Prince William County TypicalTypical Residential Deck Design Deck Details Based Based on theon Virginia Statewide Building ~ Version 2011-01-01 Virginia Uniform Uniform Statewide Building CodeCode ~ Version 2009-10-01 CONTENTS General Notes........................................................ 2 Ledger Fasteners................................................... 11 Deck Framing Plan................................................ 3 Rim Joist Attachment............................................ 11 Cross Section of Deck Connected to House....... 4 Built-Up Beam...................................................... 11 Free Standing Deck Framing Plan........................ 5 Stairway Requirements.......................................... 12 Cross Section of Free Standing Deck.................. 6 Tread, Riser, and Stringer Detail......................... 12 Lateral Support of Free Standing Deck............... 7 Stairway Landing Details....................................... 13 Framing Plan at Chimney or Bay Window........... 8 Stairway Connection to Deck................................ 14 Post-to-Beam Connection.................................... 8 Handrail Details..................................................... 14 Joist-to-Beam Connection................................... 8 Do Not Do's...........................................................15 Footing Details....................................................... 9 Stairway Illumination.............................................. 16 Guardrail Post Connection..................................... 9 Clearances............................................................. 16 Ledger Board Connection...................................... 10 Inspection and Scheduling.................................... 17 TYPICAL RESIDENTIAL DECK DESIGN PRINCE WILLIAM COUNTY, VIRGINIA Department of Development Services Building Development Division 5 County Complex Court Prince William, VA 22192-9201 703-792-6930 SHEET 1 OF 17 GENERAL NOTES THINGS TO BRING FOR PERMIT Important! Zoning Permit. You must bring a copy of your house location plan that shows the proposed location of the deck, drawn to the same scale as the plan. Show the side yard and rear yard distances (setbacks from property lines) on the plan. NOTES ON DESIGN · No changes shall be made to approved plans without prior approval from the Building Construction Review Branch. · Approved deck plans shall not be used for supporting hot-tub installation, without re-submission for review. metal connections, bolts, joist hangers, etc. shall be galvanized or corrosive resistant. · All · · Building All lumber shall be pressure treated Southern Pine, grade #2 or better. permit is not required if all portions of the top of the deck's flooring is within 16.5 inches from the finished grade unless it carries structural load, e.g. hot-tub. · All decks require zoning permit. Setback and Permit Standards for At-Grade Structures Provisions in the Prince William County Zoning Ordinance for at-grade decks and patios differ from those in the Building Code. In the Zoning Ordinance, the standards are as follows: "Patios, decks, walkways, steps and driveways constructed no higher than eight (8) inches above existing grade of the contour of the land where located may encroach within any setback provided that no permanent above-grade affixed structures such as railing, planters, benches, roofs or other appurtenances are installed." · Column spacing and joist spans shown are maximum. structural members. Smaller decks may be constructed utilizing the same The typical residential deck design shall be strictly adhered to. All deviations from these drawings shall require an independent set of design documents to be prepared and submitted to the Construction Plans · Review Branch for review. · If a proposed deck does not conform to these typical design details, a custom design can be submitted to the Building Construction Review Branch. Submit two (2) copies of the design, including framing plans, cross sections, and stringer details for review. Material requirements are as follows: · Component Requirement Nails, screws, lag screws, and hot-dipped zinc galvanized, stainless steel, or approved for use with ACQ, CA, or CA-B Hardware (joist hangers, anchors, clips and angles) shall be hot-dipped galvanized with a 1.85 oz/sf of zinc (G-185 coating) or Stainless Steel (type 304 or better) bolts shall be 1 · 1 · · Examples "Zmax" "Triple from Simpson Strong-Tie Zinc" from USP Flashing shall be copper, stainless steel, silicon, bronze, or UV-resistant plastic , and hot-dipped galvanized steel with a G30 zinc coating Notes: In all cases, electroplated galvanizing is NOT acceptable. ICC Evaluation Report and testing data are required to substantiate decay resistance of plastic. 2 1 2 Please go to www.treatedwood.com/products/preserve/ for a list of hardware manufacturers that recommend hardware for use with Alkaline Copper Quaternary (ACQ) treated wood. · Decking composed of foreign lumber, plastic or manufactured materials may be substituted only when the product has an approved evaluation report from ICC-ES or from an accredited testing laboratory. · PRINCE WILLIAM COUNTY, VIRGINIA TYPICAL RESIDENTIAL DECK DESIGN SHEET 2 OF 17 PRINCE WILLIAM COUNTY, VIRGINIA 5' Max. sheet 14 Figure 22, Handrail: Stairway: Figure 17, sheet 12 GP Intermediate Landing: Figure 19 and 20, sheet 13 5' Max. GP Typical of house GP Attachment: Figure 15, sheet 11 Typical 2' Max. Guardrail Post 4x4 (treated) Figure 16, sheet 11 Typical TP (2)-2x10 Beam: TP Treated Post 6x6 GP Rim Joist: 8' Max. 2' Max. Guardrail Post Connection: Figure 10, sheet 9 Figure 7, sheet 8 Typical TP Typical (2)-2x8 Double Joist: Ledger Connection: Figure 11 or 12, sheet 10 AND Figure 14, sheet 11 6x6 Post: 8' Max. Ground Landing: Figure 20, sheet 13 TP Chimney or Bay Window: Figure 6, sheet 8 Figure 13, Sheet 10 Double Joist Joist: 2x8 @ 16" OC Exterior wall (refer to sheet 5 for free standing deck) the wall, or cantilever. system (without at least 141 " solid band board), brick veneer, stone or cultured stone on 4x4 Rail Post sheet 8 Table 1 Decking: GP FIGURE 1: DECK FRAMING PLAN Exterior house condition shall not contain any of the following: prefabricated floor joist Spacing 10' Max. 4' Min. TYPICAL RESIDENTIAL DECK DESIGN SHEET 3 OF 17 Top Rail FIGURE 2A: CROSS SECTION OF DECK CONNECTED TO HOUSE 2x4 Min. or (refer to sheet 6 for free standing deck) GP 4x4 post 5 4 board 5'-0" OC Max. shall NOT 2x2 Min. Pickets shall Side Rail be attached to side rails 2x4 Min. by one of the following methods: be notched 36" Min. A. (1)-#8 screw top and bottom B. (2)-8d spiral nails top and bottom rim joist 11' Max. Openings shall not allow the passage of a 4" diameter 2' Max. (2)-2x10 Beam: 12, sheet 10 14, sheet 11 TP 6x6 Post 24" Min. Connection: Figure 11 or AND Figure Figure 16, sheet 11 finished grade sphere Ledger Footing: Figure 9, sheet 9 12' max. FIGURE 2B: CROSS SECTION OF DECK CONNECTED TO HOUSE (refer to sheet 6 for free standing deck) Stairway Requirements: Figure 17, sheet 12 Intermediate Landing: Figure 19 and 20, sheet 13 Joist-To-Beam: Stairway Connection: Figure 21, sheet 14 finished grade Stringer Detail: Figure 18, sheet 12 PRINCE WILLIAM COUNTY, VIRGINIA Ledger Figure 8, sheet 8 Guardrail Post Connection: Post-To-Beam: Connection: Figure 7, sheet 8 Figure 11 or Figure 10, sheet 9 12, sheet 10 AND Figure 14, sheet 11 TYPICAL RESIDENTIAL DECK DESIGN SHEET 4 OF 17 PRINCE WILLIAM COUNTY, VIRGINIA sheet 14 Figure 22, Handrail: sheet 12 Stairway: Figure 17, GP 4x4 Rail Post sheet 8 Table 1 Decking: GP GP 5' Max. Intermediate Landing: Figure 19 and 20, sheet 13 wall, or cantilever. GP Figure 15, sheet 11 Typical 2' Max. 2' Max. 2' Max. Guardrail Post 4x4 (treated) Figure 16, sheet 11 Typical TP (2)-2x10 Beam: TP Treated Post 6x6 GP Rim Joist: 8' Max. Figure 7, sheet 8 Typical TP Guardrail Post Connection: Figure 10, sheet 9 Typical Joist: Required Bridging at each guardrail post 2x8 @ 16" OC 6x6 Post: 8' Max. Ground Landing: Figure 20, sheet 13 TP Figure 16, sheet 11 Typical (2)-2x10 Beam: floor joist system (without at least 141 " solid band board), brick veneer, stone or cultured stone on the Deck shall be free standing when adjacent house condition contains any of the following: prefabricated FIGURE 3: FREE STANDING DECK FRAMING PLAN 8' Max. 4' Min. 5' Max. TYPICAL RESIDENTIAL DECK DESIGN SHEET 5 OF 17 FIGURE 4A: CROSS SECTION OF FREE STANDING DECK Top Rail Deck shall not be anchored to face of house 2x6 or GP 4x4 post board 2x2 Min. Pickets shall be attached to rails by one of the following methods: Side Rail 5'-0" OC Max. shall NOT 5 4 2x4 Min. A. (1)-#8 screw top and be notched bottom 36" Min. B. (2)-8d spiral nails top and bottom Openings shall not allow the passage of (2)-2x10 Beam: a 4" diameter Figure 16, sheet 11 2' Max. 24" Min. grade 14' Max. w/bracing 6' Max. w/o bracing finished Bracing: Figure 5, sheet 7 rim joist 8' Max. sphere 2' Max. TP 6x6 Post Footing: Figure 9, sheet 9 FIGURE 4B: CROSS SECTION OF FREE STANDING DECK Deck shall not be anchored to face of house Stairway Requirements: Figure 17, sheet 12 Intermediate Landing: Figure 19 and 20, sheet 13 Joist-To-Beam: Stairway Connection: Figure 21, sheet 14 finished grade Figure 8, sheet 8 Post-To-Beam: Figure 7, sheet 8 Guardrail Post Connection: Figure 10, sheet 9 Stringer Detail: Figure 18, sheet 12 PRINCE WILLIAM COUNTY, VIRGINIA TYPICAL RESIDENTIAL DECK DESIGN SHEET 6 OF 17 FIGURE 5A: LATERAL SUPPORT OF FREE STANDING DECK Deck bracing shall be provided when deck height is greater than 8'-0" above grade. Decking Joist 6x6 Post (2)-2x10 Beam Rim Joist (when required) 4x4 Rail Post Required bridging at each guardrail post 2x6 Diagonal Bracing (or 2x4 minimum for bracing parallel to beam) Free standing decks shall be braced with 2x6 diagonal bracing corner to corner at the underside of floor joists using an 8d nail at each joist, or by installing 2x6 decking diagonally. FIGURE 5B: LATERAL SUPPORT FOR ALL DECKS Knee bracing shall be provided when deck height is greater than 8'-0" above grade. 2' Beam 2' 2x4, Typical finished grade (1)-21 " dia. thru-bolt with washers, Typical Bracing Parallel to Beam PRINCE WILLIAM COUNTY, VIRGINIA 14' Max. 2' Beam 2' use 2x8 blocking when joist and post do not allign when joist and post are alligned Bracing Perpandicular to Beam TYPICAL RESIDENTIAL DECK DESIGN SHEET 7 OF 17 FIGURE 6: FRAMING PLAN AT CHIMNEY OR BAY WINDOW Exterior house condition shall not contain any of the following: prefabricated floor joist system (without at least 11 " solid band board), brick veneer, stone or cultured stone on the wall, or cantilever. 4 (refer to sheet 5 for free standing deck) 6' Max. 2" Min. Deck Joists Ledger Board 3' Max. Chimney or Bay Window Decking Double Joists and Joist hangers required Double Headers at intersections FIGURE 7: POST-TO-BEAM CONNECTION TABLE 1: DECKING (2)-2x10 Beam 1 2 Thickness of " diameter Diagonal Decking thru-bolt and Joist washers, Typical 6x6 Post notch post to match beam FIGURE 8: JOIST-TO-BEAM CONNECTIONS 1 2 Composite Spacing 2x 16" OC YES YES NO 12" OC YES YES YES 5 x 4 Material 2 Treated Southern Yellow Pine #2 or better ® Trex or similar, must be rated to support 40 PSF or 200 pound concentrated load hurricane tie (3)-8d toe nailed (2 on one side, 1 on the other) 1 joist hanger or similar top of joist and beam must be at the same level (2)-2x10 beam OPTION 1 PRINCE WILLIAM COUNTY, VIRGINIA OPTION 2 OPTION 3 TYPICAL RESIDENTIAL DECK DESIGN SHEET 8 OF 17 FIGURE 9: FOOTING DETAILS footings shall bear on solid ground; bearing conditions shall be verified in the field by an approved Third Party Inspector or by County Inspectors prior to placement of concrete. The bottom of all footings closer than · All 5'-0" to the exterior wall of the existing house must be extended down to undisturbed soil. Pre-manufactured post anchors shall be galvanized with 1.85 oz/sf of zinc (G-185 coating) or shall be · stainless steel. · All concrete must be properly mixed per specifications. provide seal to prevent seapage of water post anchor finished 8" Min. 24" Min. grade frost depth undisturbed 8" Min. 8" Min. post anchor pre-manufactured cast-in-place post 18" square OR soil 20" dia. round anchor Option 1 Option 2 Option 3 FIGURE 10: GUARDRAIL POST CONNECTION DETAIL guardrail post guard post hold-down anchor outside joist (optional) w/21 " hold-down rim joist anchor (optional) rim joist dia. hold-down anchor thru-bolts and (optional) w/21 " washers dia. joist PLAN thru-bolts and (at joist) washers rim joist joist hold-down anchor 1 2 outside joist " dia. thru-bolt and washers, Typical 1 2 " dia. thru-bolt and 2x8 blocking End nail w/10d nails top and bottom, each side washers, Typical attach per rim joist details (optional) (if hold-down is not used) joist (if hold-down is not used) SECTION PLAN SECTION PLAN (between joists) Guardrail Post to Outside Joist PRINCE WILLIAM COUNTY, VIRGINIA Guardrail Post to Rim Joist TYPICAL RESIDENTIAL DECK DESIGN SHEET 9 OF 17 FIGURE 11: LEDGER BOARD CONNECTION TO DIMENSIONAL BAND BOARD When using lag screws, gap between ledger board and face of house band joist shall not exceed 1 2 Flashing 1. Flashing is requred at any ledger board connection to a wall or floor assembly of ". frame construction. 2. Flashing shall be corrosion resistant. 3. Install flashing per manufacturer's Floor Joist recommendations. Decking Existing band board minimum 11 " width 4 Foundation 2x8 Deck Joist @ 16" OC, Typical Wall " diameter bolts and washers, OR 21 " diameter lag screws where the tip of the lag screws shall fully extend beyond the inside face of the band joist. 1 2 2x8 ledger board shall be pressure treated No. 2 Southern Pine or better FIGURE 12: LEDGER BOARD CONNECTION TO FOUNDATION WALL FIGURE 13: DOUBLE JOIST ATTACHMENT TO LEDGER BOARD Gap between ledger board and face of 1 house band joist shall not exceed 2 ". (2)-21 " dia. lag screws, bolts, or anchors Exterior wood framed Floor Joist house wall Double joists hanger Flashing to protect ledger board Existing band board minimum 11 " width 4 Decking 6" Max. Ledger board Foundation Wall 2x8 Deck Joist @ 16" OC, Typical If concrete wall, use 2x8 Ledger board shall be pressure treated No. 2 Southern Pine or better 1 2 " diameter expansion anchors, embeded 3" into wall. If hollow masonry wall, use 2 " diameter epoxy 1 anchors or equal, embedded 32 " into wall. PRINCE WILLIAM COUNTY, VIRGINIA 1 TYPICAL RESIDENTIAL DECK DESIGN SHEET 10 OF 17 FIGURE 14: FASTENER SPACING AND CLEARANCES AT LEDGER BOARD Provide additional lag screws, lag screws, bolts, or bolts, or anchors with washers on anchors, with washer, each side of exterior terminations Typical S/2 that penetrate the band board such as dryer vent caps and S fresh air intakes. 2" 2" 2" S Exterior penetration (typical) (2)- " lag screws, bolts, or anchors with washers at each end 1 2 TABLE 2: FASTENER SPACING (S) FOR A RESIDENTIAL SOUTHERN PINE DECK LEDGER AND A 2-INCH NOMINAL SOLID-SAWN BAND JOIST [50 PSF TOTAL LOAD] c Joist Span (ft) 6' and less 6'-1" to 8' 8'-1" to 10' On-Center Spacing of Fasteners 1 2 "x4" Lag Screw 1 2 a b c d e a,b " Bolt with washers 10'-1" to 12' d,e 30 23 18 15 36 36 34 29 1 The maximum gap between the face of the ledger board and face of the house band joist shall be 2 ". The tip of the lag screw shall be fully extended beyond the inside face of the band joist. Ledgers shall be flashed to prevent water from contacting the house band joist. Lag screws and bolts shall be staggered as shown. Deck ledger shall be 2x8 No. 2 Southern Pine (minimum), or other approved method and material as established by standard engineering practice. FIGURE 15: RIM JOIST ATTACHMENT DETAIL joists attach rim joist to end of each joist with (5)-#10x3" Min. wood screws rim joist FIGURE 16: BUILT-UP BEAM DETAIL 10d nails or #10 wood screws, staggered in 2 rows 2 nails or screws, 16" each end Typical PRINCE WILLIAM COUNTY, VIRGINIA TYPICAL RESIDENTIAL DECK DESIGN SHEET 11 OF 17 FIGURE 17: STAIRWAY REQUIREMENTS handrail shall return 34"-38" from to post at each end 5'-0" Max. OC nosing of step handrail height: 31.5" Min. guardrail spacing Opening shall not permit the 3 passage of a 48 " diameter sphere 1 2 4x4 post " diameter thru-bolt and stair Typical guardrail height 34" Min. washers, 2x12 stair stringer 4x4 post triangular opening shall not permit the passage of a 36" Min. measured from nosing of step 6" dia. sphere grade 10"x10"x8" thick 2x12 stringer 24" stair footing @ 24" OC Max. frost depth FIGURE 18: TREAD, RISER, AND STRINGER DETAIL risers may be open, but shall not allow the risers may be open, but shall not allow passage of a 4" the passage of a 4" diameter sphere 9" Min. diameter sphere 9" Min. tread depths shall not deviate from one another stringer: 3 by more than 8 " 5" Min. stringer: 8 1 " Max. cut 2x12 4 risers: 1x material, Min. riser heights shall not deviate from one another 3 by more than 8 " treads: 3 4 2x material 11' Max. span cut stringer 3 stringers Min. solid 2x12 "-141 " 4 2x4 attached to stringer on each side nosing which shall not deviate from one 3 another by more than 8 " PRINCE WILLIAM COUNTY, VIRGINIA 8 1 " Max. tread ledger: with (4)-10d nails or (4)-#8 wood screws 16' Max. span solid stringer TYPICAL RESIDENTIAL DECK DESIGN SHEET 12 OF 17 FIGURE 19: INTERMEDIATE STAIRWAY LANDING FRAMING DETAILS 2x8 joist @ 16" OC, Max. joist secured with joist hanger rim joist double joist upper stringer guardrail post down rim joist and outside joist secured with down lower stringer: bears on ground landing (2)-21 " Typical Framing Plan upper stairway: upper stairway connected to deck lower landing stairway outside joist 1 2 guardrail post (Figure 21, sheet 14) guardrail post landing decking dia. thru-bolts and washers, landing decking cut stringer to bear on double rim joist and landing decking, 1 secure to post with 2 " " diameter thru-bolt and washers, lower Typical stringer landing joist dia. thru-bolt and washers Framing Cross Section 1 2 " dia. thru- bolt and washers, Typical Framing Cross Section FIGURE 20: STAIRWAY LANDING DIMENSION DETAILS Dimensions shown are for both intermediate, and ground level landings. 36" Min. stairway direction of travel width of stairway Min. stairway landing PRINCE WILLIAM COUNTY, VIRGINIA TYPICAL RESIDENTIAL DECK DESIGN SHEET 13 OF 17 FIGURE 21: STAIRWAY CONNECTION TO DECK DETAILS (2)-21 " diameter tread depths shall not 4x4 guardrail post thru-bolts and washers each way, Typical rim joist or outside joist deviate from one another by more than " 3 8 9" Min. riser heights shall not deviate from one another 3 by more than 8 " 8 1 " Max. 4 sloped joist hanger rim joist or outside joist stringer stringer Option 1: Stringer Connection with Thru-Bolts Option 2: Stringer Connection with Joist Hanger FIGURE 22: HANDRAIL DETAILS Handrails should be continuous from top riser to bottom riser. 1 1 " Min. 2 11 4 1 1 "x11 " 2 "-2" outside 2 spacer at 24" OC, Max. diameter Guardrail Corrosion-resistant Post handrail bracket 4'-0" OC Max. Side Rail (2)-8d nails, handrail with Typical perimeter of Type I, Option 1 4"-641 " Type I, Option 2 For circular Non-circular handrails must have a perimeter of 4" handrails only min. and 61 " max. with a 4 1 1 "x11 " 2 2 spacer at 24" OC, Max. maximum cross-section dimension of 21 " 4 1 1 " Min. - 23 " Max. 4 4 3 4 " Max. handrail with perimeter greater Type II, Option 1 Handrails with a perimeter 1 greater than 64 " shall provide a graspable finger recess area on both sides of the profile than 61 " 5 16 " Min. 4 PRINCE WILLIAM COUNTY, VIRGINIA 7 8 3 " Max. 1 4 " Min. 3 8 " Min. finger recess detail TYPICAL RESIDENTIAL DECK DESIGN SHEET 14 OF 17 DO NOT DO'S Prohibited Post-to-Beam Connection Prohibited Ledger Attachment: to open web trusses Prohibited Ledger Attachment: to or thru brick veneer PRINCE WILLIAM COUNTY, VIRGINIA Prohibited Ledger Attachment: to house overhang TYPICAL RESIDENTIAL DECK DESIGN SHEET 15 OF 17 STAIRWAY ILLUMINATION FOR DECKS The International Residential code (IRC) establishes the requirements for stairway illumination. includes stairways associated with decks. illumination requirements: This section The following are a few of the ways to comply with the stairway Install an exterior light fixture within 5 feet of horizontal distance from the top landing of the stairway. The light fixture must be positioned to illuminate both the top landing and the stairway. Install an exterior 150 watt flood light fixture within 30 feet of horizontal distance from the top landing of the stairway. The light fixture must be positioned to illuminate both the top landing and the stairway. Install low voltage light fixtures that are approved for exterior use. A low voltage fixture must be installed at each step. Also, one fixture must be installed on the walkway within 3 feet of the bottom step. Any wiring must be installed and secured in a safe manner. The low voltage lights may be · · · plugged into an exterior GFI electrical outlet with an In-Use Weatherproof Cover (NEMA 3R Rated) or hard wired into the electrical panel box in the house. Other methods of complying with the illumination requirements, including justification and analysis shall be submitted to the Building Construction Review Branch for approval prior to installation. · An electrical permit and inspection is required for the installation of the required illumination of the stairway. During the final inspection of the deck, the inspector will verify that the required stairway illumination has been provided. GLAZING ADJACENT TO STAIRWAYS Glazing installed within 60 inches of the bottom of the stairways where the bottom edge is less than 60 inches above the walking surface shall be considered a hazardous location per the current edition of the IRC and shall meet the safety glazing standards outlined in the IRC. FIGURE 23: CLEARANCE FROM MECHANICAL AND ELECTRICAL INSTALLATION Clear/Unobstructed space around meter deck joist Top View Meter M Air Conditioning condensing unit Gas Meter 4'-0" Min. 6'-0" Max. instruction finished grade · Contact 6" Min. 30" Min. 42" Min. 5'-0" or per manufacturer's 6'-3" from floor or ground OR 3'-0" over equip. Whichever is higher Front View the gas company for a courtesy inspection if: the distance from finished grade to bottom of joist is less than 5'-0", a roof will be above the deck, or the deck will have a floor covering. the power company will not approve a meter location on or under a balcony, porch, carport, deck catwalk, or stairs. Contact power company for more information. · Normally Gas fireplace terminations shall be 18" from the top of the outside termination to combustible materials and overhangs or per manufacturer's specifications. · PRINCE WILLIAM COUNTY, VIRGINIA TYPICAL RESIDENTIAL DECK DESIGN SHEET 16 OF 17 REQUIRED INSPECTION AND SCHEDULING 1. Before 2. Call you dig, call Miss Utility at 811 or 1-800-552-7001. for a footing inspection (102) before placing concrete. for a final inspection (151) when the deck is complete. 4. If required, call for electrical permit and inspection (199). 3. Call To schedule inspections, go online to www.pwcgov.org/eInspections or call the · · No Automated Phone System at 703-792-6970. inspections shall be made unless an approved set of drawings are on site. Important Phone Numbers · Residential Plan Review 703-792-6939 · Building Construction Review 703-792-6930 · Building Construction Services (Permitting) 703-792-6924 · To Schedule Inspection call 703-792-6970 or visit www.pwcgov.org/eInspections · Inspection Office (703)792-7006 · Zoning Office (703)792-6830 Hours The Building Development Division reviews deck plans M-F from 8:00am To 11:00am. Please arrive by 10:30 a.m. to have your plan reviewed that day. PRINCE WILLIAM COUNTY, VIRGINIA TYPICAL RESIDENTIAL DECK DESIGN SHEET 17 OF 17
© Copyright 2024