PSS 2A-3B1 C

FIELD DEVICES – INDICATORS
Product Specifications
PSS 2A-3B1 C
65FS Series
Field-Mounted Indicating Milliammeters
The Foxboro® brand 65FS Series Field-Mounted dc Milliammeters have a range of 4 to 20 mA or 10 to
50 mA. They are normally installed in controller input loops to monitor measurement signals. However, they
may be used in any application where the current range is adequate.
MODELS 65FS-**HB AND **JB
SURFACE-MOUNTED MILLIAMMETERS
These instruments are used for surface-mounted
applications. The indicating meter plugs into a
phenolic socket which is mounted in an intrinsically
safe or explosionproof housing. They are standard
with either a 0 to 100 uniform scale, 0 to 100 square
root scale, or 0 to 10 square root scale. The
instruments are thermally compensated by an
internally mounted resistor-thermistor network.
An appropriate precision resistor wired to the
phenolic socket converts the 4 to 20 or 10 to 50 mA
input signal to 99 to 494 mV.
These instruments have been designed to be both
explosionproof and weatherproof. They are also
available for use in ordinary, hazardous, and
intrinsically safe locations.
PSS 2A-3B1 C
Page 2
PERFORMANCE SPECIFICATIONS
P E R F O R M AN C E S PE CI F I C AT I O N S
Accuracy
65FS-**HB and **JB
±2% of upper range value
2% of upper range value
Repeatability
Position Effect
0.1% of upper range value
The zero error is correctable using the mechanical
zero adjustment on front of instrument.
Ambient Temperature Effect
For total change within ambient temperature limits.
See “FUNCTIONAL SPECIFICATIONS” section
below.
65FS-**HB and **JB
Zero and span, ±2% of upper range value
F U N C T I O N A L S P E C I F I C AT I O N S
Ambient Temperature Operating Limits
65FS-**HB and **JB
-30 and +80°C (-20 and +180°F)
Position
Can be mounted at any angle between the vertical
and the horizontal. Balanced for vertical and
horizontal mounting.
Relative Humidity Operating Limits
Scale Length
95% RH maximum
Vibration Operating Limits
Approximately 50 mm (2 in) scale length at a 100°
scale arc.
50 m/s2 (5 “g”) at a frequency from 8 to 42 Hz
Scale Marking
Terminal Resistance
Black numbers on white scale. Unit of measurement
legend as specified.
65FS-**HB and **JB
2000  ±20%, shunted by 25 for 4 to 20 mA
instrument, and by 10  for 10 to 50 mA
instrument.
Indicator
65FS-**HB and **JB
Black pointer
PSS 2A-3B1 C
Page 3
PHYSICAL SPECIFICATIONS
P H Y S I C A L S P E C I F I C AT I O N S
Mounting
Connections
65FS-**HB and **JB
Surface mounting on either a magnetic or
nonmagnetic panel.
Screw terminals. Wiring enters the case through
1/2 NPT conduit connection on bottom of enclosure.
Approximate Mass
Material
65FS-**HG and JB
Aluminum housing with glass window
1.5 kg (3.4 lb), meter and enclosure
Finish
65FS-**HG and JB
Charcoal gray paint
P R O D U C T S A F E T Y S P E C I F I C AT I O N S
Testing Laboratory, Type of Protection,
and Area Classification
CSA certified intrinsically safe for Class I,
Groups B, C, and D; Division I.
Conditions of Certification
Model Code
Connect per SI 8-00465. Temperature
Class T6.
65FS-CBJB-_
CSA certified explosionproof for Class I,
Temperature Class T4A.
Groups C and D, Division I; and dustignitionproof for Class II, Groups E, F, and G,
Division 1.
Suitable for use in Class I, Groups A, B, C, and
D, Division 2 locations.
65FS-CDHB-_
65FS-CDJB-_
FM certified intrinsically safe for Class I,
Connect per TI 005-101. Connecting
Groups A, B, C, and D, Division I; and Class II, wiring not to exceed 3.2 kilometers
Groups E and G, Division I.
(2 miles) in length. As many indicators
as required may be used in a single
loop. Temperature Class T6.
65FS-FBJB-_
FM certified explosionproof for Class I,
Groups C and D, Division I; and dustignitionproof for Class II, Groups E, and G,
Division 1.
Temperature Class T6.
65FS-FDHB-_
65FS-FDJB-_
FM certified for ordinary locations and
nonincendive for Class I, Groups A, B, C, and
D, Division 2; and Class II, Group G;
Division 2.
Nonincendive source not to exceed
30 V dc. Temperature Class T6.
65FS-FNJB-_
PSS 2A-3B1 C
Page 4
MODEL CODES
M O DE L C O D E S
Model Code - Surface Mounted Indicating Milliammeters
Description
Model
Field Mounted Indicator
65FS
Electrical Classification
CSA certified intrinsically safe to Class I, Groups B, C, and D, Division 1 when used in CSA certified
configurations of SPEC 200 intrinsically safe loops (4 to 20 mA, Suffix JB only).
-CB
CSA certified flameproof for Class I, Group D; dust-ignitionproof for Class II, Groups E, F, and G; and
suitable for Class III, Division 1 hazardous locations.
-CD
FM approved intrinsically safe for Class I, Groups B, C, and D, Division 1 hazardous locations when used
in FM certified configurations of SPEC 200 intrinsically safe loops (4 to 20 mA, Suffix JB only).
-FB
FM approved explosionproof for Class I, Groups C and D, Division 1 and dust-ignitionproof for Class II,
Groups E, F, and G, Division 1 hazardous locations.
-FD
FM certified for use in Class I, Groups B, C, and D, Division 2 hazardous locations
(4 to 20 mA, Suffix JB only).
-FN
Input Signal
10 to 50 mA into 10 
4 to 20 mA into 25 
HB
JB
Scale
0 to 100 Uniform
0 to 100 Square Root
0 to 10 Square Root
-A
-B
-D
PSS 2A-3B1 C
Page 5
DIMENSIONS - NOMINAL
DIMENSIONS - NOMINAL
Figure 1. SURFACE MOUNTED INDICATORS
MODELS 65FS- **HB AND **JB
mm
in
MAY BE ROTATED IN ANY
OF FOUR POSITIONS
ALLOW 51 mm (2.0 in)
CLEARANCE FOR
COVER REMOVAL
149
5.9
20
40
60
80
10
0
0
PERCENT OF OUTPUT
ZERO ADJUSTMENT SCREW
3-MOUNTING HOLES
7 mm (0.28 in) DIAMETER
ON 124 mm (4.9 in) DIAMETER
BOLT CIRCLE
22
0.9
95
3.8
INPUT CONNECTION
TAPPED FOR 1/2 NPT
140
5.5
PSS 2A-3B1 C
Page 6
NOTES
NO T ES
NOTES
PSS 2A-3B1 C
Page 7
PSS 2A-3B1 C
Page 8
O RD E RI N G I N S T R U C T I O N S
1.
Model Number
2.
Scale Ranges and Calibration. (Refer to Chart and Dial Catalog 600)
3.
Scale Legend (e.g., psi, inH2O, etc.)
4.
Tag and Application
OTHER FOXBORO PRODUCTS
The Foxboro product lines offer a broad range of measurement
and instrument products, including solutions for pressure, flow,
analytical, temperature, positioning, controlling, and recording.
For a list of these offerings, visit our web site at:
www.fielddevices.foxboro.com
Invensys Systems, Inc.
10900 Equity Drive
Houston, TX 77041
United States of America
http://www.invensys.com
Global Customer Support
Inside U.S.: 1-866-746-6477
Outside U.S.:1-508-549-2424
Website: http://support.ips.invensys.com
Copyright 1984-2015 Invensys Systems, Inc.
All rights reserved.
Invensys and Foxboro are trademarks of Invensys
Limited, its subsidiaries, and affiliates. All other
trademarks are the property of their respective
owners.
Invensys is now part of Schneider Electric.
0515