Dust Protection Assembly - Schweitzer Engineering Laboratories, Inc.

Dimension Drawing
7.93
(201.3)
Dust-Protection Assembly
6.77
(172.0)
Part No. 915900170
3.97
(100.9)
For best results
on a duplex
printer, choose
the Flip on
Short Edge (or
equivalent)
option.
6.51
(165.3)
3.28
(83.3)
LEGEND
in
(mm)
i9205a
Factory Assistance
We appreciate your interest in SEL products and services. If you have questions
or comments, please contact us at:
Schweitzer Engineering Laboratories, Inc.
2350 NE Hopkins Court
Pullman, WA 99163-5603 USA
Telephone: +1.509.332.1890
Fax: +1.509.332.7990
Internet: www.selinc.com
Email: [email protected]
Dust-Protection
Cover
Dust-Protection Housing With
Dust-Cowling Extrusion Gasket
Relay
Dust-Cowling
Lid Gasket
 2009 by Schweitzer Engineering Laboratories, Inc. All rights reserved. All trademarks are the property of their respective
holders. SEL products appearing in this document may be covered by US and Foreign patents. The information in this document
is provided for informational use only and is subject to change without notice.
*PLS00050*
Date Code 20091104
6 Lid
Screws
Dust-Seal
Foam Block
Product Specifications
Operating Temperature:
All temperature ratings are de-rated by 10°C
Enclosure Protection:
IEC 60529:2001
IP50 for terminals enclosed in the dust-protection assembly
Application Guide
RearPanel
Screw
RearPanel
Screw
RearPanel
Screw
RearPanel
Screw
Use the dust-protection housing (915900170) with the following SEL products:
➤
All SEL-700 series relays, except the SEL-701
➤
SEL-734 Meter
➤
SEL-2410, SEL-2411, and SEL-2414
Installation
Mount the relay in the panel before attaching the dust-protection assembly. The
photo shows the housing attached to a relay before the cover is applied.
Step 1. Remove the four rear-panel screws (shown in the photo) from the
back of the relay.
Step 2. Detach the dust-protection cover from the dust-protection
assembly by removing the six lid screws.
Step 3. Align the dust-protection housing and attached dust-cowling
extrusion gasket to the relay back panel.
The dust-cowling extrusion gasket creates an effective dust seal
between the relay and the housing.
Step 4. Attach the housing to the relay using the four rear-panel screws
from Step 1.
Step 5. After completing the relay rear-panel connections required for the
application, exit the housing by guiding the cables and wires
through the dust-seal foam block as shown in the photo.
Step 6. Attach the dust-protection cover to the housing with the six screws
saved from Step 2.
The dust-cowling lid gasket, which is attached to the cover, creates
an effective dust seal between the housing and the cover.
Dust-Protection Assembly
Dust-Seal
Foam Block
Part Number 915900170