Hartley and Sugden CAST IRON OIL-FIRED BOILER Commodore Plus INSTALLATION COMMISSIONING Commodore Plus (uk) - 1007-01 AND OPERATING MANUAL Hartley and Sugden CONTENTS Page 1. Technical data ............................................................................................4 2. Layout of the heating installation of the boiler ...........................................5 3. Assembly of the boiler ...............................................................................7 4. Hydraulic installation of the boiler ........................................................... 23 5. Protection of chimneys against internal condensations ...........................26 6. Electrical connections .............................................................................. 27 7. Spare parts list ......................................................................................... 31 8. Maintenance ............................................................................................. 36 9. Guarantee conditions on the products.....................................................36 User's advices - The boiler must be installedand commissioned bya registered installer in accordance with instructions herewith. It is important for the safe operation of boilers that there is sufficient fresh air inlet and ventilation provided. Maintenance of the boiler should be done once or twice a year, depending on the conditions of use. It is inadvisable to regularly drain down the boiler as frequent additions of fresh water may bring about the premature deterioration of the boiler fabric through the deposit of mineral substances present in the water. Precautions must be taken to avoid any damage that might be caused by frost . Hartley and Sugden General rules The flues of the products of combustion must be calculated and carried out according to the standards in force, the local obligations and the regulations of the manufacturer. The hydraulic installations, fuel or gases will be established according to standards of installation and safety in force in the country of use. Page 3 / 36 Hartley and Sugden 1. Technical data 9 2 8 10 9 15 5 3 1 7 111 Outlet (3") Flue 1165 830 719 Ø 180 55 8 1007 4 83 8 6 399 38 8 Inlet (3") 5 900 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 88 63 321 450 321 450 1253* 1295 * : n° 7-8 inter (+260 mm) : n° 9-10 inter (+520 mm) : n° 11-12 inter (+780 mm) : n° 13-14 inter (+1040 mm) Main switch with on/off light Boiler thermometer Safety limit with manual reset (110°C ) Burner opening: diam. 170 mm standard. Opening drain cock: 3/4" Eyepiece to view flame First step thermostat (e.g. of adjustment : 80°C) Second step thermostat Place foreseen for the control system Place foreseen for hour meters Type ABC 122 132 241 242 234 244 335 345 355 455 Total numb. section 5 6 7 8 9 10 11 12 13 14 Net heat output (kW) 200,0 237,5 275,0 312,5 350,0 387,5 425,0 462,5 500,0 537,5 REMARK: The temperature adjusted on the second step thermostat H/L (switch nr. 8) should be lower than the one on the first step thermostat (switch nr. 7). Boiler dimension (mm) Height 1165 1165 1165 1165 1165 1165 1165 1165 1165 1165 Width 900 900 900 900 900 900 900 900 900 900 Maximum water temperature: 90°C; maximum installation pressure: 4 bar Dim. chambre de combustion Depth 1300 1300 1560 1560 1820 1820 2080 2080 2340 2340 Ø 400 400 400 400 400 400 400 400 400 400 Depth 790 920 1050 1180 1310 1440 1570 1700 1830 1960 A = number of front inter sections B = number of middle inter sections C = number of rear inter sections Commodore Plus N° 122 132 241 242 234 244 335 345 355 455 Max. heat input (kW) 178 225 246 278 312 340 375 407 430 474 Net heat output (kW) 162 204 224 253 283 310 339 371 394 432 Net heat output (kW) to 1*CE 92/42 (*) 200 237,5 275 312,5 350 387,5 425 462,5 500 537,5 Number of sections 7 8 9 10 11 12 13 14 15 16 Furnace pressure (mbar) 2,9 3,50 2,20 2,60 3,70 3,50 3,60 4,40 4,60 4,60 ǻ T ° flue - T° ambiance 156 160 156 161 160 152 162 153 141 150 Load losses water side (mbar) ǻT 15°C 4,5 7,1 8,5 14 16,7 19,5 22,6 26,7 29,6 35 Exit flue gas mass flow (g/s) 75 97 103 116 132 147 163 176 185 205 Combustion circuit (dm³) 195 226 258 290 322 354 386 418 450 482 Relative standby loss (%) 0,6 0,51 0,48 0,44 0,4 0,38 0,35 0,32 0,3 0,29 Water capacity of the boiler (l) 115 130 145 160 175 190 205 220 235 250 Heating body weight (kg) 705 800 895 980 1060 1150 1240 1330 1420 1510 Maximum water temperature: 90°C; maximum installation pressure: 4 bar (*) : for indication Page 4 / 36 Hartley and Sugden 2. Layout of the heating installation of the boiler The boiler must be installed and commissioned by a registered installer. The installer must make the necessary arrangements on site to ensure that the positioning and the fitting of the boiler, the supply of combustion air, ventilation of the boiler house, connection of the gas supply and the removal of the combustion gases via the flue system are all in conformity with the prevailing regulations and standards. In the following paragraphs, Saint We remind you of some rules concerning the above aspects. If the conditions summarised above are not strictly adhered to and resulting damage occurs then our guarantee would be invalidated. 2.1. Positioning The boiler must not be installed in areas where there is a significant risk of frost damage or where there is a risk of the combustion air being contaminated with halogenated substances (e.g. chlorine, detergents, aerosols, etc.), printing establishments, dry cleaning establishments, laboratories, etc..., unless sufficient measures have been taken to ensure the supply of unpolluted combustion air. 2.2. Aeration and ventilation of the boiler room It is important for the safe operation that there are sufficient areas of fresh air inlet and ventilation provided to the room in which the boiler is installed. 2.3. Installation of the boiler The boiler must be positioned in accordance with prevailing standards, as far as possible from any wall surface that may be damaged by heat (wood, etc...); if necessary cover the wall with an insulated panel. The boiler must be placed in such a way that it can easily be maintained and regularly checked. 2.4. Warning of the extractors and burners When using combustion gas extractors, it is necessary to control to the extractors the functioning of the burners, so that those ones cannot start if the extractors have not been brought into service beforehand and that they stop immediately in the event of stop of the extractors. 2.5. Non-specific burners compatibility When using a non-specified burner - i.e. a burner which has not been supplied with the boiler, the installer must satisfy himself that he has chosen technical compatible equipment and verify the operation of the equipment after start up. 2.6. Thermal shocks and corrosion on combustion produce side For burners it is necessary to limit the fuel flow rate, taking the efficiency into account so that the instantaneous output of the burner cannot exceed the normal or maximum boiler output or peak boiler output as determined by the manufacturer. Page 5 / 36 Hartley and Sugden 2.7. Discharge of combustion products The chimney will be determined (height and section) in function of the boiler used, it will be capable of discharging the combustion gases, maintaining a vacuum in the furnace (see "draught losses" in the table page 3). If it is impossible to provide sufficient vacuum, it is possible to use a flue gas extractor, the characteristics of this one will be given in function of the boiler to connect. TEMPERATURE OF SMOKE : 160° C OUTPUT (mm) HEIGHT (m) Page 6 / 36 Hartley and Sugden 3. Assembly of the boiler A 3.1. Cast iron body installation - A base must be built according to good engineering practice, considering the dimensions and the weight of the heating boiler - Start the installation with the rear boiler section (A1) 1. Position the rear boiler section vertically at the chosen place, also determined by the overall dimensions of the boiler (jacket included). 2. Coat the section ribs with adhesive (supplied with the installation accessories) and attach the lengths of sealing cord ( code n° 1-30-240-60410 / Ø 10mm ) in the section ribs. Carefully degrease the double-taper nipples and bores. Coat the nipples with compound ( supplied with the installation accessories ). Drive the double-taper nipples into the bores using a mallet or a hammer. It is extremely important that the nipples should be driven in smoothly and exactly in the centre line of the bore. Page 7 / 36 Hartley and Sugden 3. Insert the rear intermediate section ( attention with the visual code on the section ). 4. 5. Coat the section ribs with adhesive (supplied with the installation accessories) and attach the lengths of sealing cord ( code n° 1-30-240-60410 / Ø 10mm ) in the section ribs. Carefully degrease the double-taper nipples and bores. Coat the nipples with compound ( supplied with the installation accessories ). Drive the double-taper nipples into the bores using a mallet or a hammer. It is extremely important that the nipples should be driven in smoothly and exactly in the centre line of the bore. Repeat the operation according to the number of rear inter, see table page 3 in our exampleof illustration : 2 x. Page 8 / 36 Hartley and Sugden Follow the same procedure as for the points 3 to 5 for the inter middle sections and front inter by taking care to check well the visual code on the cast-iron section: 6. - front inter section - middle inter section 7. 9. 8. 10. Page 9 / 36 Hartley and Sugden 11. 13. 12. 14. Insert the front section. Install the assembly equipment according to the drawing hereafter and tighten the nuts of both mounting bars at the same time. Page 10 / 36 Hartley and Sugden 15. Installation of the tie rods for assembly of the cast iron body. Insert the 4 tie rods in the lugs of the front and rear sections. On the front face : 4 plain washers M16. 4 nuts DIN934 M16. On the rear face : 4 plain washers M16. 4 nuts DIN934 M16. Once the tie rods have been installed, unscrew the nut of the mounting bar and remove the front plate. Remove the mounting bars. 16. Flue gas box installation. Screwthe 2 studsDIN 939 12x90 ( code n° 1-80-300-12090 ) into the tapped holes in the rear section, the end with the shortest thread in the section. 17. Placethe siliconed rope Ø14mm(code 1-30-240-60114) in the throat of the flue gas box and fix this one with help of 2 washers M12 and 2 nuts DIN934 M12. Page 11 / 36 Hartley and Sugden 18. Place the tube of 3s with its flange on the boiler outlet. According to the configurations, there might be an inlet water injector, this one is always placed on the boiler inlet. If no inlet water injector in the configuration, place the second tube of 3s with its flange on the boiler inlet. Type Pipe injectors Pipe injectors Pipe injectors L = 70 mm L = 140 mm L = 190 mm 122 132 241 242 234 244 335 345 355 455 X X X X X X X 19. Place the plunger in the foreseen opening on the rear section, place a plug with hexagon head of 2s on the front section in upper part and a fitting reduction from 2sto 3/4s as well as a draincock 3/4sin lower part. 20. Screw the 2 hinges into the tapped holes in the front section ( left or right side according to the direction opening selected). Respect the distance of 60mm as showed on fig 21b. then place the washer M16 and the nut M16 to block la rotation of the hinge. 20b. 60 Page 12 / 36 Hartley and Sugden 21. Place 2 insulations in the burner fixing flange then come to place the door insulation by sticking it on the door, see fig. 21A. Place the rope Ø 20mm (code 1-30-240-60120) in the groove of the door insulation. Position the door on the hinges. 21A. ZONE TO AFFIX THE GLUE IN ORDER TO AVOID THE COMBUSTION GAS LEAKAGES 22. Tighten the door against the front section with help of screws M16x120 and washers M16. Then place the sight flame according to fig. 22A. 22A. 3.2. Hydraulic test - After having assembled the cast iron block, the boiler must be subjected to an hydraulic pressure test higher than 30%of the maximum installation pressure i.e. 1,3 x 4 = 5,2 bar , this before assembly of the insulation and the mantle. During this operation, no defect of leaks must appear. Page 13 / 36 Hartley and Sugden 3.3. Jacket installation Commodore Plus Casing composition Commodore Plus Basic parcel = casing (122-132) Extension Lg: 260mm 4-15-000-10006 4-15-000-10026 Extension Lg: 520mm 4-15-000-10052 Number of intermediate sections n° 5 (122) n° 6 (132) n° 7 (241) n° 8 (242) n° 9 (234) n° 10 (244) n° 11 (335) n° 12 (345) n° 13 (355) n° 14 (455) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 - 1 1 1 1 2 2 3.3.1. Insulation installation (mantle) 1. Place the insulation around the heating body while taking care to engage this one below the heating body. 2. Bind it with 3 (6) tapes (see schema here under). Caution the first(s) tape(s) A, must be at +/- 5 cm of the edge of the insulation. 3. Place the rear insulation on the rear section 4. Place the 2 rear tapes (see schema here under : example for a 132 (6) model). Pull Pull Assembly hooping and buckles reinforced: tightening DO NOT TIGHTEN TOO MUCH TO OBTAIN OPTIMAL INSULATION Page 14 / 36 Hartley and Sugden 3.3.2. Sectional drawing for the Commodore Plus 5 & 6 (122 - 132) A DÉTAIL F ECHELLE 1 : 4 Nb: The right and left lower and upper guides are locatable thanks to the square cutting of 10 x 10 in the middle of the guide and on the upper edge of the panels. Page 15 / 36 Hartley and Sugden 3.3.3. Assembled view Commodore n° 5 & 6 (122 - 132) Commodore n° 7 & 8 (241 - 242) Page 16 / 36 Hartley and Sugden Commodore n° 9 & 10 (234 - 244) Commodore n° 11 & 12 (335 - 345) Page 17 / 36 Hartley and Sugden Commodore n° 13 & 14 (355 - 455) Page 18 / 36 Hartley and Sugden 3.3.4. Assembly of the panels and plates 1. Fixing of the front right lower guide support on the front castiron section (fold backwards). - 1 Tensilock screw M8X12 2 1 2. Fixing of the front left lower guide support on the front cast-iron section (fold backwards). - 1 Tensilock screw M8X12 1 3. Fixing of the rear left lower guide support on the rear castiron section (fold inside). - 1 Tensilock screw M8X12 4. Fixing of the rear right lower guide support on the rear cast-iron section (fold inside). - 1 Tensilock screw M8X12 4 3 NB : the front right lower guide supports are the same as the rear left. the front left lower guide supports are the same as the rear right. 5. Fixing of the upper guide support on the front cast-iron section (fold backwards). - 2 nuts M16 - 2 washers M16 5 6. Fixing of the upper guide support on the rear cast-iron section (fold backwards). - 2 nuts M16 - 2 washers M16 6 7. Fixing of the left lower guide. - 2 Parker screws 4.2X10 7 7 rear part front part 8. Fixing of the right lower guide. - 2 Parker screws 4.2X10 8 front part 8 rear part Page 19 / 36 Hartley and Sugden 9 9. Fixing of the left upper guide. - 2 Parker screws 4.2X10 9 rear part front part 10. Fixing of the right upper guide. - 2 Parker screws 4.2X10 10 10 front part rear part 10 11. Placing of the set screw at the bottom of the 2 upper guides. Screw only 2 times - 2 Parker screws 4.2X10 12. Placing of the centering studs on the panels. 12.1.Screw the M4 screw on the centering stud (drawing A) (do not block). 12.2. Insert the unit (stud external side) in the oblong hole (drawing B), Slip the unit in the back of the oblong and tighten the thrust screw M4 (drawing C). - from 4 to 12 centering studs Ø8X16 (M4) according to model. 4 centering studs for the Commodore Plus 5 & 6, 8 centering studs for the Commodore Plus 7, 8, 9 & 10, 12 centering studs for the Commodore Plus 11, 12, 13 & 14. - from 4 to 12 thrust screws M4X6 according to model. 4 thrust screws for the Commodore Plus 5 & 6, 8 thrust screws for the Commodore Plus 7, 8, 9 & 10, 12 thrust screws for the Commodore Plus 11, 12, 13 & 14. 13. Encase the upper and lower slide from the right rear panel on the right lower and upper guides and make slip this one against the Parker screw 4.2x10 fixed at the end of the right guide. (rear panel locatable thanks to the oblong hole on upper edge detail A). 11 A C B A 13 13 Page 20 / 36 Hartley and Sugden 14. Proceed in the same way for the intermediate panel(s). 15. Proceed in the same way for the front panel. 16. Tighten the right front panel ahead on the lower and upper guide - 2 Parker screws 4.2X10 16 16 17. Place and screw the rear lower plate. - 6 Parker screws 4.2X10 17 18. Place and screw the rear upper plate. - 6 Parker screws 4.2X10 18 19. Assembly of the centering studs on the covers. - from 10 to 22 centering studs Ø8X16 (M4) according to model. 10 centering studs for the Commodore Plus 5 & 6, 16 centering studs for the Commodore Plus 7 , 8, 9 & 10, 22 centering studs for the Commodore Plus 11, 12, 13 & 14. - from 10 to 22 thrust screws M4X6 according to model 10 thrust screws for the Commodore Plus 5 & 6, 16 thrust screws for the Commodore Plus 7, 8, 9 & 10, 22 thrust screws for the Commodore Plus 11, 12, 13 & 14. 19 front door rear door 20. Place the front cover (A). 20 A Example for n° 122 (5 inter) - 132 (6) Page 21 / 36 Hartley and Sugden 21. Fix the control panel on the front cover. - 2 Parker screws 4.2X10 21 22. Placing of the sensors of the control panel in the plunger placed in the higher part of the rear element. 22 23. Placing of the rectangular panel for the sensors in the plunger. Rectangular panel for plunger 3/4" 24. Placing of the clips for plunger. 1 copper clips for plunger 3/4" 24 25. Placing of the intermediate covers and rear cover according to model. Page 22 / 36 Hartley and Sugden 4. Hydraulic installation of the boiler General points The installer must provide a safety valve in the flow outlet prior to any valve or connection to any hydraulic appliance. The installation must be designed in such a way that the filling and addition of water to the system takes place as infrequently as possible and must always be strictly controlled. Any uncontrolled automatic filling of the system is prohibited. Should the boiler be connected to an existing heating installation, it is necessary to carry out a careful flushing of the system in order to eliminate all impurities and sludge deposit which maybe present. Such deposits, if allowed to remain could accumulate in the boiler and cause overheating, corrosion and noises. In order to avoid the complete emptying of the system (in the event of problems occurring with the boiler or the heating circuit), We recommend : - the installation of isolating valves on the boiler flow and return connections. - hydraulic insulation of one of several circulating pumps. All necessary precautions must be taken to prevent : - Gases accumulation in the top part of the boiler - Deposits of sludge in the bottom part of the boiler. Filling of the installation Prior to the final filling of the installation we recommend on both existing and new installations that the system is completely flushed out and at the same time the water tightness of the system and hydraulic components verified. The maximum hydraulic operating pressure is (4 bar ( 4kg/cm2 ). However, it may prove necessary to adapt the operating pressure according to the characteristics of the installation, circulating pump and pressure of the expansion tank. With nitrogen the cold installation pressure must ALWAYS be higher than the nitrogen pressure of the expansion tank. During filling and when water is added to the system it will always be necessary to vent the air from the installation. Significant additions of water to the installation may bring about premature deterioration of the boiler with a deposit of mineral substances present in the water. These deposits lead to thermal and mechanical constraints, which may go as far as resulting in the cracking of the cast iron sections of the boiler. Characteristics of the water in the heating circuit In order to avoid all harmful furring-up and corrosion, one must take into account the characteristics of the water used in the heating circuit. The normal characteristics of the heating must be such that : - the THF (calcium carbonate or fur-content of the water) is less than 25° THF (2,5 mol/m³) - the resistivity is over 2,000 Ohm/cm. Should the THF-value be over 25° THF, a softening treatment for the water of the heating circuit is necessary. If the pH is lower than 7.2 and the resistivity is below 2,000 Ohm/cm and the THF-value is below 25° THF (either naturally or after softening), a treatment enabling these values to obtain or a treatment forming a film on the insides of the heating installation should be used. Furring-up and corrosion water side In order to avoid all furring-up and corrosion water side, one must take into account the characteristics of the water used. The installation will be designed in way that the fillings and additions of water be limited as possible and always controlable (water meter recommended). Any system not controlled of automatic water filling is prohibited. In all cases, a control of the addition of water must be envisaged. The expansion vessels overflows must be perfectly visible. If the conditions here above are not met, the frequent filling of the installation may involve deposits (scale deposits, mud, ...) in the boiler and compromise its life duration. Page 23 / 36 Hartley and Sugden A.Exampleof individual boiler commonpipe SWW commonpipe Page 24 / 36 Hartley and Sugden B.ExampleofEcogroup boilerapplication SWW ECOGROUP Type Commodore Plus Commodore Plus Commodore Plus Commodore Plus Commodore Plus Commodore Plus Commodore Plus Commodore Plus Commodore Plus Commodore Plus 122 132 241 242 234 244 335 345 355 455 Nominal output (kW) 162 204 224 253 283 310 339 371 394,5 432 Flow ǻ 20 k (m³/h) 6,966 8,772 9,632 10,879 12,169 13,33 14,577 15,953 16,9635 18,576 Recommended common pipe 1-60-390-69952 1-60-390-69952 1-60-390-69952 1-60-390-69952 1-60-390-69952 1-60-390-69952 1-60-390-69952 1-60-390-69952 1-60-390-69952 1-60-390-69952 Substantial savings can be made with Ecoset. These savings are obtained by splitting up the necessary output by regulating to optimize the operation of the equipment. ECOSET presents following advantages : - High performance - Safe operation - Startup savings - All-round installation possible - Efficient and appropriate regulation - Independant operation of each boiler in the set - Output adjusted to power demand - Possibility of supplying different circuits at different temperatures by means of a loop at constant or variable temperature depending on the outside temperature. Page 25 / 36 Hartley and Sugden 5. Protection of chimneys agains internal condensations The increase of boiler efficiency, the placing of an economy flap on the burners (stopping the admission of air when the burner is stopped and hence the draft into the chimney), the oversize capacity of the chimneys in relation to the reduction of the installed boiler yields, the influence of more powerful regulation devices on the functioning time of the burners, these are all parameters that necessitate the taking of certain precautions with a view to maximally reducing the risk of condensation inside the chimney with the connection of high performance boiler to chimneys, in particular when this involves existing chimneys. Precautions to be taken : 1. Setting burner output according to the nominal yield of the furnace. 2. Provide a draught stabilizer of a size according to the section of the chimney, that will: a) during the periods when the burner is working, stabilize the draught, reduce the dew point temperature of the water vapour by mixing of the combustion gases with ambient air. b)during the period when the burner is not working, ensure the ventilation of the chimney by ambient air (by setting the stabilizer to be not completely closed when the burner is stopped), which enables the remaining condensation to be removed). 3. Avoid the application of heightening tubes on chimneys which cause excessive cooling of the combustion gases. 4. In the case of a markedly oversized or particularly "cool" chimney (e.g. one situated next to an exterior wall), you are advised to provide an internal flue duct that must be placed according to the relevant technical prescriptions. Page 26 / 36 Hartley and Sugden 6. Electrical connections Remark: As far as Ecosets are concerned are the electrical connections of the circulation pump of the heating circuit made in the control box outisde the boiler control panel. The setting of the temperature on the high/lowthermostat (f.i. 65°C) has to be inferior to that of the first step thermostat (f.i. 80°C). In this way, if the boiler is cold and if there is a heat demand, the burner will start with its whole power and once the 65°C reached, it will continue to burn with reduced power until the water temperature of the flow rises to 80°C. If the heat demand is to important that the water temperature falls down instead of reaching 80°C, than the whole power will engage again. Wiring diagram : To burner Circulation pump heating circuit (not supplied) Power supply switch with phial 230V ca-50Hz Standard plug with 3 poles (not supplied) Remote thermostat (not supplied) L N L N 1 2 4 5 4 1 5 2 6 7 Standard plug with 7 poles (not supplied) B4 T6 T7 8 9 10 11 12 13 T8 T2 T1 Circulation pump water tank (not supplied) N L1 S3 B5 15 16 17 18 1 L N 20 21 2 P P 1 2 NT 174 HE/2 2nd step thermostat (30 - 90°C) 1 2 NT 174 HE/2 1st step thermostat (30 - 90°C) Remove the 4 bridges when you connect a digital regulator E9.0631 1 2 3 4 5 6 7 8 9 P Safety limit SP-051 HE (110°C) (*) If you connect a regulator E9.0631, remove the bridge between terminals 5 and 6 of the main connector block. Page 27 / 36 Hartley and Sugden 6.1. CONNECTION OF THE SAINT ROCH CLIMATIC REGULATOR The controlpanel ofthe Commodore Plus boilersis prewired to receive one ofthe optionalclimatic regulatorsE9.0300, E9.0631, GTC0 in place of the control panel precuts. 6.3.1. Components of climatic regulator HARTLEY & SUGDEN E9.0300 E9.0631 GTCO Remote control FBR2 delivered in option Climatic regulator delivered in option Tank probe SPFS delivered with the regulator External probe AFS delivered with the regulator Departure probe VFAS delivered with the regulator Boiler probe KFS delivered with the regulator In order to install this regulation, it is necessary to interpose between the boiler connector block and the regulator, a connection kit wired (9 poles) delivered with the regulator accessories. The E9.0300 and E9.0631 climatic regulators may be associated in option to a remote control with an ambient thermoresistor type FBR 2 connected on the regulator using 3 wires. Moreover, in the event of heating floor circuit, the regulator requires a valve servomotor SM 40 also available in option and connected with 4 wires. All components of the Hartley & Sugden control are easily accessible and the connections easy allowing a saving of time appreciable fort the fitter. Page 28 / 36 Hartley and Sugden 6.1.2. Connection kit of the regulator E9 10-poles connector regulator side E9.0300 / E9.0631 GTC 2 / GTC 3 II 9-poles connector (A) boiler side 8 11 9 12 7 ST 2 10 5 6 4 2 3 1 1 2 3 4 5 6 7 8 9 10 AMPconnector 12-poles (B) N PE N L1 PE circuit connector 2 controlled valve CONNECTION OF THE E9.0300 / E9.0631 REGULATOR ON THE COMMODORE PLUS BOILERS RANGE 1. 2. 3. 4. 5. 6. Remove the right cap on the control panel and engage the regulator in this housing. Remove the 9 poles male connector with its 4 bridges on the back of the control panel, or remove the S.W.W. priority Ventec module already connected. Connect the 9 poles connector (A) boiler side delivered with the regulator in the 9 poles female connector block of the boiler and tighten the screws. Connect the AMP 12 poles connector (B) delivered with the regulator in the AMP 12 poles plug of connector (A). Connect the 10 poles white connector on the connector block II of the regulator. Connect directly the following probes on the connector block I of the regulator. - AFS : external probe - KFS : boiler probe - SPFS : S.W.W. probe - VFAS : departure probe Connect the heating circulator to terminals 8 and 9 and if necessary the S.W.W. circulator to terminals 11 and 12 on the boiler 12 poles connector block ( back of the control panel ). GENERAL REMARKS - do not connect the summer / winter switch anymore, neither the S.W.W. tank thermostat, these functions being ensured directly by the E9.0300 / E9.0631 climatic regulator. place the boiler thermostat instruction at 80°C approximately. Page 29 / 36 Hartley and Sugden 6.1.3. Connection kit GTCO regulator 10-poles connector regulator side GTC 0 II 8 11 9 12 7 ST 2 10 5 6 4 2 3 1 1 2 3 4 5 6 7 8 9 10 L1 9-poles connector (A) boiler side AMPconnector 12-poles (B) N Room thermostat CONNECTION OF THE GTC0 REGULATOR ON THE COMMODORE PLUS BOILERS RANGE 1. 2. 3. 4. 5. 6. Remove the right cap on the control panel and engage the regulator in this housing. Remove the 9 poles male connector with its 4 bridges on the back of the control panel, or remove the S.W.W. priority Ventec module already connected. Connect the 9 poles connector (A) boiler side delivered with the regulator in the 9 poles female connector block of the boiler and tighten the screws. Connect the AMP 12 poles connector (B) delivered with the regulator in the AMP 12 poles plug of connector (A). Connect the 10 poles white connector on the connector block II of the regulator. Connect directly the following probes on the connector block I of the regulator. - KFS : boiler probe - SPFS : S.W.W. probe Connect the heating circulator to terminals 8 and 9 and if necessary the S.W.W. circulator to terminals 11 and 12 on the boiler 12 poles connector block ( back of the control panel ). GENERAL REMARKS - do not connect the summer / winter switch anymore, neither the S.W.W. tank thermostat, these functions being ensured directly by the GTC0 climatic regulator. place the boiler thermostat instruction at 80°C approximately. Page 30 / 36 15 13 10 5 6 7 8 1 9 3 9 11 9 11 9 11 9 12 9 12 9 14 2 17 16 4 Hartllley and Hartley d Sugd Sugden Spare parts 77. S t list li t Page 31 / 36 Hartley and Sugden Casing Commodore Plus 5 - 6 (122 -132) 14 1 1 8 13 5 9 2 2 12 7 4 5 4 10 11 3 6 6 CasingCommodore Plus 11 - 12 (335 - 345) 17 14 1 20 1 8 19 15 5 9 2 13 2 6 12 3 behind the block 7 5 18 11 16 10 6 4 3 Page 32 / 36 Hartley and Sugden ControlpanelCommodore Plus 30 34 31 32 33 33 Page 33 / 36 Hartley and Sugden Code article Quantity 0-15-000-10005 0-15-000-10006 0-15-000-10007 0-15-000-10008 0-15-000-10009 0-15-000-10010 0-15-000-10011 0-15-000-10012 0-15-000-10013 0-15-000-10014 1 1 1 1 1 1 1 1 1 1 2-15-000-00000 2-15-000-01000 2-15-000-02100 2-15-000-02100 2-15-000-02100 2-15-000-02100 2-15-000-03000 2-15-000-08100 1-30-310-00042 1-30-310-20020 1-30-240-60120 1-30-240-60410 4-15-000-73000 1-30-380-90044 2-15-000-02200 2-15-000-02200 2-15-000-02200 2-15-000-02200 2-15-000-02300 2-15-000-02300 2-15-000-02300 2-15-000-02300 1-60-700-10006 1-70-640-34101 3-99-000-02000 1-60-200-50015 1-60-200-50016 1-60-200-50017 1-30-240-60114 1 1 1 2 3 4 1 1 2 1 1 acc.nr. 1 1 2 3 4 5 1 2 4 5 1 1 suiv. nr. 1 1 1 1 3-15-000-02000 3-15-000-08001 3-15-000-08100 3-15-000-08110 3-15-000-30006 3-15-000-30008 3-15-000-30010 3-15-000-30012 3-15-000-30014 3-15-000-31006 3-15-000-31008 3-15-000-31010 3-15-000-31012 3-15-000-31014 3-15-000-01001 3-15-000-00001 3-15-000-00000 3-15-000-01000 3-15-000-03100 3-15-000-04000 3-15-000-05000 5-15-000-11000 2 2 2 2 2 2 2 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1 Description of parts Ref. boiler CommodorePlus 122 (5 inter) boiler CommodorePlus 132 (6 inter) boiler CommodorePlus 241 (7 inter) boiler CommodorePlus 242 (8 inter) boiler CommodorePlus 234 (9 inter) boiler Commodore Plus 244 (10 inter) boiler Commodore Plus 335 (11 inter) boiler Commodore Plus 345 (12 inter) boiler Commodore Plus 355 (13 inter) boiler Commodore Plus 455 (14 inter) Frontelement Rearelement Front intermediatesection CommodorePlus 122 -132 Front interm. section Commodore Plus 241 - 242 - 234 - 244 Front interm. section Commodore Plus 335 - 345 - 355 Front interm.section CommodorePlus 455 Fluegasbox Fuelnakeddoor Frontinsulation furnace Doorinsulation Ceramicfibre ropeØ20mmsiliconed CordGPE Ø 10 mm Viewflamekit Pyrexviewflame IntermediatemiddlesectionCommodorePlus122 Intermediate middlesection Commodore Plus 132-234 -335 Interm. middle section Commodore Plus 241 - 242 - 244 - 345 Interm. middlesection CommodorePlus 355-455 IntermediaterearsectionCommodorePlus 241 Intermediate rearsection CommodorePlus 122- 132 -242 Intermediate rearsection CommodorePlus 234-244 Interm. rear section Commodore Plus 335 - 345 - 355 - 455 Draincock3/4" Plunger3/4"-100 Nipple Pipe injector3" 70mm CommodorePlus 242 Pipe injector3" 140 mm Commodore Plus 234 - 244 - 335 Pipe injector3" 190 mm Commodore Plus 345 - 355 - 455 Ceramicfibre ropeØ14mmsiliconed 1 2 3 3 3 3 4 5 6 7 8 9 10 11 11 11 11 12 12 12 12 13 14 15 16 16 16 17 CasingCommodore Plus Rear&front cover Upperrear & front fixation Right front &left rearfixation (lower) Left front &right rearfixation (lower) Stiffening plate left upper and lowerpanel 122 - 132 Stiffening plate left upper and lowerpanel 241 - 242 Stiffening plate left upper and lowerpanel 234 - 244 Stiffening plate left upper and lowerpanel 335 - 345 Stiffening plate left upper and lowerpanel 355 - 455 Stiffening plate right upper and lowerpanel 122 - 132 Stiffening plate right upper and lowerpanel 241 - 242 Stiffening plate right upper and lowerpanel 234 - 244 Stiffening plate right upper and lowerpanel 335 - 345 Stiffening plate right upper and lowerpanel 355 - 455 Rightrearpanel Leftrearpanel Left front panel Rightfront panel Front plate Rearlowerplate Rear upper plate Controlpanel plate 1 2 3 4 5 5 5 5 5 6 6 6 6 6 7 8 9 10 11 12 13 14 Page 34 / 36 Hartley and Sugden Code article Quantity Description of parts Ref. 3-15-000-00026 3-15-000-00052 3-15-000-01026 3-15-000-01052 3-15-000-02026 3-15-000-02052 3-15-000-01052 3-15-000-00052 3-15-000-02052 1 1 1 1 1 1 1 1 1 Left interm. panel 260mm Comm. Plus 241 - 242 - 335 - 345 Left interm. panel 520mm Comm. Plus 234 - 244 - 355 - 455 Right interm. panel 260mm Comm. Plus 241 - 242 - 335 - 345 Right interm. panel 520mm Comm. Plus 234 - 244 - 355 - 455 Interm. cover 260mm Comm. Plus 241 - 242 - 335 - 345 Interm. cover520mm Comm. Plus 234 - 244 - 355 455 Rightinterm. panel520mm CommodorePlus 335-345 Left interm. panel520mm Commodore Plus 335- 345 Interm. cover520mm CommodorePlus 335-345 15 15 16 16 17 17 18 19 20 5-15-000-11000 1-70-380-20122 1-70-880-10120 1-70-050-02120 1-70-050-01320 1 1 1 1 1 Wired control panelCommodorePlus Main switch On / Off Boilerthermometer Thermostat 1° and 2° step NT 174 HE/2 Safety limit with manual reset SP-051 HE 30 31 32 33 34 Page 35 / 36 Hartley and Sugden 8. Maintenance Maintenance must be carried out on the boiler once or twice a year, including an inspection of the cleanliness of the flues. Remove cleaning cover (code n° 1-30-310-20010) and insulation and the furnace plate (coden° 4-20-020-44000) and insulation (code n° 1-30-310-20010). Also remove the dividers (small and/or large models) and the stoppers, if fitted. First, clean the horizontal flues then the vertical channels and finally the combustion chamber. The flue gas box has an inspection cover (code n° 2-20-000-03100), allowing removal and collection of the soot during cleaning of the interior flues. Abnormal fouling of the boiler may be caused by: incorrect burner setting obstruction of chimney We recommend having the burner setting, the combustion characteristics and the good working order of the regulation equipment verified every year by the installer. If necessary, replace the insulation. During re-assembly, replace the dividers and the stoppers (If necessary). 9. Guarantee conditions on the boilers 1. Our products are guaranteed against all manufacturing defects insofar as they have been used in normal conditions and have been installed and maintained in an approved manner, according to prevailing regulations and in accordance with the requirements of our technical services. Our technical instructions must be adhered to and annual maintenance be undertaken by a qualified person. Our guarantee does not cover damage to boilers which have been used with polluted air including corrosive elements such as chlorine, fluorine, sulphur etc. The use of water which is found to be unsuitable would also invalidate our guarantee. 2. Our guarantee specified below commences on the date of delivery. Its duration being as follows : - Cast iron block (i.e. the whole of the apparatus composing the block of the appliance) of the cast-iron boilers : 2 years. - All other accessories and pieces of equipment supplied with our boilers are subject to individual manufacturers guarantee. 3. The guarantee is restricted to either the repairing or the simple replacement - at our discretion - of any component sent to our registered office free of charge and which we recognize to be defective, with the exclusion of any labour costs, transport or travelling expenses and any damages or compensation whatsoever. 4. The replacement or repair of a component in the course of the period of guarantee will not result in the extension of this period. 5. We will not accept any costs on account of the installation, which is entirely the responsibility of the installer. Any visit to site for any of the above reasons may be construed only as technical assistance and no way binding. 6. HARTLEY & SUGDEN reserves the right to modify the technical and aesthetic characteristics of its products without notice. 7. The guarantee is effective only if the guarantee card which accompanies the boilers is sent back by the user to HARTLEY AND SUGDEN ATLAS WORKS, GIBBET STREET, HALIFAX,WEST YORKSHIRE, HX1 4DB Page 36 / 36
© Copyright 2024