technical information D emand controlled ex trac t unit Pressure measurement and airflow calculation The pressure plug integrated in BXC extract unit enables to measure the pressure by the mean of a manometer, then to deduce the airflow through a table. Please refer to installation instruction for details on the operation. Instruction: 1 Take off the plug stopper and use it to fix the humidity sensitive airflow at its minimum position as shown on the picture (push the humidity sensitive lever with fingers to help closing the driven shutter). 2 Connect a manometer to read the pressure. 1 The chart below (available in the installation instruction) enables to deduce airflow / pressure according to the fix shutter position (from 0 to 5). Pa 2 How to read this chart? 140 Read the corresponding airflow, depending on the fix shutter position (33 m3/h in this example when fix shutter is in position n.4).Please notice that this airflow corresponds to the situation when relative humidity level is below 30%. C 110 40 3 35 30 100 2 B 90 80 1 70 0 60 50 45 4 60 70 80 90 Measured pressure in Pa A 100 110 120 130 25 20 15 10 5 140 Nominal pressure and airflow according to measured pressure (BXC extract unit) Aereco S.A. - 9 allée du Clos des Charmes - Collégien - F 77615 Marne la Vallée Cdx 3 - tel: +33 1 60 06 26 63 - fax: +33 1 60 06 22 11 - www.aereco.com FLY469GB_v0 C Read the nominal pressure (87 Pa in this example). 120 50 Airflow in m3/h B Report the measured pressure (95 Pa in this example). Nominal pressure in Pa A 5 130