FIRE FIGHTERS CALL STATION - INTRODUCTION
Dear Customer!
The main focus of our research work is and always has been the development of practical devices that are
flexible, versatile, reliable, future-proof but still easy to handle.
In close cooperation with electrical consultants, system architects and operators of public address systems
ITECNET has emerged and grown. In addition, all our know-how from many years of experience in the field
of audio and digital technology have been integrated into this product ITECNET allows the build-up of the
largest and most complex audio systems, with relatively simple and clear operation and configuration.
Due to its modular design, digital IO‘s, analog inputs and a serial interface, it offers beyond its function as
a base station, a large number of monitoring and control functions. The integrated SD card reader / player
allows the storage and playback of alarm texts and announcements.
This manual describes the hardware of the ITECNET Fire Fighters Call Station.
For knowing the entire system, all its possibilities and for executing the necessary configuration tasks
the software manual is required in addition. Please observe during the installation / operation of the ITEC
Fire Fighters Call Station all listed safety instructions in this manual; furthermore data and examples
provided ensuring the optimum usage of the device.
Lots of joy and success - The ITEC Acoustics Team
2
www.itec-audio.com
ITEC FIRE FIGHTERS CALL STATION
FIRE FIGHTERS CALL STATION
Safety instructions
When installing the device, the local connecting conditions, the required protective measures and all relevant
standards (ÖNORM F 3033, TRVB S 158, etc.) have to be observed.
The installation and configuration of the ITEC Fire Fighters Call Station must be performed by trained
personnel only. For the configuration the original software ITEC NETDESIGN has to be used exclusively.
The voltage supply and communication connection is ensured via the fire alarm cable with functional integrity to the ITECNET ENS centre or any other available sub-centre.
The device has been designed for wall installation. For cabinet installations please ensure adequate air circulation. Mounting of the device in closed timber furniture is not allowed..
Only a connection to networks, which are compliant to IEEE 802.3 (Ethernet), is allowed. Never try to open
the device by force or by unscrewing. The product does not contain parts that can be repaired by amateurs.
Please contact the manufacturer or a local distributor.
Do not apply temperatures above 50 °C, humidity larger than 95% or rain to the device.
Caution: Before carrying out any modifications on the device (only by qualified personnel) the power supply
has to be disconnected.
Use a dry or slightly damp cloth to clean the housing surface and the keyboard. Aggressive or abrasive
cleaners should be avoided.
In particular in monitored systems for voice alarms you have always to ensure that microphone and integrated
speakers of the device are not concealed.
The use of other microphones without consulting the manufacturer or distributor is not allowed!
ITEC FIRE FIGHTERS CALL STATION
www.itec-audio.com
3
FIRE FIGHTERS CALL STATION
The audio network ITECNET
ITECNET is a decentralized, Ethernet-based audio network for the simultaneous transmission of up to 64
audio channels with the highest audio quality. At the same time, a huge number of system data, measurement
data and IOs are controlled and transmitted.
FIRE FIGHTERS CALL
STATION
DIGIPOWER
ITECNET SWITCH
SPIDERMIKE 2
SPIDER 44 / SPIDER 04
04
4
www.itec-audio.com
ITEC FIRE FIGHTERS CALL STATION
FIRE FIGHTERS CALL STATION
The Fire Fighters Call Station
The ITECNET Fire Brigade Call Station is a system component EN 54-16 (VACIE)-certified along with our
ITECNET VANSYS 2.0 system. The device is ÖNORM F3033-tested and part of our ENS, ÖNORM F 3012tested. The Fire Brigade Call Station must be installed, wired and functionally configured according to
TRVB S 158.
It must be connected via a cable with E30 functional integrity. The cable used must be approved by the
manufacturer. The connection cable ensures both the 24VDC voltage supply and data communication.
Using this cable the Fire Brigade Call Station can be installed 100m from the ENS. For distances up to
40km LWL cables can be used (optional upon request to the manufacturer).
Product Features:
Certified according to EN 54-16.
ÖNORM F 3033-tested by the Austrian test centre for fire protection engineering
Wall-mounted housing with lockable door in compliance with ÖNORM F 3033
Operating and display elements and functions in compliance with ÖNORM F 3033
Installation
Only by trained and certified expert personnel (in compliance
with ÖNORM F 3074)
•
•
•
•
•
Unlock door
Unscrew front plate
Screw housing to wall
insert cable and connect using appropriate tool
Screw front plate back on
Approved E30 Fire Alarm Cable:
Manufactured by EUPEN
Type: JE-H(ST)H BMK E30
4x2x0,8 mm, red
ITEC FIRE FIGHTERS CALL STATION
www.itec-audio.com
5
FIRE FIGHTERS CALL STATION
Block diagram
Ethernet
A
4 Logic Inputs
4 Logic Outputs
6 External Controls
µP
B
RS 232
Ethernet-Unit
+12 V
Sig+
Sig-
VCA
-
÷
+20 dBs
µP
MIX
-∞
µP
0 dB
+30 dB
+
VCA
-
÷
+20 dBs
-∞
OUT 1
Volume
+
EQ
Delay
Input-Matrix
3
+
Get CH 1-256
OUTPUT
UNIT 1
A/D-Converter
2
IN 2
µP
0 dB
+30 dB
IN 1
1
Feed CH 1-256
µP
Priority
OUTPUT UNIT 2
-
D/A-Converter
+12 V
DSP
EQ
Delay
OUT 2
+
-
User Interface
Fire Fighters Call Station
6
www.itec-audio.com
ITEC FIRE FIGHTERS CALL STATION
Sig+
Sig-
FIRE FIGHTERS CALL STATION
Connection Terminal Fire Fighters Call Station
24V
0V
Schirm
TX +
TX -
RX +
RX -
SD-Card
By default, every Fire Brigade Call Station has an SD slot. You can insert micro SD cards with up to 2GB
storage capacity. Up to 256 sound files can be stored on the SD card. These files can be alarm texts, safety
instructions, audio signals as well as advertising texts or jingles.
Spare Parts
•
•
•
•
•
•
•
•
•
•
ITECNET Fire fighters call station housing in compliance with ÖNORM F3033
ITECNET SpiderMike2 main print
ITECNET SpiderMike2 Fire fighters call station user interface
ITECNET DH-95NI Fire fighters call station microphone
ITECNET NKK Fire fighters call station button, red
ITECNET NKK Fire fighters call station button, green
ITECNET NKK Fire fighters call station button actuation protection
ITECNET Fire fighters call station LED, green, with installation base
ITECNET Fire fighters call station LED, orange, with installation base
ITECNET Fire fighters call station LED, red, with installation base
ITEC FIRE FIGHTERS CALL STATION
www.itec-audio.com
7
FIRE FIGHTERS CALL STATION - SPECIFICATIONS
200 mm
300 mm
GENERAL
EXTERNAL POWER SUPPLY
switching power supply or 24 V DC (18 V < V > 32 V)
Current
260 mA, measured without applied load on the 10 V DC voltage
DIMENSIONS
200 x 300 mm (W x H)
WEIGHT
4,5 kg
AUDIO
AUDIO FREQUENCY RESPONSE 40 Hz-20 kHz/-1 dB
HARMONIC DISTORTION
<0,005 %
GENERAL DYNAMICS
103 dB
BALANCED INPUTS
max. free selectable gain -20 dB to +60 dB
Phantom power
+12 V
Input impedance
6,6 kOhm
BALANCED OUTPUTS
OUT1: speaker 1 W; OUT2: balanced; max. output level +15 dB, output impedance 300
Ohm
SOUND PROCESSING
PER OUTPUT
4-band fully parametric equalizer ± 15 dB, delay: 0.023 ms-24.5 s
bandpassfilter: 1st – 4th ORDER
Filter quality
selectable from 0.1 to 70
SERIAL INTERFACES
RS 232
9200/19200 baud
DIGITAL INPUTS
4 schmitt-trigger inputs on plug in-terminal strip
INPUT VOLTAGE
Low < 1,6 V / High > 8 V
MAX. ALLOWABLE VOLTAGE
18 V
INPUT CURRENT (@10 V)
about 0,2 mA
DIGITAL OUTPUTS
6 open-collector outputs on plug in-terminal strip
MAXIMUM VOLTAGE
36 V
MAXIMUM OUTPUT CURRENT
200 mA per output / total 500 mA (sum of all outputs switched)
ANALOG INPUTS
6 analog inputs on plug in-terminal strip
RANGE
0-10 V DC
RESOLUTION
8 Bit
INPUT CURRENT (@10 V)
ca. 0,2 mA
MICRO SD-CARD SLOT
STORAGE CAPACITY
for Micro SD cards up to 2 GB
NETWORK
Ethernet 100 Base-TX, IEEE 802.3u
No responsibility is taken for the correctness of this information - Specifications subject to change
ITEC- Tontechnik und Industrieelektronik GesmbH, A-8200 Lassnitzthal 300
Tel.: +43 (0)3133 / 3780-0, [email protected], www.itec-audio.com
8