Compact Heat Pump Commissioning Manual Copyright ©2012 Kensa Engineering Ltd Compact Heat Pump Commissioning Manual Version 4 Page 1 of 35 Contents Section Description Page 1....................... Introduction .................................................................................. 3 2....................... Safety Information ........................................................................ 4 2.1........................... Access ...................................................................................................................... 4 2.2........................... Lighting .................................................................................................................... 4 2.3........................... Tools and Consumables ........................................................................................... 4 2.4........................... Handling ................................................................................................................... 4 2.5........................... Residual Hazards ...................................................................................................... 4 2.6........................... Freezing ................................................................................................................... 4 2.7........................... Disposal/Decommissioning ..................................................................................... 4 3....................... General Product Information ........................................................ 5 4....................... Client and Heat Pump Data ........................................................... 6 5....................... Heating System Data ..................................................................... 8 6....................... Ground Arrays ............................................................................... 10 7....................... Switching the Heat Pump On ......................................................... 12 8....................... Checking for Air in the Water Pump .............................................. 14 9....................... Changing the Antifreeze Alarm Point ............................................ 16 10..................... Changing the Return Water Set Point ............................................ 17 11..................... Taking the ‘B’ Readings ................................................................. 18 12..................... Weather Compensation ................................................................ 20 13..................... Commissioning Sign Off ................................................................. 21 14..................... Faults That Can Occur During Commissioning ................................ 22 14.1......................... Carel Controller Seems Dead ................................................................................... 22 14.2......................... Carel Display is Operational But Remote Display is Dead ........................................ 23 14.3......................... LP Alarm Displayed and Red Light Flashes ............................................................... 25 14.4......................... A1 Alarm Displayed and Red Light Flashes .............................................................. 26 14.5......................... E1,E2 and E3 Alarms ................................................................................................ 28 14.6......................... E4 Alarm .................................................................................................................. 29 14.7......................... HP Alarm (High Pressure Gas) ................................................................................. 31 14.8......................... Tp Alarm—Low Pressure Underfloor or Groundside ............................................... 33 14.9......................... Compressor Sounds Noisy ....................................................................................... 34 15..................... Fault Finding Summary .................................................................. 35 Compact Heat Pump Commissioning Manual Version 4 Page 2 of 35 1. Introduction—A message from the Managing Director Kensa Engineering has been manufacturing ground source heat pumps since 1999. In the early days, it was difficult to find contractors willing to consider the technology. As a consequence, Kensa made considerable efforts to simplify the installation process. With the advent of the Microgeneration Certification Scheme the number of certified installers is increasing and the company is now reaping its rewards as heat pumps become mainstream heating appliances. The purpose of this manual is to guide you as an MCS installer, through the commissioning process. It is expected that all the required information has been provided to allow you to connect the heat pump correctly and that the commissioning will be a simple process. Please note if you experience any problems please feel free will to speak to the Technical Support Team on 01872 862140. Opening hours are 8.00am to 5.00pm . Finally, please contact Kensa should you have any questions, wish to consider ground source heat pumps for any future projects or even just to share your experiences of using a ground source heat pump with us. Simon Lomax Managing director Kensa Engineering Ltd Compact Heat Pump Commissioning Manual Version 4 Page 3 of 35 2. Safety information Safe operation of this unit can only be guaranteed if it is properly installed and commissioned in compliance with the manufacturer’s requirements. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. Manufacturer:Kensa Engineering Mount Wellington Chacewater Truro Cornwall TR4 8RJ Tel 01872 862140 www.kensaengineering.com The product is designed and constructed to withstand the forces encountered during normal use. Use of the product for any other purpose, or failure to install the product in accordance with these Installation and Commissioning Instructions, could damage the product, will invalidate the warranty, and may cause injury or fatality to personnel. 2.1 Access Ensure safe access before attempting to work on the product. Arrange suitable lifting gear if required. 2.2 Lighting Ensure adequate lighting, particularly where detailed or intricate work is required. 2.3 Tools and Consumables Before starting work ensure that you have suitable tools and / or consumables available. 2.4 Handling Manual handling of large and /or heavy products may present a risk of injury. Lifting, pushing, pulling, carrying or supporting a load by bodily force can cause injury particularly to the back. You are advised to assess the risks taking into account the task, the individual, the load and the working environment and use the appropriate handling method depending on the circumstances of the work being done. 2.5 Residual Hazards Many products are not self-draining. Take due care when dismantling or removing the product from an installation. 2.6 Freezing Provision must be made to protect products which are not self-draining against frost damage in environments where they may be exposed to temperatures below freezing point. 2.7 Disposal/Decommissioning Kensa offer a life time decommissioning service for this product. This is available on a return to base basis (carriage at users’ cost). Disposal of any antifreeze water mix should follow the disposal instructions as laid out on the COSH Safety Data Sheet in the Installation and Commissioning Manual. Compact Heat Pump Commissioning Manual Version 4 Page 4 of 35 3. General Product Information This manual gives guidance on how to commission a Kensa ground source heat pump. The manual is designed for use by MCS approved installers who undertake commissioning of a Kensa Heat pump as part of the service and grant process for their clients. The Kensa Compact Single Compressor Heat Pump is designed to provide a low cost renewable heat source for a buildings heating system. In addition, and if required, the Kensa Compact can also provide domestic hot water. Heat pumps can provide lower running costs and will generate significantly lower carbon emissions compared with traditional fossil fuels. The Kensa Compact Single Compressor Heat Pump is designed for straightforward installation and the installation must conform to all relevant construction and electrical codes and comply with the requirements of the Microgeneration Certification Scheme (MCS) MIS3005 ’Requirements for Contractors undertaking the Supply, Design, Installation, Set to Work Commissioning and Handover of Microgeneration Heat Pump Systems’. The following sections detail the steps to be taken for the final commissioning of the unit. It advises the steps and possible errors that could occur during commissioning. The idea of the manual is to work through each section in turn while referring to the fault section as and when required. Many faults found with heat pumps generally occur due to wiring faults or in setting the unit up. Therefore it is recommend that initially a detailed check is carried out should there be a problem. The manual can be used as a record of the commissioning or simply as a guide through the commissioning process. Information taken during the commissioning can help with any future fault finding and also provide information to satisfy the requirements for the commissioning certificate from the Low Carbon Buildings Programme. Compact Heat Pump Commissioning Manual Version 4 Page 5 of 35 4. Client and Unit Data Commissioning Engineer Date Client Name Address Postcode Telephone Number Site Telephone Number Installation Address (If different) Installation Postcode Type of Property (Flat, Bungalow, House) Style of Property (mid-terraced, endterraced, semi, detached) Number of Bedrooms Compact Heat Pump Commissioning Manual Version 4 Page 6 of 35 Product Note : Check for initial wiring faults on three phase systems Serial Number Heating or Cooling Note : For Cooling Applications please contact Kensa Technical Department kW rating kWh per annum Note : This figure can be obtained from the clients SAP report Fuel displaced Ensure all MCB’s are turned off Compact Heat Pump Commissioning Manual Version 4 Page 7 of 35 5. Heating System Data Type of Heating System Note: If Radiators then the return flow temperature might need to be set higher. See Changing the Return Water Set Point - Section 10 Make of underfloor Type of underfloor system Ground floor First floor Second floor Note: This will affect the final running temperature of the heat pump. Screed will be 35oC, suspended floors will need to set at 40 to 45oC. See Changing the Return Water Set Point - Section 10. Number of underfloor heating manifolds Does each manifold have its own pump? Note: This only applies for systems 4kW + Have all the mixing valves been removed? Are 25% of the zones left open or is a buffer vessel fitted? Note: When switching a heat pump on for the fist time and the weather is very cold (below 3 deg C), the best way is to open one underfloor zone at a time. This puts less demand on the ground arrays. This is called a flat battery syndrome. Compact Heat Pump Commissioning Manual Version 4 Page 8 of 35 Control Philosophy Note: How is the underfloor controlled i.e. Underfloor control unit, thermostat, time clock, linked terminals Is the heat pump able to receive a call for heat Note: This is required to ensure that power can be supplied to the unit during the commissioning. This can be done via the control unit or in its simplest form linking terminals 1 and 2 on the wiring block. Link between terminals one and two Compact Heat Pump Commissioning Manual Version 4 Page 9 of 35 6. Ground Arrays Type of Ground Arrays Number Length Horizontal or vertical trench Trench separation distance Note : For slinkies this should be 5m, for straight pipe 1m Has the array been purged in both directions with a Clarke SPE1200SS purge pump Note: If No, the ground arrays need to be purged using the Clarke Purge Pump SPE1200SS available from Machine Mart. Air might be in the system if purged incorrectly. Antifreeze (quantity added) Antifreeze concentration (checked with two random samples) Sample 1 Sample 2 Note: If the consistency of antifreeze to water is not 20% or protected to -10oC the heat pump will more than likely go out on an A1 alarm which means that ice can form in the heat exchanger. The system MUST have the right amount of antifreeze protection. If low additional antifreeze must be added and the system repurged. Following this commissioning can continue. Concentration should be checked via a refractometer. Pipe visually inspected backfilling (kinks and nicks) before Pipe leak tested to BS805 Section 11.3.3.4 Pressure A B C Note : The ground array pressure will drop over the first year due to the pipe relaxing within the ground, hence the fill loop needs to be connected if the pressure needs increasing at a later date. Any short term drop generally indicates a leak. Compact Heat Pump Commissioning Manual Version 4 Page 10 of 35 Pressure gauge readings on heat pump. Load Gauges are below the water pumps within the heat pump. Ground Note : The pressure should be between 2 and 6 barg. The pressure switch activates at 0.3 barg and resets at 1.8. If the pressure to low top up using the ground fill loop or underfloor fill loop to at least 2 barg. If pressure to high release pressure using schrader valves. Load side gauge Ground side gauge Have the flow arrows been added to the manifolds? Note : Flow direction arrows need to be placed on the manifold to indicate flow and return for future reference. This is a requirement of MCS. Have the water pumps impellors been spun? Note: See directions within the installation manual. This is to ensure pumps are free to spin. The 30/10 pump (16kW and above) does not have a bleed screw Has the antifreeze been circulated thoroughly through the arrays and heat pump? Note: The antifreeze must be mixed thoroughly otherwise any unmixed solution will ice and freeze within the heat exchanger resulting in an A1 alarm. If not done this can be achieved by running the ground water pump (DO NOT SWITCH THE 25AMP MCB ON ONLY THE 4AMP). On twin compressors both the 4amps need to be turned on. It can take about 45min to completely mix. 4amp mcb, should be marked on the mcb. Usually for single phase 2nd mcb in (check on twin), three phase 4th mcb in (check on twin) Compact Heat Pump Commissioning Manual Version 4 Page 11 of 35 7. Switching the Heat Pump On Visual check of heat pump installation Note : Check to make sure no leaks, no obvious damage to the unit. Unit level? Front cover removed Note: Ensure power to the unit is isolated Visual inspection of wiring Note: If any visual damage halt the commissioning and call an electrician. Type of Consumer unit MCB fitted Amps Rating Note: Type D's are preferred, however type 'C' is acceptable for single phase heat pumps with smart starts. Power turned on to the unit Note: Power turned on via the main MCB in the consumer unit Turn only the 4amp MCBs on. Note: On a twin both 4amp MCBs need to be turned on. DO NOT TURN ANY 25AMP MCBs ON 4amp mcb, should be marked on the mcb. Usually for single phase 2nd mcb in (check on twin), three phase 4th mcb in (check on twin) Compact Heat Pump Commissioning Manual Version 4 Page 12 of 35 Reading on display Carel controller dead (see section 14.1) Carel is working but remote display is not (see section 14.2) LP alarm flashes with red light (see section 14.3) A1 alarm flashes with red light (see section 14.4) E1, E2 or E3 flashes with red light (see section 14.5) E4 alarm flashes with red light (see section 14.6) Any software errors? Heat pump comes to life and the return flow temperature is displayed Compact Heat Pump Commissioning Manual Version 4 Page 13 of 35 8. Checking for Air in the Water Pumps If not already on, switch only the 4 amp mcbs on (two on a twin). Do not switch any 25 amp mcbs on. 4amp mcb, should be marked on the mcb. Usually for single phase 2nd mcb in (check on twin), three phase 4th mcb in (check on twin) The underfloor pump should switch on and the underfloor pressure gauge should register approx 1/2 bar drop in pressure Note: If no movement see section below Repeat three times Load side gauge Ground side gauge Around 5 seconds later the contactor should operate (large clunk) and the ground pressure should increase about 1/2 bar Note: If no movement see section below Repeat three times No movement in gauges. If the ground or load side pressure gauges do not show a change in pressure this generally means that air is around the pump. Turn the 4 amp MCBs off and bleed the pipe at the top of the pipe into the heat exchanger via the Schrader valve. Note : If no fluid is around the impeller the pump generally gets very hot Compact Heat Pump Commissioning Manual Version 4 Page 14 of 35 Load side bleed point Ground side bleed point Check pump is not stuck and spin pump Note: See directions within manual. This is to ensure pumps are free to spin. The 30/10 pump (16kW and above) does not have a bleed screw Check all valves on manifolds open Check flow direction arrows on manifold pumps correct. Note : Pumps will be pumping against each another if flow direction is the same. Check power supply to pumps Note : Pumps might be faulty if power supply ok. Check if running. If pump faulty then contact Kensa Technical Department Was the system purged correctly? Note : If not repurge Compact Heat Pump Commissioning Manual Version 4 Page 15 of 35 9. Changing the Antifreeze Alarm Point The antifreeze alarm is factory set at 0oC. This needs to be reset during commissioning to -5oC. Failure to do this (or lack of antifreeze) could cause the heat pump to display an A1 alarm and turn itself off during cold weather. The antifreeze alarm point should only be changed once the correct antifreeze quantities have been added and confirmed. 1 For the upper external controller, press and hold SET until 0 is displayed. For the lower controller within the heat pump, press and hold SEL and PRG together. 2 Press and hold the UP button, and release when 66 is displayed 3 Press SEL 4 Display will now read S-P (which means "Set Parameter") 5 Press SEL, and -/- is displayed 6 Press SEL 7 Press the UP arrow until -/04- is displayed 8 Press SEL 9 Press the DOWN arrow to change from 3 to 0 10 Press SEL 11 Press PRG 12 Press the UP arrow until -d- is displayed 13 Press SEL 14 Press the UP arrow until d03 is displayed 15 Press SEL and the Antifreeze Setpoint is displayed 16 Press and hold the DOWN arrow to change from 0.0 to -5.0 17 Press SEL 18 Press PRG 19 Press the DOWN arrow until -/- is displayed 20 Press SEL 21 Press the UP arrow until -/04- is displayed 22 Press SEL 23 Press the UP arrow to change from 00 to 03 24 Press SEL 25 Press PRG twice until S-P is displayed 26 Press and hold PRG until the display returns to normal Compact Heat Pump Commissioning Manual Version 4 Page 16 of 35 External Controller Internal Controller Note: Heat pumps are shipped with the antifreeze alarm set at 0C, this needs to be reset to -5oC at commissioning. This needs to be done for both sides if it is a twin compressor model. 10. Changing the Return Water Set Point Return water set point is factory set at 30oC to provide water into the underfloor at 35oC. For underfloor in joisted systems this will possible need to be increased to 40-45oC depending on floor coverings. Radiators require a higher flow temperature and hence the temperature should be set at 45oC. A mix of underfloor and radiators will also require 45oC. 1 For the upper external controller, press and hold SET until 0 is displayed. For the lower controller within the heat pump, press and hold SEL and PRG together. 2 Using the up arrow go to 11 3 Press SEL 4 Display will now read S-P (which means "Set Parameter") 5 Press and hold SEL until -/- is displayed 6 Press the DOWN arrow until -r- is displayed 7 Press SEL and r01 is displayed 8 Press the UP arrow until r03 is displayed 9 Press SEL 10 The return water temperature setpoint is displayed 11 Press the UP or DOWN arrows to change the setpoint 12 Press SEL 13 Press PRG twice until S-P is displayed 14 Press and hold PRG until the display returns to normal For twin compressor units both controllers i.e. both internal or both external controllers will need to be set with new return flow temperatures. The right hand controller generally has a return set temperature one degree higher than the left hand controller. Return set points Single compressor Twin compressor Left compressor Compact Heat Pump Commissioning Manual Version 4 Page 17 of 35 Right compressor 11. Taking the B Readings The ‘B’ readings are measurements of the temperatures and pressures within the heat pump. They give an indication of how well the heat pump is working and will help with any diagnostics. Turn the 25amp MCB for the compressor on 25amp mcb, should be marked on the mcb and for single phase the first mcb. On three phase all three mcb's should be turned on. Compressor noisy? Note: If yes, see section 14.9 Run compressor for 5-10 mins and then record any errors. A1 alarm see section 14.4 LP alarm see section 14.3 Tp alarm see section 14.8 E1 to E3 alarm see section 14.5 E4 alarm see section 14.6 Reading the ‘B’ temperatures and pressures Note : For twins readings have to be taken and recorded from both controllers 1 Press and hold SEL until -/- is displayed 2 Press the UP arrow until -b- is displayed 3 Press SEL and b01 is displayed 4 Press SEL 5 The temperature of water b01 single returning from the underfloor is displayed twin Note: Return flow temperature should read between 0 and 30oC. If above 30oC check that the return flow temp hasn’t been changed. If the flow temperature is set correctly and reading above 30oC then check sensors are connected and call the Kensa Technical Department When taking the b01 reading you can check for no flow by watching how fast the heat is dissipated when the compressor is not running. This will confirm that flow is present. Compact Heat Pump Commissioning Manual Version 4 Page 18 of 35 6 Press SEL 7 Press the UP arrow once until b02 is displayed 8 Press SEL 9 The temperature of water return- b02 single ing from ground arrays is displayed twin Note: Return ground temperature should read between 15 and -5oC. If the b02 temperature is around room temperature, the probe could have come lose. Trace the wiring back to yellow probe on heat exchanger to confirm ok. If problem persists contact Kensa Technical Department. 10 Press SEL 11 Press the UP arrow once until b03 is displayed 12 Press SEL 13 The temperature of water going b03 single out to the ground arrays is displayed twin Note: b03 is the temperature leaving the ground side of the heat pump. If b03 is below the antifreeze set point and it has not gone to alarm, A1, then check the antifreeze alarm set point. This should be set to -5oC. See Section 9. 14 Press SEL 15 Press the UP arrow once until b04 is displayed 16 Press SEL 17 The refrigerant pressure in Barg is displayed b04 single twin Note: Take b04 when compressor running. b04 is the gas pressure and this should be between 4.6 and 2.2. If weather compensator is fitted then you will not be able to read the gas pressures. If b04 is reading below 2 then the heat pump might be low of gas. Note: When the ground is very cold the heat pump can go out on LP alarm and b04 is very low. This can happen when a heat pump is switched on for the first time and the building is cold. The building needs to be heated up one zone at a time (flat battery) Note: If b04 is to high, the expansion valve may need adjusting. Contact Kensa Technical Department. Note: Check sensor wiring as could be a bad connection. Call the Kensa Technical Department if problem still present 18 Press PRG twice until S-P is displayed 19 Press and hold PRG until the display returns to normal Check the b readings are logical, ie, that the load return temperature is below the outlet temperature and that the ground outlet is below the inlet. If not this could indicate that the sensors are incorrectly positioned. Compact Heat Pump Commissioning Manual Version 4 Page 19 of 35 12. Weather Compensation It is advised that weather compensation is not enabled for underfloor systems operating on off-peak tariffs and is only used on radiators. Even then Kensa recommend the system is left without weather compensation for at least 12 months. The heat pump must be fully commissioned before weather compensation is enabled and the b04 probe is removed. To read b04 the weather compensator from the bottom of the carel needs to be unplugged and the carel pressure probe plugged back in. The -/04– parameter needs to be reset to 1 following the same procedure as outlined below. Once the b04 reading is taken the weather compensator can be plugged back in and -/04- enabled as below. New panel mounted Carel Old Din rail mounted Carel Carel pressure probe connection 1 Unplug the pressure transducer from the rear of the Carel (or for older grey units bottom right hand side of Carel) 2 Plug the weather compensation sensor into the rear of the Carel (or for older grey units bottom right hand side of Carel) 3 Press and hold SET, and release when 0 is displayed 4 Press and hold the UP button, and release when 66 is displayed 5 Press SEL 6 Display will now read S-P (which means "Set Parameter") 7 Press SEL, and -/- is displayed 8 Press SEL 9 Press the UP arrow until -/04- is displayed 10 Press SEL 11 Press the DOWN arrow to change from 1 to 3 12 Press SEL 13 Press PRG twice until S-P is displayed 14 Press and hold PRG until the display returns to normal Compact Heat Pump Commissioning Manual Version 4 Page 20 of 35 13. Commissioning Sign Off The unit should now be commissioned and operating correctly. The user manuals should be left with the client and the data collected within this commissioning process can be used to complete any grant forms. Comments Commissioning Engineer Signature Print Date Company MCS Accreditation Number Telephone Compact Heat Pump Commissioning Manual Version 4 Page 21 of 35 14. Faults that can occur during Commissioning 14.1 Carel controller Seems Dead Check that power to the Heat pump is on Check that there is a live enable signal over terminals one and two Note: If a live enable signal can not be obtained from the heating control signal, disconnect and link terminals 1 and 2 Link between terminals one and two Check Carel fuse inside electric box Note: If the fuse has blown a spare fuse is taped to the HP sensor Carel fuse Check wiring is correct Faulty Carel Note: Contact Kensa Technical Department Compact Heat Pump Commissioning Manual Version 4 Page 22 of 35 14.2 Carel Display is Operational but Remote Display is Dead Check that the remote cable is connected correctly For older din-rail mounted units check that the RS485 'chip' is present and in position on the Carel main unit RS485 chip Compact Heat Pump Commissioning Manual Version 4 Page 23 of 35 Check the wiring to the Carel, transformer and remote display power supply Note: Push and hold the plug in the back of the remote display. If the display then works, the connection on the remote display is damaged . Grey Brown Remote Display Connection from the Carel Blue Old Din Rail mounted Carel Back of the remote display New panel mounted Carel Remote display maybe faulty Note: Contact Kensa Technical Department Compact Heat Pump Commissioning Manual Version 4 Page 24 of 35 14.3 LP Alarm Displayed and Red Light Flashes Check that LP switch wiring (on refrigerant) is correct LP pressure switch Pressure transducer (b04) Check b04 reading 1 Press and hold SEL until -/- is displayed 2 Press the UP arrow until -b- is displayed 3 Press SEL and b01 is displayed 4 Press the UP arrow once until b04 is displayed 5 Press SEL 6 The refrigerant pressure in Bar is displayed b04 single twin Note: If b04 can't be read the weather compensation might be fitted. See Section 12 Note: If b04 is below 2 barg contact Kensa Technical Department 7 Press PRG twice until S-P is displayed 8 Press and hold PRG until the display returns to normal Compact Heat Pump Commissioning Manual Version 4 Page 25 of 35 14.4 A1 Alarm Displayed and Red Light Flashes An A1 alarm generally indicates no flow or that the compressor has run with air in the ground arrays and that the heat exchanger has frozen. Also check the pump impeller is not stuck. Note : If no fluid is around the impeller the pump generally gets very hot. See Section 8 Check the b readings from the unit 1 Press and hold SEL until -/- is displayed 2 Press the UP arrow until -b- is displayed 3 Press SEL and b01 is displayed 4 Press SEL 5 The temperature of water returning b01 single from the underfloor is displayed 6 Press SEL 7 Press the UP arrow once until b02 is displayed 8 Press SEL 9 The temperature of water returning b02 single from ground arrays is displayed twin twin Note: b02 is the ground return temperature 10 Press SEL 11 Press the UP arrow once until b03 is displayed 12 Press SEL 13 The temperature of water going out b03 single to the ground arrays is displayed twin Note: b03 is the ground flow temperature, if this is below -5oC then the unit will not operate and needs to be switched of until b03 is above 0oC. If b03 is above -5oC and below 0 the A1 alarm needs to be set to -5oC to allow commissioning. 14 Press SEL 15 Press the UP arrow once until b04 is displayed 16 Press SEL 17 The refrigerant pressure in Barg is displayed 18 Press PRG twice displayed 19 Press and hold PRG until the display returns to normal until S-P b04 single is Compact Heat Pump Commissioning Manual Version 4 Page 26 of 35 twin Check to ensure flow around ground arrays Note: Check the pump. See Section 8 Double check antifreeze quantities and concentration. Note: Check the antifreeze quantities and concentration using a refractometer. Reconfirm purging. All antifreeze supplied must be added to the system. Compact Heat Pump Commissioning Manual Version 4 Page 27 of 35 14.5 E1,E2 and E3 Alarms E alarms generally mean a loss of contact with a sensor used to measure b0 temperatures. Note: any damage contact Kensa Technical Department Check that the temperature probes leading to the Carel are fitted properly and not loose. Note: The sensors mounted within the heat exchanger are not accessible. Loose connections cannot be easily rectified and if any damage contact Kensa Technical Department. Note: E1 fault can also indicate a problem with the DHW relay Old Din Rail mounted Carel Controller Sensor connector New panel mounted Carel Controller Compact Heat Pump Commissioning Manual Version 4 Page 28 of 35 14.6 E4 Alarm E4 alarms are generally a result of a faulty weather compensation sensor or incorrect commissioning. Check for a damaged external weather compensation sensor Note : If damaged contact Kensa Engineering to organise a replacement. Has the heat pump been commissioned with weather compensation Note: See section 12 Check for damaged external temperature probe wires Note : Check connections. If not easily rectified contact Kensa Technical Department Sensor Green Terminal connection block. Main Terminal Block Check refrigerant pressure transducer is ok Note : If not easily rectified contact Kensa Technical Department Pressure transducer (b04) Compact Heat Pump Commissioning Manual Version 4 Page 29 of 35 Check the temperature probe wiring is correct Note : Check connections. If not easily rectified contact Kensa Technical Department Temperature probe connections Carel pressure probe connection Old Din Rail mounted Carel controller New panel mounted Carel controller Compact Heat Pump Commissioning Manual Version 4 Page 30 of 35 14.7 HP alarm. (High Pressure Gas) HP alarms indicate the heat pump is over heating and is generally an indication of no or low flow around heating distribution circuit because of air in water pump, or stuck water pump impellor, or heating distribution system valves/actuators closed. No flow on underfloor system. Check Flow? all manifolds are open and underfloor manifold pumps are not fighting each another. Note: 90% of the time Hp fault is due to no flow on the distribution side. Note: When taking the b01 reading you can check for no flow by watching how fast the heat is dissipated when the compressor is not running. This will confirm that flow is present. Note: b04 reading needs to be taken when the compressor is running. All valves open? Air in underfloor system? Pumps fighting each another? Check 3 way diverter valves Underfloor pump running? Note: Circulation pump might be stuck. Spin pump etc. Compact Heat Pump Commissioning Manual Version 4 Page 31 of 35 Check wiring to HP switch HP Pressure Switch If HP alarm still showing then possible faults might be 1) HP switch might be faulty 2) To much gas 3) Blocked gas system. Compact Heat Pump Commissioning Manual Version 4 Page 32 of 35 Note : Contact Kensa Technical Department 14.8 tp Alarm - Low Pressure Underfloor or Ground Side ‘tp’ alarms occur due to low pressure in either the ground or the load side. This could be due to an insufficient initial pressure, pipe relaxation or leaks. Low pressure on underfloor or ground arrays, try topping the pressure up. Note: Ground arrays are topped up by using the fill loop on the heat pump. The load side (heating) system should have it’s own individual top up . On the load side there should be an expansion vessel to keep the pressure stable due to the temperature changes from the Heat pump. Note: The low pressure switch operates (for both sides) at 0.3 barg, but the pressure needs to be increased to above 1.8 barg to reset. Heat pump ground array fill Check connectors back to LP ground and load switch Low ground water pressure switch Low load water pressure switch If pressure continues to drop, this indicates a possible leak in the system. Pressure test the problem side. If tP alarm still present possible causes are: 1) LP switch and pressure gauges might be faulty Note : Contact Kensa Technical Department Compact Heat Pump Commissioning Manual Version 4 Page 33 of 35 14.9 Compressor sounds noisy Contactor chattering on or off Contactor might need changing, check contacts. Contact Kensa Technical Department. Compressor makes a loud shrieking noise hp switch is faulty or access valve not depressing. Contact Kensa Technical Department Compressor sounds like its trying to run backwards Mainly 3 phase - incorrect wiring on the phases. Check wiring and rewire. If rewiring doesn't solve the problem then call Kensa Technical Department Check compressor is not rubbing on casing Compact Heat Pump Commissioning Manual Version 4 Page 34 of 35 15. Fault Finding Summary Many faults which occur on commissioning are found to be due to incorrect wiring or setting up, therefore it is recommended that a thorough check is carried out should there be a problem. Symptom Blank display on software controller Possible Cause Action No power supply Check wall mounted electrical isolator switch or call electrician Controls MCB tripped Call electrician to investigate cause There is no call from the time-clock or thermostat for heat pump operation Programme time-clock according to manufacturer’s instructions Compressor not running but display reading temperature near setpoint Heat pump is up to temperature No fault Display flashes fault code tP Low water pressure in the ground or heating system side due to pipe relaxation or other pressure loss. Check the pressure gauges below the two water pumps. The pressures should be between 1 and 2 bar. If below this, the pressure needs to be increased above 1.8 bar To increase the pressure in either circuit, the cold fill valve will need to be opened. The Ground cold fill is provided with every Kensa heat pump, and is found on the right hand side of the heat pump, underneath. The heating distribution system should have it’s own fill point. Display flashes fault code HP Overheat warning. No or low flow around heating distribution circuit because of air in water pump, or stuck water pump impellor, or heating distribution system valves/ actuators closed. Bleed the heating distribution system pump within the heat pump, using the schrader valve above the pump. Check that the water pumps are operational and spin the impellors (see the Installation Manual) Display flashes fault code LP Display flashes fault code A1 HP can also be temporarily displayed when the heat pump reverts from DHW to space heating mode. Low gas pressure in machine. Can occur simultaneously with an A1 alarm. Can occur temporarily on first start up when unit is new or after a long period out of use. Freeze protection system activated. Low or no water flow on the ground (cold) side of the machine. Can also occur after many months of running in very cold weather. No action Check that the water pumps are operational and spin the impellors (see the Installation Manual) If symptom persists outside of the two listed circumstances, contact Kensa Technical department. No action Check antifreeze has been added and unit commissioned correctly. Check that the water pumps are operational and spin the impellors (see the Installation Manual) Ensure no flow restrictions and wait approximately 4 hours (with the machine turned off) for automatic reset. Display flashes fault code E1, E2, E3 or E4 Loss of contact with probes inside heat pump. E4 could be loss of contact with weather compensation sensor Compact Heat Pump Commissioning Manual Version 4 Page 35 of 35 Refer to Kensa Technical Department
© Copyright 2024