ANDIVI TRC-D TECHNICAL MANUAL 08/14, fw. ver. V1.2, V1.3 www.andivi.com

ANDIVI TRC-d
TECHNICAL MANUAL
08/14, fw. ver. V1.2, V1.3
www.andivi.com
Andivi – TRC-D – Technical Manual
ATTENTION!
In the event of an incorrect connection of the room controller or a short circuit in
the installation and actuators, irreparable damage to the room controller can occur.
Therefore, pay special attention during the installation and follow the instructions
carefully!
• Carefully read these instructions before starting the installation.
• Room controller Andivi must be installed according to applicable standards.
• Before any intervention, make sure the power is turned off.
2
08/14, fw. ver. V1.2, V1.3
Andivi – TRC-D – Technical Manual
index
3
FRONT VIEW (LEGEND OF SYMBOLS)
4
INSTALLATION
MOUNTING ON ELECTRIC BOX
MOUNTING THE FRONT COVER
WIRING EXAMPLE
5
5
5
5
OPERATION ROOM CONTROLLER TYPES
USER MODE OPERATION WORKING MODE
Cooling MODE heating MODE “ON” FUNCTION ANTI-FREEZING PROTECTION
ECONOMY MODE
PROTECT MODE FIRMWARE VERSION
ENGINEER MODE OPERATION
Table: Engineer Mode menu items description
NETWORK SPECIFICATIONS
Table: Read/Write Coils (function code 01/05/15)
Table: Read discrete input (function code 02)
Table: Read/write holding register (function code 03/06/16/23)
Table: Read input register (function code 04)
6
6
6
7
7
8
8
8
9
9
9
10
11
13
14
15
16
18
WARRANTY, CONDITIONS
08/14, fw. ver. V1.2, V1.3
19
Intelligent room controller
TRC-D Technical Manual
15
14

13
2
12
3
11
4
10
9
5
8
6
7
Fig 1-1: Front view
4
Item
Description
1
FIRE icon or Flake icon
Fire icon for Heating action; Flake icon for Cooling action
2
ON/Active icon
Indicate room controller ON status
3
Sleep icon
[not used]
4
Clock icon
Indicate Protect mode
5
DOWN button
Decrease setting / Previous item
6
UP button
Increase setting / Next item
7
FAN SPEED button
Toggle to change fan speed over Auto / Off / Stage I / Stage II / Stage III
8
Power On/Off button
Turn room controller on/off
9
MODE button
Cooling/Heating changeover / Setting confirmation
10
House with thermometer icon
Indicate Anti-Freezing active
11
AUTO icon
Automatic fan mode
12
Fan icon
Indicate fan state
13
LCD
Display temperature and operation data
14
Moon icon
Indicate Economy mode
15
Thermometer icon
Temperature set-point mode
08/14, fw. ver. V1.2, V1.3
Andivi – TRC-D – Technical Manual
Installation
MOUNTING ON ELECTRIC BOX
1. Separate the back plate from the controller by loosening the cover screw.
2. Align the mounting holes on the screw holes of the electric box. Suitable is a 3-module electric box 3M, for example Gewiss
GW24203, GW24207; TEM Catez DM30, HM30. The electric box is mounted vertically.
3. Fix the back plate on the electric box by tightening the back plate screws. Suggested for use is Philips wider “truss head”
or “washer head” #6-32x 3/4”(20mm).
4. DO NOT let the bolt head rise above the wall of the mounting holes of the back plate. It might cause a short circuit of the
room controller.
MOUNTING FRONT COVER
1. Lock front cover on the back plate by tightening the cover screw underneath with screwdriver of Philips electronic instrument
type or similar.
WIRING EXAMPLE
All wires that come from electric box must be inserted above the retainers of respective terminal block before tightening the
captive screws.
N
L
N
L
1
2
Cooling/Heating valve
3
4
5
6
7
8
I.
II.
III.
Fan
RS 9
COM 10
Remote sensor (RS)
Protect mode input (PROT)
ESI 11
C+ 12
Modbus
C - 13
Economy mode input (ECON)
ESI2 14
Fig. 2-1:
2-Pipe Control, 230VAC
15
16
Cooling valve
Heating valve
I.
II.
III.
FAN
Remote sensor (RS)
Protect mode input (PROT)
Modbus
Economy mode input (ECON)
Fig. 2-2:
4-Pipe Control, 230VAC
5
08/14, fw. ver. V1.2, V1.3
Andivi – TRC-D – Technical Manual
operation
ROOM CONTROLLER TYPES
The type of room controller is selectable in the Engineer mode and over the Modbus communication.
Item
Description
B - Type
4-Pipe Heating or Cooling (Manually Selectable)
C - Type
4-Pipe Heating and Cooling (Auto changeover)
E - Type
2-Pipe Heating or Cooling (Manually Selectable)
USER MODE OPERATION
The first tier of operation includes settings as Figure 3-1 shows. To operate:
1. Press Power button ON or OFF to turn on/off the room controller. In on state, icon ON is activated.
2. At state ON, press any other button to start the User Mode operation. Press FAN SPEED button to toggle over different fan
speeds. Press MODE button to toggle working modes over Cooling/Heating. Press Up or Down button to increase/decrease
temperature set-point.
3. If no button is pressed for 10 seconds, it will return to current temperature display with the latest setting.
Item
Description
1
Current Temperature
Display current temperature
2
Temperature Setting
Set the temperature set-point
3
Cooling/Heating Select
Toggle to change the working
mode over Cooling/Heating
4
Fan Auto/Continuous
Remarks
Only applied to models with Cooling/
Heating mode selectable types.
Toggle to change fan speed over
Auto / Off / Stage I / Stage II / Stage III
1
Current
Temperature
FAN
AUTO
Continuous
4
2
Temperature
Setting
0.5ºC
Cooling/
Heating
Select **
3
* Back to 1 when no
button was pressed for 10s
Fig. 3-1:
User Mode operation
sequence
6
08/14, fw. ver. V1.2, V1.3
** For Cool or Heat
selectable Models only
Andivi – TRC-D – Technical Manual
WORKING MODE
1. For Cooling or Heating mode manually
selectable type (B, E), working mode
depends on the users’ setting.
2. For Cooling and Heating mode
automatical changeover type (C),
working mode depends on the Room
temperature as following:
Cooling Mode
Heating Mode
Room
Temperature
Set-point
(SP)
Dead Band
(DB)
½ DB
Cooling MODE
Stage
Differential
Valve control for Cooling mode
Stage
Differential
Valve
active
Valve
not active
Valve
active
Valve
not active
Room
Temperature
Set-point
Room
Temperature
Set-point
Cooling
Cooling
FAN control for Cooling mode
1/3 PB
1/3 PB
Stage
Stage
Differential
Differential
Fan Stage III
Fan Stage III
1/3 1/3
Proportional
Proportional
Band
(PB)(PB)
Band
Fan Stage
FanIII
Stage III
FanIII
Stage III
Fan Stage
Fan OffFan Off
Room
Room
Temperature
Temperature
Set-point
Set-point
Cooling
Cooling
7
08/14, fw. ver. V1.2, V1.3
Andivi – TRC-D – Technical Manual
heating MODE
Stage
Differential
Valve control for Heating mode
Stage
Differential
Valve
active
Valve
Valve
active
not active
Valve
not active
Heating
Set-point
Current
Temperature
Set-point
Current
Temperature
Heating
FAN control for Heating mode
1/3 PB
1/3 PB
Fan Stage III
Stage
Differential
Stage
Differential
Fan Stage
Stage III
III
Fan
1/3
Proportional
Band (PB)
Fan Stage III
1/3
Proportional
Band (PB)
Fan Stage III
Fan Off
Set-point
Room
Temperature
Set-point
Room
Temperature
Fan Off
Heating
Heating
ON FUNCTION
If Power ON/OFF button is locked, it is not possible to switch the room controller ON or OFF locally with the button. But the ON/
OFF state can be changed by the Modbus communication.
ANTI-FREEZING PROTECTION
1. If the present temperature falls under 10°C (adjustable in Engineer mode and Modbus), a Heating valve opens to 100%. This
is active always, even when the room controller is off. In the 4-Pipe system (B or C), a Heating valve on terminal 4 activates.
In the 2-Pipes system (E), a valve output on terminal 2 activates. Anti-Freezing Protection is ON by default, but it is also
switchable to OFF in the Engineer mode and Modbus.
2. If the present temperature falls under PtCF (default 10°C), a fire icon and a house with thermometer will be active on
LCD.
8
08/14, fw. ver. V1.2, V1.3
Andivi – TRC-D – Technical Manual
Type
Room controller OFF
Room controller ON
2-Pipe system (E)
Valve is always ON
Valve is always ON
4-Pipe system (B or C)
Heating valve is always ON
Heating valve is always ON
0.5
Differential (°C)
Valve control for Anti-Freezing
Protection
Valve
active
Valve
not active
Room
Temperature
PtCF
(Temp. for
Anti-Freezing)
AntiFreezing
ECONOMY MODE
Economy mode can be activated with the digital input on terminal 14 or with the Modbus coil, address 3. Active Economy
mode is indicated with the Moon icon on LCD. If the present temperature in this mode is between Economy Cooling setpoint and Economy Heating set-point, no cooling or heating action is active. If the present temperature is outside these limits,
corresponding cooling or heating action will be activated. If both, Economy and Protect mode are active, Protect mode will have
priority.
PROTECT MODE
Protect mode can be activated with the digital input on terminal 11 or with the Modbus coil, address 2. Active Protect mode is
indicated with the Clock icon on LCD. If the present temperature in this mode is between Protect Cooling set-point and Protect
Heating set-point, no cooling or heating action is active. If the present temperature is outside these limits, corresponding
Cooling or Heating action will be activated. If both, Economy and Protect mode are active, Protect mode will have priority.
FIRMWARE VERSION
The firmware version can be read with the Power On/Off button pressed for over 5 seconds. 9
08/14, fw. ver. V1.2, V1.3
Andivi – TRC-D – Technical Manual
ENGINEER MODE OPERATION
It is highly recommended for this mode to be operated by trained engineers because it is related to system parameters that will
affect the control results. To operate:
1. Press Up and Down buttons for over 5 seconds to enter Engineer mode.
2. Press UP or DOWN button to rotate the menu item and press MODE button to enter the item.
3. Press UP or DOWN button to change the setting and press MODE button to confirm the setting and return to menu item
selection. If no button is pressed for 10 seconds, it will go back to menu item selection. The setting won’t be changed then.
4. To leave Engineer mode, rotate till “End” and press MODE button or leave the button intact for 10 seconds.
5. Engineer mode can be locked for the user. In this case, it is not possible to enter this mode with the above procedure. For
safety reasons, entering the Engineer mode is still possible with the Up and Down buttons pressed for over 60 seconds.
6. Engineer mode operation flowchart:
E01
E01
Setting
E02
E02
Setting
No button pressed
for 10s under menu
item selection
Previous
End
Fig. 4-1:
Engineer mode operation
sequence
10
08/14, fw. ver. V1.2, V1.3
User
Mode
Andivi – TRC-D – Technical Manual
Engineer mode menu items description
Item Mnemonic
1
2
3
ESIC
ESIH
LOC
°C Type
Default
Range
Description
Protect (PROT) Cooling set-point
Protect (PROT) Heating set-point
Locking buttons and functions
Examples:
Bit Value:
0: Unlock / enable all
0: Unlock / enable
1: Lock / disable
1: Disable Local
PROTECT
Bit Definition:
Bit 0: Local PROTECT 2: Lock MODE button
detection
3: Both 1 and 2
4: Lock Up/Down Bit 1: MODE button
Bit 2: Up/Down
button
5: Both 1 and 4
button
Bit 3: FAN SPEED
7: 1, 2, and 4
button
8: Lock Fan speed
Bit 4: On/Off button button
Bit 5: Local Economy 16: Lock Power
detection
button
Bit 6: Engineer mode 127: Lock/disable all
Bit 7: Not used
30.0
15.0
18
(Lock
MODE
and
Power
buttons)
Step
20.0~40.0
00.0~25.0
86.0
59.0
68.0~104.0 0.1°C/°F
32.0~77.0 0.1°C/°F
0~127
18
(Lock
MODE
and
Power
buttons)
0~127
1
247
°C
E-type
7.2
2400 bps
4800 bps
9600 bps
19200 bps
8O1
8E1
8N1
8N2
1~247
1
°C/°F
B,C,E
0~18.0
0.1°C/°F
0.1~1.0
0~50.0
0~50.0
0~1
-9.0~9.0
0.9
50.0
86.0
1
0.0
0.1~1.8
32.0~122.0
32.0~122.0
0~1
-17.0~17.0
0
0~2
0
0~2
Proportional band for fan control
Not used
4.0
0~10
7.2
0~18
Lowest fan speed used for fan auto mode
0
0~1
0
0~1
0
0~1
0
0~1
10
On
0~15
On/Off
50
On
32~59
On/Off
20
1
0.0
27.0
18.0
0
0~120
0~1
-9.0~9.0
20.0~40.0
00.0~25.0
0~600
20
1
0.0
80.6
64.4
0
0~120
0~1
-17.0~17.0
68.0~104.0
32.0~77.0
0~600
4
baud
Baud rate
19200
5
Prty
Parity / Data / Stop bits
8N2
6
7
8
9
10
11
12
13
14
15
nodE
Unit
type
db
Pb
diFF
SP-L
SP-H
ESI
OFSt
Modbus Node ID
Unit
Type of room controller
Deadband for Cooling/Heating valve control
Not used
Stage differential
Low limit for temperature set-point
High limit for temperature set-point
PROTECT contact definition
Offset for built-in temperature sensor
247
°C
E-type
4.0
2400 bps
4800 bps
9600 bps
19200 bps
8O1
8E1
8N1
8N2
1~247
°C/°F
B,C,E
0~10.0
0.5
10.0
30.0
1
0.0
16
rS
Source of temperature sensor
17
18
F-Pb
i-db
19
LFAn
20
PvLC
21
22
23
24
25
26
27
28
29
PtCF
AntF
I-t
Pit
ESI2
EoSt
ES2C
ES2H
Fand
11
°F Type
Default
Range
Display present value of temperature or setpoint for normal displaying
Present temperature to anti-freezing
Anti-Freezing Protection
Not used
Period of sensor suffocating time
Economy contact definition
Offset for external temperature sensor
Economy (ECON) Cooling set-point
Economy (ECON) Heating set-point
Fan off delay
08/14, fw. ver. V1.2, V1.3
19200
8N2
0.1°C/°F
0.1°C/°F
0.1°C/°F
0: N.O. / 1: N.C.
0.1°C/°F
0: Built-in /
1: Remote
2: Built-in +
remote
(average)
0.1°C/°F
0: Stop /
1: Low speed
0: Display PV /
1: Display SP
0.1°C/°F
1 sec.
0: N.O. / 1: N.C.
0.1°C/°F
0.1°C/°F
0.1°C/°F
10 sec.
Andivi – TRC-D – Technical Manual
30
31
32
33
34
OP-L
SPAn
rE-C
rE-H
HFAn
35
OutC
36
Outr
Not used
Not used
Not used
Not used
Maximum fan speed
3
Output control
Bit Value:
0: output controlled with internal r. controller
1: output directly controlled via Modbus
communication
Bit definition:
Bit 0: DO1 - output Cooling valve
0
Bit 1: DO2 - output Heating valve
Bit 2: DO3 - output Fan Stage I
Bit 3: DO4 - output Fan Stage II
Bit 4: DO5 - output Fan Stage III
Bit 5 – Bit7: Not used
Note: Max. 3 outputs can be active at the
same time.
Inverted valve outputs
Bit Value:
0: Normal output N.O.
1: Inverted output N.C.
0
Bit definition:
Bit 0: DO1 - output Cooling valve
Bit 1: DO2 - output Heating valve
Bit 2 - bit7: Not used
0~3
3
0~3
1
0~31
0
0~31
1
0~3
0
0~3
1
0: In fan Manual
mode fan is
active also in
case of inactive
Cooling/Heating
valve /
1: Fan can be
active only in
case of active
Cooling/Heating
valve
0: Disabled /
1: Enabled
0: Disabled /
1: Enabled
37
FAnr
Fan control
1
0~1
1
0~1
38
FCOL
Fan enable in Cooling mode
1
0~1
1
0~1
39
FHEt
Fan enable in Heating mode
1
0~1
1
0~1
40
41
42
Ao1d
AO2d
tFAn
300
0~9990
300
0~9990
10 sec.
43
IFAn
1000
0~9990
1000
0~9990
10 sec.
44
ESIt
0
0~600
0
0~600
10 sec.
45
46
47
48
FOnt
Ret1
tESt
End
Not used
Not used
Minimum time previous fan stage upward
Integral time (I-part) PI regulator for fan
control
Protect mode ON delay time via digital
input
Fan ON delay time in AUTO mode
Return to factory defaults
Self-diagnostic
Exit Engineer mode
10
0~9990
10
0~9990
10 sec.
12
08/14, fw. ver. V1.2, V1.3
Andivi – TRC-D – Technical Manual
NETWORK SPECIFICATIONS
Transmission
• Physical layer: RS485 (2 wires)
• Baud rate: 19200 bps
• Data format (RTU mode): 1 start bit, 8 data bits, no parity check, 2 stop bit
Modbus
• Address range: 1~247.
• Suppose function code: 1, 2, 3, 4, 5, 6, 15, 16, 23.
• Data format: address | function code | data 1 | … | data n | CRC-16 low byte | CRC-16 high byte
• Data bytes: 252 bytes (max.)
• Temperature representation: the original temperature degree value has to be multiplied by 10 to be saved in the register.
• Examples: 25.5°C is represented by: 00 FF (in hex) i.e. 255 (in dec.)
• 5.0°C is represented by: 00 32 (in hex) i.e. 50 (in dec.)
13
08/14, fw. ver. V1.2, V1.3
Andivi – TRC-D – Technical Manual
Read/Write Coils (function code 01/05/15)
Function Register
code
address
01
1
01
2
01
3
01
4
01
5
01
6
01
7
01
8
Function Register
code
address
05/15
1
05/15
2
05/15
3
05/15
4
05/15
5
05/15
6
05/15
7
05/15
8
14
Description
Definition
Status of room controller
Status of Protect mode
(Active only when the local PROTECT detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
Status of Economy mode
(Active only when the local ECONOMY detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
Status of direct control for DO1 – Cooling valve
(Active only in case of active bit 0 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 – OutC.)
Status of direct control for DO2 – Heating valve
(Active only in case of active bit 1 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 – OutC.)
Status of direct control for DO3 - Fan Stage I
(Active only in case of active bit 2 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
Status of direct control for DO4 - Fan Stage II
(Active only in case of active bit 3 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
Status of direct control for DO5 - Fan Stage III
(Active only in case of active bit 4 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
0: Off / 1: On
Description
Definition
Remote room controller On/Off control
Remote control for Protect mode
(Active only when the local PROTECT detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
Remote control for Economy mode
(Active only when the local ECONOMY detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
Direct control for DO1 - Cooling valve
(Active only in case of active bit 0 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
Direct control for DO2 - Heating valve
(Active only in case of active bit 1 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
Direct control for DO3 - Fan Stage I
(Active only in case of active bit 2 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
Direct control for DO4 - Fan Stage II
(Active only in case of active bit 3 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
Direct control for DO5 - Fan Stage III
(Active only in case of active bit 4 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
0: Off / 1: On
08/14, fw. ver. V1.2, V1.3
0: Protect mode not active /
1: Protect mode active
0: Economy mode not active /
1: Economy mode active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
0: Protect mode not active /
1: Protect mode active
0: Economy mode not active /
1: Economy mode active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
Andivi – TRC-D – Technical Manual
Read discrete input (function code 02)
Function Register
code
address
15
02
1
02
02
02
02
02
02
2
3
4
5
6
7
02
8
02
9
Description
Status of Protect mode
(Effective only when the local PROTECT detection is enabled. Please
refer to Modbus holding register address 6, and Engineer table
parameter 03 - LOC.)
Status of Heating/Cooling action
Relay 1 (Cooling valve)
Relay 2 (Heating valve)
Relay 3 (Fan Stage I)
Relay 4 (Fan Stage II)
Relay 5 (Fan Stage III)
Status of Economy mode
(Effective only when the local ECONOMY detection is enabled.
Please refer to Modbus holding register address 6, and Engineer
table parameter 03 - LOC.)
Status of Anti-Freezing Protection
08/14, fw. ver. V1.2, V1.3
Definition
0: Protect mode not active /
1: Protect mode active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
0: Economy mode not active /
1: Economy mode active
0: Not active / 1: Active
Andivi – TRC-D – Technical Manual
Read/write holding register (function code 03/06/16/23)
Function
code
Register
address
03/06/16/23
1
03/06*/16*/23*
2
03/06/16/23
3
03/06/16/23
03/06/16/23
4
5
03/06/16/23
6
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
7
8
9
10
11
12
13
14
15
16
17
18
03/06/16/23
19
03/06/16/23
03/06/16/23
03/06/16/23
20
21
22
03/06/16/23
23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
24
25
26
27
28
29
30
31
32
33
34
35
36
16
08/14, fw. ver. V1.2, V1.3
Description
Definition
SP
0~500 (0~50.0°C)
Heating/Cooling mode (*“Command write” only for
0: Cool / 1: Heat
Cooling or Heating mode selectable type)
0: Off / 1: Manual Stage I / 2: Manual Stage II /
Fan mode
3: Manual Stage III / 4: Auto
Protect (PROT) Cooling set-point
°C: 200~400 (20.0~40.0°C) / °F: 680~1040 (68.0~104.0°F)
Protect (PROT) Heating set-point
°C: 0~250 (00.0~25.0°C) / °F: 320~770 (32.0~77.0°F)
Examples:
Bit Value:
0: Unlock / enable all
0: Unlock / enable
1: Disable Local
1: Lock / disable
Bit Definition (Low Byte): PROTECT
2: Lock MODE 0: Local PROTECT
button
detection
3: Both 1 and 2
1: MODE button
4: Lock Up/Down 2: Up/Down buttons
LOCK
button
3: FAN SPEED button
Locking buttons and functions
4: Power On/Off button 5: Both 1 and 4
7: 1, 2, and 4
5: Local ECONOMY 8: Lock Fan speed
detection
button
6: Engineer mode
16: Lock PowER
7: Not used
button
127: Lock/disable all
Baud rate
0: 2400 / 1: 4800 / 2: 9600 / 3: 19200
Data/Parity/Stop bits
0: 8O1 / 1: 8E1 / 2: 8N1 / 3: 8N2
Modbus node ID
1~255
°C / °F
0: °C / 1: °F
Type of room controller
0: E type / 1: B type / 2: C type
Deadband for Cooling/Heating valve control
°C: 0~100 (0~10.0°C) / °F: 0~180 (0~18.0°F)
Not used
Stage differential
°C: 1~10 (0.1~1.0°C) / °F: 1~18 (0.1~1.8°F)
Low limit for temperature set-point
°C: 0~500 (0~50.0°C) / °F: 320~1220 (32.0~122.0°F)
High limit for temperature set-point
°C: 0~500 (0~50.0°C) / °F: 320~1220 (32.0~122.0°F)
PROTECT contact definition
0: N.O. / 1: N.C
Offset for built-in temperature sensor
°C: -90~90 (-9.0~9.0°C) / °F: -170~170 (-17.0~17.0°F)
0: Built-in / 1: Remote / 2: Built-in + Remote
Sensor
(average)
Proportional band for fan control
°C: 0~100 (0~10.0°C) / °F: 0~180 (0~18.0°F)
Not used
Lowest fan speed used for fan auto mode
0: Stop / 1: Low speed
Display present value of temperature or set-point
0: Display PV / 1: Display SP
for normal displaying
Present temperature to anti-freezing
°C: 0~150 (0~15.0°C) / °F: 320~1220 (32.0~122.0°F)
Anti-Freezing Protection
0: Off / 1: On
Not used
Sensor suffocating time
0~20 seconds
ECONOMY contact definition
0: N.O. / 1: N.C
Offset for external temperature sensor
°C: - 90~90 (-9.0~9.0°C) / °F: -170~170 (-17.0~17.0°F)
Economy (ECON) Cooling set-point
°C: 200~400 (20.0~40.0°C) / °F: 680~1040 (68.0~104.0°F)
Economy (ECON) Heating set-point
°C: 0~250 (00.0~25.0°C) / °F: 320~770 (32.0~77.0°F)
Fan off delay
0~600 s
Not used
Not used
Not used
Not used
Andivi – TRC-D – Technical Manual
03/06/16/23
37
03/06/16/23
38
Maximum fan speed
Output control
Note: Max. 3 outputs can be active at the same
time.
03/06/16/23
39
Inverted valve outputs
03/06/16/23
40
Fan control
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06/16/23
03/06
41
42
43
44
45
46
47
48
49
Fan enable in Cooling mode
Fan enable in Heating mode
Not used
Not used
Minimum time previous fan stage upward
Integral time (I-part) PI regulator for fan control
Protect mode ON delay time via digital input
Fan ON delay time in AUTO mode
Return to factory defaults
17
08/14, fw. ver. V1.2, V1.3
0: Off / 1: Stage I / 2: Stage II / 3: Stage III
Bit value:
0: Output controlled with internal r. controller
1: Output directly controlled via Modbus
communication
Bit definition:
Bit 0: DO1 - output Cooling valve
Bit 1: DO2 - output Heating valve
Bit 2: DO3 - output Fan Stage I
Bit 3: DO4 - output Fan Stage II
Bit 4: DO5 - output Fan Stage III
Bit 5 - bit7: Not used
Bit value:
0: Normal output N.O.
1: Inverted output N.C.
Bit definition:
Bit 0: DO1 - output Cooling valve
Bit 1: DO2 - output Heating valve
Bit 2 - bit7: Not used
0: In fan Manual mode fan is active also in case
of inactive Cooling/Heating valve / 1: Fan can be
active only in case of active Cooling/Heating valve
0: Disabled / 1: Enabled
0: Disabled / 1: Enabled
0~9990 sec.
0~9990 sec.
0~600 sec.
0~9990 sec.
1: Reset to factory defaults
Andivi – TRC-D – Technical Manual
Read input register (function code 04)
Function
code
Register
address
04
1
Current temperature
04
2
Fan speed
04
04
04
04
04
04
04
3
4
5
6
7
8
9
Cooling controller
Heating controller
Cooling valve output
Heating valve output
Temperature of built-in sensor
Temperature of external sensor
Software version
Description
Definition
200~1000 (-20.0~100.0°C)
0: Off / 1: Stage I /
2: Stage II / 3: Stage III
0: Not active / 100: Active
0: Not active / 100: Active
0: Not active / 100: Active
0: Not active / 100: Active
-200~1000 (-20.0~100.0°C)
-200~1000 (-20.0~100.0°C)
10H~FFH (V1.0~VF.F)
NOTICE:
If a value of a register is changed on the room controller (with buttons), a next write command to “this value” will be ignored,
and the room controller will not reply back anything. Those registers are:
1. Modbus Function 05,15 register address 01.
2. Modbus Function 06,16,23 register address 01~48.
For example, if users re-set the set-point value with buttons, a next Modbus command Fun.06/16/23 reg. address 01 from DDC/
BMS will be ignored and the room controller will not reply back any to DDC/BMS sent. (Note: While a value of a register is changing on the room controller (with buttons), any write command to “this value” will be ignored, but the room controller will reply
back the same data which DDC/BMS sent.)
This special strategy is integrated because registers must be changeable on both sites (master and slave).
18
08/14, fw. ver. V1.2, V1.3
Andivi – TRC-D – Technical Manual
Attention!
In the event of an incorrect connection of the room controller or a short
circuit in the installation and actuators, irreparable damage to the room
controller can occur. Therefore, pay special attention during the installation
and follow the instructions carefully!
EU DECLARATION OF CONFORMITY
We, Andivi, declare that this device is in compliance with the essential
requirements and other relevant provisions of Directive 2004/108/EC.
SAFETY WARNINGS
This device must be installed according to the applicable norms.
This device is for indoor use only.
Do not attempt to repair the device yourself; an after-sales service is
available. Any changes or modifications to this unit not expressly approved
by the party responsible for compliance could void the user’s authority to
operate the equipment.
IMPORTANT INFORMATION ABOUT YOUR RIGHTS AND OBLIGATIONS, AS
WELL AS LIMITATIONS AND EXCLUSIONS THAT MAY APPLY TO YOU,
YOUR RIGHTS AND THIS LIMITED WARRANTY
This Limited Warranty gives you specific legal rights. You may also have
other legal rights that vary by state, province or jurisdiction. The disclaimers,
exclusions, and limitations of liability under this Limited Warranty will not
apply to the extent prohibited by applicable law. For a full description of
your legal rights you should refer to the laws applicable in your jurisdiction
and you may wish to contact a relevant consumer advisory service.
WHAT THIS LIMITED WARRANTY COVERS; PERIOD OF COVERAGE
Andivi d.o.o., Zagrebska cesta 102, 2000 Maribor, Slovenia (“Andivi”)
warrants to the owner of the enclosed product that the product contained in
this box (“Product”) will be free from defects in materials and workmanship
for a period of two (2) years [one (1) year for Factory Refurbished Products]
from the date of delivery following the original retail purchase (the
“Warranty Period”). If the Product fails to conform to this Limited Warranty
during the Warranty Period, Andivi will, at its sole discretion, either (a)
repair or replace any defective Product or component; or (b) accept the
return of the Product and refund the money actually paid by the original
purchaser for the Product. Repair or replacement may be made with a new
or refurbished Product or components, at Andivi’s sole discretion.
If the Product or a component incorporated within it is no longer available,
Andivi may replace the Product with a similar product of similar function, at
Andivi’s sole discretion. This is your sole and exclusive remedy for breach of
this Limited Warranty. Any Product that has either been repaired or replaced
under this Limited Warranty will be covered by the terms of this Limited
Warranty for the longer of ninety (90) days from the date of delivery or the
remaining Warranty Period. This Limited Warranty is transferable from the
original purchaser to subsequent owners, but the Warranty Period will not
be extended in duration or expanded in coverage for any such transfer.
TOTAL SATISFACTION RETURN POLICY
If you are the original purchaser of the Product and you are not satisfied
with this Product for any reason, you may return it in its original condition
within thirty (30) days of the original purchase and receive a full refund.
WARRANTY CONDITIONS; HOW TO GET SERVICE IF YOU WANT TO CLAIM
UNDER THIS LIMITED WARRANTY
Before being able to claim under this Limited Warranty, the owner of the
Product must (a) notify Andivi of the intention to claim by sending and e-mail
to [email protected]<mailto:[email protected]> during the Warranty Period
and providing a description of the alleged failure, and (b) comply with Andivi’s
return shipping instructions, and (c) ship the Product at owner’s cost (except
where prohibited by applicable law) to Andivi for repair or replacement.
Andivi will have no warranty obligations with respect to a returned Product if
it determines, in its reasonable discretion after examination of the returned
Product, that the Product is an Ineligible Product (defined below). Andivi
will bear all costs of return shipping to owner, except with respect to any
Ineligible Product, for which owner will bear all shipping costs.
19
08/14, fw. ver. V1.2, V1.3
WHAT THIS LIMITED WARRANTY DOES NOT COVER
This warranty does not cover the following (collectively “Ineligible
Products”): Products marked as “sample” or sold “as is”; or Products that
have been subject to: (a) modifications, alterations, tampering, or improper
maintenance or repairs; (b) handling, storage, installation, testing, or use
not in accordance with the Installation Guide or other instructions provided
by Andivi; (c) abuse or misuse of the Product; (d) breakdowns, fluctuations,
or interruptions in electric power or the telecommunications network;
or (e) Acts of God, including lightning, fire, flood, tornado, earthquake,
or hurricane. This warranty does not cover consumable parts, unless
damage is due to defects in materials or workmanship of the Product, or
software (even if packaged or sold with the Product). Andivi recommends
that you use only authorised service providers for maintenance or repair.
Unauthorised use of the Product or software can impair the Product’s
performance and may invalidate this Limited Warranty.
Andivi does not warrant that operation of the Product will be error-free
or uninterrupted or that the Product will in every case process all data
correctly.
DISCLAIMER OF WARRANTIES
Except as stated above in this limited warranty, and to the maximum extent
permitted by applicable law, Andivi disclaims all express, implied, and
statutory warranties and conditions with respect to the Product, including
the implied warranties of merchantability, fitness for a particular purpose.
To the maximum extent permitted by applicable law, Andivi also limits the
duration of any implied warranties or conditions to the duration of this
limited warranty.
LIMITATION OF DAMAGES
In addition to the above warranty disclaimers, in no event will Andivi be
liable for any consequential, incidental, exemplary, or special damages,
including any damages for lost data or lost profits, arising from or relating
to this limited warranty or the Product, and Andivi’s total cumulative
liability arising from or related to this limited warranty or the Product
will not exceed the amount actually paid for the Product by the original
purchaser.
LIMITATION OF LIABILITY
Andivi disclaims all liability of any kind of Andivi’s distributors. The type of
Product peripherals that may be connected to your Product may change
from time to time. The services may be used to control your heating,
ventilation, and AC system or Product peripherals via the Product. Without
limiting the generality of the disclaimers above, all Product information is
provided for your convenience, “as is”, and “as available”. Andivi does not
represent, warrant, or guarantee that Product information will be available,
accurate, or reliable or that Product information or use of the services or
Product will decrease the energy consumption of your building. You are
solely responsible for all energy bills incurred by your home. You use all
Product information, the services, and the Product at your own discretion
and risk. You will be solely responsible for (and Andivi disclaims) any and
all loss, liability, or damages, including to your HVAC system, plumbing,
building, Product, Product peripherals, and all other items in your building,
resulting from your use of the Product information, services, or Product.
Product information provided by the services is not intended as a substitute
for direct means of obtaining the information. For example, a temperature
reading in the Product information provided by the services is not intended
as a substitute for reading the temperature as directly displayed by the
Product.
VARIATIONS THAT MIGHT APPLY TO THIS LIMITED WARRANTY
Some jurisdictions do not allow limitations on how long an implied
warranty lasts or exclusions/limitations on incidental or consequential
damages, so some of the limitations set out above may not apply to you.
Copyright Andivi © 2014 All rights reserved. Reproduction and distribution
prohibited without written authorization from Andivi.