Document 182447

Technical Guide
When and how to use two new powerful options in the Arc Flash module V7.0
In this paper, we will discuss the importance of becoming familiar with two new powerful options
available for arc flash incident calculations in the SKM Arc Flash module V7.0.
As we can see in Figure 1, the Arc Flash Study Options (Report Options tab) screen, two options are
shown: Main device fail to operate, use upstream devices and Use Maintenance Mode function for
main device.
Figure 1
Each of these two new options has a specific use. We are going to explain and give examples of
both options.
Option #1: Main device fail to operate, use upstream device
When any electrical equipment has a main overcurrent protection device - in contrast to main lugs
only type equipment - there are two areas inside the equipment with different arc flash incident
energies. They consist of the line-side incident energy area and the load-side incident energy area.
The line-side incident energy is present in the area upstream from the line-side terminals of the main
overcurrent protection device, where the incoming conductors enter the equipment. This energy is
not limited by the main overcurrent protection device but by the next upstream overcurrent
protection device.
The load-side incident energy is present in the area downstream from the load-side terminals of the
main overcurrent protection device. See Figure 2.
Technical Guide
Figure 2
NOTE: The main overcurrent protection device is not always the overcurrent protection device that
is connected to the incoming wires from the utility side. The main overcurrent protection device is
defined in SKM as the overcurrent protection device that carries the biggest percentage of the fault
current to the bus. In some very particular cases, a tiebreaker or even a feeder breaker might
qualify as the main overcurrent protection device.
Normally, the line-side incident energy is higher than the load-side incident energy so it is advisable
to calculate both.
There have been many articles written about the importance of calculating the incident energy at the
line side of a main overcurrent protection device in addition to the load-side incident energy. One
situation in the mind of many engineers is the following: What happens when the main overcurrent
protection device fails to operate?
In this case, the upstream device from the main overcurrent protection device will be the one limiting
the incident energy to the entire equipment. Now, instead of having two areas with different incident
energy, (line-side and load-side incident energies), the electrical equipment has only the higher and
worst case line-side incident energy. See Figure 3.
Figure 3
Technical Guide
The preferred method to calculate the line-side incident energy (i.e. when the main overcurrent
protection device fails to clear the arcing current) is to include a bus at the line-side of the main
overcurrent protection device, as shown in Figure 2. However, this method will add many non-existent
buses to the project database. If you have a software license with a limited number of buses, the
database created using this method (of adding line-side non-existent buses) might easily exceed the
number of buses allowed in your license. In this case, the option Main device failed to operate; use
upstream device is very useful.
When you choose this option, at all locations where there is a main overcurrent protection device, the
incident energy will be calculated assuming the following:
1.
2.
3.
The arc flash event occurred at the bus
The main overcurrent protection device failed to operate, therefore it is ignored
The first upstream overcurrent protection device from the main overcurrent protection
device is the one that clears the arc flash event.
Figure 4 shows the arc flash table results for an arc flash event on location PNL-T1. The option Main
device failed to operate; use upstream device has been checked and we have considered a maximum
arcing time of 2 seconds.
Figure 4
The location of the arc flash event (Bus Name) is shown as PNL-T1. The last tripped protective device
is shown as CB-MDP-2-1, which is the upstream overcurrent protection device. The arc flash trip time
(Trip/Delay Time) is shown as 2 seconds. Since the arc flash trip time of the upstream overcurrent
protection device is 9 seconds – see Figure 5 - the Trip/Delay Time considers only up to the maximum
arcing time of 2 seconds. And finally, on the PPE Level column, we can see code *N22 and the name
of the main overcurrent protection device CB-PNL-T1-MAIN. The code *N22 is explained below as
“Main Device failed, use upstream device”. Figure 5 shows the time-current curve (TCC) for this
situation.
Technical Guide
Figure 5
Here we can visualize that the upstream overcurrent protection device is much slower to open the
arcing current that the main overcurrent protection device. Without the option Main device failed to
operate; use upstream device checked, the load-side incident energy (at location PNL-T1) would have
been 1.1 cal/cm2 and the trip time of the main overcurrent protection device (CB-PNL-T1-MAIN)
would have been of 0.028 seconds. But if you check this option, the main overcurrent protection
device is ignored and the upstream overcurrent protection device (CB-MDP-2-1) is the one that clears
the arcing current in 9 seconds. But since we have chosen a maximum arcing time of 2 seconds, the
trip time of 9 seconds is changed to 2 seconds. This trip time gives a very high line-side trip time of
55 cal/cm2 that applies not only to the incoming section but also to the entire electrical equipment.
As previously discussed, you could decide to choose the option Main device failed to operate; use
upstream device when you want to evaluate the incident energy when the main overcurrent
protection device fails to operate. But there are additional justifications to choose this option. You
might want to know the incident energy at the incoming section of the equipment to perform
Technical Guide
energized maintenance. Or the electrical panel has an open-frame construction and the incident
energy at the incoming section (which corresponds to the line-side incident energy) might easily
migrate to the adjacent feeder section where you are planning to work. Or it is the company policy to
choose the worst case incident energy (normally the line-side incident energy) present in electrical
equipment. Whatever your reason might be, the option Main device failed to operate; use upstream
device allows you to calculate the line-side incident energy at any equipment, which has a main
overcurrent protection device, easily and efficiently.
Option #2: Use Maintenance Mode function for Main Device
Arc flash incident energy mitigation is an important part of an arc flash hazard analysis. Once the
incident energies are calculated, locations with high incident energies (normally ≥ 8 cal/cm2) could be
identified.
The high incident energies identified at these locations, could be mitigated using many methods and
technologies. The preferred method is to change the settings of existing circuit breakers so the arcing
current will be cleared faster without any costly changes. But these setting changes could - and
normally do - upset the coordination of the system making it more susceptible to partial or total
blackouts. A new technology called “arc flash reduction maintenance system (ARMS)” allows a
reasonable compromise between safety and continuity of service.
The ARMS device is normally a specialized circuit breaker with two independent functions. One
function (normally named “phase”) is selected when the system is in normal operation. The other
function (normally assigned the named “ARMS”) is activated ONLY when performing energized work
on the protected equipment. Both functions (phase and ARMS) can’t be active at the same time.
In the phase (normal) function, the settings of the ARMS device are chosen for protection and
coordination of the electrical system during normal operations. In the ARMS (maintenance) function,
the settings of the ARMS device are chosen to have a very fast response (no intentional delay) to the
expected arcing current (not the available short circuit current). This fast response substantially
diminishes the trip time and therefore the incident energy at the protected equipment.
The drawback for this gain in safety is the loss of coordination while the ARMS function is active.
It is important that the ARMS device should be located one level upstream from the equipment to be
protected. For example, if the equipment to be protected is a power panel (with or without a main
overcurrent protection device), the ARMS device should be installed in the upstream feeder panel. It
is not recommended to install the ARMS device as the main overcurrent protection device at the
protected power panel. See Figure 6.
Technical Guide
Figure 6
If the ARMS device is installed as the main overcurrent protection device, the load-side incident
energy will be substantially reduced, but the more dangerous line-side AFIE will not be affected. In
contrast, when the ARMS circuit breaker is installed in a separate enclosure, upstream from the
equipment to be protected, the line-side and load-side incident energies are reduced.
To use the ARMS option in the Arc Flash module, you have to add an ARMS function to the circuit
breaker to the already existing phase function. The scope of this article does not cover how to add
this new function. We assume in this paper that the ARMS function already exists.
Since the ARMS device has two functions (each with its own settings), the Arc Flash module in SKM
needs to know which of the two functions is active before running the study. To do so, you have two
options.
First option: Enter the component editor of the ARMS device (a the Protective Device subview), then
click on the Function button. This opens the Protection Functions screen. Now check the Use in Arc
Flash check box corresponding to the ARMS function. Then click on the OK button. This will take you
back to the Component Editor subview. Verify that the ARMS function name is shown to the left of
the Toggle button. See sequence of Figure 7A and Figure 7B.
Technical Guide
Figure 7A
Figure 7B
Note that from this moment on, all arc flash calculations will be based on the ARMS function settings.
If you want to calculate the incident energy using the normal phase function settings, it will be
necessary to revert his procedure. This is a tedious process.
Second Option: Activate the Use Maintenance Mode function for Main Device. When this option is
activated in the Arc Flash – Study Options (Report Options tab) screen, the arc flash study will use the
maintenance function settings if the checkbox Maintenance Mode in the Protection Function screen
Technical Guide
is checked for the ARMS device. See Figure 8. Therefore, when you create this ARMS function in
your ARMS device, make sure that this checkbox is checked.
Figure 8
If you want to calculate the incident energies without the ARMS maintenance function settings active
(i.e. calculate using the phase or normal settings), uncheck the Use Maintenance Mode function for
Main Device check box from the Arc Flash – Study Options screen on the Report Options tab. This
procedure is much simpler than going to the Component Editor of the overcurrent protection device,
then to the Protection Function screen and finally unchecking the Used in Arc Flash checkbox for the
ARMS function and checking the Used in Arc Flash checkbox for the Phase function.