RVS46.. AVS75.. AVS37.. Albatros

Albatros2
Zone controller
User Manual OEM
RVS46..
AVS75..
AVS37..
QAA75..
QAA78..
QAA55..
Edition 3.0
CE1U2353en01a
7 November 2007
Building Technologies
HVAC Products
2/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
CE1U2353en01a
7 November 2007
Contents
1
Overview of OEM settings ............................................................................... 5
2
The settings in detail...................................................................................... 20
2.1
Operator section ............................................................................................ 20
Operation and display.................................................................................... 20
2.2
Heating circuits .............................................................................................. 20
Mixing valve control ....................................................................................... 20
2.3
Cooling circuit ................................................................................................ 21
Mixing valve control ....................................................................................... 21
2.4
DHW .............................................................................................................. 21
Setpoints........................................................................................................ 21
2.5
Hx pumps ...................................................................................................... 21
Pump Hx........................................................................................................ 21
2.6
Primary controller / system pump .................................................................. 21
Flow temperature setpoint limits.................................................................... 21
Mixing valve control ....................................................................................... 22
2.7
Solar .............................................................................................................. 22
Start function ................................................................................................. 22
2.8
DHW storage tank ......................................................................................... 23
Release ......................................................................................................... 23
Charging control ............................................................................................ 23
Charging time limitation ................................................................................. 24
Discharging protection................................................................................... 24
Overtemperature protection........................................................................... 24
DHW push ..................................................................................................... 25
Mixing valve precontrol.................................................................................. 25
Transfer ......................................................................................................... 26
2.9
Instantaneous DHW heater ........................................................................... 26
Mixing valve control ....................................................................................... 26
2.10
Configuration ................................................................................................. 27
Building and room model............................................................................... 27
Pressure acquisition H1, H2 .......................................................................... 27
Device hours run ........................................................................................... 27
2.11
LPB system ................................................................................................... 28
Error/maintenance/alarms ............................................................................. 28
Action changeover functions ......................................................................... 28
2.12
Faults............................................................................................................. 28
History 1..10 .................................................................................................. 28
2.13
Diagnostics, consumers ................................................................................ 29
Heating circuit 1, heating circuit 2, heating circuit P ...................................... 29
3
Revision history ............................................................................................. 31
3/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
Contents
CE1U2353en01a
7 November 2007
4/32
Siemens Switzerland Ltd
HVAC Products
User Manual
Overview of OEM settings
CE1U2353en01a
7 November 2007
1
Overview of OEM settings
The table below shows all available settings. However, certain operating lines may be
hidden, depending on the type of unit.
Time of day and date
1
E Hours / minutes
2
E Day/month
3
E Year
5
F Start of summertime
6
F End of summertime
Operator section
20
E Language
25.03
25.10
00:00
01.01
2004
01.01
01.01
O = OEM
23:59
31.12
2099
31.12
31.12
German
Unit
Max
F = Heating engineer
Min
Function
user level
Operating line
Default value
E = Enduser
I = Commissioning
BZ = Operating line
1)
QAA75../78.. only
4)
RVS46.543 only
Legend
hh:mm
dd.MM
yyyy
dd.MM
dd.MM
-
German ¦ …
21
O
Display special operation
On
Off ¦ On
22
F
Info
Temporarily
-
Off
-
Off
-
Temporarily ¦ Permanently
26
F
Operation lock
Off ¦ On
27
F
Programming lock
Off ¦ On
28
I
Direct adjustment
Save with acknowledgment
Automatic storage ¦ Save with acknowledgment
30
O
Save basic settings
No
No ¦ Yes
31
O
Activate basic settings
No
No ¦ Yes
401)
I
Used as
Room unit 1
-
Heating circuit 1
-
Commonly with HC1
-
Commonly with HC1
-
Heating circuit 1
-
Room unit 1 ¦ Room unit 2 ¦ Room unit P ¦ Operator unit
1 ¦ Operator unit 2 ¦ Operator unit P ¦ Service unit
42
I
Assignment device 1
Heating circuit 1 ¦ Heating circuits 1 and 2 ¦ Heating
circuits 1 and P ¦ All heating circuits
44
I
Operation HC2
Commonly with HC1 ¦ Independently
46
I
Operation HCP
Commonly with HC1 ¦ Independently
481)
I
Action occupancy button
None ¦ Heating circuit 1 ¦ Heating circuit 2 ¦ Commonly
541)
F
70
F
Radio
120
I
Readjustment room sensor
Software version
0.0
-
Binding
No
-3
0
3
99.9
°C
-
No ¦ Yes
121
I
Test mode
Off
Off ¦ On
5/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
Overview of OEM settings
CE1U2353en01a
7 November 2007
I
Room unit 1
Unit
Max
Min
Default value
Function
user level
Operating line
130
-
-
-
-
Missing ¦ Ready ¦ No recept’n ¦ Change batt
131
I
Room unit 2
Missing ¦ Ready ¦ No recept’n ¦ Change batt
132
I
Room unit P
-
Missing ¦ Ready ¦ No recept’n ¦ Change batt
133
I
OutsideSens
-
-
-
-
Missing ¦ Ready ¦ No recept’n ¦ Change batt
134
I
Repeater
Missing ¦ Ready ¦ No recept’n ¦ Change batt
135
I
Operator unit 1
-
Missing ¦ Ready ¦ No recept’n ¦ Change batt
136
I
Operator unit 2
-
Missing ¦ Ready ¦ No recept’n ¦ Change batt
137
I
Operator unit P
-
-
-
-
No
-
Mo - Su
-
Missing ¦ Ready ¦ No recept’n ¦ Change batt
138
I
Service unit
Missing ¦ Ready ¦ No recept’n ¦ Change batt
140
I
Delete all devices
No ¦ Yes
Time prog heating circuit 1
500
E Preselection
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su
501
502
503
504
505
506
516
E
E
E
E
E
E
E
1. phase on
1. phase off
2. phase on
2. phase off
3. phase on
3. phase off
Default values
6:00
22:00
24:00
24:00
24:00
24:00
No
00:00
00:00
00:00
00:00
00:00
00:00
24:00
24:00
24:00
24:00
24:00
24:00
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
-
No ¦ Yes
Time prog heating circuit 2
520
E Preselection
Mo - Su
-
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su
521
522
523
524
525
526
536
E
E
E
E
E
E
E
1. phase on
1. phase off
2. phase on
2. phase off
3. phase on
3. phase off
Default values
6:00
22:00
24:00
24:00
24:00
24:00
No
00:00
00:00
00:00
00:00
00:00
00:00
24:00
24:00
24:00
24:00
24:00
24:00
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
-
No ¦ Yes
Time program 3/HCP
540
E Preselection
Mo - Su
-
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su
541
542
543
544
545
546
E
E
E
E
E
E
1. phase on
1. phase off
2. phase on
2. phase off
3. phase on
3. phase off
6:00
22:00
24:00
24:00
24:00
24:00
00:00
00:00
00:00
00:00
00:00
00:00
24:00
24:00
24:00
24:00
24:00
24:00
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
6/32
Siemens Switzerland Ltd
HVAC Products
User Manual
Overview of OEM settings
CE1U2353en01a
7 November 2007
E
Default values
Unit
Max
Min
Default value
Function
user level
Operating line
556
No
-
Mo - Su
-
No ¦ Yes
Time program 4/DHW
560
E Preselection
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su
561
562
563
564
565
566
576
E
E
E
E
E
E
E
1. phase on
1. phase off
2. phase on
2. phase off
3. phase on
3. phase off
Default values
6:00
22:00
24:00
24:00
24:00
24:00
No
00:00
00:00
00:00
00:00
00:00
00:00
24:00
24:00
24:00
24:00
24:00
24:00
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
-
No ¦ Yes
Time program 5
600
E Preselection
Mo - Su
-
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su
601
602
603
604
605
606
616
E
E
E
E
E
E
E
1. phase on
1. phase off
2. phase on
2. phase off
3. phase on
3. phase off
Default values
6:00
22:00
24:00
24:00
24:00
24:00
No
00:00
00:00
00:00
00:00
00:00
00:00
24:00
24:00
24:00
24:00
24:00
24:00
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
-
No ¦ Yes
Holidays heating circuit 1
641
E Preselection
Period 1
-
Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8
642
643
648
E
E
E
Start
End
operating level
--.-01.01
--.-01.01
Frost protection
31.12
31.12
dd.MM
dd.MM
-
Frost protection ¦ Reduced
Holidays heating circuit 2
651
E Preselection
Period 1
-
Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8
652
653
658
E
E
E
Start
End
operating level
--.-01.01
--.-01.01
Frost protection
31.12
31.12
dd.MM
dd.MM
-
Frost protection ¦ Reduced
Holidays heating circuit P
661
E Preselection
Period 1
-
Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8
662
663
668
E
E
E
Start
End
operating level
--.-01.01
--.-01.01
Frost protection
31.12
31.12
dd.MM
dd.MM
-
Frost protection ¦ Reduced
Heating circuit 1
710
E Comfort cooling setpoint
712
E Reduced setpoint
714
E Frost protection setpoint
20.0
16
10.0
Operating line 712 Operating line 716
Operating line 714 Operating line 710
4
Operating line 712
°C
°C
°C
7/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
Overview of OEM settings
CE1U2353en01a
7 November 2007
F
E
F
F
730
732
740
741
750
760
770
780
E
F
I
I
F
F
F
F
Comfort setpoint maximum
Heating curve slope
Heating curve displacement
Heating curve adaption
35.0
1.50
0.0
Off
Unit
Max
Min
Default value
Function
user level
Operating line
716
720
721
726
Operating line 710 35
0.10
4.00
-4.5
4.5
°C
°C
-
Off ¦ On
Summer/winter heating limit
24-hour heating limit
Flow temp setpoint min
Flow temp setpoint max
Room influence
Room temp limitation
Boost heating
Quick setback
18
−−−/8
-3
− − − / -10
8
8
80
Operating line 740
20
−−−/1
1
− − − / 0.5
5
−−−/0
Down to reduced setpoint
30
10
Operating line 741
95
100
4
20
°C
°C
°C
°C
%
°C
°C
-
0
0
−−−
-15
On
360
360
10
Operating line 800
min
min
°C
°C
-
5
0
3-position
50
°C
-
2
120
32
120
Off
20
873
100
873
°C
s
°C
s
-
95
°C
-
Off ¦ Down to reduced setpoint ¦ Down to frost prot setp
790
791
800
801
820
F
F
F
F
F
Optimum start control max
Optimum top control max
Reduced setp increase start
Reduced setp increase end
Overtemp prot pump circuit
830
832
F
F
Mixing valve boost
Actuator type
833
834
835
836
850
F
F
O
O
I
Switching differential 2-pos
Actuator running time
Mixing valve Xp
Mixing valve Tn
Floor curing function
0
0
− − − / -30
-30
Off ¦ On
2-position ¦ 3-position
0
30
1
10
Off ¦ Functional heating ¦ Curing heating ¦ Functional/
curing heating¦ Curing/functional heating ¦ Manually
851
861
I
F
Floor curing setp manual
Excess heat draw
870
F
With buffer storage tank
25
0
Always
Off ¦ Heating mode ¦ Always
Yes
-
Yes
-
Protection mode
-
Automatically
-
No ¦ Yes
872
F
With primary controller / system pump
No ¦ Yes
900
F
Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic
Cooling circuit 1
901
E Operating mode
Off ¦ Automatic
902
907
E
E
908
909
912
913
918
919
I
I
I
F
F
F
Comfort cooling setpoint
release
24.0
15
24 h/day
40
°C
-
20
16
20
24
26
35
35
35
355
100
35
35
°C
°C
°C
h
°C
°C
24h/day ¦ Time programs HCs ¦ Time program 5
Flow setpoint at OT 25°C
Flow setpoint at OT 35°C
Cooling limit at OT (outside temperature)
Locking period at end of heating
Start of summer compensation at OT
End of summer compensation at OT
8
8
−−−/8
−−−/8
20
20
8/32
Siemens Switzerland Ltd
HVAC Products
User Manual
Overview of OEM settings
CE1U2353en01a
7 November 2007
F
I
I
F
F
F
F
Summer compensation setpoint increase
Flow setpoint min. OT 25°C
Flow setpoint min. OT 35°C
Room influence
Room temp limitation
Mixing valve cooling offset
Actuator type
940
941
942
943
945
F
F
O
O
F
Switching differential 2-pos
Actuator running time
Mixing valve Xp
Mixing valve Tn
Mixing valve in heating mode
Unit
Max
Min
Default value
Function
user level
Operating line
920
923
924
928
932
938
939
4
−−−/1
18
8
18
8
80
−−−/1
0.5
− − − / 0.5
0
0
3-position
10
35
35
100
4
20
°C
°C
°C
%
°C
°C
-
2
120
12
90
Controls
0
30
1
10
20
873
100
873
°C
s
°C
s
60
3
60
2
No
− − − / 10
−−−/1
0
−−−/0
600
10
100
10
min
°C
%
°C
-
2-position ¦ 3-position
Control ¦ Open
946
947
948
950
962
F
F
F
I
F
Dewpt monitor locking time
Flow setpt increase hygro
Start flow increase at R.H.
Flow temp diff dewpoint
With buffer storage tank
963
F
With primary controller / system pump
No ¦ Yes
No
-
Off
-
No ¦ Yes
969
I
Optg mode changeover
None ¦ Off ¦ Automatic
Heating circuit 2
1010 E Comfort cooling setpoint
20.0
1012
E
Reduced setpoint
16
1014
1016
E
F
Frost protection setpoint
Comfort setpoint maximum
10.0
35.0
1020
1021
1026
E
F
F
Heating curve slope
Heating curve displacement
Heating curve adaption
1.50
0.0
Off
1030
1032
1040
1041
E
F
I
I
Summer/winter heating limit
24-hour heating limit
Flow temp setpoint min
Flow temp setpoint max
1050
1060
1070
1080
F
F
F
F
Room influence
Room temp limitation
Boost heating
Quick setback
Operating line
1012
Operating line
1014
4
Operating line
1010
0.10
-4.5
Operating line 1016 °C
Operating line 1010 °C
Operating line 1012 °C
35
°C
4.00
4.5
°C
-
−−−/8
− − − / -10
8
Operating line
1040
20
−−−/1
1
− − − / 0.5
5
−−−/0
Down to reduced setpoint
30
10
Operating line 1041
95
°C
°C
°C
°C
100
4
20
%
°C
°C
-
0
0
−−−
-15
360
360
10
Operating line 1100
min
min
°C
°C
Off ¦ On
18
-3
8
80
Off ¦ Down to reduced setpoint ¦ Down to frost prot setp
1090
1091
1100
1101
F
F
F
F
Optimum start control max
Optimum top control max
Reduced setp increase start
Reduced setp increase end
0
0
− − − / -30
-30
9/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
Overview of OEM settings
CE1U2353en01a
7 November 2007
F
Overtemp prot pump circuit
Unit
Max
Min
Default value
Function
user level
Operating line
1120
On
-
Off ¦ On
1130
1132
F
F
Mixing valve boost
Actuator type
1133
1134
1135
1136
1150
F
F
O
O
F
Switching differential 2-pos
Actuator running time
Mixing valve Xp
Mixing valve Tn
Floor curing function
5
0
3-position
50
°C
-
2
120
32
120
Off
20
873
100
873
°C
s
°C
s
-
95
°C
-
2-position ¦ 3-position
0
30
1
10
Off ¦ Functional heating ¦ Curing heating ¦ Functional/
curing heating¦ Curing/functional heating ¦ Manually
1151
1161
F
F
Floor curing setp manual
Excess heat draw
1170
F
With buffer storage tank
25
0
Always
Off ¦ Heating mode ¦ Always
Yes
-
Yes
-
Protection mode
-
Automatically
-
No ¦ Yes
1172
F
With primary controller / system pump
No ¦ Yes
1200
F
Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic
Heating circuit P
1300 E Operating mode
Protection ¦ Automatic ¦ Reduced ¦ Comfort
1310
E
Comfort cooling setpoint
20.0
1312
E
Reduced setpoint
16
1314
1316
E
F
Frost protection setpoint
Comfort setpoint maximum
10.0
35.0
1320
1321
1326
E
F
F
Heating curve slope
Heating curve displacement
Heating curve adaption
1.50
0.0
Off
1330
1332
1340
1341
E
F
F
F
Summer/winter heating limit
24-hour heating limit
Flow temp setpoint min
Flow temp setpoint max
1350
1360
1370
1380
F
F
F
F
Room influence
Room temp limitation
Boost heating
Quick setback
1390
1391
1400
1401
1420
F
F
F
F
F
Optimum start control max
Optimum top control max
Reduced setp increase start
Reduced setp increase end
Overtemp prot pump circuit
Operating line
1312
Operating line
1314
4
Operating line
1310
0.10
-4.5
Operating line 1316 °C
Operating line 1310 °C
Operating line 1312 °C
35
°C
4.00
4.5
°C
-
−−−/8
− − − / -10
8
Operating line
1340
20
−−−/1
1
− − − / 0.5
5
−−−/0
Down to reduced setpoint
30
10
Operating line 1341
95
°C
°C
°C
°C
100
4
20
%
°C
°C
-
0
0
−−−
-15
On
360
360
10
Operating line 1400
min
min
°C
°C
-
Off ¦ On
18
-3
8
80
Off ¦ Down to reduced setpoint ¦ Down to frost prot setp
0
0
− − − / -30
-30
Off ¦ On
10/32
Siemens Switzerland Ltd
HVAC Products
User Manual
Overview of OEM settings
CE1U2353en01a
7 November 2007
I
Floor curing function
Off
Unit
Max
Min
Default value
Function
user level
Operating line
1450
-
Off ¦ Functional heating ¦ Curing heating ¦ Functional/
curing heating¦ Curing/functional heating ¦ Manually
1451
1455
1456
1457
1461
I
F
F
F
F
Floor curing setp manual
Floor curing setp current
Floor curing day current
Floor curing days complete
Excess heat draw
25
0
0
0
Always
0
0
0
0
95
95
32
32
°C
°C
-
Off ¦ Heating mode ¦ Always
1470
F
With buffer storage tank
Yes
-
Yes
-
Protection mode
-
No ¦ Yes
1472
F
With primary controller / system pump
No ¦ Yes
1500
F
Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic
DHW
1610 E
Nominal setpoint
1612
1614
1620
Reduced setpoint
nominal setpoint max
release
F
O
I
55
Operating line
1612
40
8
65
8
Time programs HCs
BZ 1614 OEM
°C
Operating line 1610 °C
80
°C
-
24h/day ¦ Time programs HCs ¦ Time program 4/DHW
1630
I
Charging priority
MC shifting, PC absolute
-
Fixed weekday
-
Absolute ¦ Shifting ¦ None ¦ MC shifting, PC absolute
1640
F
Legionella function
Off ¦ Periodically ¦ Fixed weekday
1641
1642
F
F
Legionella funct periodically
Legionella funct weekday
3
1
Monday
7
Days
−−−
65
30
On
23:50
95
360
hh:mm
°C
min
-
Monday ¦ Tuesday ¦ Wednesday ¦ Thursday ¦ Friday ¦
Saturday ¦ Sunday
1644
1645
1646
16474)
F
F
F
F
Legionella function time
Setpoint of Legionella function
Legionella function dwelling time
Legionella funct circ pump
− − − / 00:00
55
− − − / 10
Off ¦ On
1660
4)
F
Circulating pump release
DHW release
-
On
-
Time program 3/HCP ¦ DHW release ¦ Time program
4/DHW¦ Time program 5
16614) F
Circulating pump cycling
Off ¦ On
16634) F
Circulation setpoint
Hx pumps
2008 O H1 DHW charging priority
45
8
80
°C
Yes
-
On
-
Yes
-
Yes
-
2-pipe system
-
Yes
-
No ¦ Yes
2010
F
H1 Excess heat draw
Off ¦ On
2012
F
H1 with buffer storage tank
No ¦ Yes
2014
F
H1 prim contr/system pump
No ¦ Yes
2015
F
H1 Refrig demand
2-pipe system ¦ 4-pipe system
2033
O
H2 DHW charging priority
No ¦ Yes
11/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
Overview of OEM settings
CE1U2353en01a
7 November 2007
F
H2 Excess heat draw
Unit
Max
Min
Default value
Function
user level
Operating line
2035
On
-
Yes
-
Yes
-
2-pipe system
-
Off ¦ On
2037
F
H2 with buffer storage tank
No ¦ Yes
2039
F
H2 prim contr/system pump
No ¦ Yes
2040
F
H2 Refrig demand
2-pipe system ¦ 4-pipe system
Primary controller / system pump
2110 O Flow temp setpoint min
2111 O Flow temp setpoint max
2112 O Flow setpoint, cooling min
2130 O Mixing valve boost
2131 O Mixing valve cooling offset
2132 O Actuator type
8
8
80
8
8
8
10
0
0
0
3-position
95
95
20
50
20
°C
°C
°C
°C
°C
-
2
0
120
30
32
1
120
10
After buffer st tank
20
873
100
873
°C
s
°C
s
-
8
4
−−−
−−−
20
07:00
19:00
−−−
−−−
−−−
−−−
None
0
0
−−−/8
−−−/5
5
00:00
00:00
−−−/1
− − − / -20
− − − / 30
− − − / 60
40
40
95
60
120
23:50
23:50
20
5
350
350
°C
°C
°C
min
s
hh:mm
hh:mm
Min/°C
°C
°C
°C
-
30
200
1
10
100
1500
%
l/h
2-position ¦ 3-position
2133
2134
2135
2136
2150
O
O
O
O
I
Switching differential 2-pos
Actuator running time
Mixing valve Xp
Mixing valve Tn
Primary controller / system pump
Before buffer st tank ¦ After buffer st tank
Solar
38104)
38114)
38124)
38304)
38314)
38324)
38334)
38344)
38404)
38504)
38604)
38804)
F
F
F
O
F
O
O
F
F
F
F
F
Temp diff on
Temp diff off
Charg temp min DHW st tank
Collector start function
Min run time collector pump
Collector start function on
Collector start function off
Collector start funct gradient
Collector frost protection
Collector overtemp prot
Evaporation heat carrier
Antifreeze
None ¦ Ethylene glycol ¦ ¦ Propylene glycol ¦ Ethyl and
propyl glycol
38814) F Antifreeze concentration
38844) F Pump capacity
DHW storage tank
50104) O Charging
Several times / day
-
Once/day ¦ Several times/day
50204) F
50214) F
50224) F
Flow setpoint boost
Increase of transfer boost
Type of charging
16
0
8
0
With B3 and B31
30
30
°C
°C
-
5
0
150
− − − / 10
Automatically
20
600
°C
min
-
80
BZ 5051 OEM
°C
with B3 ¦ With B3 and B31 ¦ Legio B3 and B31
50244) O
50304) O
50404) O
Switching differential
Charging time limitation
Discharging protection
Off ¦ Always ¦ Automatically
5050
4)
F
Charging temperature max
8
12/32
Siemens Switzerland Ltd
HVAC Products
User Manual
Overview of OEM settings
CE1U2353en01a
7 November 2007
8
8
Unit
90
80
Off
Max
Storage tank temp max
Recooling temp
Recooling heat gen/HCs
Min
Default value
Function
user level
Operating line
50514) O
50554) F
50564) F
95
95
°C
°C
-
Off ¦ On
5057
4)
F
Recooling collector
Off
-
Substitute
-
DHW release
-
DHW sensor
-
On
-
Off ¦ Summer ¦ Always
50604) F
electric immersion heater:operating mode
Substitute ¦ Summer ¦ Always
50614) F
Electric immersion heater release
24h/day ¦ DHW release¦ Time program4/ DHW
50624) F
El immersion heater control
External thermostat ¦ DHW sensor
50704) O
Automatic push
Off ¦ On
50714) O
50854) F
Charging prio time push
Excess heat draw
0
On
0
120
min
-
Off ¦ On
5090
4)
F
With buffer storage tank
No
-
No
-
Yes
-
No ¦ Yes
50924) F
With primary controller / system pump
No ¦ Yes
50934) F
With solar integration
No ¦ Yes
51204)
51244)
51254)
51264)
51304)
O
O
O
O
O
Mixing valve boost
Actuator running time
Mixing valve Xp
Mixing valve Tn
Transfer strategy
2
120
32
120
Always
0
30
1
10
50
873
100
873
°C
s
°C
s
480
200
873
30
s
°C
s
s
Always ¦ DHW release
51314) O
Comparison temp transfer
DHW sensor B3
DHW sensor B3 ¦ DHW sensor B31
Instantaneous DHW heater
55444) F Actuator running time
55454) O Mixing valve Xp
55464) O Mixing valve Tn
55474) O Mixing valve Tv
Configuration
5710 I
Heating circuit 1
60
20
150
4.5
7.5
1
10
0
On
-
Off ¦ On
5711
I
Cooling circuit 1
-
Off ¦ 4-pipe system ¦ 2-pipe system
5712
I
Use of mixing valve 1
Heating and cooling
-
Off
-
Sensors
-
Charging pump
-
None
-
Heating ¦ Cooling ¦ Heating and cooling
5715
I
Heating circuit 2
Off ¦ On
57304) I
DHW sensor B3
Sensor ¦ Thermostat
57314) I
DHW control element Q3
None ¦ Charging pump ¦ Diverting valve
58904) I
Relay output QX1
None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦
Collector pump Q5 ¦ H1 pump Q15 ¦ Alarm output K10 ¦
2nd pump speed HC1 Q21 ¦ 2nd pump speed HC2 Q22
¦ 2nd pump speed HCP Q23 ¦ Heat circuit pump HCP
13/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
Overview of OEM settings
CE1U2353en01a
7 November 2007
Unit
Max
Min
Default value
Function
user level
Operating line
Q20 ¦ H2 pump Q18 ¦ System pump Q14 ¦ Scheduler 5
K13 ¦ DHW mixing pump Q35 ¦ DHW iterm circ pump
Q33 ¦ Heat request K27 ¦ Refrig request K28 ¦ Air
dehumidifier K29 ¦ Diverting valve, cooling Y21
59304) I
Sensor input BX1
None
-
None
-
Optg mode changeover
HCs+DHW
-
N/O
-
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39 ¦ DHW charging sensor B36 ¦
Solar flow sensor B63 ¦ Solar return sensor B64
59314) I
Sensor input BX2
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39 ¦ DHW charging sensor B36 ¦
Solar flow sensor B63 ¦ Solar return sensor B64
5950
I
Function input H1
Optg mode changeover HCs + DHW ¦ Optg mode
changeover HCs ¦ Optg mode changeover HC1 ¦ Optg
mode changeover HC2 ¦ Optg mode changeover HCP ¦
Error/alarm message ¦ Min flow temp setpoint ¦ Excess
heat discharge ¦ Dewpoint monitor ¦ Flow temp. setpt
increase, hygro ¦ Refrig request ¦ Heat request 10V ¦
Refrig. request 10V ¦ Pressure measurement 10V ¦ Rel.
room humidity 10V ¦ Room temperature 10V
5951
I
Contact type H1
NC ¦ NO
5952
5953
5954
5955
5956
6014
I
I
I
I
I
I
Function value, contact type H1
Voltage value 1, H1
Function value 1, H1
Voltage value 2, H1
Function value 2, H1
Function mixing group 1
70
8
0
0
0
-100
10
0
70
-100
Heating circuit
130
10
500
10
500
°C
Volt
Volt
-
Heating circuit 1 ¦ Prim contr/system pump ¦ DHW
primary controller4) ¦ Instantaneous DHW heater4) ¦
Cooling circuit 1 ¦ Heating circuit / Cooling circuit 1
6020
I
Function extension module 1
None
-
None
-
None
-
None
-
No function ¦ Multifunctional ¦ Heating circuit 2 ¦ Solar
DHW4) ¦ Prim contr/system pump ¦ DHW primary
controller4) ¦ Instantaneous DHW heater4) ¦ Cooling
circuit 1
6021
I
Function extension module 2
No function ¦ Multifunctional ¦ Heating circuit 2 ¦ Solar
DHW4) ¦ Prim contr/system pump ¦ DHW primary
controller4) ¦ Instantaneous DHW heater4) ¦ Cooling
circuit 1
6030
I
Relay output QX21
None ¦ Circulating pump Q44) ¦
None ¦ Circulating pump Q44) ¦ El imm heater DHW K6
¦ Collector pump Q54) ¦ H1 pump Q15 ¦ Alarm output
K10 ¦ 2nd pump speed HC1 Q21 ¦ 2nd pump speed
HC2 Q22 ¦ 2nd pump speed HCP Q23 ¦ Heat circuit
pump HCP Q20 ¦ H2 pump Q18 ¦ System pump Q14 ¦
Scheduler 5 K13 ¦ DHW mixing pump Q354) ¦ DHW
iterm circ pump Q334) ¦ Heat request K27 ¦ Refrig
request K28 ¦ Air dehumidifier K29 ¦ Diverting valve,
cooling Y21
6031
I
Relay output QX22
None ¦ Circulating pump Q44) ¦ El imm heater DHW K6
¦ Collector pump Q54) ¦ H1 pump Q15 ¦ Alarm output
K10 ¦ 2nd pump speed HC1 Q21 ¦ 2nd pump speed
HC2 Q22 ¦ 2nd pump speed HCP Q23 ¦ Heat circuit
pump HCP Q20 ¦ H2 pump Q18 ¦ System pump Q14 ¦
Scheduler 5 K13 ¦ DHW mixing pump Q354) ¦ DHW
iterm circ pump Q334) ¦ Heat request K27 ¦ Refrig
request K28 ¦ Air dehumidifier K29 ¦ Diverting valve,
14/32
Siemens Switzerland Ltd
HVAC Products
User Manual
Overview of OEM settings
CE1U2353en01a
7 November 2007
Unit
Max
Min
Default value
Function
user level
Operating line
cooling Y21
6032
I
Relay output QX23
None
-
None
-
None
-
Optg mode changeover
HCs+DHW
-
N/O
-
None ¦ Circulating pump Q44) ¦
None ¦ Circulating pump Q44) ¦ El imm heater DHW K6
¦ Collector pump Q54) ¦ H1 pump Q15 ¦ Alarm output
K10 ¦ 2nd pump speed HC1 Q21 ¦ 2nd pump speed
HC2 Q22 ¦ 2nd pump speed HCP Q23 ¦ Heat circuit
pump HCP Q20 ¦ H2 pump Q18 ¦ System pump Q14 ¦
Scheduler 5 K13 ¦ DHW mixing pump Q354) ¦ DHW
iterm circ pump Q334) ¦ Heat request K27 ¦ Refrig
request K28 ¦ Air dehumidifier K29 ¦ Diverting valve,
cooling Y21
60404) I
Sensor input BX21
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39 ¦ DHW charging sensor B36 ¦
Solar flow sensor B63 ¦ Solar return sensor B64
60414) I
Sensor input BX22
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39 ¦ DHW charging sensor B36 ¦
Solar flow sensor B63 ¦ Solar return sensor B64
6046
I
Function input H2
Optg mode changeover HCs + DHW ¦ Optg mode
changeover HCs ¦ Optg mode changeover HC1 ¦ Optg
mode changeover HC2 ¦ Optg mode changeover HCP ¦
Error/alarm message ¦ Min flow temp setpoint ¦ Excess
heat discharge ¦ Dewpoint monitor ¦ Flow temp. setpt
increase, hygro ¦ Refrig request ¦ Heat request 10V ¦
Refrig. request 10V ¦ Pressure measurement 10V ¦ Rel.
room humidity 10V ¦ Room temperature 10V
6047
I
Contact type H2
NC ¦ NO
6048
6049
6050
6051
6052
60974)
I
I
I
I
I
F
Function value, contact H2
Voltage value 1, H2
Function value 1, H2
Voltage value 2, H2
Function value 2, H2
Sensor type collector
70
8
0
0
0
-100
10
0
70
-100
NTC 10k
130
10
500
10
500
°C
Volt
Volt
-
0
0
15
60
Off
-20
-3.0
0
0
20
3.0
50
300
°C
°C
h
Min/°C
-
−−−
−−−
Off
− − − / -50
− − − / -50
50
50
°C
°C
-
NTC 10k ¦ Platinum 1000
6098
6100
6110
6112
6120
4)
F
F
F
O
F
Readjustm collector sensor
Readjustm outside sensor
Time constant building
Gradient room model
Frost protection for the plant
Off ¦ On
6128 F
6129 F
61314) F
Heat request below OT
Heat request above OT
Heat req in economy mode
Off ¦ On DHW ¦ On
6135
F
Air dehumidifier
Off
-
24 h/day
-
Off ¦ On
6136
F
Air dehumidifier enable
24h/day ¦ Time progr. heating circuit ¦ Time program 5
6137
6138
6140
6141
6142
F
F
O
O
O
Air dehumidifier r.h. EIN
Air dehumidifier r.h. SD
Water pressure max
Water pressure min
Water pressure critical min
55
5
−−−
−−−
−−−
0
2
− − − / 0.0
− − − / 0.0
− − − / 0.0
100
50
10.0
10.0
10.0
%
%
bar
bar
bar
15/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
Overview of OEM settings
CE1U2353en01a
7 November 2007
6204
O
Save parameters
−−−
−−−
−−−
No
− − − / 0.0
− − − / 0.0
− − − / 0.0
Unit
Water pressure 2 max
Water pressure 2 min
Water press 2 critical min
Save sensors
Max
O
O
O
I
Min
Default value
Function
user level
Operating line
6150
6151
6152
6200
10.0
10.0
10.0
bar
bar
bar
-
No ¦ Yes
No
-
No
-
No ¦ Yes
6205
F
Reset to default parameters
No ¦ Yes
62124) I
Check-No. heat source 1
6215 I
Check-No. storage tank
6217 I
Check-No. heating circuits
6220 F Software version
6222 O Device hours run
LPB-System
6600 I
Device address
6601 F Segment address
6604 F Bus power supply function
0
0
0
0
0
0
1
0
0
0
Automatically
199999
199999
199999
99.9
65535
h
16
14
-
Off ¦ Automatically
6605
F
Bus power supply state
On
-
Yes
-
Off ¦ On
6610
O
Display system messages
No ¦ Yes
6612
6620
O
O
Alarm delay
Action changeover functions
6621
F
Summer changeover
−−−
−−−/2
System
60
min
-
Segment ¦ System
Locally
-
Centrally
-
All HCs in system
-
Locally
-
Autonomously
-
Locally¦ Centrally
6623
F
Optg mode changeover
Locally¦ Centrally
6625
F
Assignment of DHW heating
Local HCs ¦ All HCs in segment ¦ All HCs in system
6627
F
Refrigeration demand
Locally¦ Centrally
6640
I
Clock mode
Autonomously ¦ Slave without remote ¦ Slave with
remote setting ¦ Master
6650 F
Faults
6710 I
Outside temp source
0
Reset alarm relay
No
0
239
-
No ¦ Yes
6740
6741
67454)
6746
6800
6802
6804
6806
F
F
F
F
F
F
F
F
F
F
F
Flow temp 1 alarm
Flow temp 2 alarm
DHW charging alarm
Flow temp alarm, cooling 1
History 1
Error code 1
History 2
Error code 2
History 3
Error code 3
History 4
−−−
−−−
−−−
−−−
-
− − − / 10
− − − / 10
−−−/1
− − − / 10
240
240
48
240
min
min
h
min
0
255
-
0
255
-
0
255
-
16/32
Siemens Switzerland Ltd
HVAC Products
User Manual
Overview of OEM settings
CE1U2353en01a
7 November 2007
6810
6812
6814
6816
6818
6820
F
F
F
F
F
F
F
F
F
F
F
F
F
O
Error code 4
History 5
Error code 5
History 6
Error code 6
History 7
Error code 7
History 8
Error code 8
History 9
Error code 9
History 10
Error code 10
Reset history
No
Unit
Max
Min
Default value
Function
user level
Operating line
6808
0
255
-
0
255
-
0
255
-
0
255
-
0
255
-
0
255
-
0
255
-
240
240
Months
Months
-
No ¦ Yes
Maintenance / special operation
7044 F Maintenance interval
7045 F Time since maintenance
71194) F Economy function
−−−
−−−/1
0
0
Locked
Locked ¦ released
71204) E
Economy mode
Off
-
Off
-
Off ¦ On
7140
E
manual operation
Off ¦ On
7150 I
Simulation outside temperature
7170 I
Telephone customer service
Input / output test
7700 I
Relay test
-
-50.0
50
No test
°C
-
No test ¦ Everything off ¦ DHW pump Q3 ¦ Heating circuit
pump Q2 ¦ Heating circ mix valve op Y1 ¦ Heat circ mix
valve cl Y2 ¦ Relay output QX14) ¦ Relay output QX21
module 1 ¦ Relay output QX22 module 1 ¦ Relay output
QX23 module 1 ¦ Relay output QX21 module 2 ¦ Relay
output QX22 module 2 ¦ Relay output QX23 module 2
7730
7732
77504)
78204)
78214)
78304)
78314)
78324)
78334)
7840
7841
I
I
I
I
I
I
I
I
I
I
I
Outside temp B9
Flow temp B1
DHW temp B3
Sensor temp BX1
Sensor temp BX2
Sensor temp BX21 module 1
Sensor temp BX22 module 1
Sensor temp BX21 module 2
Sensor temp BX22 module 2
Voltage signal H1
Contact state H1
7845
7846
I
I
Voltage signal H2
Contact state H2
0
0
0
0
-
-50.0
0.0
0.0
-28.0
-28.0
-28
-28
-28
-28
0
50
140
140
350
350
350
350
350
350
10
°C
°C
°C
°C
°C
°C
°C
°C
°C
Volt
-
0
-
0
10
Volt
-
Open ¦ Closed
Open ¦ Closed
State
8000 I
State of heating circuit 1
-
17/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
Overview of OEM settings
CE1U2353en01a
7 November 2007
-
Unit
Max
Min
Default value
Function
user level
Operating line
8001 I
State of heating circuit 2
8002 I
State heating circuit P
8003 I
State of DHW
8004 I
State of cooling circuit 1
80074) I
State of solar
Diagnostics, heat generation
85104) I
Collector temp 1
85114) I
Collector temp 1 max
85124) I
Collector temp 1 min
85134) I
dT collector 1/DHW
85194) I
Solar flow temp
4)
8520 I
Solar return temp
85264) E 24-hour yield solar energy
85274) E Total yield solar energy
85304) F Hours run solar yield
85314) F Hours run collect overtemp
Diagnostics, consumers
8700 I
Outside temperature (OT)
8703 I
Outside temp attenuated
8704 I
Outside temperature composite
8720 I
Relative room humidity
8721 I
Outside temperature (OT)
8722 I
Dewpoint temperature 1
8730 I
Heating circuit pump Q2
-
0
0
0
0
0
0
-
-28.0
-28.0
-28.0
-168.0
-28.0
-28.0
0
0
0
0
350
350
350
350
350
350
999.9
9999999.9
65535
65535
°C
°C
°C
°C
°C
°C
kWh
kWh
h
h
-
-50.0
-50.0
-50.0
0
0
0
50.0
50.0
50.0
100
50.0
50.0
°C
°C
°C
%
°C
°C
-
Off ¦ On
8731
I
Heating circ mix valve op Y1
-
-
-
-
Off ¦ On
8732
I
Heat circ mix valve cl Y2
Off ¦ On
8740
8741
8742
8743
8744
8751
I
I
O
I
I
I
Room temp 1
Room setpoint 1
Room temp 1 model
Flow temperature 1
Flow temp setpoint 1
Cooling circuit pump 1
8752
I
Cooling circuit mixing valve 1 Open
-
0.0
4.0
0.0
0.0
0.0
50.0
35.0
50.0
140.0
140.0
°C
°C
°C
°C
°C
-
Off ¦ On
-
-
-
-
-
-
Off ¦ On
8753
I
Cooling circuit mixing valve 1 Closed
Off ¦ On
8754
I
Cooling diverting valve 1
Off ¦ On
8756
8757
8760
I
I
I
8761
I
Flow temperature, cooling 1
Flow temperature, cooling 1
Heating circuit pump 2
-
0
0
140
140
°C
°C
-
Off ¦ On
Heat circ mix valve 2 open
-
-
-
-
Off ¦ On
8762
I
Heat circ mix valve 2 close
Off ¦ On
18/32
Siemens Switzerland Ltd
HVAC Products
User Manual
Overview of OEM settings
CE1U2353en01a
7 November 2007
Default value
8830
8831
88324)
88354)
88364)
88504)
88514)
88524)
88534)
8930
8931
89504)
89514)
89574)
9000
9001
9005
9006
90314)
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
DHW temp 1
DHW temp setpoint
DHW temp 2
DHW circulation temp
DHW charging temp
DHW primary controller temp
DHW primary controller setp
Instant DHW heater temp
Instant DHW heater setpoint
Primary controller temp
Primary controller setpoint
Common flow temp
Common flow temp setpoint
Common flow temp setpoint refrig
Flow temperature setpoint H1
Flow temp setpoint H2
Water pressure H1
Water pressure H2
Relay output QX1
9050
I
Unit
Room temp 2
Room setpoint 2
Room temp 2 model
Flow temperature 2
Flow temp setpoint 2
Room temp P
Room setpoint P
Room temp P model
Flow temp setpoint P
DHW pump Q3
Max
I
I
O
I
I
I
I
O
I
I
Min
Function
user level
Operating line
8770
8771
8772
8773
8774
8800
8801
8802
8803
88204)
-
0.0
4.0
0.0
0.0
0.0
0.0
4.0
0.0
0.0
50
35
50
140
140
50
35
50
140
°C
°C
°C
°C
°C
°C
°C
°C
°C
-
0
0
0
0
0
0
-
0.0
8.0
0.0
0.0
0
0
0
0
0
0.0
0.0
0.0
0.0
0
5.0
5.0
0.0
0.0
140
80
140
140
140
140
140
140
140
140.0
140.0
140.0
140.0
140
130.0
130.0
10.0
10.0
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
bar
bar
-
Off ¦ On
Off ¦ On
Relay output QX21 module 1
-
-
-
-
-
-
-
-
-
-
-
-
Off ¦ On
9051
I
Relay output QX22 module 1
Off ¦ On
9052
I
Relay output QX23 module 1
Off ¦ On
9053
I
Relay output QX21 module 2
Off ¦ On
9054
I
Relay output QX22 module 2
Off ¦ On
9055
I
Relay output QX23 module 2
Off ¦ On
19/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
Overview of OEM settings
CE1U2353en01a
7 November 2007
2
The settings in detail
2.1 Operator section
Operation and display
Line no.
Operating line
21
Display special operation
Off
On
30
Save basic settings
No
Yes
31
Activate basic settings
No
Yes
Save basic settings
The setting data of all operating levels are copied from the controller to the memory of
the operator unit. This means that previous data in the operator unit are overwritten.
Activate basic settings
With the exception of the data listed below, the setting data of all operating levels are
transferred from the memory of the operator unit to the connected controller. Previous
setting data in the controller are overwritten.
The following operating lines will not be overwritten:
Line no.
6600
6601
6222
Operating line
Device address
Segment address
Device hours run
The following data will not be overwritten either:
RF list, hours run / start counter, yield meter, maintenance meter, slave pointer, and
error history.
2.2 Heating circuits
Mixing valve control
HC1
835
836
Mixing valve Xp
Line no.
HC2 HC3P
1135
1136
Operating line
Mixing valve Xp
Mixing valve Tn
By setting the right proportional band, the control action of the mixing valve actuator is
matched to the behavior of the plant (controlled system).
Xp influences the controller’s P-action.
Mixing valve Tn
By setting the right integral action time, the control action of the mixing valve's actuator
is matched to the behavior of the plant (controlled system).
Tn influences the controller’s I-action.
20/32
Siemens Switzerland Ltd
HVAC Products
User Manual
The settings in detail
CE1U2353en01a
7 November 2007
2.3 Cooling circuit
Mixing valve control
Mixing valve Xp
Line no.
Operating line
942
943
Mixing valve Xp
Mixing valve Tn
By setting the right proportional band, the control action of the mixing valve actuator is
matched to the behavior of the plant (controlled system).
Xp influences the controller’s P-action.
Mixing valve Tn
By setting the right integral action time, the control action of the mixing valve's actuator
is matched to the behavior of the plant (controlled system).
Tn influences the controller’s I-action.
2.4 DHW
Setpoints
Line no.
Operating line
1614
nominal setpoint max
This operating line is used to limit the “Nominal setpoint“ (operating line 1610) at the
top.
2.5 Hx pumps
Pump Hx
H1
Line no.
H2
2008 2033
Operating line
H1/H2 DHW charging priority
Off ¦ On
H1/H2 DHW charging
priority
When using this setting, the connected pump H can be excluded from / included in the
effect of DHW charging priority.
In the case of a ventilation system, for example, it is thus possible to ensure a constant
supply of heat with no impact from the DHW charging priority.
2.6 Primary controller / system pump
Flow temperature setpoint limits
Line no.
Operating line
2110
2111
2112
Flow temp setpoint min
Flow temp setpoint max
Flow setpoint, cooling min
21/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
The settings in detail
CE1U2353en01a
7 November 2007
These limit values can be used to define a temperature range for the heating flow
temperature setpoint.
TV
TVmax
max
2358Z09
Flow temp setpoint
minimum/maximum
TVw
akt
TVmin
min
0
TVw
TVmax
Tvmin
Flow setpoint, cooling min
10
20
30
40
50
60
70
80
90
100 °C
Current flow temperature setpoint
Flow temp setpoint max
Flow temp setpoint minimum
This limit value can be used to define the low limit for the flow temperature setpoint for
cooling.
Mixing valve control
Line no.
Operating line
2130
2131
2132
2133
2134
2135
2136
Mixing valve boost
Mixing valve cooling offset
Actuator type
Switching differential 2-pos
Actuator running time
Mixing valve Xp
Mixing valve Tn
Mixing valve boostFor mixing, the actual value of the boiler flow temperature must be
higher than the required setpoint of the mixing valve flow temperature since otherwise
that temperature cannot be controlled. The controller generates the boiler temperature
setpoint based on the increase set here and the current flow temperature setpoint.
Mixing valve cooling
offset
RVS46.543 only
To ensure proper mixing, the actual flow temperature of the cooling aggregate must be
lower than the required mixing valve flow temperature setpoint. The cooling demand is
reduced by the value set here.
2.7 Solar
Start function
Collector start function
Line no.
Operating line
3830
3832
3833
Collector start function
Collector start function on
Collector start function off
If the temperature at the collector (especially in the case of vacuum tubes) cannot be
correctly acquired when the pump is deactivated, the pump can be activated from time
to time.
22/32
Siemens Switzerland Ltd
HVAC Products
User Manual
The settings in detail
CE1U2353en01a
7 November 2007
RVS46.543 only
2.8 DHW storage tank
Release
Line no.
Operating line
5010
Charging
Once/day ¦ Several times/day
Charging
Selection of charging “Once/day“ or “Several times/day” is active only if DHW release is
set according to the time programs of the heating circuits
Once / day
Release of DHW charging is given 2.5 hours before the first heat request from the
heating circuit is received. Then, the reduced DHW setpoint applies for the whole day.
Heizprogramm
Time
program
Einmal
Once
perpro
day Tag
DHW
release
TWW-Freigabe
2.5h
In the case of continuous heating (with no setback periods), release of DHW charging
is given at 0:00. The same rule also applies if the first request for heat from the heating
circuit is received before 02:30. If a request for heat is received at midnight, DHW
charging is released after the first setback period, but no earlier than 2.5 hours before
midnight.
Day
Tag11
Day
Tag2 2
Day 33
Tag
Day
Tag4 4
Time
program
Heizprogramm
DHW
release
TWW-Freigabe
2.5h
0:00
24:00
2.5h
2.5h
22:00
2.5h
Several times / day
When selecting “Several times/day“, release of DHW charging is put forward in time by
1 hour against the periods of time the heating circuit calls for heat, and is then
maintained during those periods of time.
Heizprogramm
Time
program
Several times
perTag
Mehrmals
pro
day
DHW
release
TWW-Freigabe
1h
1h
Charging control
Switching differential
Line no.
Operating line
5024
Switching differential
If the DHW temperature is lower than the current setpoint minus the switching
differential set here, DHW charging will be started.
DHW charging will be terminated when the temperature reaches the current setpoint.
When DHW heating is released for the first time in a 24-hour period, forced charging
will be initiated. DHW charging is also started when the DHW temperature lies within
the switching differential, provided it does not lie less than K below the setpoint.
23/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
The settings in detail
CE1U2353en01a
7 November 2007
Charging time limitation
Charging time limitation
Line no.
Operating line
5030
Charging time limitation
During DHW charging, space heating may obtain no or too little energy, depending on
the selected charging priority (operating line 1630) and the type of hydraulic circuit. For
this reason, it is often practical to set a time limit to DHW charging.
--Charging time limitation is deactivated. The DHW is heated up to the nominal setpoint,
even if space heating cannot draw sufficient amounts of heat for a certain period of
time.
10 – 600
DHW charging is stopped after the set period of time in minutes and then locked for the
same period of time before it is resumed. During this period of time, the heat produced
by the boiler is made available for space heating. This cycle is repeated until the
nominal DHW setpoint is reached.
When space heating is switched off (summer operation, Eco function, etc.), DHW
charging will not be stopped, independent of the selected setting.
Discharging protection
Discharging protection
Line no.
Operating line
5040
Discharging protection
This function ensures that the DHW charging pump (Q3) will be activated only when the
boiler temperature is high enough.
•
With sensor
The charging pump will be activated only when the boiler temperature reaches the
level of the DHW temperature plus one half the charging boost. If, during charging,
the boiler temperature drops to a level below the DHW temperature plus 1/8 the
charging boost, the charging pump will be deactivated again. If 2 DHW sensors are
parameterized for DHW charging, the lower temperature is used for the discharging
protection function (usually sensor B31).
•
With thermostat
The charging pump will be activated only when the boiler temperature lies above
the nominal DHW setpoint. If, during charging, the boiler temperature drops below
the nominal DHW temperature minus the DHW switching differential, the charging
pump will be deactivated again.
Off
Function is deactivated.
Always
The function is always active.
Automatically
The function is active only if the heat source is not able to deliver heat, or is not
available (fault, heat generation lock).
Overtemperature protection
24/32
Siemens Switzerland Ltd
HVAC Products
User Manual
The settings in detail
CE1U2353en01a
7 November 2007
Storage tank temp max
Line no.
Operating line
5051
Storage tank temp max
If the storage tank reaches the maximum storage tank temperature set here, charging
is aborted. It will be released again when the storage tank temperature has dropped 1
°C below the maximum storage tank temperature.
The protective collector overtemperature function can reactivate the collector pump
until the storage tank’s safety temperature is reached.
T
TSpMax
TSp
L
2354Z10
1°C
1
0
t
TSpMax
TSp
L
Storage tank temp max (operating line 5051)
Actual value of the storage tank temperature
Storage tank charging: 1 = on, 0 = off
DHW push
Line no.
Operating line
5070
Automatic push
Off
On
5071
Automatic push
Charging prio time push
The DHW push can be triggered either manually or automatically.
In that case, the DHW is heated up once to the nominal setpoint.
Off
The DHW push must be triggered manually.
On
If the DHW temperature falls below the reduced setpoint (operating line 1612) by at
least 2 switching differentials (operating line 5024), one-time charging to the nominal
DHW setpoint (operating line 1610) will take place again.
The automatic DHW push only works when the DHW operating mode is activated.
Charging prio time push
In the case of a DHW push, the DHW storage tank is charged with absolute priority for
the period of time set here.
Mixing valve precontrol
Line no.
Operating line
5120
5124
5125
5126
Mixing valve boost
Actuator running time
Mixing valve Xp
Mixing valve Tn
25/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
The settings in detail
CE1U2353en01a
7 November 2007
Mixing valve boost
To ensure proper mixing valve flow temperature control, the flow temperature must be
higher than the demanded setpoint of the mixing valve flow temperature. The value set
here is added to the request.
Actuator running time
Setting the running time of the actuator used with the mixing valve.
Mixing valve Xp
By setting the right proportional band, the control action of the mixing valve’s actuator is
matched to the behavior of the plant (controlled system).
Xp influences the controller’s P-action.
Mixing valve Tn
By setting the right integral action time, the control action of the mixing valve's actuator
is matched to the behavior of the plant (controlled system).
Tn influences the controller’s I-action.
Transfer
Line no.
Operating line
5130
Transfer strategy
5131
Comparison temp transfer
Always ¦ DHW release
DHW sensor B3 ¦ DHW sensor B31
Transfer strategy
Transfer is permitted either always or at the release times set (operating line 1620).
Comparison temp transfer
For the transfer, the respective DHW sensor can be selected to get a comparative
temperature.
RVS46.543 only
2.9 Instantaneous DHW heater
Mixing valve control
Mixing valve Xp
Line no.
Operating line
5545
5546
5547
Mixing valve Xp
Mixing valve Tn
Mixing valve Tv
By setting the right proportional band, the control action of the mixing valve’s actuator is
matched to the behavior of the plant (controlled system).
Xp influences the controller’s P-action.
Mixing valve Tn
By setting the right integral action time, the control action of the mixing valve's actuator
is matched to the behavior of the plant (controlled system).
Tn influences the controller’s I-action.
Mixing valve Tv
By setting the right derivative action time, the control action is matched to the behavior
of the plant (controlled system).
Tv influences the controller’s D-action. With Tv = 0, the D-action is deactivated.
26/32
Siemens Switzerland Ltd
HVAC Products
User Manual
The settings in detail
CE1U2353en01a
7 November 2007
2.10 Configuration
Building and room model
Gradient room model
Line no.
Operating line
6112
Gradient room model
The room model gradient gives the period of time in minutes room heating needs to
raise the temperature by 1 °C. The settings made applies to all circuits.
The setting is used to calculate the fictive room temperature of rooms that have no
room temperature sensor installed (operating lines 8742, 8772, and 8802).
Pressure acquisition H1, H2
H1
Line no.
H2
6140 6150
6141 6151
6142 6152
Water pressure max
Operating line
Water pressure max
Water pressure min
Water pressure critical min
If the pressure acquired at input H1 or H2 exceeds the limit value set here, an error
message will be delivered.
117: Water pressure too high
176: Water pressure 2 too high
If the pressure drops below the limit value by one switching differential, the error will be
cancelled.
Water pressure min
If the pressure acquired at input Hx drops below the set limit value (parameter “Water
pressure min“), the appropriate maintenance alarm will be delivered.
5:
Water pressure too low
18:
Water pressure 2 too low
If the pressure exceeds the limit value by one switching differential, the error is
cancelled.
Water pressure critical min
If the pressure acquired at input H1 or H2 falls below the limit value set here, an
appropriate error message will be delivered and both burner stages immediately shut
down.
118: Water pressure too low
177: Water pressure 2 too low
If the pressure exceeds the limit value by one switching differential, the error is
cancelled.
Device hours run
Line no.
Operating line
6222
Device hours run
This indicates the total number of hours run since the controller was first
commissioned.
27/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
The settings in detail
CE1U2353en01a
7 November 2007
2.11 LPB system
Error/maintenance/alarms
Line no.
Operating line
6610
6612
Display system messages
Alarm delay
Display system messages
This setting enables system messages transmitted via LPB to be suppressed at the
connected operator unit.
Alarm delay
Delivery of the alarm to the OCI can be delayed in the basic unit by setting a delay.
This ensures that unnecessary notifications of a service center resulting from short-time
errors (e.g. temperature limiter cut out, communication error) can be prevented.
It is to be noted, however, that errors occurring for a short period of time, and
reoccurring constantly and rapidly, will also be filtered.
Action changeover functions
Line no.
Operating line
6620
Action changeover functions
Segment ¦ System
The setting is only relevant for device address 1.
Range of action of
changeover
The range of action of central changeover can be defined.
This concerns:
Summer changeover (when selecting ”Central“ on line 6623)
Summer changeover (with ”Central“ setting on operating line 6621)
Entries:
Segment: Changeover takes place with all controllers in the same segment.
System: Changeover takes place with all controllers in the entire system (in all
segments). The controller must be located in segment 0!
2.12 Faults
History 1..10
Line no.
Operating line
6820
Reset history
No
Yes
Reset history
The error history with the last 10 errors will be deleted.
28/32
Siemens Switzerland Ltd
HVAC Products
User Manual
The settings in detail
CE1U2353en01a
7 November 2007
2.13 Diagnostics, consumers
Heating circuit 1, heating circuit 2, heating circuit P
Room temperature 1 / 2 /
P model
Line no.
Operating line
8742
8772
8802
Room temp 1 model
Room temp 2 model
Room temp P model
The room model calculates a fictive room temperature for rooms that have no room
temperature sensor. The value calculated for each heating circuit is indicated on these
operating lines.
This allows boost heating, quick setback and optimum start and stop control to be
implemented with no need for using a room temperature sensor.
The calculation takes into account the attenuated outside temperature (operating line
8703), the room model gradient (operating line 6112) for switching to a higher setpoint
and the building’s time constant (operating line 6110) for switching to a lower setpoint.
29/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
The settings in detail
CE1U2353en01a
7 November 2007
Index
A
Action changeover functions .....................................28
Actuator running time ................................................22
Actuator runtime DHW ..............................................25
Actuator type primary controller / system pump ........22
Alarm delay ...............................................................28
Attenuated outside temperature ................................29
Automatic push..........................................................25
B
Building’s time constant.............................................29
C
Charging DHW ..........................................................23
Charging prio time push ............................................25
Charging time limitation.............................................24
Collector start function solar......................................22
Comparison temp transfer.........................................26
Copy settings.............................................................20
D
Data
Read ....................................................................20
Write.....................................................................20
Device hours run .......................................................27
DHH charging Hx pump ............................................21
DHW..........................................................................21
DHW charging ...........................................................23
DHW nominal setpoint, maximum .............................21
DHW push .................................................................25
DHW switching differential ........................................23
Discharging protection...............................................24
Display system messages.........................................28
E
Error history...............................................................28
Error/maintenance/alarms .........................................28
F
Flow setpoint limitations ............................................21
Flow setpoint, cooling min .........................................22
Flow temp setpoint max ............................................22
Flow temp setpoint min .............................................22
G
Gradient room model...........................................27, 29
H
Heating circuits..........................................................20
History reset ..............................................................28
Hours run device .......................................................27
Hx pumps ..................................................................21
I
Instantaneous DHW heater .......................................26
L
Limitation of charging time ........................................24
LPB system .............................................................. 28
M
Mixing valve
Integral action time.............................................. 22
P-band................................................................. 22
Mixing valve boost .................................................... 22
Mixing valve boost DHW .......................................... 25
Mixing valve cooling offset........................................ 22
Mixing valve derivative action time Tn DHW ............ 26
Mixing valve heating circuit....................................... 20
Mixing valve integral action time Tn DHW.......... 25, 26
Mixing valve integral action time Tn heating circuit .. 20
Mixing valve P-band Xp DHW ............................ 25, 26
Mixing valve P-band Xp, heating circuit.................... 20
Mixing valve precontrol DHW ................................... 25
Model room temperature 1 / 2 / P............................. 29
O
Once / day ................................................................ 23
Optimum start control ............................................... 29
Optimum stop control ............................................... 29
P
P-band Xp heating circuit ......................................... 20
Pressure measurement ............................................ 27
Primary controller / system pump ............................. 21
Protection against overtemperatures........................ 25
push.......................................................................... 25
Q
Quick setback / boost heating .................................. 29
R
Reset
Error history......................................................... 28
Room model gradient ............................................... 27
Room temperature model 1 / 2 / P ........................... 29
S
Setpoint DHW........................................................... 21
Several times / day ................................................... 23
Solar ......................................................................... 22
Solar start function.................................................... 22
Storage tank temp max ............................................ 25
Summer changeover ................................................ 28
Switching differential 2-pos....................................... 22
Switching differential DHW ....................................... 23
System messages .................................................... 28
T
Transfer strategy DHW ............................................. 26
W
Water pressure ......................................................... 27
30/32
Siemens Switzerland Ltd
HVAC Products
User Manual
CE1U2354en01a
7 November 2007
3
Revision history
All changes made to the document since the last issue (see front page) are identified
with the Winword function "Highlight". To show such text, use the following key
combinations:
Display: Ctrl Shift (Num) +
Hide: Ctrl Shift (Num) Or select the same functionality with the following Winword menu:
Menu: [Tools] - [Options]
Command:
[Highlight]
The revision history is not visible in the print file (PDF).
31/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
CE1U2353en01a
7 November 2007
Siemens Switzerland Ltd
Building Technologies Group / HVAC Products
Gubelstrasse 22
CH -6301 Zug
Tel. +41 41-724 24 24
Fax +41 41-724 35 22
www.sbt.siemens.com
© 2005-2007 Siemens Building Technologies Ltd.
Subject to change
32/32
Siemens Switzerland Ltd
HVAC Products
User Manual OEM
CE1U2353en01a
7 November 2007