The Premier Electrical Maintenance and Safety Event I Know How to Add the Numbers – But What Is the Power Factor Telling Me? Keith Hill Doble Engineering Company 1 - Hill INTRODUCTION: The purpose of this paper is to advance the technical ability of the tester to correctly identify and interpret power factor test data. In the paper I Have a Lot of Numbers, What do they Mean – Basic Interpretation of Two Winding Transformers, presented at PowerTest 2013, the tester learned how to verify that the tests were performed correctly. In this paper, we will dig deeper into the interpretation of irregular test data for the following types of transformers: twowindings, auto with tertiary and three winding. This data will include an excellent example of what we mean by ‘average power factor”. Several case studies for various types of transformers, along with various problems are included in this paper. This data will point out problems that are often encountered in the field and it is often times difficult for the tester to interpret the results. These case studies will detail how to verify the test results and what to look for when analyzing the test data. Some terminology listed in this paper may be new to you so an attempt is being made to identify these components with a brief description. More detailed information can be located in the operator’s manual provided by the manufacturer of your equipment. For this paper it will be assumed that the tester knows how to operate the test set and how to verify that the tests were performed properly. It is important that the tester fully understands the test forms or software being used. It is imperative that the test data for the apparatus be analyzed in the field and not back in the office after the apparatus has been returned to service. One of the most important parts of analyzing test data is to make sure that the tests were performed correctly. Test data will be invalid if the test procedures used were incorrect. The following terminology will be used in this paper: CH, CL, CHL, CH’, CL’, and C1 CH is used to describe all of the high voltage components to ground. This will include the high side insulation, high side bushings, structural insulating members, insulating fluid, and deenergized tap changed, if present. CL is used to describe all of the low voltage components to ground. This will include the low side insulation, low side bushings, structural insulating members, insulating fluid and load tap changer, if present. CT is used to describe all of the tertiary components to ground. This will include the low side insulation, low side bushings, structural insulating members, and insulating fluid. 2 - Hill CHL is used to describe the insulation between the windings, winding barriers, and the insulating fluid. CHL HIGH LOW CH CL Tank & Core Figure 1 Dielectric Circuit of a Two-Winding Transformer The CH’ and CL’ may be new terminology to both inexperienced and experienced testers who may normally use test equipment manufactured by various manufacturers. CH’ is the CH insulation minus the sum of the C1 results for the primary bushings. CL’ is the CL insulation minus the sum of the C1 results for the secondary bushings. C1 is the test performed on the bushings (Figure 2), with a capacitance tap, by energizing the main conductor and measuring to the tap in the Ungrounded Specimen Test (UST) mode. 3 - Hill Figure 2 HANDY FORMULAS and THINGS TO KEEP IN MIND Power Factor = watts x 10 mA Capacitance = 265 x mA (60 Hz) (Rule of thumb is good up to about 15% power factor) Capacitance = 318 x mA (50 Hz) (Rule of thumb is good up to about 15% power factor) It must be remembered that a change in current or capacitance from prior tests is a physical change, while a change in watts is usually from contamination or deterioration. From the above power factor formula, one can see that if the capacitance and current are the same, as in prior tests, that the change in power factor would have to be from a change in the watts. One should remember that when we state “power factor” we should be stating “average power factor” as good insulation and defective insulation are averaged together. REVIEW OF TEST PROCEDURE VERIFICATION By performing some simple math we can verify that the tests were performed correctly. For the primary winding the summation of the currents and watts for Test 2 (CH) and Test 3 (CHL) add to be Test 1 (CH + CHL). Test 4 is the calculated CHL which is calculated by subtracting the currents and watts of test 2 (CH) from test 1 (CH +CHL). As you can see the CHs will cancel out leaving the CHL. For the secondary winding the summation of the currents and watts for Test 6 (CL) and 4 - Hill Test 7 (CHL) add to be Test 5 (CL + CHL). Test 8 is the calculated CHL which is calculated by subtracting the currents and watts of test 6 (CL) from test 5 (CL +CHL). As you can see the CLs will cancel out leaving the CHL. For some test sets, all data is referenced to 10 kV. This means that the CHL insulation tests 3, 4, 7, and 8 should be “equal” even when tested at different voltages. If a difference in the data is noted there may be a voltage related test problem. Transformer 1 Test Data Two Winding Test # 1 2 3 4 5 6 7 8 9 10 ENG H H H 1-2 L L L 5-6 67 kV/12.47 kV Test kV 10 10 10 10 10 210 mA Watts 31.889 10.287 21.605 21.602 66.615 45.013 21.613 21.602 6.550 35.312 1.063 0.408 0.655 0.655 2.557 1.930 0.622 0.627 0.243 1.534 15 MVA % PF Meas ----0.40 0.30 0.30 ----0.43 0.29 0.29 0.37 0.43 % PF Corr 0.39 0.29 0.29 ----0.42 0.28 0.28 0.36 0.42 Corr Factor 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 Cap Meas. 8458.8 2728.7 5730.9 5730.1 17669.8 11939.8 5732.9 5730 1737.47 9366.64 CH+CHL CH CHL(UST) CHL CL+CHL CL CHL(UST) CHL CH’ CL’ Figure 3 After doing the “math” for Transformer 1, the tester should feel comfortable that the tests performed on the primary were performed correctly since tests 2 and 3 add to be test 1 and that tests 3 and 4 are “equal”. The secondary tests were also performed correctly since tests 6 and 7 add to be test 5 and that tests 7 and 8 are “equal”. To verify the results, tests 3, 4, 7, and 8 should be “equal”. (These four tests should be “equal” even when the windings are tested at different voltages). The data for the CH’ and CL’ are the CH and CL without the bushings If taps are not present or the C1 tests were not performed CH’ and CL’ cannot be calculated. Now since the tests were performed correctly the tester should analyze the corrected 5 - Hill power factor results. The measured power factor results have not been compensated for the oil temperature. The apparatus or top oil temperature can often time greatly affect watts which will affect the corrected power factor results. All oil filled equipment should be corrected to 20 degree C (68 degree F). This temperature correction factor compensates for the different temperatures that may occur for different test periods (hot vs. cold) or loading factors which can often times affect the temperature of the insulating fluid. From the data above you can see that the oil temperature resulted in a correction factor of .98. The measured power factors are multiplied by the correction factor .98 to determine the corrected power factors. The data for Transformer 1 is acceptable as the “numbers” add up correctly and the corrected power factor is below the expected limit of 0.5% for this type of transformer. Transformer 2 Test Data Two Winding Test # 1 2 3 4 5 6 7 8 9 10 ENG H H H 1-2 L L L 5-6 2400/480 volt Test kV 2.5 2.5 2.5 ----1.0 1.0 1.0 ----- mA Watts 12.920 4.911 8.018 8.018 18.710 10.700 8.018 8.010 3.605 1.268 2.338 2.337 5.620 3.282 2.336 2.338 D-Y % PF Meas ----2.58 2.92 2.92 ----3.07 2.91 2.92 % PF Corr ----2.06 2.34 2.34 ----2.46 2.33 2.34 750 kVA Corr Factor .80 .80 .80 .80 .80 .80 .80 .80 Cap Meas. 3426 1302 2125 2124 4963 2838 2125 2125 CH+CHL CH CHL(UST) CHL CL+CHL CL CHL(UST) CHL CH’ CL’ Figure 4 As Found Test Results After doing the “math” for Transformer 2, the tester should feel comfortable that the tests performed on the primary were performed correctly since tests 2 and 3 add to be test 1 and that tests 3 and 4 are “equal”. The secondary tests were also performed correctly since tests 6 and 7 add to be test 5 and that tests 7 and 8 are “equal”. To verify the results, tests 3, 4, 7, and 8 are “equal” even when the windings were tested at different voltages. There will be no data for the CH’ and CL’ since the bushings did not have taps. If taps 6 - Hill are not present or the C1 tests were not performed CH’ and CL’ cannot be calculated. From the data above you can see that the oil temperature resulted in a correction factor of .80. The measured power factors are multiplied by the correction factor .80 to determine the corrected power factors. Noting that all of the power factor results exceed the recommended limits (1.0%) the tester must determine some of the possible causes for the abnormal test results. Using the information provided that described CH, CL, and CHL the tester can narrow the possible problems. Since CH, CL, and CHL are all higher than the recommended limits, the only thing common to all three insulation systems is the insulating fluid, so if we have contaminated fluid, we have contaminated windings. Transformer 2 Test Data – after repairs Test # 1 2 3 4 5 6 7 8 9 10 ENG H H H 1-2 L L L 5-6 Test kV 2.5 2.5 2.5 ----1.0 1.0 1.0 ----- mA Watts 11.810 4.552 7.271 7.258 17.040 9.777 7.271 7.263 0.327 0.143 0.182 0.184 0.541 0.356 0.179 0.185 % PF Meas ----0.31 0.25 0.23 ----0.36 0.25 0.25 % PF Corr ----0.28 0.23 0.23 ----0.32 0.23 0.23 Corr Factor .90 .90 .90 .90 .90 .90 .90 .90 .90 .90 Cap Meas. 3134 1207 1928 1927 4521 2593 1928 1928 CH+CHL CH CHL(UST) CHL CL+CHL CL CHL(UST) CHL CH’ CL’ Figure 5 As Left Test After baking the windings and replacing the insulating fluid the transformer now has power factors that are normally expected on a new transformer. A new power transformer (over 500 kVA) would normally be specified to have a power factor less than 0.5%, but in reality one would normally expect to see a power factor that is in the 0.25% to 0.30% range. This 25 year old transformer now has power factor results expected on a new transformer. 7 - Hill Transformer 3 Test Data Two Winding 230 kV/25 kV Y-D Test # ENG Test kV mA Watts % PF Meas 1 2 3 4 5 6 7 8 9 10 H H H 1-2 L L L 5-6 10 10 10 262.11 258.45 3.633 3.660 677.76 674.08 3.639 3.680 251.373 640.064 10.905 10.918 0.0210 -0.013 27.797 27.728 0.0180 0.069 10.732 26.768 ----0.42 0.06 -0.04 ----0.41 0.05 0.19 0.43 0.42 3. 3 2. % PF Corr ----0.42 0.06 -.04 ----0.41 0.05 0.19 0.43 0.42 900 MVA Corr Factor Cap Meas. 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 69525.8 68555.6 963.55 970.200 179779.7 178803.1 965.27 976.600 66678.49 169780.4 CH+CHL CH CHL(UST) CHL CL+CHL CL CHL(UST) CHL CH’ CL’ Figure 6 Please note the data for Figure 6 as the primary currents and watts for tests 1 and 2 are basically the same while the currents and watts for tests 3 and 4 are basically zero. The same is true for the secondary as tests 5 and 6 are basically the same while tests 7 and 8 are zero. This two winding transformer was used in an application from a very high voltage (230 kV) to a much lower voltage (25 kV). Electrostatically shield transformers are used to protect sensitive electrical equipment from undesirable high frequency signals commonly generated by lighting, switching surges, motors, and SCR feeds. Electrostatic Shield Figure 7 Shielded Transformer 8 - Hill This shield (Figure 7) is not always represented on a transformer nameplate and this can be very troublesome to a tester since the power factor test results for a shielded transformer will be very different compared to the expected non-shielded results. Since the currents and watts for tests 3, 4, 7, and 8 are often “0” we do not pay a lot of attention to the measured or corrected power factors. A very small current can often result in a very high power factor which in this case is not accurate for the condition of the windings. Transformer 4 Test Data Three Winding Test # 1 2 3 4 5 6 7 8 9 10 11 12 13 ENG H H H 1-2 L L L 5-6 T T T 9-10 All Test kV 10 10 10 4 4 4 1 1 1 mA Watts 61.430 18.110 43.300 43.300 23.260 6.411 16.840 16.849 52.890 52.690 0.179 .200 2.044 0.502 1.553 1.542 1.020 .425 0.612 0.595 2.688 2.676 0.006 0.102 % PF Meas ----0.28 0.36 0.36 ----0.66 0.36 0.35 ----0.52 0.34 0.60 % PF Corr ----0.27 0.35 0.35 ----0.64 0.35 0.34 ----0.49 0.33 0.58 Electrostatic Shield Corr Cap Factor 0.97 19556 0.97 5765 0.97 13785 0.97 13791 0.97 7405 0.97 2040 0.97 5362 0.97 5365 0.97 16837 0.97 16774 0.97 57.040 0.97 63 Meas. CH+CHL CH CHL(UST) CHL CL+CLT CL CLT(UST) CLT CT+CHT CT CHT(UST) CHT CH,CL,CT Figure 8 After performing the math for the primary and secondary windings, for the three winding transformer (Figure 8), it appears the tests were performed correctly. The test results for the tertiary may be questionable as the test results for the tertiary winding are similar to the results for the shielded transformer (Transformer 3). Transformer 4 is not a shielded transformer, however the low voltage winding for this transformer is acting as a “shield” since the low voltage is “guarded” or taken out of the test when performing the tests on the tertiary winding. For test 9 the winding is guarded, test 10 the 9 - Hill winding is guarded, and for the UST test the winding is grounded in which case ground current is not measured. Please note Figure 9 for the winding layout. CHL Figure 9 Three Winding Transformer 10 - Hill Transformer 5 Test Data Two Winding Transformer Test # 1 2 3 4 5 6 7 8 9 10 ENG H H H 1-2 L L L 5-6 Test kV 10 10 10 2 2 2 mA Watts 32.380 9.969 22.390 22.411 40.720 18.320 22.400 22.400 7.753 2.558 1.855 0.694 0.703 1.484 0.737 0.734 0.747 -0.15 % PF Meas ----1.86 0.31 0.31 ----0.40 0.33 0.33 -0.19 % PF Corr ----1.86 0.31 0.31 ----0.40 0.33 0.33 -0.19 Corr Factor 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 Cap Meas. 8591 2644 5941 5947 10803 4860 5942 5943 2058.8 CH+CHL CH CHL(UST) CHL CL+CHL CL CHL(UST) CHL CH’ CL’ Figure 9 Analysis of the data in Figure 9 reveals a very high power factor for test 2 which is the CH. Since CH is the only insulation system that has a very high power factor we do not suspect the oil or any items that part of the secondary winding. From the data on line 9 we determine that C1 tests have been performed on the primary bushings and the CH, without the bushings, now has negative watts. The C1 test data for the primary bushings were: H1 H2 H3 mA Watts 0.761 0.736 0.719 0.798 0.653 0.555 % Power Factor 10.5 8.87 7.72 Figure 10 We can see from the above data (Figure 10) that the summation of the watts (0.798 + 0.653 + 0.555 = 2.006 watts) for the C1 test exceeds the watts for the CH (1.855 watts) which makes the watts for test 9 negative ( 1.855 – 2.006 = -0.19). 11 - Hill Transformer 6 Test Data 2 Winding Transformer Test # 1 2 3 4 5 6 7 8 9 10 ENG H H H 1-2 L L L 5-6 Test kV 10 10 10 10 10 10 mA Watts 33.080 12.860 20.210 20.220 59.360 39.140 20.210 20.220 8.133 35.668 16.220 3.612 12.610 12.608 23.630 11.040 12.610 12.590 3.495 10.813 % PF Meas ----2.81 6.24 6.24 ----2.82 6.24 6.23 4.30 3.03 % PF Corr ----2.84 6.30 6.30 ----2.85 6.30 6.29 4.34 3.06 Corr Factor 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 Cap Meas. 8765 3411 5352 5354 15734 10380 5353 5354 2157 9459 CH+CHL CH CHL(UST) CHL CL+CHL CL CHL(UST) CHL CH’ CL’ Figure 11 The data in Figure 11 indicates that the power factor without the bushings (Line 9) is greater than the power factor with the bushings (Line 2). Review of the data indicates that all of the overall power factors are above the acceptable limits for this transformer. Since all of the power factors are elevated one would first suspect that the insulating fluid and windings are contaminated. As stated earlier we are reviewing the average power factors of the insulations. The good bushings made the contaminated winding look “better”. 12 - Hill Transformer 7 Test Data Auto Transformer with a Tertiary Test # 1 2 3 4 5 6 7 8 ENG HL HL HL 1-2 T T T 5-6 Test kV 10 10 10 10 10 10 mA Watts 50.720 22.200 28.490 28.520 95.080 66.550 28.490 28.530 1.039 0.528 0.518 0.511 1.752 1.228 0.520 0.524 % PF Meas ----0.24 0.18 0.18 ----0.18 0.18 0.18 % PF Corr ----0.24 0.18 0.18 ----0.18 0.18 0.18 Corr Factor 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 Cap Meas. 13456 5890 7557 7566 25220 17655 7557 7565 CH+CHT CH CHT(UST) CHT CT+CHT CT CHT(UST) CHT Figure 12 An auto transformer with a tertiary is actually a two winding transformer. Interpretation of an auto with tertiary is the same as for the two winding. The currents and watts add up correctly so are comfortable that the tests were performed correctly. All of the power factors are below the acceptable limits so this transformer is acceptable. Transformer 8 Two Winding Transformer – Acceptance Tests The following transformer data can be devastating for a testing company as it may cost you an excellent customer. The owner of the transformer questioned if you can have “negative” results. He was informed that it was possible but that it was very abnormal and usually was the result of a test procedure error. The first dataset was the results attained by testing company number #1 while the second dataset was provided by testing company #2. 13 - Hill Data provided by Testing Company #1 Test # 1 2 3 4 5 6 7 8 ENG H H H 1-2 L L L 5-6 Test kV 2 2 2 1 1 1 mA Watts 11.76 3.040 8.729 8.720 15.23 6.514 8.729 8.716 0.600 0.955 -0.350 -0.355 1.634 1.952 -0.330 -0.318 ACCEPTANCE TEST % PF Meas ----3.14 -0.40 -0.41 ----3.00 -0.38 -0.36 % PF Corr ----2.23 -0.3 -0.3 ----2.13 -0.3 -0.3 Corr Factor 0.71 0.71 0.71 0.71 0.71 0.71 0.71 0.71 Cap Meas. 3121 805.9 2315 2315 4041 1727 2315 2314 CH+CHL CH CHL(UST) CHL CL+CHL CL CHL(UST) CHL Figure 13 The numbers add up (Figure 13) to indicate that the test were performed correctly but the power factors for tests 2 and 6 are well above the recommended limits for a new power transformer. Tests 3, 4, 7, and 8 have negative power factors since the watts for test 2 were greater than the watts for test 1. The watts were also great for test 6 than test 5. The troubling thing about these results is that the tester was asked if the transformer was grounded for the tests and he stated that it was grounded for all of the tests. This “tester” (really a button pusher) had no concern for the high power factors, the negative results for watts and power factors, and the inaccurate report that was provide to his customer. Data provided by Testing Company #2 RETEST Test # 1 2 3 4 5 6 7 8 % PF Meas ----0.35 0.24 0.24 ----0.18 0.22 0.25 ENG H H H 1-2 L L L 5-6 Test kV 10 10 10 1 1 1 mA Watts 11.82 3.206 8.616 8.614 15.49 6.874 8.616 8.616 0.314 0.111 0.205 0.203 0.335 0.123 0.191 0.212 Figure 14 14 - Hill % PF Corr ----0.28 0.19 0.19 ----0.14 0.18 0.20 Corr Factor 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 Cap Meas. 3135 850.4 2285 2284 4109 1823 2285 2286 CH+CHL CH CHL(UST) CHL CL+CHL CL CHL(UST) CHL The math for the retest adds up (Figure 14) and the power factors are well below the acceptable limits for a new power transformer. When questioned about these results and what he identified when he arrived on site the 2nd tester stated that the transformer was not grounded. The tester for the second testing company connected the substation ground to the transformer as it was sitting on the concrete pad ungrounded. Who would you call in the future? Conclusion: As one can see, interpretation of power factor test data can be involved and very often time consuming. As mentioned earlier in the paper, it is imperative that the data is analyzed in the field in case other diagnostics tests need to be performed. Do not wait until you get back into the office to perform the math and to analyze the power factors. Do not be a “button pusher”! Biography Keith Hill has been employed at Doble Engineering since 2001, and currently works as a Principal Engineer in the Client Service Department. Keith has over 38 years of experience in substation maintenance, electrical testing, and project management. Mr. Hill is a member of IEEE, a former NETA certified technician, and is a level I and II certified thermographer. Prior to Doble, Mr. Hill was the Electrical Supervisor of Engineering Services for a major refinery. Mr. Hill has published several papers relating to equipment testing and maintenance for various conferences and publications. At the present time, Keith serves as the secretary of the Doble Arresters, Capacitors, Cables, and Accessories committee. Keith received his BS from the University of Houston with a major in Electric Power. 15 - Hill
© Copyright 2024