2620 S Hibernation Pl. Meridian, ID 83642 (208) 884-4221 Fax (208) 898-8876 Report ID# : SAMPLE Schedule Date : Thursday, November 15, 2007 Mr. & Mrs. Buyer Subject Property 1234 Sample Home Boise, ID 83709 CHP Inspections 2620 S Hibernation Pl. INSPECTION Meridian, ID 83642 (208) 884-4221 Fax (208) 898-8876 ORDER FORM REPORT #: SAMPLE Work/Day Phone: Home/Eve Phone: - 921-2072 Other #: Client First/Last : Mr. & Mrs. Buyer Client Address : City/State/Zip : Order Date : Tuesday, February 22, 2011 Ordered by: Referred By: Payment : Schedule Date : 11/15/2007 Time: 1:00 pm Age: 1998 Property Description : Single Family # of units: 1 Square Footage: 1,885 Additions /Alterations: Roof age: Slab Crawlspace Air Conditioning: Yes Bedrooms: Previously Inspected : No Occupied: Yes Utilities: On per agent # of Baths: Base Fee: $285.00 Fees : Additional Services : Property Address : 1234 Sample Home Map Coordinate: Subdivision: Eve. Phone: Day Phone: City/State/Zip : Boise ID 83709 Owner/Tenant : Cross Street : DIRECTIONS : - Attending (Planned): Client Work Phone: - 343-5412 Res. Phone: Cell - 447-7247 Buyers Agent : Real Estate Agent Office : Real Estate Agency C Address : 1234 State Street Fax #: City/State/Zip : Boise ID 83702 - 342-3309 Other #: Mail - amolenaar@windermere. Sellers Agent : Work Phone: Office : Address : Res. Phone: Fax #: - City/State/Zip : Other #: - Special Instruction : Meet at property Inspection Set-Up : w/ Buyer's Agent Confirmation Prior : INSPECTOR : Curt Liles w/ Seller's Agent FOR INSPECTOR'S USE Payment Type: Check INSPECTION FEES: BASE FEE: $285.00 MILEAGE TIME Start: Finish: Total: w/ Client Hrs. Start: End: Total: Signed Contract: Yes Closed Date: Nov, 15, 2007 Date Paid: Nov 15, 2007 ACTUAL ATTENDEES Client Buyer's Agent Seller's Agent Seller Agent was present but did not assist in the inspection. © I.T.A Copyright 1993/2000 ADDITIONAL SERVICES: TOTAL FEES: $285.00 SUB TOTAL: $285.00 PAYMENT: $285.00 TOTAL DUE: $0.00 Page 2 KEY TO THE INSPECTION REPORT Report #: SAMPLE The "Matrix" Report lists the systems and components inspected by this company. Items not found in this report are considered beyond the scope of this inspection, and should not be considered inspected at this time. When "APPEAR SERVICEABLE" is checked it means that we did not observe conditions that would lead us to believe problems existed with this system or component. The item is capable of being used. Some serviceable items may, however, show wear and tear. Significantly deficient systems or components May be identified as: A number or an astericks in brackets found in the key below, not functional / unsafe / worn, or near the end of lifespan. When an item of concern is found, have that item and the entire system evaluated by a specialist in that field. Please read the entire report for all items checked. Notice: This report contains technical information that may not be readily understandable to the lay person. Therefore, a verbal consultation with the inspector is a mandatory part of this inspection report. If you choose not to consult with the inspector, this inspection company cannot be held liable for your understanding or misunderstanding of this report's contents. If you were not present during this inspection please call the office to arrange for your verbal consultation. KEY TO THE INSPECTION REPORT * Items that have an asterisk next to them. This item or component warrants additional attention, repair or monitoring. (1) (1) (2) (3) (4) (5) Items that have a (1) next to them. The Bracketed Numbers are defined as follows: Recommended evaluation by a qualified licensed structural engineer / geotechnical engineer. Recommend a complete evaluation of the system for further review and repairs as needed by a qualified license contractor or specialty tradesman dealing with that item and / or system. Recommend further review for the presence of any wood destroying pests or organisms by qualified Pest Inspector. This item is a safety hazard - correction is needed. Recommend upgrading for safety enhancement. This building may have been constructed before current safety standards were developed. NOTICE: AN ABRIDGED VERSION OF THIS KEY IS PRINTED AT THE TOP OF EACH REPORT PAGE. If you do not understand how to read this report please contact our office. I have read and understand the Key to the Matrix Inspection Report. Client's Initials ____________ Representative/Agent's Initials___________ I agree to read the special "NOTICES" in each section of the report for further information concerning the limitations of this inspection. Client's Initials ____________ Representative/Agent's Initials____________ Present During The Inspection: Client Buyer's Agent Seller's Agent Seller Agent was present but did not assist in the inspection. INSPECTOR : Curt Liles Inspection Date: Nov/15/2007, Thursday Start Time: Completion Time: The weather condition at the time of inspection was Dry Approximate temperature during 50.0 inspection Property Information: The subject property inspected was a (an): Approximate age of building: 1998 Approximate age of roof: Additions / Alterations to: Single Family. # of units Stated by: Stated by: Stated by: 1 NOTICE: It is always wise to check with the building department for permit information, especially if additions or alterations are noted. IMPORTANT NOTICE TO THIRD PARTIES OR OTHER PURCHASERS: RECEIPT OF THIS REPORT BY ANY PURCHASERS OF THIS PROPERTY OTHER THAN THE PARTY(IES) IDENTIFIED ON THE CONTRACT PAGE #1 IS NOT AUTHORIZED BY THE INSPECTOR. THE INSPECTOR STRONGLY ADVISES AGAINST ANY RELIANCE ON THIS REPORT. WE RECOMMEND THAT YOU RETAIN A QUALIFIED PROFESSIONAL INSPECTOR TO PROVIDE YOU WITH YOUR OWN INSPECTION AND REPORT ON THIS PROPERTY. © I.T.A Copyright 1993/2000 Page 3 COMPILED COMMENTS REPORT This compiled Comments report is provided as a courtesy for quick access to the information within the inspection report. It is not intended as a substitute for reading the inspection report. Report #: Client: Mr. & Mrs. Buyer 1. Driveway SAMPLE GROUNDS Page 4 2. Sidewalks 3. Retaining Walls 4. Patio 5. Patio Cover 6. Decks/Porches The 6x6 posts at the rear deck are rotting at the ground. The furthest west post appears to have boring insects. Sawdust like wood at the decayed areas. (2)(3) (see photo) 7. Fences & Gates 8. Exterior Stairs EXTERIOR Page 5 9.Exterior Walls Suggest caulking at the skirt board along the front of the house to prevent water from getting trapped behind board. Common problem for moisture damage. (*) Minor moisture damage at this location. (see photo) 10. Trim /Eaves, Soffits & Facia Trim board / weather strip is pulling away next to the vehicle door. (*) (see photo) Suggest caulking over trim of window on the north side of the house. Minor moisture damage has occurred at this location. (*) (see photo) Minor chipping of paint at trim of rear french door. (*) 11. Chimney 12. Sprinklers 13. Hose Faucets 14. Gutters & Downspouts Gutter at the front of the house is full of leaves. Suggest cleaning for proper drainage. (*) (see photo) 15. Lot Drainage / Grading CHP Inspections FOUNDATION Report # : SAMPLE Page 6 Part - 1 There is a small tree growing too close to the foundation on the south side of the house, (*) (see photo) 16. Slab on Grade, 17. Raised Foundation, 18. Basement Wood Frame: Floor Joist There is a small moisture stain in the floor below the threshold of the master shower, visible from the crawlspace.(2) Excessive moisture level readings were found in the floor at this location.(2)(see photo) 18. Basement 19. Main Roof ROOF Page 7 20. Second Roof 21. Third Roof 22. Exposed Flashing 23. Main Line PLUMBING Page 8 24. Water Supply Lines 25. Waste Lines 26. Fule System 27. Water Heater(s) 28. Description HEATING Page 9 29. Condition 30. Venting 31. Combustion Air 32. Burners 33. Distribution 34. Normal Controls CHP Inspections HEATING Continued & AIR COOLING Report # : SAMPLE Page 10 Part - 2 35. Air Filters There is a bent piece of metal at the back of the air plenum in the furnace where the air filter goes. This piece of metal is preventing the air filter from being installed properly. (2) (see photo) Wrong size air filter is currently installed. It appears the the correct size filter should be 25x17x1. (*) 36. Heating Notes 37.& 38.Evaporative Cooler/Air Conditioner Comments The air conditioning unit was not tested due to the outside air temperature being below 65 deg. (*) 39. Electric Service ELECTRICAL Page11 40. Main Panel 41. Conductors,42. Sub-panel(s),43. Panel Notes 44. Wiring Notes There is an electrical wire laying on the ground in the crawlspace at the south west end. (2) (see photo) 45. Entry Doors INTERIOR Page12 Piece of weather stripping is loose at the bottom of the rear french door. (*) 46. & 47 .Interior & Exterior Doors Torn screen at the rear patio door. 48. Windows There is a piece of back stop that is coming loose from around the eyebrow window at the front of the house. (2) (see photo) Damaged screen at east window of master bedroom. 49. Interior Walls 50. Ceilings 51. Floors 52. Fireplace 53. Interior Features INTERIOR Continued Page13 54. Smoke Detectors 55. Laundry E i b ild fd CHP Inspections li t i th d t (2) Report # : SAMPLE Part - 3 Excessive build up of dryer lint in the dryer vent. (2) 56. Attic Ventilation 57. Floor GARAGE Page14 58. Firewall/Ceiling 59. Ventilation 60. Door to Living Space 61. Exterior Door 62. Vehicle Door There is some damage to the top of the single vehicle door. (2) (see photo) Minor damage to the weather stripping at the bottom of the vehicle door. 63. Automatic Opener The door opener at the single vehicle door has been pulled loose and is now disconnected. The door is damaged at the top from where the arm to the opener has been pulled loose. (2) (see photo) 64. Electrical 65. Comment 66. & 67 .Kitchen Sink(s), General Features KITCHEN Page15 68. Garbage Disposal 69. Range / Oven / Cooktop 70. Dishwasher 71. Special Features 72. Toilet BATHROOMS Page16 73. Sink The drain to the sink is cracked in the main bathroom at the drain stopper. (2) (see photo) 74 Ventilation / Heat CHP Inspections Report # : SAMPLE Part - 4 73. Sink The drain to the sink is cracked in the main bathroom at the drain stopper. (2) (see photo) 74. Ventilation / Heat 75. Bathtub 76. Shower There is minor swelling of the floor in front of the entry to the shower in the master bathroom. (2). Excessively high moisture level readings in front of the shower in the master bathroom. (2) Excessively high moisture level reading in the north and east wall in the shower of the master bathroom. (2) 77. & 78. Body Type Plaster/Gunite, & Heater POOL / SPA EQUIPMENT PAGE 17 79. Filter 80. Pumps 81. Blowers 82. Electrical 83. General CHP Inspections Report # : SAMPLE Part - 5 CHP Inspections Page 4 KEY: GROUNDS Report # : SAMPLE (1) Recommend evaluation by a structural engineer/geo-technical engineer. (2) Recommended complete evaluation of system and repairs by a liscenced contractor (3)Refer to qualified termite report for further information 1 Driveway Appears serviceable Eroded Asphalt* No cracks found N/A Not Functional* Maintenance* Common cracks Asphalt Unsafe* Worn* Sealant needed* Major cracks* (4) This item is a safety hazard - correction is needed (5) Upgrades are recommended for safety enhancement (*) This item warrants attention/repair or monitoring Concrete Near end of lifespan* Not fully visible* Deterioration* Evidence of poor drainage* Trip hazards* Surface raised* Surface settled* Comments: 2 Sidewalks Appears serviceable No cracks found Concrete is above* N/A Not Functional* Common cracks Concrete Brick Paver / Tile Unsafe* Worn* Near end of lifespan* Not fully visible* Major cracks* Trip hazards* Surface raised* Surface settled* Evidence of poor drainage* Other* Comments: 3 Retaining Walls Appears serviceable No cracks found Comments: N/A LOCATION(S): Not Functional* Common cracks Unsafe* Worn* Major cracks (1) Concrete Near end of lifespan* Moisture penetration* N/A LOCATION(S): Rear 4 Patio Appears serviceable No cracks found Concrete is above* Not Functional* Common cracks Concrete Stucco Block Not fully visible* No drainage openings* Brick Unsafe* Worn* Near end of lifespan* Not fully visible* Major cracks (1) Trip hazards* Surface raised* Surface settled* Evidence of* Comments: 5 Patio Cover Appears serviceable Attachment to house * Moisture at N/A LOCATION(S): Not Functional* Open Design Unsafe* Worn* Patio cover lacks Earth contact (3) Covered Roof (refer to Roof Page)* Near end of lifespan* Not fully visible* Wood appears Comments: 6 Decks / Porch N/A WOOD Waterproofed Coating Concrete LOCATION(S): A Front Porch B Rear Deck C Not Functional* Appears Serviceable Unsafe* Worn* Near end of lifespan* Not fully visible* Deck is on grade--unable to inspect* Piers need Posts need Cracks Moisture Deck appears unsound (1) (2) (A) (B) (C) Flashing Earth-to-wood contact (3) (A) (B) (C) Porch* Steps* Uneven* Screens* Panels* Unable to Railings are serviceable N/A Railing Railing of Comments: The 6x6 posts at the rear deck are rotting at the ground. The furthest west post appears to have boring insects. Sawdust like wood at the decayed areas. (2)(3) (see photo) 7 Fences & Gates N/A Appears serviceable Not Functional* Posts are No cracks Common cracks Gate(s) need Comments: NOT INSPECTED Wood Chain Link Unsafe* Worn* Near end of lifespan* Not fully visible* Blocks are Boards are Major cracks (2) Fence height at Self closing device is Post rusted & leaning* Page 4 © I.T.A Copyright 1993/2000 CHP Inspections Page 5 KEY: EXTERIOR Report # : SAMPLE (1) Recommend evaluation by a structural engineer/geo-technical engineer. (2) Recommended complete evaluation of system and repairs by a liscenced contractor (3)Refer to qualified termite report for further information 8 Exterior Stairs Appears serviceable Moisture Railings serviceable (4) This item is a safety hazard - correction is needed (5) Upgrades are recommended for safety enhancement (*) This item warrants attention/repair or monitoring N/A Type: Location: A Not Functional* Unsafe* Worn* Uneven B Near end of lifespan* N/A Railings C Not fully visible* Openings in rails too large (5) Comments: 9 Exterior Walls N/A Structure: WOOD FRAME Wall Covering is: Masonite Lap Siding Near end of lifespan* Not Functional* Unsafe* Worn* Not fully visible* Common cracks* Major cracks (1) Cracks / openings need repair (2) Soil contact *(3) Damaged Nailing defects * Appears serviceable No cracks found Moisture stains/damage* Comments: Suggest caulking at the skirt board along the front of the house to prevent water from getting trapped behind board. Common problem for moisture damage. (*) Minor moisture damage at this location. (see photo) Notice: Wall insulation type and value is not verified* UFFI insulation or hazard are not identified* testing is not performed* N/A 10 Trim / Eaves,Fascia,Soffits WOOD Conditions inside the wall cannot be judged* METAL VINYL Lead paint Masonite Eaves, soffits, facia & trim appears serviceable Not Functional* Unsafe* Worn* Near end of lifespan* Moisture stains at Not fully visible* N/A Flashings / Trim : Not visible at: Comments: Trim board / weather strip is pulling away next to the vehicle door. (*) (see photo) Suggest caulking over trim of window on the north side of the house. Minor moisture damage has occurred at this location. (*) (see photo) Minor chipping of paint at trim of rear french door. (*) 11 Chimney(s) N/A Location: A B C D D METAL FLUE WOOD FRAME Material: A B C Appears serviceable Not Functional* Unsafe* Worn* Near end of lifespan* Not fully visible* Chimney / brick / mortar is: Settlement (2) Flashing is Spark screen present Raincap / screen recommended * Spark screen: Unlined flue (2) Cracks in chimney cap * Cracks/separations/sealing needed at Ash dump / door is: Damage / deterioration / defect * Comments: Notice: The interior of the flue was not inspected at this time. We recommend that you retain a qualified chimney sweep to clean and evaluate the flue * 12 Sprinklers N/A Appears serviceable Not Functional* Valve Head Line Adjust spray away from Comments: Not inspected* Unsafe* Non operational (2) Control box location Garage Worn* Near end of lifespan* Not fully visible* Anti-siphon valves needed * Areas of inadequate spray coverage * Adjust heads * Notice: Underground pipes cannot be judged for breaks or possible root intrusions. Association-maintained systems are not tested. Grove systems are not tested.* 13 Hose Faucets Appears serviceable Comments: N/A Faucets are Frost Free Type Some inoperative / corroded (2) 14 Gutters & Downspouts Appears serviceable Not Functional* Drains blocked* Debris filled* Add gutters & downspouts for drainage* Roof / gutters not draining properly* N/A Full Leaks (2) Missing handle(s)* Partial Broken handle(s)* None Installed Unsafe* Worn* Near end of lifespan* Not fully visible* Gutters / downspouts: Add splashblocks for drainage* Route downspouts away from building* No secondary drain(s) on roof (2) Subsurface drains not tested* Comments: Gutter at the front of the house is full of leaves. Suggest cleaning for proper drainage. (*) (see photo) Notice: Gutters and subsurface drains are not water tested for leakage or blockage.* to avoid water problems at the roof and foundation.* Regular maintenance of drainage systems is required © I.T.A Copyright 1993/2000 Page 5 CHP Inspections Page 6 KEY: FOUNDATION Report # : SAMPLE (1) Recommend evaluation by a structural engineer/geo-technical engineer. (2) Recommended complete evaluation of system and repairs by a liscenced contractor (3)Refer to qualified termite report for further information 15 Grading N/A Level Site Slope Minor (4) This item is a safety hazard - correction is needed (5) Upgrades are recommended for safety enhancement (*) This item warrants attention/repair or monitoring Moderate Steep (1) Drainage of site/slope of soil at foundation is proper based upon visual observation Improper soil slope toward foundation* Soil / pavement is high at foundation* Plants touch Trees planted close to structure * Surface drains noted, not tested - underground pipes cannot be judged* Stairstepped Banks Not fully visible* Earth-to-wood contact visible* (3) Overgrown landscaping* Signs of poor drainage / erosion* Comments: There is a small tree growing too close to the foundation on the south side of the house, (*) (see photo) Notice: This inspection does not include geological conditions or site stability information. For information concerning these conditions, a geologist or soils engineer should be consulted. 16 Slab-on-grade 17 Crawlspace 18 Basement N/A Foundation: Poured Concrete Masonry Block Brick Stone Piers Wood Columns: Concrete Steel Wood Masonry Block Brick Not Visible* Entered crawl space No access* Partial access* Viewed from access opening only* Door Cover : Damaged* Missing* Crawlspace Basement Visible Partially visible* Not visible at* Foundations: Appears serviceable Not Functional* Unsafe* Worn* Near end of lifespan* Not fully visible* No cracks found Further evaluation needed (1) No moisture present Exposed footing* Unable to inspect Slab not visible due to Cracks appear common in size and type* Settlement Ventilation: Serviceable N/A Vents Comments: Notice: All slabs experience some degree of cracking due to shrinkage in the drying process. In most instances floor coverings prevent recognition of cracks or settlement in all but the most severe cases. The inspector will, at additional cost, reinspect, provided the client removes floor covering and releases the inspector from damage caused by this process. Floor coverings are not removed during this inspection.* JOISTS TRUSSES CONCRETE NOT VISIBLE N/A CONVENTIONAL WOOD FRAMING TRUSS Appears serviceable Not Functional* Unsafe* Worn* Near end of lifespan* Not fully visible* Framing is Missing framing Moisture Damaged Missing Earth-to-wood contact (2) (3) Joists Beams Post Columns Debris under house* Concrete floors: Evidence of Anchor bolts Shear panels Probing where deterioration is suspected revealed: Engineer recommended (1) Insulation fiberglass N/A Installed Not installed* Not visible* Loose* Installed incorrectly* VAPOR RETARDER Sump pump N/A Serviceable Not functional* Pump not tested* Sump pump needed* Floor Construction: Wood Frame: Comments: There is a small moisture stain in the floor below the threshold of the master shower, visible from the crawlspace.(2) Excessive moisture level readings were found in the floor at this location.(2)(see photo) BASEMENT STAIRS Railings N/A Serviceable Uneven rise(2)(4) Uneven run(2)(4) Stairs too steep (2)(4)(5) loose step(s) (2)(4) Ceiling is Comments: Notice: The inspector does not determine the effectiveness of any system installed to control or remove suspected hazardous substances* No engineering is performed during this inspection * © I.T.A Copyright 1993/2000 Page 6 CHP Inspections Page 7 KEY: ROOF Report # : SAMPLE (1) Recommend evaluation by a structural engineer/geo-technical engineer. (2) Recommended complete evaluation of system and repairs by a liscenced contractor (3)Refer to qualified termite report for further information (4) This item is a safety hazard - correction is needed (5) Upgrades are recommended for safety enhancement (*) This item warrants attention/repair or monitoring Second Roof Third Roof Roof style: Main Roof Gable How inspected: Walked Viewed from ladder* Viewed from ground* With binoculars* Inspection is limited* Not fully visible due to: Height Weather Snow Type Debris N/A 19 Main Roof N/A Roof Covering is: Asphalt Composition Shingle # of layers: 1 Appears serviceable/within useful life Not Functional* Unsafe* Worn* Near end of lifespan*(2) Not fully visible* Typical maintenance recommended. This usually consists of repair/replacement of damaged/missing ridge and other shakes/shingles. This maintenance should help ensure the water tightness of the building and be performed on a regular basis.* General condition favorable with signs of weathering and aging-regular maintenance and inspection advised.* Roof covering has Moisture stained / damage* Weathering* Burnt through (2) Cracking* Holes/opening (2) Exposed (2) Deteriorated membrane (2) Aging* Loose Displaced Damaged Missing: Pitch appears insufficient (2) Moss covered* Roof material appears to be improperly installed (2) Fasteners are (2) Roof appears to be Evidence of prior patching / repairs (2) Comments: 20 Second Roof N/A Roof Covering is: Appears serviceable/within useful life Not Functional* Fasteners (2) Condition: Loose Displaced Damaged Missing Roof material appears improperly installed (2) Unsafe* # of layers: Worn* Near end of lifespan*(2) Not fully visible* Dented Rusted Deteriorated paint (2) Prior repairs (2) Insufficient Pitch(2) Moss covered* Holes/openings(2) Exposed(2) Deteriorated membrane(2) Comments: Notice: Roofs of this material are often not walked on to avoid causing damage. Not all tiles/slates are checked for attachment.* Inspection is limited* 21 Third Roof N/A Roof Covering is: # of layers: Appears serviceable/within useful life Not Functional* Unsafe* Worn* Near end of lifespan*(2) Not fully visible* Typical maintenance recommended. This usually consists of covering exposed/bare with additional coating/aggregate material. Repair of open seams, cracks in flashings, deteriorated roof coverings, etc. * Excessive damage (2) Excessive deterioration (2) Roof material appears to be improperly installed (2) Blistering* Cracking* Alligatoring* Open seams (2) Moss covered (2) Deteriorated surface (2) Evidence of Bare areas exposed to the sun (2) Fasteners Roof appears to be Evidence of prior patching / repairs (2) Comments: Roof Notes N/A NOTICE: Comments: Notice: The report is an opinion of the general quality and condition of the roof.* The Inspector cannot, and does not, offer an opinion or warranty and to whether the roof has leaked in the past, or may be subject to future leakage. Notice: The report is an opinion of the general quality and condition of the roof.* 22 Exposed Flashings N/A Flashings appears serviceable Not Functional* Unsafe* Worn* Near end of lifespan*(2) Not fully visible* Separation (s) / improper at: Roof* Wall* Drip edge* Vent Pipes* Skylight* Other * Vent caps appear serviceable Needs repair* Missing caps* Rusty flashing* Mastic covered* Damaged flashing* Improper flashing at: No visible flashing at: Skylight(s) appear serviceable Cracked (2) Defect (2) Non professional skylight* Damaged (2) Comments: Notice: Determining the presence of asbestos or hazardous materials is beyond the scope of this inspection.* Roofs, skylights and flashing are not water tested for leaks.* Notice: Tenting a home for fumigation may cause damage to roofs -- recommend reinspection for damage after tenting is completed.* © I.T.A Copyright 1993/2000 Page 7 CHP Inspections Page 8 KEY: PLUMBING Report # : SAMPLE (1) Recommend evaluation by a structural engineer/geo-technical engineer. (2) Recommended complete evaluation of system and repairs by a liscenced contractor (3)Refer to qualified termite report for further information (4) This item is a safety hazard - correction is needed (5) Upgrades are recommended for safety enhancement (*) This item warrants attention/repair or monitoring N/A Main pipe is Black Poly AM PM Size: 1" Pressure: OK Pressure is above 80 psi - recommend: Appears serviceable Not Functional* Unsafe* Worn* Near end of lifespan* Not fully visible* Main valve location: Not located* Operational Not operational (2) Not inspected* Handle is Excessive corrosion on valve (2) Copper pipe not protected from concrete* Leaks at main valve (2) Leaks at water conditioner (2) Water softener installed (water condition/quality is not tested*) 23 Main Line Comments: 24 Supply Lines N/A Supply lines are PEX Appear serviceable Not Functional* Unsafe* Worn* Near end of lifespan* Not fully visible* Supply pipes show Leaking noted at: Water flow appears Noise in pipes (2) Pipes lack support at: Cross connection(s) present at: Evidence of Copper and galvanized pipe contact visible (2) Insulated : N/A Yes No Comments: Notice: Underground pipes or pipes inside walls cannot be judged for size, leaks or corrosion.* Water quality testing or testing for hazards such as lead is not part of this inspection.* advised that some "Polybutylene" plastic piping systems have experienced documented problems. 25 Waste Lines N/A Notice: Be Waste lines are ABS Appear serviceable Not Functional* Waste pipes show Plumbing Insufficient fall for adequate drainage (2) Unsafe* Worn* Near end of lifespan* Not fully visible* Pipes lack proper support at: All vents/traps not fully visible* Leaking noted at: Open waste line (2) Trap Comments: Notice: City sewer service, septic systems and all underground pipes are not a part of this inspection. Future drainage performance is also not determined.* Be advised that some "ABS" plastic piping systems have experienced documented problems. Contact the manufacturer or plumbing expert for further information and evaluation.* 26 Fuel System Appears serviceable Pipes not Improper piping at: No shutoff valve at: N/A Shut Valve Location: South Side Fuel type is Natural Gas Fuel system is not on for inspection-suggest utilities company light and test all fuel appliances* Not Functional* Unsafe* Worn* Near end of lifespan* Not fully visible* Pipe is corroded (2) Pipe is under strain (2) Exposed plastic pipe (2) Pipe is not 6" above ground (2) Improper union at: Pipes lack proper support (2) Comments: Notice: Underground piping & fuel tanks cannot be judged. Pipes inside walls or pipes concealed from view cannot be judged and the inspector does not perform tests for gas leaks or pipe size.* 27 Water Heaters N/A Location A Garage Type Natural Gas Capacity 40 Gallons Location B Type Capacity Appears serviceable Not Functional* Unsafe* Worn* Near end of lifespan* Not fully visible* Rust flakes in burner chamber* Burner flame appears improper (2) Heater leaks Heater in garage is not on 18" raised platform* (5) Water shutoff valve installed (no test) Corrosion on pipes* Temperature Pressure Relief Valve installed (no test) Combustion air Insufficient clearance to combustible material (2) Pilot / system off -- could not inspect* Vent flue piping is serviceable Vent flue piping Seismic straps appear serviceable Seismic straps Thermal blanket Unit needs a catch pan with an exterior routed drain line* Recommend protecting heater from physical damage* Enclosure Firewall Comments: Notice: Estimate of remaining life is not part of this inspection. Solar systems are not part of this inspection. Hot water recalculating pumps/systems are not part of this inspection.* © I.T.A Copyright 1993/2000 Page 8 CHP Inspections Page 9 KEY: HEATING Report # : SAMPLE (1) Recommend evaluation by a structural engineer/geo-technical engineer. (2) Recommended complete evaluation of system and repairs by a liscenced contractor (3)Refer to qualified termite report for further information 28 Description (4) This item is a safety hazard - correction is needed (5) Upgrades are recommended for safety enhancement (*) This item warrants attention/repair or monitoring N/A Approximate BTU's Unit A 100,000 Location A Garage Heating Type: Forced air Fuel Type: Natural gas Comments: Location B Heating Type: Fuel Type: Unit B Unit C Location C Heating Type: Fuel Type: Notice: If a fuel burning heater / furnace is located in a bedroom, we recommend evaluation by a qualified heating contractor for safety and air volume requirements.* 29 Condition N/A System(s) appear serviceable Not Functional Unsafe Worn System(s) Not inspected* Did not respond to normal controls (2) Near end of lifespan Damage Deterioration Comments: Notice: Inspector does not light pilots. If pilots are "OFF" , a full inspection is not possible. TRANSACTION. * 30 Venting N/A It is suggested that heating systems be activated and fully inspected PRIOR TO CLOSE OF Backventing (2) Appears serviceable Damage (2) Vent lacks clearance from combustibles (2)(4) Improper materials used for vent pipe Soot/Rust on Vent terminates near window/opening (2) Unable to fully inspect vent pipe* Not accessible* Improper vent rise Improper elbow angle Defective Comments: 31 Combustion Air N/A Air supply Appears serviceable Damage* Deteriorated* Combustion and return air sources are too close or mixing (2) Recommend sealing platform at: Defects* Comments: 32 Burners N/A Burner flame appears typical Rust flakes in burn chamber (2) Closed system / unable to inspect* Unusual flame pattern (2) Damaged Chamber Comments: Notice: The inspector is not equipped to thoroughly inspect heat exchangers for evidence of cracks or holes, as this can only be done by dismantling the unit or other technical procedures.* Some furnaces are designed in such a way that inspection is almost impossible .* Safety devices are not tested by this company .* 33 Distribution Appears serviceable Register(s) Zone valve did not operate Radiator inoperative (2) Leaks on radiator (2) N/A Type: Ducts & Registers Ducts: Not fully visible* Low air volume (2) Asbestos-like materials (4) Insulation Circulating pump Radiator cold (2) Convector inoperative (2) Convector cold (2) Leaks on convector (2) Leaks on fitting (2) Comments: Notice: Asbestos materials have been commonly used in heating systems.* Determining the presence of asbestos can ONLY be performed © byI.T.A Copyright 1993/2000 laboratory testing and is beyond the scope of this inspection.* Page 9 CHP Inspections Page 10 HEATING Continued KEY: & AIR COOLING (1) Recommend evaluation by a structural engineer/geo-technical engineer. (2) Recommended complete evaluation of system and repairs by a liscenced contractor (3)Refer to qualified termite report for further information 34 Normal Controls N/A Report # : SAMPLE (4) This item is a safety hazard - correction is needed (5) Upgrades are recommended for safety enhancement (*) This item warrants attention/repair or monitoring Unable to inspect* Utilities off* Thermostat Damage* Deterioration* Defects* Gauges need Corrosion at: Appears serviceable Controls need Leaks at: Switch is Expansion tank Comments: Notice: Thermostats are not checked for calibration or timed functions.* 35 Air Filter Appears serviceable N/A Adequacy, efficiency or even heat distribution of the system through the house is not part of this inspection. * Missing* Suggest changing Wrong size* Unable to inspect* Cleaning filter* No filter hold-down* Comments: There is a bent piece of metal at the back of the air plenum in the furnace where the air filter goes. This piece of metal is preventing the air filter from being installed properly. (2) (see photo) Wrong size air filter is currently installed. It appears the the correct size filter should be 25x17x1. (*) Notice: Electronic air cleaners, humidifiers and dehumidifiers are beyond the scope of this inspection. * Have these systems evaluated by a qualified individual. * 36 Heating Notes N/A Recommend complete system evaluation (2) Suggest cleaning & servicing Heater makes unusual noise during operation, further evaluation needed (2) High Low Air leaks at: Condensate lines: Unable to locate heat in all rooms* Fuel tank leak (2) (4) Undercut doors off carpet* Leakage at: Termination location: Comments: Notice: Verification of the location or condition of underground fuel storage tanks is not part of this inspection.* Environmental risks, if any, are not included. * Notice: Asbestos materials have been commonly used in heating systems.* Determining the presence of asbestos can ONLY be performed by laboratory testing and is beyond the scope of this inspection.* 37 Cooler & 38 Air N/A Location(s) Unit A South Side Ext. Type: Central air conditioning Appears operational Unsafe* Not Functional* Unit makes unusual noise during operation (2) Pads Unit Comments: B C Power: One speed fan only* 120volt 240volt Near end of lifespan* Not fully visible* Unit is not level* Float valve Pump Leaking noted* Worn* No power - unable to test* Warm air only (2) Air temp below 65 degrees - unable to test system(s)* (operation could cause damage) One speed fan only* Not level(2) Makes unusual noise(2) Air temperature differential is incorrect (2) Coil is damaged (2) Recommend servicing system and checking refrigerant level* N/A 120 Volts 240 Volts Electrical disconnect present Gas* (not inspected) POWER: No electrical disconnect provided (2) Improper conduit (2) Proper grounding not provided (2) No conduit (2) Junction box Cover Heat pump auxiliary heat not functional(2) CONDENSATE: N/A Condensate line installed Line not fully visible* Termination location: No trap in line* Condensate lines: REFRIGERANT LINES: N/A Insulation installed on-lines Ice on unit (2) Insulation damaged* Insulation deteriorated* Ice on lines (2) Lines not fully visible Leaks at: Line(s) appear damaged (2) Comments N/A DATA PLATE: Unit appears to be 3 ton unit. Comments: The air conditioning unit was not tested due to the outside air temperature being below 65 deg. (*) Notice: The inspector does not perform pressure tests on coolant systems; therefore no representation is made regarding coolant charge © I.T.A Copyright 1993/2000 or line integrity. Subjective judgment of system capacity is not part of the inspection. Page 10 CHP Inspections Page11 KEY: ELECTRICAL Report # : SAMPLE (1) Recommend evaluation by a structural engineer/geo-technical engineer. (2) Recommended complete evaluation of system and repairs by a liscenced contractor (3)Refer to qualified termite report for further information 39 Service N/A (4) This item is a safety hazard - correction is needed (5) Upgrades are recommended for safety enhancement (*) This item warrants attention/repair or monitoring Overhead 120V* Deterioration* Underground Number of conductors 2 240V 120V AMPS 200 AMP AMPS NOT DETERMINED Appears serviceable Defects* Unsafe* Near end of lifespan* Loose connections at Damaged connections at Frayed wires (2) Improper splices on main wires (2) Improper tap on main wires (2) Conductors too close to Wires touch trees* Contact utility company(4) Ground present Ground loose at: Ground Ground clamp not visible* Ground system not visible* More than six breakers with no main shutoff (2) Main disconnect inspected at: Main Panel No drip loop on service wires (2) Comments: 40 Main Panel Appears serviceable Comments: N/A Defects* #A - Location Garage Panel rating 200 AMP Not verified Power is off at main.No inspection performed* Recommend further evaluation* Deterioration* Unsafe* Near end of lifespan* Not accessible* Notice: Six or fewer breakers usually do not require a main breaker, however this may indicate minimal electrical capacity.* If the service amperage is less than 100, upgrade may be needed to operate larger electrical appliances* 41 Conductors N/A 42 Sub-panel(s) N/A 43 Panel Notes Service Wire: Aluminum Branch Wire: Wiring Methods: Non-Metallic Cable #B-Location Panel >> Panel >> N/A #C-Location #D-Location is locked-could not inspect.* Further evaluation is needed* is inaccessible-could not inspect.* Further evaluation is needed* Wiring Methods: Panel(s) appear(s) serviceable Not Functional* Improper wiring at panel# (2): Two wires connected to one breaker at panel # (2): Overfusing fuse/breaker size too large for wire panel #(2): Neutral and ground wires connected at sub-panel #(2): Direct tap Panel bond is not provided for safety at panel #(2): Missing 240 volt - split branch coupler(s) at panel #*: Fused neutral wire(s) at panel # (2): Electrical system appears outdated by today's standards (2) Comments: Breakers Fuses Unsafe* Worn* Near end of lifespan* Breaker is off at panel #*: Signs of Aluminum wiring noted at the general 120volt circuits(2) (Aluminum connections should be checked by a licensed electrician) * Antioxidant not visible on aluminum wire connections* Unprotected opening(s) in panel # (2): N/A Breakers Fuses Opening(s) dead front cover(s) at panel #*(2)(4): N/A Sample of switches and outlets tested appear to be serviceable Grounding and polarity of receptacles within 6' of plumbing fixtures Appears serviceable (tested) Furnishings prevent testing of all outlets and switches* Three prong outlets did not test properly grounded (2)(4) at: Reverse polarity (2)(4) at: Evidence of Outlet not operational (2)(4) at: Light not operational *(2)(4) at: Outlets Switches Open neutral (2)(4) at: Not exterior rated Missing cover plates *(2)(4) at: Exposed wiring needs protection (2)(4) at: Damaged cover plates *(2)(4) at: Box cover missing *(4) at: Exposed splices (2)(4) at: Improper wiring (2)(4) at: Extension cord used as wiring (2)(4) at: 'GFCI(s) responded to test 'GFCI' not operational (2)(4) at: 'GFCI', (a safety device for outlets near water) recommended at: (5) Closet light is subject to damage at:* Closet light is subject to hazard at:* Doorbell worked Fixture Comments: There is an electrical wire laying on the ground in the crawlspace at the south west end. (2) (see photo) 44 Wiring Notes © I.T.A Copyright 1993/2000 Page11 CHP Inspections Page12 KEY: INTERIOR Report # : SAMPLE (1) Recommend evaluation by a structural engineer/geo-technical engineer. (2) Recommended complete evaluation of system and repairs by a liscenced contractor (3)Refer to qualified termite report for further information 45 DOORS (Entry) N/A (4) This item is a safety hazard - correction is needed (5) Upgrades are recommended for safety enhancement (*) This item warrants attention/repair or monitoring Appears serviceable Damage* Hardware operational Doorbell Door jamb operational Comments: Piece of weather stripping is loose at the bottom of the rear french door. (*) 46 & 47 DOORS (Interior & Exterior) Appears serviceable Hardware is operational Door(s) rub at: Damaged at: Tempered glass Tracks serviceable Screen doors not checked* N/A Deterioration* Defects* Weather stripping serviceable Several frames are not square - may indicate movement (1) Damaged jamb* Needs adjustment at: Missing* Loose* Not operational* Door stick at: Difficult to operate at: Unable to determine tempered glass* Door won't latch at: Not tempered (5) Deteriorated track(s) at: Screens Comments: Torn screen at the rear patio door. 48 Windows N/A Type: Vinyl Insulated Sample tested appears serviceable Window Window Stains* Damage* Screens Security bars Window Broken * Comments: There is a piece of back stop that is coming loose from around the eyebrow window at the front of the house. (2) (see photo) Damaged screen at east window of master bedroom. Notice: Determining condition of all insulated windows is not possible due to temperature, weather and lighting variations. Check with owner for further information. 49 Interior Walls N/A Drywall Plaster Paneling General condition serviceable Wall Wall needs repair at: Wall Furnishings prevent full inspection-do a careful check on your final walk-through Recommend evaluation by engineer (1) Comments: Notice: The condition of walls behind wallpaper, paneling and furnishings cannot be judged. 50 Ceilings N/A General condition serviceable Ceiling(s) Ceiling(s) Drywall Acoustic Spray Plaster Ceiling(s) Comments: Notice: Determining whether acoustic sprayed ceilings contain asbestos is beyond the scope of this inspection. For more information please contact the American Lung Association or an asbestos specialist. 51 Floors N/A Carpet Vinyl Wood Tile General condition serviceable Damage * Deterioration * Cracked tiles at: Damaged* Uneven area at: Furnishings prevent full inspection-do a careful final walk-through* Loose carpet noted* Floor squeaks noted* Comments: Notice: Determining odors or stains is not included!* Floor covering damage / stains may be hidden by furniture.* The condition of wood flooring below carpet is not inspected.* 52 Fireplace(s) Fireplace(s) Fireplace(s) Fireplace(s) Gas was Gas at fireplace Fans/blowers at fireplace N/A Location(s) A Type B Not Functional* Unsafe* Fireplace(s) C INSERT (have checked by removal*) Worn* Near end of lifespan* Gas at fireplace Gas at fireplace Remove or block damper open if gas log is used* Comments: Notice: Recommend installing safety spacer on damper when gas logs are present* Wood and ashes are not moved for inspection, Recommend clearing debris and further evaluation.* © I.T.A Copyright 1993/2000 Page12 CHP Inspections Page13 KEY: INTERIOR Continued (1) Recommend evaluation by a structural engineer/geo-technical engineer. (2) Recommended complete evaluation of system and repairs by a liscenced contractor (3)Refer to qualified termite report for further information 53 Interior Features N/A Interior stairs appear serviceable Stair handrails appear serviceable Wet bar faucet appears serviceable Counter appears serviceable Plumbing under sink serviceable Items installed but not inspected: Comments: 54 Smoke Detector N/A Smoke detector test button responds Did not respond to test button* Couldn't test / no test button* Report # : SAMPLE (4) This item is a safety hazard - correction is needed (5) Upgrades are recommended for safety enhancement (*) This item warrants attention/repair or monitoring Ceiling fan(s) operational Fan (s) Uneven Railing is Faucet is not operational (2) Damage to Leaks (2) Central vacuum Security system Stairway is Openings in rails too wide* (5) Faucet leaks (2) Hot/Cold Cold water reversed(4) only Deterioration to Improper piping Icemaker not on Intercom 50 N/A A: Locations: C: Hall B: Bedrooms D: A B C D Not tested* A B C D A B C D None found (5) A B C D Indicator light on Suggest additional detectors in appropriate locations* (5) Comments: 55 Laundry N/A Garage Basement Service Area Piping (water&waste) serviceable Unable to view / not tested* Damage* Deterioration* Door / jambs* Electrical outlet grounded (120 Volt) Unable to test* Ungrounded* Not operational (2) Miswired (2) 240 volt outlet operational Inoperative* No 240 outlet Not viewed* Not inspected* Gas piping appears serviceable N/A No gas provided Unable to view* Dryer venting provided Dryer venting not provided* Dryer vents into attic* Dryer vents into crawl space* Laundry sink serviceable N/A Damage on sink* Deterioration on sink* Sink is loose* Slow draining* Plumbing below sink serviceable Deterioration* Corrosion* Improper piping (2) Leaks (2) Faucet operational Deterioration* Corrosion* Faucet leaks (2) Hot/Cold reversed(4) Comments: Excessive build up of dryer lint in the dryer vent. (2) Notice: Washing machines and dryers are not moved during this inspection - condition of walls or flooring under these machines cannot be judged.* The inspector does not test washing machine drains or supply valves. * Water supply valves if turned may be subject to leaking. * N/A 56 Attic Full Partial Roof Frame: Ceiling Frame: Truss Rafter Framing Truss Joist Framing X X Location: Garage Entered Access Inspection limited to view from access* Appears serviceable Not Functional* Unsafe* Worn* Near end of lifespan* Not fully visible* No stains visible Small stains* Moderate stains (2) Major stains (2) Unable to determine leakage* Sagging framing (1)(2) Broken framing (1)(2) Truss(es) Framing appears undersized* (1) Vents provided None* Blocked* Minimal* Poor ventilation* Missing wind resistant straps(2) Power ventilator operational N/A Not inspected* Not operational* Screens Insulation Type: Fiberglass No insulation* Poor coverage* Compressed* Wrong side up* Approximate depth: 12 inches Insulation covers N/A Installed Vent pipe Air/vapor retarder How Inspected: Comments: N/A Ventilation Exhaust fan Appears serviceable at: All locations Exhaust fan Comments: Notice: Determining the presence of asbestos or other hazardous materials is beyond the scope of this inspection.* Tenting a home for fumigation may cause damage to roofs-recommend reinspection for damage after tenting is completed* © I.T.A Copyright 1993/2000 Page13 CHP Inspections Page14 KEY: GARAGE Report # : SAMPLE (1) Recommend evaluation by a structural engineer/geo-technical engineer. (2) Recommended complete evaluation of system and repairs by a liscenced contractor (3)Refer to qualified termite report for further information GARAGE / CARPORT: N/A N/A 57 Floor No cracks found Floor raised* Attached Detached Major cracks (1) Poor drainage* Carport Damage* Appears serviceable Not fully visible* Floor settled* (4) This item is a safety hazard - correction is needed (5) Upgrades are recommended for safety enhancement (*) This item warrants attention/repair or monitoring Deterioration* Defects* Possible flammable material on floor*(4) N/A Comments: 58 Firewall / Ceiling N/A Not fully visible* Moisture stains* Exterior: Appears serviceable Framing: Damage* Does not appear fire rated (4) N/A Holes* Damage* Missing wall covering* Comments: 59 Ventilation N/A Appears serviceable Screens N/A Solid Blocked* Window None* Comments: 60 Door To Interior Damaged* Appears serviceable Bad seal*(4) Enters in a Bedroom*(4) Self closer operational N/A Rated Door Deterioration* Door does not latch*(4) Closer non-operational* Hollow Core (Non-Fire Resistive)* Pet door interrupts integrity of fire door (2)(4) Door lacks threshold* Door lacks weatherstrip* Closer missing* Closer needs adjustment* Comments: N/A 61 Exterior Door Lock inoperative* Not inspected* Door jamb* Locked* Damaged* Appears serviceable Damaged door jamb* Door threshold* Blocked* Rubs jamb* Delaminated* Needs adjustment* Damaged* Comments: 62 Vehicle Door(s) N/A Roll Up Tilt-Up Sliding Damage* Deterioration* Defects* Door / jambs* Moisture stained* Damaged* Appears serviceable Tension rods loose* Door warped* Needs adjustment* Needs balancing* Hinges loose* Damaged* Safety springs installed Not safety type springs* (4)(5) Broken springs (2)(4) Broken safety wire(2)(4) Vehicle door(s) are locked - could not test* Rollers damaged(2) Tracks damaged(2) Comments: There is some damage to the top of the single vehicle door. (2) (see photo) Minor damage to the weather stripping at the bottom of the vehicle door. 63 Automatic Opener N/A # of Units 2 Appears serviceable Automatic reverse operated Non-operational* Opener / auto-reverse was not tested* Unit Electronic sensor: Automatic reverse did not operate (2)(4)(5) Not inspected* Comments: The door opener at the single vehicle door has been pulled loose and is now disconnected. The door is damaged at the top from where the arm to the opener has been pulled loose. (2) (see photo) 64 Electrical Improper wiring (2)(4) Outlets serviceable Open splices (2)(4) N/A Appears serviceable Damage / deterioration / defects* Not fully visible* Exposed wiring subject to damage *(4) Extension cords used as permanent wiring (2)(4) Open ground (2)(4) Reverse polarity (2)(4) Improper light fixture wiring (2)(4) Junction boxes missing covers*(4) 'GFCI' recommended(5) 'GFCI' defective(2)(4) Some outlet(s) are inaccessible* Outlet(s) not functional (2) Loose/damaged outlet(2) Loose/damaged cover* Comments: 65 Comments N/A Moisture stains on garage ceiling* Moisture stains on garage wall* Occupants' belongings block view of entire garage-unable to fully inspect.* Do a careful check on your final walk-through.* Comments: Notice: Determining the rating of fire walls is beyond the scope of this inspection © I.T.A Copyright 1993/2000 Page14 CHP Inspections Page15 KEY: KITCHEN Report # : SAMPLE (1) Recommend evaluation by a structural engineer/geo-technical engineer. (2) Recommended complete evaluation of system and repairs by a liscenced contractor (3)Refer to qualified termite report for further information 66 Kitchen Sink(s) N/A (4) This item is a safety hazard - correction is needed (5) Upgrades are recommended for safety enhancement (*) This item warrants attention/repair or monitoring Dishes block access to sink, could not inspect* Minor wear Heavy wear* Chipped* Sink is loose* Slow draining* Sink(s) appear(s) serviceable Recommend sealing at sink to counter connection* No hot water* Hot & cold water reversed*(4) Non-operational(2) Defective(2) Faucet: Spray wand defective* Faucet serviceable Pipes are Improper piping (2) Plumbing under sink serviceable Moisture stains below sink* Moisture damage below sink* Restricted view below sink* 67 Kitchen (general) N/A Counters Floor Lights Doors Drawers Counter Minor cracked tile(s)* Cabinets appear serviceable Counters: Tile Not fully visible* Laminate Grout* Caulking* Handles* Appear serviceable Other Minor* Moderate* Heavy wear* Cracks* Damage* Moderate damage* Heavy damage* Missing * Minor wear Moderate damage* Heavy damage* Heavy wear* Comments: 68 Disposal N/A Dishes block access to sink and disposal, could not inspect* Not fully visible* Not Functional* Unsafe* Worn* Near end of lifespan* Non operational (2) Appears serviceable Blades appear to be Unit makes unusual noise* Splash guard damaged* Not inspected* Improper wiring noted (2)(4) Loose wire clamp at disposal* Missing wire clamp at disposal* Wiring serviceable Switch is in a hazardous location (2)(4) Exposed wire splices (2)(4) Missing junction box cover(s)* Power off* Comments: 69 Range / Cooktop N/A # of ovens: 1 Gas Electric Combination Electric Ignition Not Functional* Unsafe* Worn* Near end of lifespan* Range / oven appears serviceable Upper Lower Right Left Front Rear No inspection (power/gas off)* Free standing oven - not tested* Ranges / Cooktop not inspected* Lower Non operational (2) Oven door(s) appear(s) serviceable Door(s) gasket(s) appear(s) serviceable Damage noted* Door does not close properly* Cracked glass (2) Separate cooktop serviceable Not applicable Damaged gasket(s)* Clock not tested Appears non functional* Gas shutoff valve installed N/A Burner did not operate (2) Element did not operate (2) Gas shutoff valve not provided (2) Gas valve is not visible* Exhaust ventilation appears serviceable Comments: Notice: Self and/or continuous cleaning operations, clocks, timing devices, lights and thermostat accuracy are not tested during this inspection.* Appliances are not moved.* 70 Dishwasher N/A No test (power/water off)* Not Functional* Unsafe* Worn* Near end of lifespan* Not fully visible* Appears serviceable Rust at: Damage at: Condition:door, liner & racks serviceable Soap dish inoperative* Washer arm appears frozen (2) Unit is not secured to cabinets* Deteriorated* Leaking (2) Door Door seals appear serviceable Air gap device Hi-loop method Drain line is improperly installed (2) DRAIN LINE INSTALLATION: Air gap device None Improper* Leaking noted at drain lines Leaking noted at air gap device* Comments: Notice: Determining the adequacy of washing and drying functions of dishwashers is not part of this inspection.* 71 Special Features N/A Special features not inspected* Trash compactor appears serviceable Non operational (2) No Key* Microwave appears serviceable Non operational (2) Other features/appliances present but not inspected include Not inspected* Not inspected* Comments: Notice: Refrigerators, freezers and built-in ice maker are not part of this inspection* © I.T.A Copyright 1993/2000 Page15 CHP Inspections Page16 KEY: BATHROOMS Report # : SAMPLE (1) Recommend evaluation by a structural engineer/geo-technical engineer. (2) Recommended complete evaluation of system and repairs by a liscenced contractor (3)Refer to qualified termite report for further information LOCATION: Bath A Main 72 Toilet B Master Bathroom N/A C B B B B C C C C D D D D Sink cracked* Faucet appears serviceable Sink faucet leaks* Low water volume* Drain appears serviceable Slow draining* Rust / corroded drain line* Leaking drain line (2) Counter & cabinet Appears serviceable Damage to counter* Grout needed at counter* A E E E E N/A Appears serviceable 73 Sink D Appears serviceable A A A A Toilet loose at floor* Recommend new wax seal (2) Water runs continually in tank* Does not flush properly* Comments: (4) This item is a safety hazard - correction is needed (5) Upgrades are recommended for safety enhancement (*) This item warrants attention/repair or monitoring B C D E E Loose toilet tank* Cracked Tank * Rust in Tank * Moisture around toilet (2) A B B B B C C C D D D E E E Corrosion at sink faucet* A A B B C C D D E E Corrosion on supply valve below sink* A B C D E A A B B C C D D E E B C D E A B C D E A B C D E B B B B C C C C D D D D E E E E C D E Hot & cold water reversed*(4) Corrosion under sink* A B C D E A A A A A A A A A A B B C C D D E E Sink drain stopper nonfunctional / missing* A B C D E Improper drain trap (2) Restricted view below sink* A B C D E A B C D E Deterioration to cabinet* Moisture damage below sink* A B C D E A B C D E Not applicable to this bathroom Whirlpool not functional (2) A A B B C C D D E E Comments: The drain to the sink is cracked in the main bathroom at the drain stopper. (2) (see photo) 74 Vent / Heat N/A Appears serviceable A B C D E Appears serviceable A B C D E Comments: 75 Bathtub N/A Damage to tub* Faucet appears serviceable Hot & Cold water reversed(4) A A B B C C D D E E A B C D E Damage at faucet* A B C D E Whirlpool not tested(2) A B C D E Drain appears serviceable Slow draining at bathtub* A B C D E Drain stopper missing* A B C D E A B C D E Grout needed tub to wall* A B C D E A A A A B B B B C C C C D D D D E E E E A A A B B B C C C D D D E E E A A B B C C D D E E A A B B C C D D E E Comments: 76 Shower N/A Appears serviceable A B C D E Not applicable to this bathroom Cracked tile(s)* Caulking needed at floor* Floor needs caulking* Low water volume at shower(2) E E Shower diverter non-functional(2) Unable to determine if glass is tempered* Damage to shower walls* Grout needed at shower walls* Moisture damage to wall (2)(3) Slow draining at shower A A A A B B B B C C C C D D D D E E E E Leaking at water valve(s) (2) Shower head drip(2) A A B B C C D D Enclosure appears serviceable Glass does not appear to be tempered* A A B B C C D D E E Broken glass* Caulking needed at enclosure* A A B B C C D D E E Not applicable to this bathroom Corroded fixtures* Doors difficulty to operate* Damaged enclosure* Comments: There is minor swelling of the floor in front of the entry to the shower in the master bathroom. (2). Excessively high moisture level readings in front of the shower in the master bathroom. (2) Excessively high moisture level reading in the north and east wall in the shower of the master bathroom. (2) Notice: Determining whether shower pans are watertight is beyond the scope of this inspection.* © I.T.A Copyright 1993/2000 Page16 Page 17 PICTURES PAGE Client: Mr. & Mrs. Buyer Schedule Date : Thursday, November 15, 2007 Report # : SAMPLE Subject Property 1234 Sample Home Boise, ID 83709 Picture 1 Front Picture 2 Suggest caulking at the skirt board along the front of the house to prevent water from getting trapped behind board. Common problem for moisture damage. (*) © I.T.A Copyright 1993/2000 Page 18 PICTURES PAGE Client: Mr. & Mrs. Buyer Schedule Date : Thursday, November 15, 2007 Report # : SAMPLE Subject Property 1234 Sample Home Boise, ID 83709 Picture 3 Suggest caulking at the skirt board along the front of the house to prevent water from getting trapped behind board. Common problem for moisture damage. (*) Minor moisture damage at this location. Picture 4 Some damage to the top of the single vehicle door. (2) © I.T.A Copyright 1993/2000 Page 19 PICTURES PAGE Client: Mr. & Mrs. Buyer Schedule Date : Thursday, November 15, 2007 Report # : SAMPLE Subject Property 1234 Sample Home Boise, ID 83709 Picture 5 The bottom of the trim board / weather strip next to the vehicle door is beginning to pull away from the house. (*) Picture 6 The back stop is coming loose from around the eyebrow window at the front of the house. (2) © I.T.A Copyright 1993/2000 Page 20 PICTURES PAGE Client: Mr. & Mrs. Buyer Schedule Date : Thursday, November 15, 2007 Report # : SAMPLE Subject Property 1234 Sample Home Boise, ID 83709 Picture 7 There is a small tree growing too close to the foundation on the south side of the house. (*) Picture 8 Suggest caulking over trim of window on the north side of the house. Minor moisture damage has occurred at this location. (*) © I.T.A Copyright 1993/2000 Page 21 PICTURES PAGE Client: Mr. & Mrs. Buyer Schedule Date : Thursday, November 15, 2007 Report # : SAMPLE Subject Property 1234 Sample Home Boise, ID 83709 Picture 9 The 6x6 posts at the rear deck are rotting at the ground. The furthest west post appears to have boring insects. Wood like sawdust is present at the decayed areas. (2)(3) Picture 10 Gutter at the front of the house is full of leaves. Suggest cleaning for proper drainage. (*) Suggest keeping the limbs trimmed back at the front of the house. Damage to the house can occur. (*) © I.T.A Copyright 1993/2000 Page 22 PICTURES PAGE Client: Mr. & Mrs. Buyer Schedule Date : Thursday, November 15, 2007 Report # : SAMPLE Subject Property 1234 Sample Home Boise, ID 83709 Picture 11 The door opener at the single vehicle door become disconnected. The door is damaged at the top where the arm to the opener has been pulled loose. (2) Picture 12 There is a bent piece of metal at the back of the air plenum in the furnace where the air filter goes. This piece of metal is preventing the air filter from being installed properly. (2) © I.T.A Copyright 1993/2000 Page 23 PICTURES PAGE Client: Mr. & Mrs. Buyer Schedule Date : Thursday, November 15, 2007 Report # : SAMPLE Subject Property 1234 Sample Home Boise, ID 83709 Picture 13 Wrong size air filter is currently installed. It appears the the correct size filter should be 25x17x1. (*) Picture 14 The drain to the sink is cracked in the main bathroom at the drain stopper. (2) © I.T.A Copyright 1993/2000 Page 24 PICTURES PAGE Client: Mr. & Mrs. Buyer Schedule Date : Thursday, November 15, 2007 Report # : SAMPLE Subject Property 1234 Sample Home Boise, ID 83709 Picture 15 There is a small moisture stain in the floor below the threshold of the master shower, visible from the crawlspace.(2) Excessive moisture readings were found in the floor at this location. (2) Picture 16 There is an electrical wire laying on the ground at the south west end of the crawlspace. (2) © I.T.A Copyright 1993/2000 2620 S Hibernation Pl. Meridian, ID 83642 (208) 884-4221 Fax (208) 898-8876 THIS IS INTENDED TO BE A LEGALLY BINDING CONTRACT... PLEASE READ CAREFULLY. Report #: SAMPLE Client: Mr. & Mrs. Buyer Address: City/State/Zip: Subject Property 1234 Sample Home Boise, ID 83709 I/We (Client) hereby request a limited visual inspection of the structure at the above address to be conducted by , (Inspector), for my/our sole use and benefit. I/We warrant that I/We will read the following agreement carefully. I/We understand that I/We are bound by all the terms of this contract. I further warrant that I will read the entire inspection report when I receive it and promptly call the inspector with any questions I may have. Initial Here _________________________ ____________________________ STANDARD INSPECTION AGREEMENT SCOPE OF THE INSPECTION: The real estate inspection to be performed for Client is a non-invasive physical examination, performed for the fee set forth below, designed to identify material defects in the systems, structures, and components of the above-referenced primary building and its associated primary parking structure as they exist at the time of the inspection. A material defect is a condition that significantly affects the value, desirability, habitability or safety of the building. Style or aesthetics shall not be considered in determining whether a specific system, structure, or component is defective. The inspection shall be limited to those specific systems, structures, and components that are present and visually accessible. Components and systems shall be operated with normal user controls only and as conditions permit. This inspection is not intended to be technically exhaustive. Inspector shall prepare a written inspection report for the sole use and benefit of Client. The inspection report shall describe and identify the inspected systems, structures, and components of the building and shall identify material defects in those systems, structures, and components observed during the inspection. Client agrees to read the entire inspection report when it is received and shall promptly call the Inspector with any questions or concerns client may have regarding the real estate inspection or the inspection report. I have read and agree to the Scope of the Inspection : X ____________________________________________________ LIMITATIONS, EXCEPTIONS AND EXCLUSIONS: Excluded from this real estate inspection is any system, structure, or component of the building which is inaccessible, concealed from view, or cannot be inspected due to circumstances beyond the control of Inspector, or which Client has agreed is not to be inspected. The following are excluded from the scope of this real estate inspection unless specifically agreed otherwise between Inspector and Client: · Determining compliance with installation guidelines, manufacturers' specifications, building codes, ordinances, regulations, covenants, or other restrictions, including local interpretations thereof. · Obtaining or reviewing information from any third-parties including, but not limited to: government agencies (such as permits), component or system manufacturers (including product defects, recalls or similar notices), contractors, managers, sellers, occupants, neighbors, consultants, homeowner or similar associations, attorneys, agents or brokers. · Geotechnical, engineering, structural, architectural, geological, hydrological, land surveying or soils-related examinations. · Examination of conditions related to animals, rodents, insects, wood-destroying insects, organisms, mold, and mildew or the damage caused thereby. · Certain factors relating to any systems, structures, or components of the building, including, but not limited to: adequacy, efficiency, durability or remaining useful life, costs to repair, replace or operate, fair market value, marketability, quality, or advisability of purchase. · Environmental hazards or conditions, including, but not limited to, toxic, reactive, combustible, corrosive contaminants, wildfire, geologic or flood. · Dismantling of any system, structure, or component, or perform any intrusive or destructive examination, test or analysis. · Examining or evaluating fire-resistive qualities of any system, structure or component of the building. · Systems, structures, or components of the building which are not permanently installed. · Systems, structures, or components not specifically identified in the written inspection report. · Common areas, or systems, structures, or components thereof, including, but not limited to, those of a common interest development as defined in California Civil Code section 1351, et seq. · Examining or evaluating the acoustical or other nuisance characteristics of any system, structure, or component of a building, complex, adjoining properties, or neighborhood. · Operating or evaluating low voltage electrical, antennas, security systems, cable or satellite television, telephone, remote controls, radio controls, timers, intercoms, computers, photo-electric, motion sensing, or other such similar non-primary electrical power devices, components, or systems. · Examining or operating any sewage disposal system or component including, but not limited to: septic tanks and/or any underground system or portion thereof, or ejector pumps for rain or waste. I have read and agree to the Limitations, Exceptions & Exclusions: X________________________________________ Services for inspecting or evaluating the excluded items listed above may be available from Inspector for an additional fee or from specialists qualified to inspect or evaluate a particular category or item. Inspector is a home inspection generalist and is not acting as an expert in any craft or trade. The inspection report may contain recommendations for further evaluation by an individual other than Inspector herein who is qualified as an expert or specialist. If Inspector recommends consulting other specialized experts, Client agrees to do so at their own expense. It is Client's duty and obligation to exercise reasonable care to protect himself or herself regarding the condition of the subject property, including those facts which are known to or within the diligent attention and observation of Client. Page 1 of 2 Initial Here _________________________ ____________________________ © I.T.A Copyright 1993/2000 Contract continued Client: Mr. & Mrs. Buyer Report #: SAMPLE THIS IS INTENDED TO BE A LEGALLY BINDING CONTRACT... PLEASE READ CAREFULLY. CONFIDENTIAL REPORT: The inspection report to be prepared for Client is solely and exclusively for Client's own information and may not be relied upon by any other person. Client agrees to maintain the confidentiality of the inspection report and agrees not to disclose any part of it to any other person. Client may distribute copies of the inspection report to the seller and the real estate agents directly involved in this transaction, but Client and Inspector do not in any way intend to benefit said seller or the real estate agents directly or indirectly through this Agreement or the inspection report. CLIENT AGREES TO INDEMNIFY, DEFEND AND HOLD INSPECTOR HARMLESS FROM ANY THIRD PARTY CLAIMS ARISING OUT OF CLIENT'S UNAUTHORIZED DISTRIBUTION OF THE INSPECTION REPORT. SEVERABILITY: Should any provision of this contract be held by a court of competent jurisdiction to be either invalid or unenforceable, the remaining provisions of this contract shall remain in full force and effect, unimpaired by the courts' holding. ARBITRATION: Any dispute concerning the interpretation of this Agreement or arising from this inspection and report, except one for inspection fee payment, shall be resolved between the parties by BINDING ARBITRATION conducted in accordance with the rules of the American Arbitration Association except that the parties shall select an arbitrator who is familiar with the home inspection industry. ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ Initials _____________ Initials _____________ GENERAL PROVISIONS: This inspection contract, the real estate inspection, and the inspection report do not constitute a home warranty, guarantee, or insurance policy of any kind whatsoever. The real estate inspection and inspection report are not a substitute disclosure for real estate transactions which may be required by law. No legal action or proceeding of any kind, including those sounding in tort or contract, can be commenced against Inspector/Inspection Company, or its officers, agents or employees more than one year after the date of the subject inspection. Time is expressly of the essence herein. THIS TIME PERIOD IS SHORTER THAN OTHERWISE PROVIDED BY LAW. In the event Client discovers a material defect or other deficiency that was not identified and reported by Inspector, Client shall so notify Inspector in writing and allow Inspector and/or Inspector's designated representative to re-inspect and document the condition(s) of the material defect or deficiency prior to making any repair, alteration or replacement to said material defect or deficiency. The written report to be prepared by Inspector shall be considered the final and exclusive findings of the Inspector regarding the inspection of the property. Client shall not rely on any oral statements made by the Inspector prior to issuance of the written report. This Agreement shall be binding upon and insure to the benefit of the parties hereto and their heirs, successors and assigns. This agreement constitutes the entire integrated agreement between the parties hereto pertaining to the subject matter hereof, and may be modified only by a written agreement signed by all of the parties hereto. No oral agreements, understandings, or representations shall change, modify, or amend any part of this agreement. Each party signing this Agreement warrants and represents that he/she has the full capacity and authority to execute this Agreement on behalf of the named party. If this Agreement is executed on behalf of Client by any third party, the person executing this Agreement expressly represents to Inspector that he/she has the full and complete authority to execute this Agreement on Client's behalf and to fully and completely bind Client to all of the terms, conditions, limitations, exceptions and exclusions of this Agreement. ADDITIONAL SERVICES: Signed: _______________________________________ Date: ________________ Signed: _______________________________________ Date: ________________ Signed: _______________________________________ Date: ________________ Inspector Page 2 of 2 BASE FEE: TOTAL INSPECTION FEES: $285.00 PAYMENT: DUE: $285.00 © I.T.A Copyright 1993/2000 $285.00 $0.00 2620 S Hibernation Pl. Meridian, ID 83642 (208) 884-4221 Invoice Mr. & Mrs. Buyer Subject Property: 1234 Sample Home Boise, ID 83709 Invoice Date: Inspection Date: Invoice #: Report #: Inspector : Nov 15, 2007 Nov 15, 2007 1001 SAMPLE Curt Liles Received By ______________________ Date Received ______________ Payment Due Net 10 INSPECTION FEES DESCRIPTION AMOUNT BASE FEE: $285.00 SUB TOTAL : $285.00 CHECK PAYMENT: $285.00 TOTAL DUE : $0.00 Thank You Curtis Liles 2620 S Hibernation Pl Meridian ID 83642 (208) 884-4221 Fax (208) 898-8876
© Copyright 2024