Non directional REX ABB make Non directional REX ABB make Non directional REX ABB make Non directional REX Non directional REX ABB make Non directional REX ABB make Non directional REX ABB make Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) No Yes Yes No No Yes No Yes No Yes No No No Yes No No No Yes No No No Yes No Yes Yes Yes No Yes Yes Yes No Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes No Yes Yes No No Yes Yes Yes Yes Yes Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side 1. Owner of132/66 Transformer : Assam, AEGCL kV Kolasib LV side (Bawktlang) 12.5 MVA HV side 132/33 kV Kolasib LV side 2 (Bawktlang) 12.5 MVA HV side 66/33 kV Kolasib LV side (Bawktlang) 6.3 MVA HV side 132/33 kV Serchip (Bukpui) LV side 12.5 MVA Transformer I HV side 3 132/33 kV Serchip (Bukpui) LV side 6.3 MVA Transformer II HV side 132/33 kV Lunglei (Khawiva) LV side 12.5 MVA Transformers I HV side 4 132/33 kV Lunglei (Khawiva) LV side 12.5 MVA Transformers II HV side 132/33 kV Khawzawl 12.5 LV side 5 MVA Transformers I HV side 132/33 kV Luangmual, 12.5 LV side MVA Transformers I HV side 132/33 kV Luangmual, 12.5 LV side 6 MVA Transformers II HV side 132/33 kV Luangmual, 12.5 LV side MVA Transformers III HV side 132/33 kV Saitual 1x6.3 LV side 7 MVA Transformer HV side 132/33 kV Zemabawk LV side (Zuangtui) 12.5 MVA HV side 8 132/33 kV Zemabawk LV side (Zuangtui) 12.5 MVA HV side 5. Owner of Transformer : NEEPCO 53 MVA, 11 kV/132 kV LV side 1 Generator Transformer at HV side Ranganadi 2 3 400 kV/132 kV, 120 MVA ICT-I at Ranganadi 400 kV/132 kV, 120 MVA ICT-II at Ranganadi 11/220 kV, 50 MVA 4 Generator Transformer 1 at AGBPP 11/220 kV, 50 MVA 5 Generator Transformer 2 at Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) Differential Protection exits (Yes/No) Over Fluxing Protection exits (Yes/No) REF Protection exists (Yes/No) Directional Over Current Protection exits (Yes/No) No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No Yes Yes No No No No Yes Yes No No No No Yes Yes No No No No Yes Yes No No No No Yes Yes No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes No No Yes Yes Yes Yes No Yes Yes No No Yes No No Yes Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes Yes Yes No LV side Yes Yes HV side No LV side Yes Yes HV side No LV side Yes Yes Yes No No Yes Yes Yes Yes No Yes HV side Yes No Yes No No Yes Yes Yes Yes No Yes LV side Yes Yes Yes No No Yes Yes Yes Yes No Yes Yes ( Neutral Displacemen t Protection) Yes ( Neutral Displacemen t Protection) No No Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side 5 Generator Transformer 2 at 1. Owner of Transformer : Assam, AEGCL HV side AGBPP 11/220 kV, 50 MVA LV side 6 Generator Transformer 3 at HV side AGBPP 11/220 kV, 50 MVA LV side 7 Generator Transformer 4 at HV side AGBPP 8 9 10 11 12 13 14 11/220 kV, 50 MVA Generator Transformer 5 at AGBPP 11/220 kV, 50 MVA Generator Transformer 6 at AGBPP 11/220 kV, 50 MVA Generator Transformer 7 at AGBPP 11/220 kV, 50 MVA Generator Transformer 8 at AGBPP 11/220 kV, 50 MVA Generator Transformer 9 at AGBPP 11/132 kV, 3x12.5(37.5) MVA Generator Transformer 1 at AGTPP 11/132 kV, 3x12.5(37.5) MVA Generator Transformer 2 at AGTPP 11/132 kV, 3x12.5(37.5) 15 MVA Generator Transformer 3 at AGTPP 11/132 kV, 3x12.5(37.5) 16 MVA Generator Transformer 4 at AGTPP 6. Owner of Transformer : NHPC 1 11/132 kV, Generator Transformer at Loktak Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) Differential Protection exits (Yes/No) Over Fluxing Protection exits (Yes/No) REF Protection exists (Yes/No) Directional Over Current Protection exits (Yes/No) Yes No Yes No No Yes Yes Yes Yes No Yes Yes Yes Yes No No Yes Yes Yes Yes No Yes Yes No Yes No No Yes Yes Yes Yes No Yes Yes Yes Yes No No Yes Yes Yes Yes No Yes Yes No Yes No No Yes Yes Yes Yes No Yes LV side Yes Yes Yes No No Yes Yes Yes Yes No Yes HV side Yes No Yes No No Yes Yes Yes Yes No Yes LV side Yes Yes Yes No No Yes Yes Yes Yes No Yes HV side Yes No Yes No No Yes Yes Yes Yes No Yes LV side Yes Yes Yes No No Yes Yes Yes Yes No Yes HV side Yes No Yes No No Yes Yes Yes Yes No Yes LV side Yes Yes Yes No No Yes Yes Yes Yes No Yes HV side Yes No Yes No No Yes Yes Yes Yes No Yes LV side Yes Yes Yes No No Yes Yes Yes Yes No Yes HV side Yes No Yes No No Yes Yes Yes Yes No Yes LV side Yes Yes Yes No Yes Yes Yes Yes Yes No Yes Yes No No HV side Yes No Yes No No Yes Yes Yes Yes No Yes Yes No No LV side Yes Yes Yes No Yes Yes Yes Yes Yes No Yes Yes No No HV side Yes No Yes No No Yes Yes Yes Yes No Yes Yes No No LV side Yes Yes Yes No Yes Yes Yes Yes Yes No Yes Yes No No HV side Yes No Yes No No Yes Yes Yes Yes No Yes Yes No No LV side Yes Yes Yes No Yes Yes Yes Yes Yes No Yes Yes No No HV side Yes No Yes No No Yes Yes Yes Yes No Yes Yes No No Yes Yes Yes No No Yes Yes Yes No No No Yes No Yes LV side HV side Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side 1. AEGCL 7. Owner of Transformer : Assam, POWERGRID 400/220kV, 315 MVA ICT at LV side 1 Bongaigaon HV side 400/220kV, 315 MVA ICT at LV side 2 Balipara HV side 220/132, 50 MVA ICT 1 at LV side 3 Balipara (NEEPCO asset) HV side 220/132, 50 MVA ICT2 at LV side 4 Balipara (AEGCL asset) HV side 400/220kV, 315 MVA ICT 1 LV side 5 at Misa HV side 400/220kV, 315 MVA ICT 2 LV side 6 at Misa HV side 400/220kV, 200 MVA ICT 1 LV side 5 at Silchar HV side 400/220kV, 200 MVA ICT 2 LV side 6 at Silchar HV side 220/132kV, 50 MVA ICT 1 LV side 7 at Salakati HV side 8 9 10 11 12 13 14 15 16 17 LV side 220/132kV, 50 MVA ICT 2 at Salakati HV side 220/132kV, 100 MVA ICT 1 at Dimapur 220/132kV, 100 MVA ICT 2 at Dimapur 132/33 kV, 15 MVA ICT at Ziro 132/33 kV, 5 MVA ICT at Kumarghat 132/33 kV, 16 MVA ICT at Nirjuli 132/33 kV, 10 MVA ICT at Nirjuli 220/132 kV, 160 MVA ICT at Kopili 132/33 kV, 50 MVA ICT 1 at Imphal 132/33 kV, 50 MVA ICT 2 at Imphal LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side Differential Protection exits (Yes/No) Over Fluxing Protection exits (Yes/No) REF Protection exists (Yes/No) Directional Over Current Protection exits (Yes/No) Yes, P643 Yes Yes, P643 Yes Yes, DuoBias-M Yes, DuoBias-M Yes Yes Yes, P643 Yes Yes, P633 P127 Yes, P633 Yes Yes, P633 P127 Yes, P643 Yes Yes, DuoBias-M/PC 05770 Yes Yes, DTH-31 Yes Yes, RET670 Yes Yes, P643 Yes Yes, DTH Yes Yes, P643 Yes Yes, P643 Yes Yes, RET670 Yes Yes, P632 P127 Yes, P632 P127 Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side 1. Owner of Transformer : TSECL Assam, AEGCL 8. 25 MVA 132/33 KV 1 Budhjungnagar 25 MVA 132/33 KV 15 MVA 132/33 KV 2 Jirania 15 MVA 132/11 KV 15 MVA 3 Gamaitila 132/11 KV 25 MVA 132/33 KV 4 Ambassa 7.5/2.5/5 MVA 15 MVA 132/33 KV 5 P K Bari 15 MVA 132/11 KV 15 MVA 132/33 KV 7.5/2.5/5 6 Kailashahar MVA 7.5/2.5/5 MVA 7.5/2.5/5 MVA 7.5/2.5/5 MVA 7 Missiontilla 7.5/2.5/5 MVA 25 MVA 132/33 KV 10 MVA 132/11 KV 8 Kamalpur 10 MVA 132/11 KV 15 MVA 132/11 KV 9 Dhalabil 7.5 MVA 132/33 KV Differential Protection exits (Yes/No) Over Fluxing Protection exits (Yes/No) REF Protection exists (Yes/No) Directional Over Current Protection exits (Yes/No) LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side LV side HV side Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes No Yes No Yes No Yes No Yes No No No No No No No No No No No No No No No No No No No No No No No No No No Yes No Yes No Yes Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No Yes at tertiary No No No No No No Yes at tertiary Yes at tertiary Yes at tertiary Yes at tertiary Yes at tertiary No No No No No No No No No No Transformer Protection Details Sl. No. Name of Transformer LV side/ HV side Differential Protection exits (Yes/No) Over Fluxing Protection exits (Yes/No) REF Protection exists (Yes/No) Directional Over Current Protection exits (Yes/No) Annexure II MOG Tertiary Impedance Buchholz WTI OTI with low OSR for Overload PRD Winding Protection Operation Protection Protection oil level OLTC SA exists Alarm exists Protection exists exits exists exists alarm exists (Yes/No) exists (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) 1. Owner of Transformer : Assam, AEGCL 15 MVA LV side Yes No No No No No No 132/11 KV HV side Yes No Yes No No Yes Yes 10 Udaipur 15 MVA LV side Yes No No No No No No 132/11 KV HV side Yes No Yes No No Yes Yes 50 MVA LV side Yes No Yes No No No No 132/33 KV HV side Yes No No No No Yes Yes 11 Surjyamaninagar 50 MVA LV side Yes No Yes No No No No 132/33 KV HV side Yes No No No No Yes Yes 25 MVA LV side Yes No No No No No No 132/33 KV HV side Yes No Yes No No Yes Yes 15 MVA LV side Yes No No No No No No 132/11 KV HV side Yes No Yes No No Yes Yes 15 MVA LV side Yes No No No No No No 132/33 KV HV side Yes No Yes No No Yes Yes 12 Grid, 79 Tilla 15 MVA LV side Yes No No No No No No 132/33 KV HV side Yes No Yes No No Yes Yes 15 MVA LV side Yes No No No No No No 132/33 KV HV side Yes No Yes No No Yes Yes 25 MVA LV side Yes No No No No No No 132/33 KV HV side Yes No Yes No No Yes Yes Note : 1. REF : Restricted Earth Fault, 2. WTI : Winding Temperature Indicator., 3. OTI : Oil Temperature Indicator) 4. MOG : Magnetic Oil Gauge, 5. OSR : Oil Surge Relay, 6. OLTC : On Load Tap Changer 7. PRD : Pressure Relieve Device, 8. SA : Surge Arrestor 9. List of inbuilt features of Numerical Relays are also to be furnished alongwith this format No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No No No No No No No No No No No No No No No No No No No No No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No No No No No No No No Reactor Protection Details Sl. No. Name of Line Reactor/ Bus Reactor/ Tertiary Reactor Differential Protection exists (Yes/No) Annexure II REF Definite Time Earth Fault Buchholz WTI OTI MOG with Protection Over Current Protection Operation Protection Protection low oil level SA exists exists Protection exists exists exists exists exists alarm exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) 1. Owner of Reactor : Assam, AEGCL 400 kV Silchar - Azara (Mirza) 1 line reactor of 63 MVAR at Yes Yes Azara (Mirza) end Bus Reactor of 63 MVAR at 2 Yes Yes Azara (Mirza) Bus Reactor I & II of 12.5 3 MVAR at Mariani Bus Reactor I & II of 12.5 4 MVAR at Samaguri Bus Reactor I & II of 12.5 5 MVAR at Mariani 2. Owner of Reactor/ Capacitor Bank : Meghalaya, MePTCL 63 MVAR Bus Reactor at 1 Killing (Byrnihat) 132KV Capacitor Bank at 2 No No Mawlai 132KV Capacitor Bank at EPIP 3 No No I 132KV Capacitor Bank at EPIP 4 No No II Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes REACTOR NOT IN OPERATION REACTOR NOT IN OPERATION REACTOR NOT IN OPERATION Yes Yes No No No No Yes Yes Yes No No No No Yes Yes Yes No No No No Yes Reactor Protection Details Sl. No. Name of Line Reactor/ Bus Reactor/ Tertiary Reactor Differential Protection exists (Yes/No) 1. Owner of Reactor :NEEPCO : Assam, AEGCL 3. 50 MVAR line Reactor -I in 1 400 kV Balipara-RHEP I at Yes Ranganadi end 50 MVAR line Reactor -II in 2 400 kV Balipara-RHEP II at Yes Ranganadi end 4. Owner of BUS Reactors :POWERGRID Yes, 50 MVAR 400 kV Bus Reactor1 Differential I at Bongaigaon SS (CAG) Yes, 50 MVAR 400kV Bus Reactor2 Differential II at Bongaigaon SS (CAG) Yes, 80 MVAR 400 kV Bus Reactor3 Differential 3 at Bongaigaon SS (CAG) Yes, 80 MVAR 400kV Bus Reactor4 Differential 4 at Bongaigaon SS (CAG) Yes, 50 MVAR 400kV Bus Reactor5 Differential 1 Balipara SS (CAG) Yes, 80 MVAR 400kV Bus Reactor6 Differential 2 Balipara SS (CAG) Yes, 50 MVAR 400kV Bus Reactor 7 Differential Misa SS (CAG) Annexure II REF Definite Time Earth Fault Buchholz WTI OTI MOG with Protection Over Current Protection Operation Protection Protection low oil level SA exists exists Protection exists exists exists exists exists alarm exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) Yes No No Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Reactor Protection Details Sl. No. Name of Line Reactor/ Bus Reactor/ Tertiary Reactor Differential Protection exists (Yes/No) 1. Owner of Reactor : Assam, AEGCL Yes, 63 MVAR 400kV Bus Reactor8 Differential 1 Sichar SS (CAG) Yes, 63 MVAR 400kV Bus Reactor9 Differential 2 Sichar SS (P633) Yes, 20 MVAR 220 kV Bus Reactor 10 Differential at Mariani SS (P632) Yes, 20 MVAR 132kV Bus Reactor 11 Differential Kumarghat SS (CAG) Yes, 20 MVAR 132kV Bus Reactor 12 Differential Aizwal SS (CAG) Yes, 20 MVAR 132kV Bus Reactor 13 Differential Imphal SS (P633) Yes, 20 MVAR 132kV Bus Reactor 14 Differential Ziro SS (P633) Yes, 15 25 MVAR 33kV Reactor-Misa Differential (CAG) Yes, 25 MVAR 33kV Reactor16 Differential Balipara (CAG) Annexure II REF Definite Time Earth Fault Buchholz WTI OTI MOG with Protection Over Current Protection Operation Protection Protection low oil level SA exists exists Protection exists exists exists exists exists alarm exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) Reactor Protection Details Sl. No. Name of Line Reactor/ Bus Reactor/ Tertiary Reactor Differential Protection exists (Yes/No) 1. Owner of Reactor : Assam, AEGCL Yes, 25 MVAR 33kV Reactor17 Differential Bongaiagaon (CAG) 5. Owner of Line Reactors: POWERGRID Yes , Differential (CAG) Yes, 50 MVAR 400 KV D/C MisaDifferential Mariani (CAG) Yes, 63/50 MVAR 400 KV D/C Differential Balipara-Bongaigaon-I (CAG34AF71 A) Yes, 63/50 MVAR 400 KV D/C Differential Balipara-Bongaigaon-II (CAG34AF71 A) Yes, 63 MVAR 400 KV D/C Differential Balipara-Bongaigaon-3 (CAG34AF71 A) Yes, 63 MVAR 400 KV D/C Differential Balipara-Bongaigaon-4 (CAG34AF71 A) Yes, 50 MVAR 400KV D/C Differential Balipara-Ranganadi-I (DTH31) 50 MVAR 400 KV D/C Misa1 Kathalguri 2 3 4 5 6 7 Annexure II REF Definite Time Earth Fault Buchholz WTI OTI MOG with Protection Over Current Protection Operation Protection Protection low oil level SA exists exists Protection exists exists exists exists exists alarm exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) Reactor Protection Details Sl. No. Name of Line Reactor/ Bus Reactor/ Tertiary Reactor Differential Protection exists (Yes/No) 1. Owner of Reactor : Assam, AEGCL Yes, 50 MVAR 400KV D/C 8 Differential Balipara-Ranganadi-II (DTH31) Yes, 63 MVAR 400kV Bongaigaon9 Differential Siliguri - I (CAG3471) Yes, 63 MVAR 400kV Bongaigaon10 Differential Siliguri - II (CAG3471) Yes, 63 MVAR 400kV Bongaigaon11 Differential Azara (CAG3471) Yes, 63 MVAR 400kV Bongaigaon12 Differential Byrnihat (CAG3471) Yes, 50 MVAR 400kV SilChar13 Differential Azara (CAG3471) Yes, 50 MVAR 400kV Sichar14 Differential Byrnihat (CAG3471) Yes, 50 MVAR 400kV SilChar13 Differential Pallatana-1 (P633) Yes, 50 MVAR 400kV SilChar14 Differential Pallatana-1 (P633) Annexure II REF Definite Time Earth Fault Buchholz WTI OTI MOG with Protection Over Current Protection Operation Protection Protection low oil level SA exists exists Protection exists exists exists exists exists alarm exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) Reactor Protection Details Sl. No. Name of Line Reactor/ Bus Reactor/ Tertiary Reactor Differential Protection exists (Yes/No) Annexure II REF Definite Time Earth Fault Buchholz WTI OTI MOG with Protection Over Current Protection Operation Protection Protection low oil level SA exists exists Protection exists exists exists exists exists alarm exists (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) (Yes/No) 1. Owner of Reactor : Assam, AEGCL Note : 1. REF : Restricted Earth Fault, 2. WTI : Winding Temperature Indicator., 3. OTI : Oil Temperature Indicator) 4. MOG : Magnetic Oil Gauge, 5. SA : Surge Arrestor 6. List of inbuilt features of Numerical Relays are also to be furnished alongwith this format Annexure II Bus Bar & Local Breaker Backup(LBB) Protection Details Sl.No. Name of Substation Voltage level 1. Owner of Bus Bar: MSPCL, Manipur 132 kV Bus Bar 1 Churachandpur 33 kV Bus Bar 132 kV Bus Bar 2 Jiribam 33 kV Bus Bar 132 kV Bus Bar 3 Kakching 33 kV Bus Bar 132 kV Bus Bar 4 Karong 33 kV Bus Bar 132 kV Bus Bar 5 Ningthoukong 33 kV Bus Bar 132 kV Bus Bar 6 Rengpang 33 kV Bus Bar 132 kV Bus Bar 7 Yaingangpokpi 33 kV Bus Bar 132 kV Bus Bar 8 Yurembam. 33 kV Bus Bar 132 kV Bus Bar 9 Kongba 33 kV Bus Bar 2. Owner of Bus Bar: MePTCL, Meghalaya 1 Mawlai 132 kV Bus Bar Bus Bar Protection exists (Yes/No) LBB Protection exists (Yes/No) No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No 2 NEHU 132 kV Bus Bar No No 3 NEIGRIHMS 132 kV Bus Bar No No 4 Khliehriat 132 kV Bus Bar No No 5 Lumshnong 132 kV Bus Bar No No 6 Umiam 132 kV Bus Bar No No 7 Mawphlang 132 kV Bus Bar No No 8 Cherra 132 kV Bus Bar No No 9 Nongstoin 132 kV Bus Bar No No 10 Nangal 132 kV Bus Bar No No 11 Rongkhon 132 kV Bus Bar No No 12 EPIP-I 132 kV Bus Bar No No 13 EPIP-II 132 kV Bus Bar No No 14 Stage-I PH 132 kV Bus Bar No No 15 Stage-II PH 132 kV Bus Bar No No 16 Stage-III PH 132 kV Bus Bar No No 17 Stage-IV PH 132 kV Bus Bar No No 18 Umtru PH 132 kV Bus Bar No No 19 Leshka PH 132 kV Bus Bar No No Bus Bar & Local Breaker Backup(LBB) Protection Details Sl.No. Name of Substation Voltage level 1. Owner of Bus Bar: MSPCL, 132Manipur kV Bus Bar 20 Killing 220 kV Bus Bar 3. Owner of Bus Bar: P&E, Mizoram 132 kV Bus Bar 1 Kolasib 66 kV Bus Bar 33 kV Bus Bar 132 kV Bus Bar 2 Luangmual 33 kV Bus Bar 132 kV Bus Bar 3 Lunglei 33 kV Bus Bar 132 kV Bus Bar 4 Serchip 33 kV Bus Bar 132 kV Bus Bar 5 Saitul 33 kV Bus Bar 132 kV Bus Bar 6 Zemabawk 33 kV Bus Bar 132 kV Bus Bar 7 Bairabi 33 kV Bus Bar 132 kV Bus Bar 8 Khawzawl 33 kV Bus Bar 4. Owner of Bus Bar: NEEPCO 400 kV Bus Bar 1 Ranganadi 132 kV Bus Bar 2 AGBPP 220 kV Bus Bar 3 AGTPP 132 kV Bus Bar 5. Owner of Bus Bar: NHPC 1 Loktak 132 kV Bus Bar 6. Owner of Bus Bar: POWEWRGRID 1 Aizawl 132 kV Bus Bar 2 Badarpur 132 kV Bus Bar 400 kV Bus Bar 3 Balipara 220 kV Bus Bar 4 Bongaigaon 400 kV Bus Bar 5 Biswanath Chariali 6 Dimapur 7 8 9 10 11 12 13 Haflong Imphal Jiribam Khliehriat Kumarghat Mariani Melriat 220 kV Bus Bar 132 kV Bus Bar 132 kV Bus Bar 132 kV Bus Bar 132 kV Bus Bar 132 kV Bus Bar 132 kV Bus Bar 220 kV Bus Bar 132 kV Bus Bar Bus Bar Protection exists (Yes/No) LBB Protection exists (Yes/No) Yes No Yes No No No No No No No No No No No No No No Yes (EM) No No No No No No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Bus Bar & Local Breaker Backup(LBB) Protection Details Sl.No. Name of Substation Voltage level 1. Owner of Bus Bar: MSPCL, 400Manipur kV Bus Bar 14 Misa 220 kV Bus Bar 220 kV Bus Bar 15 Mokokchung 132 kV Bus Bar 16 Namsai 132 kV Bus Bar 17 Nirjuli 132 kV Bus Bar 18 Roing 132 kV Bus Bar 19 Salakati 220 kV Bus Bar 400 kV Bus Bar 20 Silchar 132 kV Bus Bar 21 Tezu 132 kV Bus Bar 22 Ziro 132kV Bus Bar Bus Bar Protection exists (Yes/No) LBB Protection exists (Yes/No) Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Annexure -A.9 (II) Bus Coupler Protection Details Sl.No. Name of Substation Voltage level 1. Owner of Bus Coupler: MSPCL, Manipur 132 kV Bus Coupler 1 Churachandpur 33 kV Bus Coupler 132 kV Bus Coupler 2 Jiribam 33 kV Bus Coupler 132 kV Bus Coupler 3 Kakching 33 kV Bus Coupler 132 kV Bus Coupler 4 Karong 33 kV Bus Coupler 132 kV Bus Coupler 5 Ningthoukong 33 kV Bus Coupler 132 kV Bus Coupler 6 Rengpang 33 kV Bus Coupler 132 kV Bus Coupler 7 Yaingangpokpi 33 kV Bus Coupler 132 kV Bus Coupler 8 Yurembam. 33 kV Bus Coupler 132 kV Bus Coupler 9 Kongba 33 kV Bus Coupler 2. Owner of Bus Coupler: MePTCL, Meghalaya 1 Mawlai 132 kV Bus Coupler Non directional O/C Protection exists (Yes/No) Non directional E/F Protection exists (Yes/No) No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No 2 NEHU 132 kV Bus Coupler Yes Yes 3 NEIGRIHMS 132 kV Bus Coupler No No 4 Khliehriat 132 kV Bus Coupler No No 5 Lumshnong 132 kV Bus Coupler No No 6 Umiam 132 kV Bus Coupler No No 7 Mawphlang 132 kV Bus Coupler Yes Yes 8 Cherra 132 kV Bus Coupler No No 9 Nongstoin 132 kV Bus Coupler No No 10 Nangal 132 kV Bus Coupler No No 11 Rongkhon 132 kV Bus Coupler No No 12 EPIP-I 132 kV Bus Coupler No No 13 EPIP-II 132 kV Bus Coupler No No 14 Stage-I PH 132 kV Bus Coupler Yes Yes 15 Stage-II PH 132 kV Bus Coupler Yes Yes 16 Stage-III PH 132 kV Bus Coupler Yes Yes 17 Stage-IV PH 132 kV Bus Coupler Yes Yes 18 Umtru PH 132 kV Bus Coupler No No Bus Coupler Protection Details Non directional O/C Protection exists (Yes/No) Non directional E/F Protection exists (Yes/No) 1. Owner of BusPH Coupler: MSPCL, 19 Leshka 132 kVManipur Bus Coupler Yes Yes 132 kV Bus Coupler Yes Yes 220 kV Bus Coupler Yes Yes 3. Owner of Bus Coupler: P&E, Mizoram 132 kV Bus Coupler 1 Kolasib 66 kV Bus Coupler 33 kV Bus Coupler 132 kV Bus Coupler 2 Luangmual 33 kV Bus Coupler 132 kV Bus Coupler 3 Lunglei 33 kV Bus Coupler 132 kV Bus Coupler 4 Serchip 33 kV Bus Coupler 132 kV Bus Coupler 5 Saitul 33 kV Bus Coupler 132 kV Bus Coupler 6 Zemabawk 33 kV Bus Coupler 132 kV Bus Coupler 7 Bairabi 33 kV Bus Coupler 132 kV Bus Coupler 8 Khawzawl 33 kV Bus Coupler 4. Owner of Bus Coupler: NEEPCO Yes No No No No Yes No Yes No No No No No No No No No Yes No No No No Yes No Yes No No No No No No No No No Buscoupler Backup Protection (50/51A,B,C) Directional O/C Protection Yes Yes Buscoupler Backup Protection (50/51N) Directional E/F Protection Yes Yes Yes Yes Sl.No. Name of Substation 20 Killing Voltage level 400 kV Bus Coupler 1 Ranganadi 132 kV Bus Coupler 2 3 AGBPP AGTPP 220 kV Bus Bar 132 kV Bus Bar 5. Owner of Bus Coupler: NHPC 1 Loktak 132 kV Bus Coupler
© Copyright 2024