ZS-112148 A (Feeder Terminal Unit) OPERATION MANUAL

ZS-112148 A
(Feeder Terminal Unit)
OPERATION MANUAL
0
Elemote FRTU
1
Elemote FRTU
‫ﻣﻌﺮﻓﻲ ﺷﺮﻛﺖ ﺯﺭﻳﻦ ﺳﺎﻣﺎﻧﻪ ﺷﺮﻕ‬
‫ﺷﺮﻛﺖ ﺯﺭﻳﻦ ﺳﺎﻣﺎﻧﻪ ﺷﺮﻕ ﺑﻪ ﻋﻨﻮﺍﻥ ﺍﻭﻟﻴﻦ ﻃﺮﺍﺡ ﻭ ﺳﺎﺯﻧﺪﻩ ﺗﺠﻬﻴﺰﺍﺕ ﺍﻧﺘﻘﺎﻝ ﺍﻃﻼﻋـﺎﺕ ﻭ ﻛﻨﺘـﺮﻝ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ ﺩﺭ ﺻـﻨﻌﺖ‬
‫ﻓﻌﺎﻟﻴﺖ ﺭﺳﻤﻲ ﺧﻮﺩ ﺭﺍ ﺍﺯ ﺳﺎﻝ ‪ 1374‬ﺑﺎ ﻧﺎﻡ ﺷﺮﻛﺖ ﺗﻌﺎﻭﻧﻲ ﻧﻴﻚ ﺗﻜﻨﻴﻚ ﺁﻏﺎﺯ ﻧﻤﻮﺩﻩ ﻭ ﺩﺭ ﺳﺎﻝ ‪ 1386‬ﺑﻪ ﺩﻟﻴـﻞ ﺳﻴﺎﺳـﺖ‪-‬‬
‫ﻫﺎﻱ ﻛﺎﺭﻱ ﺧﻮﺩ‪ ،‬ﺑﻪ ﻧﺎﻡ ﺷﺮﻛﺖ ﺯﺭﻳﻦ ﺳﺎﻣﺎﻧﻪ ﺷﺮﻕ ﻓﻌﺎﻟﻴﺖ ﺧﻮﺩ ﺭﺍ ﺍﺩﺍﻣﻪ ﺩﺍﺩﻩ ﺍﺳﺖ‪ .‬ﺩﺭ ﺣﺎﻝ ﺣﺎﺿﺮ ﺍﻳﻦ ﺷـﺮﻛﺖ ﻋـﻼﻭﻩ ﺑـﺮ‬
‫ﺍﺟﺮﺍﻱ ﺑﻴﺸﺘﺮﻳﻦ ﺗﻌﺪﺍﺩ ﻧﻮﺩﻫﺎ ﺩﺭ ﺻﻨﻌﺖ ﺁﺏ ﺩﺭ ﺳﺮﺍﺳﺮ ﻛﺸﻮﺭ‪ ،‬ﻓﻌﺎﻟﻴﺖﻫﺎﻱ ﺧﻮﺩ ﺭﺍ ﺩﺭ ﺻﻨﻌﺖ ﺑﺮﻕ ﻭ ﺍﺗﻮﻣﺎﺳﻴﻮﻥ ﺷﺒﻜﻪﻫﺎﻱ‬
‫ﺗﻮﺯﻳﻊ ﻧﻴﺰ ﮔﺴﺘﺮﺵ ﺩﺍﺩﻩ ﺍﺳﺖ‪.‬‬
‫ﺷﺮﻛﺖ ﺯﺭﻳﻦ ﺳﺎﻣﺎﻧﻪ ﺷﺮﻕ ﺩﺭ ﺭﺍﺳﺘﺎﻱ ﺑﻮﻣﻲ ﺳﺎﺯﻱ‪ ،‬ﻛﻠﻴﻪ ﺗﺠﻬﻴﺰﺍﺕ ﺳﺨﺖ ﺍﻓﺰﺍﺭﻱ ﻭ ﻧﺮﻡ ﺍﻓﺰﺍﺭﻫﺎﻱ ﻣﻮﺭﺩ ﻧﻴـﺎﺯﺧﻮﺩ ﺭﺍ ﺩﺭ‬
‫ﺭﺍﺳﺘﺎﻱ ﺍﺟﺮﺍﻱ ﭘﺮﻭژﻩ ﻫﺎﻱ ﺍﺗﻮﻣﺎﺳﻴﻮﻥ ﺻﻨﻌﺘﻲ ﻭ ﺍﺗﻮﻣﺎﺳﻴﻮﻥ ﺗﻮﺯﻳﻊ ﺷﺎﻣﻞ ﻃﺮﺍﺣﻲ‪ ،‬ﺳـﺎﺧﺖ‪ ،‬ﻣﻮﻧﺘـﺎژ‪ ،‬ﺑﺮﻧﺎﻣـﻪ ﻧﻮﻳﺴـﻲ ﺑﻄـﻮﺭ‬
‫ﻛﺎﻣﻞ ﺩﺍﺧﻞ ﺷﺮﻛﺖ ﻭ ﺗﻮﺳﻂ ﻣﺘﺨﺼﺼﻴﻦ ﻣﺠﺮﺏ ﺧﻮﺩ ﺍﻧﺠﺎﻡ ﻣﻲ ﺩﻫﺪ‪.‬‬
‫‪Elemote FRTU‬‬
‫‪2‬‬
‫ﻗﺎﺑﻠﻴﺖ ﻫﺎ ‪:‬‬
‫‪ ZS-112148A‬ﺑﺮﺍﻱ ﺍﺳﺘﻔﺎﺩﻩ ﺩﺭ ﺍﺗﻮﻣﺎﺳﻴﻮﻥ ﺷﺒﻜﻪ ﻫﺎﻱ ﺗﻮﺯﻳﻊ ﻭ ﻫﻤﻴﻨﻄﻮﺭ ﺑﺮﺍﻱ ﻛﺎﻫﺶ ﺯﻣﺎﻥ ﺧﺎﻣﻮﺷﻲ ﺩﺭ‬
‫ﺷﺒﻜﻪ ﻫﺎﻱ ﺩﺍﺭﺍﻱ ﺧﻄﺎ‪ ،‬ﻃﺮﺍﺣﻲ ﻭ ﺳﺎﺧﺘﻪ ﺷﺪﻩ ﺍﺳﺖ‪ .‬ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ ﺩﺍﺭﺍﻱ ﺗﻮﺍﺑﻌﻲ ﻗﺪﺭﺗﻤﻨﺪ ﻣﻲ ﺑﺎﺷﺪ ﻛﻪ ﻣﻮﺭﺩ ﻧﻴﺎﺯ‬
‫ﺍﺗﻮﻣﺎﺳﻴﻮﻥ ﺷﺒﻜﻪ ﻫﺎﻱ ﺗﻮﺯﻳﻊ ﺍﺳﺖ‪ .‬ﺑﻪ ﻋﻨﻮﺍﻥ ﻣﺜﺎﻝ ﻣﻲ ﺗﻮﺍﻥ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺗﻤﺎﻣﻲ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺍﻟﻜﺘﺮﻳﻜﻲ ﻭ ﺍﺭﺗﺒﺎﻃﻲ ﻭ‬
‫ﻫﻤﭽﻨﻴﻦ ﻛﻠﻴﻪ ﻣﻘﺎﺩﻳﺮ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﻓﻮﻕ ﺭﺍ ﺑﻪ ﻣﻨﻈﻮﺭ ﻛﻨﺘﺮﻝ ﺳﻮﺋﻴﭻ ﻫﺎ ﺑﻪ ﺻﻮﺭﺕ ﻛﻨﺘﺮﻝ ﻣﺤﻠﻲ ﻭ ﻛﻨﺘﺮﻝ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ‬
‫ﺍﻧﺠﺎﻡ ﺩﺍﺩ‪.‬‬
‫ﺍﺯ ﺩﻳﮕﺮ ﻗﺎﺑﻠﻴﺖ ﻫﺎﻱ ﺍﻳﻦ ﺗﺠﻬﻴﺰ ﺍﺗﺼﺎﻝ ﺑﻪ ﺍﻧﻮﺍﻉ ﺑﺴﺘﺮﻫﺎﻱ ﺍﺭﺗﺒﺎﻃﻲ ﻭ ﻣﺨﺎﺑﺮﺍﺗﻲ ﻣﻲ ﺑﺎﺷﺪ‪ ZS-112148A .‬ﺩﺍﺭﺍﻱ‬
‫ﺍﻣﻜﺎﻥ ﺛﺒﺖ ﻭﻗﺎﻳﻊ ﻭ ﺭﺧﺪﺍﺩﻫﺎ ﻧﻴﺰ ﻣﻲ ﺑﺎﺷﺪ ﻛﻪ ﺑﺮﺍﻱ ﺗﺤﻠﻴﻞ ﺷﺒﻜﻪ ﻭ ﺑﺎﺭ ﻣﻮﺭﺩ ﺍﺳﺘﻔﺎﺩﻩ ﻗﺮﺍﺭ ﻣﻲ ﮔﻴﺮﺩ‪ .‬ﺗﻤﺎﻣﻲ ﺍﻃﻼﻋﺎﺕ‬
‫ﻣﺮﺑﻮﻁ ﺑﻪ ﺧﻄﺎﻫﺎ ﻭ ﺭﺧﺪﺍﺩﻫﺎ ﺑﻪ ﺻﻮﺭﺕ ﻓﺮﻣﺖ ‪ Text‬ﻣﻲ ﺗﻮﺍﻧﻨﺪ ﺑﺮ ﺭﻭﻱ ﺻﻔﺤﻪ ﻧﻤﺎﻳﺶ ﻧﺸﺎﻥ ﺩﺍﺩﻩ ﺷﻮﻧﺪ ﻭ ﻳﺎ ﺑﺎ ﺍﺳﺘﻔﺎﺩﻩ‬
‫ﺍﺯ ﻧﺮﻡ ﺍﻓﺰﺍﺭﻫﺎﻱ ﺟﺎﻧﺒﻲ ﺑﻪ ﺻﻮﺭﺕ ﮔﺮﺍﻓﻴﻜﻲ ﺑﻪ ﻧﻤﺎﻳﺶ ﺩﺭ ﺁﻳﻨﺪ‪.‬‬
‫ﻛﺎﺭﺑﺮ ﻣﻲ ﺗﻮﺍﻧﺪ ﻣﺘﻨﺎﺳﺐ ﺑﺎ ﺷﺮﺍﻳﻂ ﻣﺨﺘﻠﻒ ﺑﻬﺮﻩ ﺑﺮﺩﺍﺭﻱ‪ ،‬ﺗﻨﻈﻴﻤﺎﺕ ‪ ZS-112148A‬ﺭﺍ ﺑﻪ ﺻﻮﺭﺕ ﭘﻴﺶ ﻓﺮﺽ ﺗﻨﻈﻴﻢ‬
‫ﻧﻤﺎﻳﺪ‪ .‬ﻫﻤﭽﻨﻴﻦ ﺑﺎ ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ﻛﻠﻴﺪﻫﺎﻱ ‪ Remote/ Local‬ﺍﻳﻦ ﺍﻣﻜﺎﻥ ﺭﺍ ﺩﺍﺭﺩ ﻛﻪ ﺳﻴﺴﺘﻢ ﺭﺍ ﺍﺯ ﺣﺎﻟﺖ ﺭﺍﻩ ﺩﻭﺭ ﺧﺎﺭﺝ‬
‫ﻛﺮﺩﻩ ﻭ ﺑﻪ ﺣﺎﻟﺖ ﻣﺤﻠﻲ ﻭ ﻳﺎ ﺑﺎﻟﻌﻜﺲ ﺑﺒﺮﺩ‪.‬‬
‫‪Elemote FRTU‬‬
‫‪3‬‬
‫) ‪( Phase & Ground Fault Detection‬‬
‫‪ ZS-112148A‬ﺍﺳﺎﺳﺎ ﺑﺮﺍﻱ ﺍﻳﻦ ﻃﺮﺍﺣﻲ ﺷﺪﻩ ﺍﺳﺖ ﻛﻪ ﺧﻄﺎﻱ ﻣﺮﺑﻮﻁ ﺑﻪ ﺳﻪ ﻓﺎﺯ ﻭ ﻫﻤﭽﻨﻴﻦ ﺍﺗﺼﺎﻝ ﺯﻣﻴﻦ ﺭﺍ‬
‫ﺁﺷﻜﺎﺭ ﻧﻤﺎﻳﺪ‪ .‬ﺟﺮﻳﺎﻥ ﻫﺎ ﻭ ﺍﺗﺼﺎﻝ ﺯﻣﻴﻦ ﺩﺍﺭﺍﻱ ﻳﻚ ﻣﻘﺪﺍﺭ ﭘﻴﺶ ﺗﻨﻈﻴﻢ ﻣﻲ ﺑﺎﺷﻨﺪ ﻭ ﭼﻨﺎﻧﭽﻪ ﻫﺮﻳﻚ ﺍﺯ ﺟﺮﻳﺎﻥ ﻫﺎ ﺍﺯ‬
‫ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻤﻲ ﺁﻥ ﺑﻴﺸﺘﺮ ﺷﻮﺩ‪ ،‬ﻧﻤﺎﻳﺸﮕﺮ ﺧﻄﺎﻱ ﻣﺮﺑﻮﻃﻪ ﺭﻭﺷﻦ ﻣﻲ ﮔﺮﺩﺩ‪.‬‬
‫‪SEF (Selective Earth Fault) Protection‬‬
‫ﺩﺭ ﻳﻚ ﺷﺒﻜﻪ ﺑﺮﻕ ﺑﺪﻭﻥ ﺍﺗﺼﺎﻝ ﺑﻪ ﺯﻣﻴﻦ ﺑﻪ ﺩﻟﻴﻞ ﺟﺮﻳﺎﻥ ﻛﻢ ﺯﻣﻴﻦ ﺑﻪ ﺳﺨﺘﻲ ﻣﻲ ﺗﻮﺍﻥ ﺧﻄﺎﻫﺎﻱ ﺟﺮﻳﺎﻧﻲ ﺭﺍ‬
‫ﻣﺸﺨﺺ ﻛﺮﺩ‪ .‬ﺑﻨﺎﺑﺮﺍﻳﻦ ‪ ZS-112148A‬ﺑﻪ ﮔﻮﻧﻪ ﺍﻱ ﻃﺮﺍﺣﻲ ﺷﺪﻩ ﺍﺳﺖ ﻛﻪ ﺑﺘﻮﺍﻧﺪ ﺑﺎ ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ‪ CT‬ﻫﺎﻱ ﺧﺎﺭﺟﻲ ﺑﻪ‬
‫ﺁﺷﻜﺎﺭﺳﺎﺯﻱ ﺧﻄﺎ ﺩﺭ ﻓﺎﺯﻫﺎ ﺍﻗﺪﺍﻡ ﻧﻤﺎﻳﺪ‪ .‬ﺍﻳﻦ ﺗﺎﺑﻊ ﺑﻪ ﻃﻮﺭ ﺧﻼﺻﻪ ‪ SEF‬ﻧﺎﻣﻴﺪﻩ ﻣﻲ ﺷﻮﺩ‪ .‬ﺩﺭ ﻣﻮﺍﺭﺩﻱ ﻛﻪ ﺩﺭ ﻳﻚ ﺷﺒﻜﻪ‬
‫ﺯﻣﻴﻦ ﺷﺪﻩ‪ ،‬ﺧﻄﺎﻱ ﺍﺗﺼﺎﻝ ﺯﻣﻴﻦ ﺭﻭﻱ ﺩﻫﺪ‪ ،‬ﻣﻲ ﺗﻮﺍﻧﺪ ﺧﻄﺎ ﺭﺍ ﺗﺸﺨﻴﺺ ﺩﻫﺪ‪) .‬ﺿﻤﻨﺎ ﻗﺎﺑﻠﻴﺖ ﺗﺸﺨﻴﺺ ﺟﺮﻳﺎﻥ ﻟﺤﻈﻪ ﺍﻱ‬
‫ﺑﺎﻻﻱ ‪ 100‬ﻣﻴﻠﻲ ﺛﺎﻧﻴﻪ ﺭﺍ ﺩﺍﺭﺩ‪(.‬‬
‫‪Cold Load pick up‬‬
‫ﺩﺭ ﻳﻚ ﺷﺒﻜﻪ ﻫﺮﮔﺎﻩ ﺧﻂ ﻣﺠﺪﺩﺍ ﻓﻌﺎﻝ ﺷﻮﺩ ﻣﻤﻜﻦ ﺍﺳﺖ ﭘﺪﻳﺪﻩ ﺍﻱ ﺭﻭﻱ ﺩﻫﺪ ﻛﻪ ﺟﺮﻳﺎﻥ ﺑﻪ ﺻﻮﺭﺕ ﻟﺤﻈﻪ ﺍﻱ ﺍﺯ‬
‫ﻣﻘﺪﺍﺭ ﺑﺎﺭﮔﻴﺮﻱ ﺷﺪﻩ )‪ (Pick up‬ﺑﻴﺸﺘﺮ ﺷﺪﻩ ﻭ ﺳﭙﺲ ﺑﻪ ﻣﻘﺪﺍﺭ ﻋﺎﺩﻱ ﺧﻮﺩ ﻛﺎﻫﺶ ﻣﻲ ﻳﺎﺑﺪ ﻛﻪ ﺍﻳﻦ ﺟﺮﻳﺎﻥ ‪ ،‬ﺟﺮﻳﺎﻥ‬
‫ﺑﺎﺭ ﺳﺮﺩ ﻧﺎﻣﻴﺪﻩ ﻣﻲ ﺷﻮﺩ ‪ .‬ﻣﻘﺪﺍﺭ ﺑﺎﺭﮔﻴﺮﻱ ﺑﺎﺭ ﺳﺮﺩ )‪ (Cold Load Pick up‬ﺑﺮﺍﻱ ﺗﻔﻜﻴﻚ ﺍﻳﻦ ﭘﺪﻳﺪﻩ ﺍﺯ ﺟﺮﻳﺎﻥ ﻫﺎﻱ‬
‫ﺧﻄﺎﺳﺖ‪ .‬ﺑﻪ ﻋﻨﻮﺍﻥ ﻣﺜﺎﻝ ﺑﺪﻭﻥ ﺗﻐﻴﻴﺮ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺗﻨﻈﻴﻤﻲ‪ ،‬ﺳﻄﺢ ‪ Pickup‬ﺩﺭ ﺯﻣﺎﻥ ﻭﻗﻮﻉ ﺟﺮﻳﺎﻥ ﺑﺎﺭ ﺳﺮﺩ ﺑﻪ ﻃﻮﺭ‬
‫ﺍﺗﻮﻣﺎﺕ ﺗﻐﻴﻴﺮ ﻛﺮﺩﻩ ﻭ ﺑﻌﺪ ﺍﺯ ﮔﺬﺷﺖ ﺯﻣﺎﻥ‪ ،‬ﺟﺮﻳﺎﻥ ﺳﺮﺩ ﻛﻪ ﻗﺎﺑﻞ ﺗﻨﻈﻴﻢ ﺍﺳﺖ ﺑﻪ ﺳﻄﺢ ﺑﺎﺭ ﮔﻴﺮﻱ ﺍﻭﻟﻴﻪ ﺑﺮ ﻣﻲ ﮔﺮﺩﺩ‪.‬‬
‫ﺍﻳﻦ ﺗﻨﻈﻴﻤﺎﺕ ﺑﺮﺍﻱ ﻓﺎﺯﻫﺎ ﻭ ﺟﺮﻳﺎﻥ ﺯﻣﻴﻦ ﻣﻲ ﺑﺎﺷﺪ‪ .‬ﻣﻘﺪﺍﺭ ﺻﻔﺮ ﺑﺮﺍﻱ ‪ Cold Load Multier‬ﺑﺪﻳﻦ ﻣﻌﻨﺎﺳﺖ ﻛﻪ‬
‫‪ Cold Load Pickup‬ﻏﻴﺮﻓﻌﺎﻝ ﺍﺳﺖ ‪.‬‬
‫‪Elemote FRTU‬‬
‫‪4‬‬
‫ﻭﻳﮋﮔﻲ ﻫﺎ ‪:‬‬
‫ﺗﺸﺨﻴﺺ ﺧﻄﺎﻱ ﻓﺎﺯ ‪ ،‬ﺧﻄﺎﻱ ﺯﻣﻴﻦ‬
‫ﺗﺸﺨﻴﺺ ﺧﻄﺎ‬
‫ﺗﺸﺨﻴﺺ ﺧﻄﺎﻱ ﺑﺎﺭﮔﻴﺮﻱ ﺍﻭﻟﻴﻪ ﻭ ﺟﺮﻳﺎﻥ ﻫﺎﻱ ﻫﺠﻮﻣﻲ ﺳﻮﺋﭽﻴﻨﮓ‬
‫ﺗﺸﺨﻴﺺ ﻭﻟﺘﺎژ ﺳﻤﺖ ﺑﺎﺭ ﻭ ﻣﻨﺒﻊ‬
‫ﺗﺸﺨﻴﺺ ﺳﻨﻜﺮﻭﻥ ﺑﻮﺩﻥ ﻭﻟﺘﺎژﻫﺎﻱ ﺑﺎﺭ ﻭ ﻣﻨﺒﻊ ﺩﺭ ﺣﺎﻟﺖ ﺭﻳﻨﮓ‬
‫ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ‬
‫ﻭﻟﺘﺎژ ﻣﻨﺒﻊ ﻭ ﺑﺎﺭ ﻭ ﺟﺮﻳﺎﻥ ﻫﺮ ﺳﻪ ﻓﺎﺯ‬
‫ﻓﺮﻛﺎﻧﺲ ‪ ،‬ﺿﺮﻳﺐ ﺗﻮﺍﻥ ﻭ ﺯﺍﻭﻳﻪ ﺑﻴﻦ ‪ Va‬ﻭ ‪Vs‬‬
‫ﻛﻨﺘﺮﻝ ﻭﺿﻌﻴﺖ )ﻣﺤﻠﻲ ‪ ،‬ﺭﺍﻩ ﺩﻭﺭ(‬
‫ﻛﻨﺘﺮﻝ‬
‫ﻛﻨﺘﺮﻝ ‪) LBS‬ﺑﺎﺯ ‪ ،‬ﺑﺴﺘﻪ(‬
‫ﻧﻤﺎﻳﺶ ﺧﻄﺎ ) ﺭﻳﺴﺖ ﺩﺳﺘﻲ ﻧﻤﺎﻳﺸﮕﺮ ﺧﻄﺎ (‪ ،‬ﺗﺴﺖ ﺑﺎﻃﺮﻱ‬
‫ﻭﺿﻌﻴﺖ ﻛﻠﻴﺪ )ﺑﺎﺯ ‪ ،‬ﺑﺴﺘﻪ(‬
‫ﻧﻤﺎﻳﺶ ﻭﺿﻌﻴﺖ‬
‫ﻣﻮﻗﻌﻴﺖ ﻛﻨﺘﺮﻝ )ﻣﺤﻠﻲ ‪ ،‬ﺭﺍﻩ ﺩﻭﺭ(‬
‫ﻧﻤﺎﻳﺶ ﺧﻄﺎ )‪(Ia/Ib/Ic/In‬‬
‫ﻗﻄﻊ ﺑﻮﺩﻥ ﺑﺮﻕ ﺗﻐﺬﻳﻪ ‪ ، AC‬ﺑﺎﺯ ﺑﻮﺩﻥ ﺩﺭﺏ ﺗﺎﺑﻠﻮ‬
‫‪Low Battery‬‬
‫ﺷﻤﺎﺭﻧﺪﻩ ﺩﻓﻌﺎﺕ ﺭﺍﻩ ﺍﻧﺪﺍﺯﻱ ﻣﺠﺪﺩ ‪RTU‬‬
‫ﺷﻤﺎﺭﻧﺪﻩ‬
‫ﺷﻤﺎﺭﻧﺪﻩ ﺩﻓﻌﺎﺕ ﺑﺎﺯ ﻭ ﺑﺴﺘﻪ ﺷﺪﻥ ﻛﻠﻴﺪ‬
‫ﭘﺮﻭﺗﻜﻞ ﺍﺭﺗﺒﺎﻃﻲ‬
‫ﺍﺳﻜﺎﺩﺍ ‪Modbus ،DNP3:‬‬
‫‪Elemote FRTU‬‬
‫ﺷﻤﺎﺭﻧﺪﻩ ﺗﻌﺪﺍﺩ ﺧﻄﺎ‬
‫ﺗﻨﻈﻴﻤﺎﺕ ‪Modbus :‬‬
‫‪5‬‬
‫‪ : Display .1‬ﻧﻤﺎﻳﺸﮕﺮ‬
‫‪ .2‬ﻧﻤﺎﻳﺶ ﻭﺿﻌﻴﺖ ﺩﺭﺏ ﺍﻳﺴﺘﮕﺎﻩ‬
‫‪ .3‬ﻧﻤﺎﻳﺶ ﻭﺿﻌﻴﺖ ﺩﺭﺏ ﺗﺎﺑﻠﻮ‬
‫‪ .4‬ﺩﺭﻳﺎﻓﺖ ﺍﻃﻼﻋﺎﺕ ﺍﺯ ﻣﺮﻛﺰ ﺍﺳﻜﺎﺩﺍ‪ ،‬ﺍﺭﺳﺎﻝ ﺍﻃﻼﻋﺎﺕ ﺑﻪ ﻣﺮﻛﺰ ﺍﺳﻜﺎﺩﺍ‬
‫‪ .5‬ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ‬
‫‪ .6‬ﭘﺎﻳﻴﻦ ﺑﻮﺩﻥ ﺩﻣﺎﻱ ﺭﻭﻏﻦ ﺗﺮﺍﻧﺲ‬
‫‪ .7‬ﻧﺸﺎﻥ ﺩﻫﻨﺪﻩ ﻭﺿﻌﻴﺖ ﺍﺭﺗﺒﺎﻁ ﺑﺎ ‪RTU‬‬
‫‪ .8‬ﭘﺎﻳﻴﻦ ﺑﻮﺩﻥ ﺳﻄﺢ ﺭﻭﻏﻦ ﺗﺮﺍﻧﺲ‬
‫‪ .9‬ﻧﻤﺎﻳﺶ ﭘﺎﻳﻴﻦ ﺑﻮﺩﻥ ﻓﺸﺎﺭ ﮔﺎﺯ‬
‫‪ .10‬ﭘﺎﻳﻴﻦ ﺑﻮﺩﻥ ﻭﻟﺘﺎژ ﺑﺎﻃﺮﻱ‬
‫‪ .11‬ﻧﻤﺎﻳﺶ ﺧﻄﺎﻱ ‪Different Phase‬‬
‫‪ .12‬ﻧﻤﺎﻳﺶ ﺧﻄﺎﻱ ‪Volt Indicator‬‬
‫‪ .13‬ﻧﻤﺎﻳﺶ ﺧﻄﺎﻱ ‪Fault Indicator‬‬
‫‪Elemote FRTU‬‬
‫‪6‬‬
‫‪ .14‬ﺷﺼﺘﻲ ﻛﻨﺘﺮﻝ ﻭﺿﻌﻴﺖ ﺗﺎﺑﻠﻮ ﺑﻪ ﺣﺎﻟﺖ ﻣﺤﻠﻲ ﻳﺎ ﺭﺍﻩ ﺩﻭﺭ‬
‫‪ .15‬ﻗﻄﻊ ﺑﻮﺩﻥ ﺗﻐﺬﻳﻪ ‪AC‬‬
‫‪ .16‬ﺷﺼﺘﻲ ﻣﻴﺎﻧﺒﺮ ﺟﻬﺖ ﻧﻤﺎﻳﺶ ﻭﻟﺘﺎژ ﻭ ﺟﺮﻳﺎﻥ‬
‫‪ : Enter .17‬ﺷﺼﺘﻲ ﺗﺎﻳﻴﺪ‬
‫‪ : Left/Right /UP/Down .18‬ﺷﺼﺘﻲ ﻫﺎﻱ ﺑﺎﻻ ‪ ،‬ﭘﺎﻳﻴﻦ ‪ ،‬ﭼﭗ ﻭ ﺭﺍﺳﺖ‬
‫‪ .19‬ﺷﺼﺘﻲ ﺭﻳﺴﺖ ﻛﺮﺩﻥ ﺧﻄﺎﻫﺎ ﺑﻪ ﺻﻮﺭﺕ ﺩﺳﺘﻲ‬
‫‪ : Back .20‬ﺷﺼﺘﻲ ﺑﺎﺯﮔﺸﺖ‬
‫‪ .21‬ﺷﺼﺘﻲ ﺭﻳﺴﺖ ﻛﺮﺩﻥ ﺧﻄﺎﻫﺎ ﺑﻪ ﺻﻮﺭﺕ ﺩﺳﺘﻲ‬
‫‪ .22‬ﻧﻤﺎﻳﺶ ﻭﺿﻌﻴﺖ ‪Earth‬‬
‫‪ .23‬ﺷﺼﺘﻲ ﻓﻌﺎﻝ ﻧﻤﻮﺩﻥ ﻓﺮﻣﺎﻥ ﺑﺎﺯ ﻛﻠﻴﺪ ﺑﻪ ﺻﻮﺭﺕ ﺩﺳﺘﻲ‬
‫‪ .24‬ﺷﺼﺘﻲ ﻓﻌﺎﻝ ﻧﻤﻮﺩﻥ ﻓﺮﻣﺎﻥ ﺑﺴﺘﻪ ﻛﻠﻴﺪ ﺑﻪ ﺻﻮﺭﺕ ﺩﺳﺘﻲ‬
‫‪ .25‬ﺷﺼﺘﻲ ﻏﻴﺮﻓﻌﺎﻝ ﻧﻤﻮﺩﻥ ﺗﻐﻴﻴﺮ ﻭﺿﻌﻴﺖ ﻛﻠﻴﺪ )ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ ﻭ ﻣﺤﻠﻲ(‬
‫‪ .26‬ﻧﻤﺎﻳﺶ ﻭﺿﻌﻴﺖ ﺧﺮﻭﺟﻲ ﻫﺎ )‪(Open , Close , Earth‬‬
‫‪Elemote FRTU‬‬
‫‪7‬‬
‫‪:LCD‬‬
‫ﮔﺮﺍﻓﻴﻜﻲ ‪ 64*128‬ﭘﻴﻜﺴﻞ‪ ،‬ﺩﺍﺭﺍﻱ ‪Backlight‬‬
‫ﺗﻨﻈﻴﻢ ﻭ ﭘﻴﻜﺮﻩ ﺑﻨﺪﻱ ﺳﻴﺴﺘﻢ ‪ ،‬ﻧﻤﺎﻳﺶ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ‬
‫‪: OK/UP/Down/Right/Left/Esc‬‬
‫ﻛﻠﻴﺪﻫﺎﻱ ﻓﻮﻕ ﺑﺮﺍﻱ ﻛﺎﺭ ﺑﺎ ﻧﻤﺎﻳﺸﮕﺮ ﻭ ﭘﻴﻜﺮﻩ ﺑﻨﺪﻱ ﺳﻴﺴﺘﻢ ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﺷﻮﺩ‪.‬‬
‫‪: Reset‬‬
‫ﺑﺮﺍﻱ ﺭﻳﺴﺖ ﻛﺮﺩﻥ ﻧﺸﺎﻥ ﺩﻫﻨﺪﻩ ﻫﺎﻱ ﺧﻄﺎ ﻭ ﺧﻄﺎﻱ ﺳﻴﺴﺘﻢ ﺑﻪ ﻛﺎﺭ ﻣﻲ ﺭﻭﺩ‪.‬‬
‫‪: Battery test‬‬
‫ﺍﻳﻦ ﻛﻠﻴﺪ ﺑﺮﺍﻱ ﺗﺴﺖ ﺑﺎﻃﺮﻱ ﻭ ﻣﺪﺍﺭ ﺷﺎﺭژ ﺁﻥ ﺑﻪ ﻛﺎﺭ ﻣﻲ ﺭﻭﺩ ‪ .‬ﺩﺭ ﺻﻮﺭﺕ ﻋﺎﺩﻱ ﺑﻮﺩﻥ ﻭﺿﻌﻴﺖ ﺑﺎﻃﺮﻱ ‪ LED‬ﻣﺮﺑﻮﻁ ﺑﻪ‬
‫ﺁﻥ ﺧﺎﻣﻮﺵ ﻭ ﺩﺭ ﻏﻴﺮ ﺍﻳﻨﺼﻮﺭﺕ ‪ LED‬ﺁﻥ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ‪ .‬ﺩﺭ ﺯﻣﺎﻥ ﺍﺗﺼﺎﻝ ﺑﺮﻕ ‪ AC‬ﻭﺭﻭﺩﻱ‪ ،‬ﺑﺎﻃﺮﻱ ﺑﻪ ﻃﻮﺭ ﺍﺗﻮﻣﺎﺕ‬
‫ﺗﺴﺖ ﻧﻤﻲ ﮔﺮﺩﺩ ﻭ ﺑﺮﺍﻱ ﺗﺴﺖ ﻣﻲ ﺑﺎﻳﺴﺖ ﺍﺯ ﺷﺼﺘﻲ ‪ BAT_Test‬ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﻮﺩ‪.‬‬
‫‪: Remote control‬‬
‫ﻭﺿﻌﻴﺖ ﻓﺮﻣﺎﻥ ﭘﺬﻳﺮﻱ ﻛﻨﺘﺮﻟﺮ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﻲ ﻛﻨﺪ‪ .‬ﺍﻳﻦ ﻛﻠﻴﺪ ﻓﻘﻂ ﺑﻪ ﺻﻮﺭﺕ ﻣﺤﻠﻲ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﺍﻣﺎ ﻣﺎﻧﻴﺘﻮﺭﻳﻨﮓ ﺁﻥ ﺍﺯ‬
‫ﺭﺍﻩ ﺩﻭﺭ ﻧﻴﺰ ﺍﻣﻜﺎﻥ ﭘﺬﻳﺮ ﺍﺳﺖ‪ .‬ﺍﻳﻦ ﺍﻣﺮ ﺑﺮﺍﻱ ﺣﻔﻆ ﺍﻣﻨﻴﺖ ﺑﻬﺮﻩ ﺑﺮﺩﺍﺭ ﻭ ﻳﺎ ﻛﺎﺭﺑﺮ ﭘﻴﺶ ﺑﻴﻨﻲ ﺷﺪﻩ ﺍﺳﺖ ‪.‬‬
‫ﺟﻬﺖ ﻛﺎﺭ ﺑﺎ ﻫﺮﻳﻚ ﺍﺯ ﺷﺼﺘﻲ ﻫﺎﻱ ‪ BAT_Test ، Close ، Open ، Reset‬ﻭﺿﻌﻴﺖ ﻛﻨﺘﺮﻝ ﺑﺎﻳﺪ ﺩﺭ ﺣﺎﻟﺖ ﻣﺤﻠﻲ‬
‫ﺑﺎﺷﺪ ‪.‬‬
‫‪:open/close‬‬
‫ﺍﻳﻦ ﻛﻠﻴﺪ ﻫﺎ ﺑﻪ ﻣﻨﻈﻮﺭ ﻓﺮﻣﺎﻥ ﻣﺤﻠﻲ ‪ open/close‬ﻛﻠﻴﺪ ﺑﻪ ﻛﺎﺭ ﻣﻲ ﺭﻭﺩ‪ .‬ﻗﺒﻞ ﺍﺯ ﺑﺎﺯ ﻭ ﻳﺎ ﺑﺴﺘﻦ ﻛﻠﻴﺪ ﺍﺑﺘﺪﺍ ﺑﻪ ﻭﺿﻌﻴﺖ‬
‫ﻣﺤﻠﻲ ﺁﻥ ﺑﺎﻳﺪ ﺗﻮﺟﻪ ﻛﺮﺩ ﺳﭙﺲ ﻓﺮﻣﺎﻥ ﺑﺎﺯ ﻭ ﺑﺴﺘﻪ ﺷﺪﻥ ﻛﻠﻴﺪ ﺭﺍ ﻓﺸﺎﺭ ﺩﻫﻴﺪ‪ .‬ﺑﺮﺍﻱ ﺗﻐﻴﻴﺮ ﻭﺿﻌﻴﺖ ﻣﺮﺍﺣﻞ ﻓﻮﻕ ﺗﻜﺮﺍﺭ‬
‫ﻣﻲ ﺷﻮﺩ‪.‬‬
‫‪Elemote FRTU‬‬
‫‪8‬‬
‫ﻣﺸﺨﺼﺎﺕ ﻓﻨﻲ‬
‫ﺁﺷﻜﺎﺭﺳﺎﺯﻱ ﺧﻄﺎ‬
‫ﺗﺸﺨﻴﺺ ﻗﻄﻊ ﻓﺎﺯ‬
‫ﺗﺴﺖ ﻫﻤﺰﻣﺎﻧﻲ‬
‫ﺳﻄﺢ ﺗﺸﺨﻴﺺ ﻭﺟﻮﺩ ﻭﻟﺘﺎژ ‪ ( 50 – 90) % :‬ﻭﻟﺘﺎژ ﻧﺎﻣﻲ‬
‫ﺳﻄﺢ ﺗﺸﺨﻴﺺ ﻗﻄﻊ ﻭﻟﺘﺎژ ‪ ( 35 – 70) % :‬ﻭﻟﺘﺎژ ﻧﺎﻣﻲ‬
‫ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮ ‪ 0/1 – 30 :‬ﺛﺎﻧﻴﻪ‬
‫ﺍﺧﺘﻼﻑ ﻓﺎﺯ ﺧﻄﺎﻱ ﺳﻨﻜﺮﻭﻥ ‪ 5 – 60 :‬ﺩﺭﺟﻪ‬
‫ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮ ‪ 1 – 30 :‬ﺛﺎﻧﻴﻪ‬
‫ﭘﻴﻜﺮﻩ ﺑﻨﺪﻱ ﺳﻴﺴﺘﻢ‬
‫ﻣﻘﺎﺩﻳﺮ ﻧﺎﻣﻲ‬
‫ﻭﺭﻭﺩﻱ‪ /‬ﺧﺮﻭﺟﻲ‬
‫ﻓﺮﻛﺎﻧﺲ ‪50 :‬‬
‫ﻭﻟﺘﺎژ ﻧﺎﻣﻲ ‪ 3/8 – 21 :‬ﻛﻴﻠﻮ ﻭﻟﺖ‬
‫ﻧﺴﺒﺖ ﺗﺮﺍﻧﺲ ﺟﺮﻳﺎﻥ ‪100/1 – 2000/1 :‬‬
‫ﺯﻣﺎﻥ ﺩﻳﺒﺎﻧﺲ ﻭﺭﻭﺩﻱ ﺩﻳﺠﻴﺘﺎﻝ ‪ 10 – 500 :‬ﺛﺎﻧﻴﻪ‬
‫ﻋﺮﺽ ﭘﺎﻟﺲ ﺧﺮﻭﺟﻲ ﺩﻳﺠﻴﺘﺎﻝ ‪ 10 – 2000 :‬ﻣﻴﻠﻲ ﺛﺎﻧﻴﻪ‬
‫ﻧﻤﺎﻳﺶ ﻭﺿﻌﻴﺖ ﻫﺎ‬
‫ﻭﺿﻌﻴﺖ ﻫﺎ‬
‫ﻛﻨﺘﺮﻝ‬
‫ﺑﺎﺯ ‪ /‬ﺑﺴﺘﻪ‬
‫ﻣﺤﻠﻲ ‪ /‬ﺭﺍﻩ ﺩﻭﺭ‬
‫ﻗﻔﻞ ﺩﺳﺘﻲ‬
‫ﻓﺸﺎﺭ ﭘﺎﻳﻴﻦ ﮔﺎﺯ‬
‫ﺑﺎﺯ ﺑﻮﺩﻥ ﺩﺭﺏ‬
‫ﺧﻄﺎﻱ ﻓﺎﺯ‬
‫ﺗﺨﻠﻴﻪ ﺑﺎﻃﺮﻱ‬
‫ﻗﻄﻊ ﺗﻐﺬﻳﻪ ‪ 220‬ﻭﻟﺖ‬
‫ﺧﻄﺎﻱ ﺳﻴﺴﺘﻢ ‪RTU‬‬
‫ﻭﺿﻌﻴﺖ ﺍﺭﺗﺒﺎﻁ‬
‫ﻣﺤﻠﻲ ‪ /‬ﺭﺍﻩ ﺩﻭﺭ‬
‫ﺗﻌﻴﻴﻦ ﻧﻮﻉ ﻛﻨﺘﺮﻝ‬
‫ﺭﻳﺴﺖ‬
‫ﺭﻳﺴﺖ ﻛﻠﻴﻪ ﺧﻄﺎﻫﺎ‬
‫ﺑﺎﺯ ﻭ ﺑﺴﺘﻪ‬
‫ﺗﺴﺖ ﺑﺎﻃﺮﻱ‬
‫‪Elemote FRTU‬‬
‫ﻓﺮﻣﺎﻥ ﺑﺎﺯ ﻳﺎ ﺑﺴﺘﻦ ﻛﻠﻴﺪ‬
‫ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺳﻄﺢ ﻭﻟﺘﺎژ ﺑﺎﻃﺮﻱ ﺩﺭ ﺣﺎﻟﺖ ﻗﻄﻊ ﻣﺪﺍﺭ ﺷﺎﺭژﺭ‬
‫‪9‬‬
‫ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ‬
‫ﺟﺮﻳﺎﻥ‬
‫ﻭﻟﺘﺎژ‬
‫ﺿﺮﻳﺐ ﺗﻮﺍﻥ‬
‫ﻛﺎﻧﺘﺮ‬
‫‪Elemote FRTU‬‬
‫ﻣﻘﺪﺍﺭ ﻭﺍﻗﻌﻲ ﺟﺮﻳﺎﻥ ‪ :‬ﺟﺮﻳﺎﻥ ﻓﺎﺯ ‪ 1‬ﻭ ‪ 2‬ﻭ‪3‬‬
‫ﺩﻗﺖ ‪ 1 :‬ﺁﻣﭙﺮ ﺑﻪ ﺍﺯﺍﻱ ‪FullScale‬‬
‫ﻣﺤﺪﻭﺩﻩ ﺟﺮﻳﺎﻥ ﻭﺭﻭﺩﻱ ‪ 6-1000 :‬ﺁﻣﭙﺮ‬
‫ﻣﻘﺪﺍﺭ ﻭﺍﻗﻌﻲ ﻭﻟﺘﺎژ ‪ :‬ﻭﻟﺘﺎژ ﻓﺎﺯﻫﺎﻱ ‪a,b,c,r,s,t‬‬
‫ﺩﻗﺖ ‪± 0/5% :‬‬
‫ﻓﺎﺯ ‪ ، A‬ﻓﺎﺯ‪ ، B‬ﻓﺎﺯ‪ C‬ﻭ ﻣﻴﺎﻧﮕﻴﻦ ﺳﻪ ﻓﺎﺯ‬
‫ﺗﻌﺪﺍﺩ ﺭﺍﻩ ﺍﻧﺪﺍﺯﻱ ﻣﺠﺪﺩ ‪CPU‬‬
‫ﺗﻌﺪﺍﺩ ﺑﺎﺯ ﺷﺪﻥ ﻛﻠﻴﺪ‬
‫ﺗﻌﺪﺍﺩ ﺧﻄﺎﻫﺎ‬
‫‪10‬‬
‫ﻣﺸﺨﺼﺎﺕ ﻋﻤﻮﻣﻲ‬
‫ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ ﻭﺭﻭﺩﻱ‬
‫ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ ‪FRTU‬‬
‫ﺑﺎﻃﺮﻱ‬
‫ﻭﺭﻭﺩﻱ ‪ ± 0/10% : AC‬ﻭ ‪ 220 ± 0/5%‬ﻭﻟﺖ ﺑﺎ ﻓﺮﻛﺎﻧﺲ ‪ 50‬ﻫﺮﺗﺰ‬
‫ﺧﺮﻭﺟﻲ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ‪ 25 :‬ﻭﻟﺖ ‪ 200 ، AC‬ﻭﻟﺖ ﺁﻣﭙﺮ‬
‫ﻭﻟﺘﺎژ ﻭﺭﻭﺩﻱ ‪ 30 :‬ﻭﻟﺖ ‪AC‬‬
‫ﻭﻟﺘﺎژ ﺧﺮﻭﺟﻲ ‪ 24 :‬ﻳﺎ ‪ 48‬ﻭﻟﺖ ‪DC‬‬
‫ﻭﻟﺘﺎژ ﺷﺎﺭژ ﺑﺎﻃﺮﻱ ‪ 27 :‬ﻳﺎ ‪ 55‬ﻭﻟﺖ‬
‫ﺧﺮﻭﺟﻲ ‪ 12 :‬ﻭﻟﺖ ‪DC‬‬
‫ﻇﺮﻓﻴﺖ ‪ 18 :‬ﺁﻣﭙﺮ ﺑﺮ ﺳﺎﻋﺖ ﺩﺭ ﺩﻣﺎﻱ ‪ 25‬ﺩﺭﺟﻪ ﺳﺎﻧﺘﻴﮕﺮﺍﺩ‬
‫ﻋﻤﺮ ﺑﺎﻃﺮﻱ ‪ 24 :‬ﺳﺎﻋﺖ ﺑﺪﻭﻥ ﺗﻐﺬﻳﻪ ‪AC‬‬
‫ﺳﻮﺋﻴﭻ ﻛﻠﻴﺪ ‪ 100 :‬ﺑﺎﺭ ﺑﺪﻭﻥ ﺗﻐﺬﻳﻪ ‪AC‬‬
‫ﺯﻣﺎﻥ ﺷﺎﺭژ ﺷﺪﻥ ‪ 10 :‬ﺳﺎﻋﺖ‬
‫ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ ‪RTU‬‬
‫‪ 24‬ﻭﻟﺖ ‪DC‬‬
‫‪Plugin‬‬
‫ﺗﻮﺍﻥ ﻣﺼﺮﻓﻲ ‪ 50 :‬ﻭﺍﺕ‬
‫ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ ﻣﻮﺩﻡ‬
‫ﻫﻴﺘﺮ‬
‫ﺩﻣﺎﻱ ﻛﺎﺭ‬
‫ﺭﻃﻮﺑﺖ‬
‫ﺍﺑﻌﺎﺩ‬
‫ﻭﺯﻥ‬
‫‪Elemote FRTU‬‬
‫‪ 13/8 – 24‬ﻭﻟﺖ ‪DC‬‬
‫ﺳﻮﻛﺖ ‪ 48‬ﭘﻴﻦ‬
‫ﺳﻮﻛﺖ ‪ 32‬ﭘﻴﻦ‬
‫‪ -30‬ﺗﺎ ‪ 60‬ﺩﺭﺟﻪ ﺳﺎﻧﺘﻴﮕﺮﺍﺩ‬
‫‪≤95%RH‬‬
‫ﺗﺎﺑﻠﻮ ‪) 70*65*27 cm2 :‬ﺍﺭﺗﻔﺎﻉ*ﻋﺮﺽ*ﻃﻮﻝ(‬
‫‪) 27*16*14 cm2: PLC‬ﺍﺭﺗﻔﺎﻉ*ﻋﺮﺽ*ﻃﻮﻝ(‬
‫ﺗﺎﺑﻠﻮ ‪ 40 :‬ﻛﻴﻠﻮﮔﺮﻡ‬
‫‪ 2/7 : PLC‬ﻛﻴﻠﻮﮔﺮﻡ‬
‫‪11‬‬
‫ﭘﻮﺭﺕ ﻫﺎﻱ ﺍﺭﺗﺒﺎﻃﻲ‪:‬‬
‫ﭘﻮﺭﺕ)‪RS-232 (1‬‬
‫ﭘﻮﺭﺕ)‪RS-232 (2‬‬
‫ﭘﻮﺭﺕ)‪ETHERNET (3‬‬
‫ﺭﺍﺑﻂ ﺳﺮﻳﺎﻝ ﺍﺭﺗﺒﺎﻃﻲ ﺑﺎ ﻣﺮﻛﺰ ﺍﺳﻜﺎﺩﺍ‬
‫ﭘﺮﻭﺗﻜﻞ ‪DNP3 :‬‬
‫ﺳﺮﻋﺖ ﺍﻧﺘﻘﺎﻝ ﺩﺍﺩﻩ ‪1200 – 19200 Bit/S:‬‬
‫ﺁﺩﺭﺱ ‪0 – 65534 : Master‬‬
‫ﺁﺩﺭﺱ ‪0 – 65534 : Slave‬‬
‫ﻧﻮﻉ ﻛﺎﻧﻜﺘﻮﺭ ‪ :‬ﻛﺎﻧﻜﺘﻮﺭ ﻣﺎﺩﮔﻲ ‪DB9‬‬
‫ﺭﺍﺑﻂ ﺳﺮﻳﺎﻝ ﺟﻬﺖ ﺗﻨﻈﻴﻤﺎﺕ ﻭ ﭘﻴﻜﺮﻩ ﺑﻨﺪﻱ ﺳﻴﺴﺘﻢ ﻭ ﺗﺨﻠﻴﻪ ﺩﻳﺘﺎ‬
‫ﺫﺧﻴﺮﻩ ﺷﺪﻩ‬
‫ﭘﺮﻭﺗﻜﻞ ‪Modbus :‬‬
‫ﺳﺮﻋﺖ ﺍﻧﺘﻘﺎﻝ ﺩﺍﺩﻩ ‪1200 – 19200 Bit/S:‬‬
‫ﻧﻮﻉ ﻛﺎﻧﻜﺘﻮﺭ ‪ :‬ﻛﺎﻧﻜﺘﻮﺭ ﻣﺎﺩﮔﻲ ‪DB9‬‬
‫ﺭﺍﺑﻂ ﺷﺒﻜﻪ ﺍﺭﺗﺒﺎﻃﻲ ﺑﺎ ﻣﺮﻛﺰ ﺍﺳﻜﺎﺩﺍ‬
‫ﭘﺮﻭﺗﻜﻞ ‪Modbus Over TCP/IP ، DNP3 Over TCP/IP :‬‬
‫ﺳﺮﻋﺖ ﺍﻧﺘﻘﺎﻝ ﺩﺍﺩﻩ ‪10 – 100 Mb/S:‬‬
‫ﻧﻮﻉ ﻛﺎﻧﻜﺘﻮﺭ ‪ :‬ﻛﺎﻧﻜﺘﻮﺭ ‪RJ45‬‬
‫‪Elemote FRTU‬‬
‫‪12‬‬
13
Elemote FRTU
14
Elemote FRTU
15
Elemote FRTU
16
Elemote FRTU
17
Elemote FRTU
18
Elemote FRTU
‫ﺁﺩﺭﺱ ‪:‬‬
‫ﻣﺸﻬﺪ‪ .‬ﺧﻴﺎﺑﺎﻥ ﺁﺑﻜﻮﻩ‪ .‬ﺑﻌﺪ ﺍﺯ ﺗﻘﺎﻃﻊ ﻛﻼﻫﺪﻭﺯ‪ .‬ﺭﻭﺑﺮﻭﻱ ﺑﺎﻧﻚ ﺻﺎﺩﺭﺍﺕ‪ .‬ﭘﻼﻙ ‪ .440‬ﺷﺮﻛﺖ ﻣﻬﻨﺪﺳﻲ ﺯﺭﻳﻦ ﺳﺎﻣﺎﻧﻪ ﺷﺮﻕ‬
‫ﺗﻠﻔﻦ‪:‬‬
‫‪ 5 – (0511)8422323‬ﺧﻂ‬
‫ﭘﺴﺖ ﺍﻟﻜﺘﺮﻭﻧﻴﻜﻲ ‪:‬‬
‫‪Elemote FRTU‬‬
‫‪[email protected]‬‬
‫‪19‬‬