6 F 2 T 0 1 7 6 INSTRUCTION MANUAL UNDER/OVERVOLTAGE PROTECTION RELAY GRE130 © TOSHIBA Corporation 2014 All Rights Reserved. ( Ver. 2.0) 6 F 2 T 0 1 7 6 Safety Precautions Before using this product, please read this chapter carefully. This chapter describes the safety precautions recommended when using the GRE130. Before installing and using the equipment, this chapter must be thoroughly read and understood. Explanation of symbols used Signal words such as DANGER, WARNING, and two kinds of CAUTION, will be followed by important safety information that must be carefully reviewed. DANGER Indicates an imminently hazardous situation which will result in death or serious injury if you do not follow the instructions. WARNING Indicates a potentially hazardous situation which could result in death or serious injury if you do not follow the instructions. CAUTION Indicates a potentially hazardous situation which if not avoided, may result in minor injury or moderate injury. CAUTION Indicates a potentially hazardous situation which if not avoided, may result in property damage. 1 6 F 2 T 0 1 7 6 DANGER • Exposed terminals Do not touch the terminals of this equipment while the power is on, as the high voltage generated is dangerous. • Residual voltage Hazardous voltage can be present in the DC circuit immediately after switching off the power supply. It takes approximately 30 seconds for the voltage to discharge. CAUTION • Earth The earthing terminal of the equipment must be securely earthed. CAUTION • Operating environment The equipment must only be used within the range of ambient temperature, humidity and dust detailed in the specification and in an environment free of abnormal vibration. • Ratings Before applying AC voltage or the power supply to the equipment, check that they conform to the equipment ratings. • Printed circuit board Do not attach and remove printed circuit boards when the DC power to the equipment is on, as this may cause the equipment to malfunction. • External circuit When connecting the output contacts of the equipment to an external circuit, carefully check the supply voltage used in order to prevent the connected circuit from overheating. • Connection cable Carefully handle the connection cable without applying excessive force. • Power supply If a power supply has not been supplied to the relay for two days or more, then all fault records, event records and disturbance records and the internal clock may be cleared soon after restoring the power. This is because the back-up RAM may have discharged and may contain uncertain data. • Modification Do not modify this equipment, as this may cause the equipment to malfunction. • Disposal This product does not contain expendable supplies nor parts that can be recycled. When disposing of this equipment, do so in a safe manner according to local regulations as an industrial waste. If any points are unclear, please contact our sales representatives. 2 6 F 2 T 0 1 7 6 Contents Safety Precautions 1 1. Introduction 6 2. Application Notes 8 2.1 Overvoltage and Undervoltage Protection 2.1.1 Phase Overvoltage Protection 2.1.2 Phase Undervoltage Protection 2.1.3 Zero Phase Sequence Overvoltage Protection 2.1.4 Negative Phase Sequence Overvoltage Protection 2.2 Frequency Protection 2.2.1 Frequency element 2.2.2 Frequency rate-of-change element 2.3 Trip and Alarm Signal Output 3. Technical Description 8 8 12 16 19 22 22 22 27 29 3.1 Hardware Description 3.1.1 Outline of Hardware Modules 3.2 Input and Output Signals 3.2.1 AC Input Signals 3.2.2 Binary Input Signals 3.2.3 Binary Output Signals 3.2.4 PLC (Programmable Logic Controller) Function 3.3 Automatic Supervision 3.3.1 Basic Concept of Supervision 3.3.2 Relay Monitoring 3.3.3 Trip Circuit Supervision 3.3.4 Circuit Breaker Monitoring 3.3.5 Failure Alarms 3.3.6 Trip Blocking 3.3.7 Setting 3.4 Recording Function 3.4.1 Fault Recording 3.4.2 Event Recording 3.4.3 Disturbance Recording 3.5 Metering Function 3.6 Control Function 4. User Interface 29 29 31 31 31 35 36 37 37 37 38 40 40 41 42 42 42 43 43 45 46 47 4.1 Outline of User Interface 4.1.1 Front Panel 4.1.2 Communication Ports 4.2 Operation of the User Interface 3 47 47 49 50 6 F 2 T 0 1 7 6 4.3 4.4 4.5 4.6 4.7 4.8 4.2.1 LCD and LED Displays 4.2.2 Relay Menu 4.2.3 Displaying Records 4.2.4 Status Display 4.2.5 Viewing the Settings 4.2.6 Changing the Settings 4.2.7 Control 4.2.8 Testing Personal Computer Interface Modbus Interface IEC 60870-5-103 Interface IEC 61850 Communication Clock Function Special Mode 5. Installation 50 52 55 61 65 67 101 103 106 106 106 106 107 108 109 5.1 Receipt of Relays 5.2 Relay Mounting 5.2.1 Flush Mounting 5.2.2 Dimensions 5.3 Electrostatic Discharge 5.4 Handling Precautions 5.5 External Connections 5.6 Optinal case model S1-GRE130 6. Commissioning and Maintenance 6.1 Outline of Commissioning Tests 6.2 Cautions 6.2.1 Safety Precautions 6.2.2 Precautions for Testing 6.3 Preparations 6.4 Hardware Tests 6.4.1 User Interfaces 6.4.2 Binary Input Circuits 6.4.3 Binary Output Circuits 6.4.4 AC Input Circuits 6.5 Function Test 6.5.1 Measuring Element 6.5.2 Protection Scheme 6.5.3 Metering and Recording 6.6 Conjunctive Tests 6.6.1 On Load Test 6.6.2 Tripping Circuit Test 6.7 Maintenance 6.7.1 Regular Testing 4 109 109 109 111 113 113 114 114 115 115 115 115 116 116 117 117 117 118 119 120 120 125 126 126 126 126 128 128 6 F 2 T 0 1 7 6 6.7.2 6.7.3 6.7.4 6.7.5 Failure Tracing and Repair Replacing Failed Relay Unit Resumption of Service Storage 128 129 129 129 7. Putting Relay into Service 130 Appendix A 131 Signal List 131 Appendix B 140 Event Record Items 140 Appendix C 146 Binary Output Default Setting List Appendix D 146 148 Details of Relay Menu and LCD & Button Operation Appendix E 148 159 Case Outline 159 Appendix F 162 Typical External Connection 162 Appendix G 169 Relay Setting Sheet 169 Appendix H 179 Commissioning Test Sheet (sample) Appendix I 179 183 Return Repair Form 183 Appendix J 188 Technical Data 188 Appendix K 194 Symbols Used in Scheme Logic Appendix L 194 197 Modbus: Interoperability 197 Appendix M 222 IEC60870-5-103: Interoperability Appendix P 222 229 IEC61850: Interoperability 229 Appendix O 268 Ordering 268 The data given in this manual are subject to change without notice. (Ver.2.0) 5 6 F 2 T 0 1 7 6 1. Introduction GRE130 series relays provide overvoltage and undervoltage protection for distribution substations, generators, motors and transformers. The GRE130 provides the following protection schemes. • Overvoltage and undervoltage protection with definite time or inverse time characteristics • Instantaneous overvoltage and undervoltage protection The GRE130 series provides the following protection schemes. • Zero phase sequence overvoltage protection • Negative phase sequence overvoltage protection The GRE130 series provides the following functions. • Two settings groups • Configurable binary inputs and outputs • Circuit breaker control and condition monitoring • Control hierarchy change • Trip circuit supervision • Automatic self-supervision • Menu-based HMI system • Configurable LED indication • Metering and recording functions • Front mounted USB port for PC communications • Rear mounted RS485 serial port for communication GRE130 provides continuous monitoring of internal circuits and of software. External circuits are also monitored, by trip circuit supervision and CB condition monitoring features. A user-friendly HMI is provided through a backlit LCD, programmable LEDs, keypad and menu-based operating system. PC access is also provided, either for local connection via a front-mounted USB port, or for remote connection via a rear-mounted RS485 port. The communication system allows the user to read and modify the relay settings, and to access data gathered by the relay’s metering and recording functions. Further, data communication with substation control and automation systems is supported according to the MODBUS RTU. Table 1.1.1 shows the members of the GRE130 series and identifies the functions to be provided by each member. 6 6 F 2 T 0 1 7 6 Table 1.1.1 Series Members and Functions GRE130 - Model Number [APPL] setting 410A, 411A, 412A 1PP 1PN 2PP 2PZ 3PP 3PN 3PV O/V IDMT O/V DT U/V IDMT U/V DT ZPS IDMT * ZPS DT * NPS IDMT NPS DT FRQ DFRQ Trip circuit supervision Self supervision CB state monitoring Trip counter alarm Multiple settings groups Metering Fault records Event records Disturbance records MODBUS RTU communication IEC60850-5-103 communication IEC61850 communication ()* ()* ()* ()* ()* ()* (option) [APPL]setting; 1PP: single phase-to-phase voltage 1PN: single phase-to-neutral voltage 2PP: two phase-to-phase voltage 2PZ: two phase-to-phase voltage with zero phase voltage input 3PP: three phase-to-phase voltage 3PN: three phase-to-neutral voltage 3PV: three phase-to-neutral voltage with zero phase voltage input Ve: zero phase sequence voltage V0 IDMT: inverse definite minimum time DT: definite time O/V: overvoltage protection U/V: undervoltage protection ZPS: zero phase sequence overvoltage NPS: negative phase sequence overvoltage FRQ: Frequency protection DFRQ: Frequency rate-of-change protection ∗: V0 calculated from three phase voltages ()*: Optional communication for 412A model . CAUTION: Do not change the APPL setting under service condition of the relay. 7 ()* 6 F 2 T 0 1 7 6 2. Application Notes 2.1 Overvoltage and Undervoltage Protection 2.1.1 Phase Overvoltage Protection GRE130 provides three independent phase overvoltage elements with programmable dropoff/pickup(DO/PU) ratio. OV1 and OV2 are programmable for inverse time (IDMT) or definite time (DT) operation. OV3 has definite time characteristic only. Figure 2.1.1 shows the characteristic of overvoltage elements. Pickup Dropoff 0 Figure 2.1.1 V Characteristic of Overvoltage Elements The overvoltage protection element OV1 and OV2 have the IDMT characteristic defined by equation (1) following the form described in IEC 60255-127: k + c t (G ) = TMS × a V − 1 Vs (1) ( ) where: t = operating time for constant voltage V (seconds), V = energising voltage (V), Vs = overvoltage setting (V), TMS = time multiplier setting. k, a, c = constants defining curve. The IDMT characteristic is illustrated in Figure 2.1.2. In addition to the IDMT curve in Figure 2.1.2, a user configurable curve is available via scheme switches [OV1EN] and [OV2EN]. If required, set the scheme switch [OV∗EN] to “C” and set the curve defining constants k, a, c. These curves are defined in Table 2.1.1. Table 2.1.1 Specification of Inverse Time Curves Curve Description k a c “IDMT” 1 1 0 “C” (User Configurable) 0.000 – 30.000 by 0.001 step 0.00 – 5.00 by 0.01 step 0.000 – 5.000 by 0.001 step 8 6 F 2 T 0 1 7 6 Overvoltage Inverse Time Curves 1000.000 Operating Time (secs) 100.000 10.000 TMS = 10 TMS = 5 TMS = 2 1.000 TMS = 1 0.100 1 1.5 2 2.5 3 Applied Voltage (x Vs) Figure 2.1.2 IDMT Characteristic The OV3 element is used for definite time overvoltage protection. Definite time reset The definite time resetting characteristic is applied to the OV1 and OV2 elements when the inverse time delay is used. If definite time resetting is selected, and the delay period is set to instantaneous, then no intentional delay is added. As soon as the energising voltage falls below the reset threshold, the element returns to its reset condition. If the delay period is set to some value in seconds, then an intentional delay is added to the reset period. If the energising voltage exceeds the setting for a transient period without causing tripping, then resetting is delayed for a user-definable period. When the energising voltage falls below the reset threshold, the integral state (the point towards operation that it has travelled) of the timing function (IDMT) is held for that period. This does not apply following a trip operation, in which case resetting is always instantaneous. Both OV1 and OV2 have a programmable drop off/pickup(DO/PU) ratio. Scheme Logic Figures 2.1.3 to 2.1.5show the scheme logic of the overvoltage protection OV1 to OV3. The OV1 protection allows the user to select either a definite time or an inverse time characteristic as shown in Figure 2.1.3. The definite time protection is enabled by setting [OV1EN] to “DT”, and trip signal OV1 TRIP is given through the delayed pick-up timer TOV1. The inverse time protection is enabled by setting [OV1EN] to “IDMT”, and trip signal OV1 TRIP is given. The OV2 protection also provides selective definite time or inverse time characteristic as shown in 9 6 F 2 T 0 1 7 6 Figure 2.1.4. The scheme logic of OV2 is the same as that of the OV1. Figure 2.1.5 and Figure 2.1.5 show the scheme logic of the definite time overvoltage protection OV3. The OV3 gives alarm signals OV3_ALARM through the delayed pick-up timers TOV3. The OV1 to OV3 protection can be disabled by the scheme switches [OV1EN] to [OV3EN]. OV1 2(∗) 64 3(∗) 65 1(∗) TOV1 63 1(∗) 51 & & t 0 & & t 0 & & t 0 102 ≥1 103 ≥1 104 ≥1 OV1 2(∗) 52 INST 3(∗) 53 OV1-B_TRIP OV1-C_TRIP 0.00 - 300.00s & [OV1EN] "DT" OV1-A_TRIP ≥1 101 OV1_TRIP ≥1 & + "IDMT" 15 OV1_BLOCK 1 & Figure 2.1.3 OV2 2(∗) 67 3(∗) 68 OV2 2(∗) INST 3(∗) TOV2 66 1(∗) 1(∗) OV1 Overvoltage Protection 57 & & t 0 & & t 0 & & t 0 109 ≥1 110 ≥1 111 ≥1 58 OV2-A_TRIP OV2-B_TRIP OV2-C_TRIP 0.00 - 300.00s 59 & [OV2EN] "DT" ≥1 108 OV2_TRIP ≥1 & + "IDMT" 16 OV2_BLOCK 1 & Figure 2.1.4 1(∗) TOV3 69 OV3 2(∗) 70 3(∗) 71 [OV3EN] + OV3_BLOCK OV2 Overvoltage Protection 17 0 116 & & t & & t 0 117 & & t 0 118 0.00 - 300.00s 1 Figure 2.1.5 OV3 Overvoltage Protection (∗)Note : Phases 1, 2 and 3 are replaced with the followings: 10 ≥1 115 OV3-A_ALARM OV3-B_ ALARM OV3-C_ ALARM OV3_ ALARM 6 F 2 T 0 1 7 6 Phase [APPL] setting 1PP 1PN 2PP / 2PZ 3PN / 3PV 3PP 1 phase-to-phase phase-to-neutral A - B phase A phase A - B phase 2 - - B - C phase B phase B - C phase 3 - - - C phase C - A phase Setting The table shows the setting elements necessary for the overvoltage protection and their setting ranges. Element Range Step Default Remarks OV1 10.0 – 200.0 V 0.1 V 120.0 V OV1 threshold setting TOV1M 0.05 – 100.00 0.01 1.00 OV1 time multiplier setting. Required if [OV1EN] = IDMT. TOV1 0.00 – 300.00 s 0.01 s 1.00 s OV1 definite time setting. Required if [OV1EN] = DT. TOV1R 0.0 – 300.0 s 0.1 s 0.0 s OV1 definite time delayed reset. OV1DPR 10 – 98 % 1% 95 % OV1 DO/PU ratio setting. OV2 10.0 – 200.0 V 0.1 V 140.0 V OV2 threshold setting TOV2M 0.05 – 100.00 0.01 1.00 OV2 time multiplier setting. Required if [OV2EN] = IDMT. TOV2 0.00 – 300.00 s 0.01 s 1.00 s OV2 definite time setting. Required if [OV2EN] = DT. TOV2R 0.0 – 300.0 s 0.1 s 0.0 s OV2 definite time delayed reset. OV2DPR 10 – 98 % 1% 95 % OV2 DO/PU ratio setting. OV3 10.0 – 200.0 V 0.1 V 140.0 V OV3 threshold setting. TOV3 0.00 – 300.00 s 0.01 s 1.00 s OV3 definite time setting. OV3DPR 10 - 98 % 1% 95 % OV3 DO/PU ratio setting. [OV1EN] Off/DT/IDMT/C Off OV1 Enable [OV2EN] Off/DT/IDMT/C Off OV2 Enable [OV3EN] Off / On Off OV3 Enable 11 6 F 2 T 0 1 7 6 2.1.2 Phase Undervoltage Protection GRE130 provides three independent phase undervoltage elements. UV1 and UV2 are programmable for inverse time (IDMT) or definite time (DT) operation. UV3 has definite time characteristic only. Figure 2.1.7 shows the characteristic of the undervoltage elements. 0 Figure 2.1.7 V Characteristic of Undervoltage Elements The undervoltage protection element UV1 has an IDMT characteristic defined by equation (2) following the form described in IEC 60255-127: k t (G ) = TMS × 1 − V Vs ( ) + c a (2) where: t = operating time for constant voltage V (seconds), V = energising voltage (V), Vs = undervoltage setting (V), TMS = time multiplier setting. k, a, c = constants defining curve. The IDMT characteristic is illustrated in Figure 2.1.8. In addition to the IDMT curve in Figure 2.1.8, a user configurable curve is available via scheme switches [UV1EN] and [UV2EN]. If required, set the scheme switch [UV∗EN] to “C” and set the curve defining constants k, a, c. These curves are defined in Table 2.1.1. The UV3 element is used for definite time overvoltage protection. Definite time reset The definite time resetting characteristic is applied to the UV1 and UV2 elements when the inverse time delay is used. If definite time resetting is selected, and the delay period is set to instantaneous, then no intentional delay is added. As soon as the energising voltage rises above the reset threshold, the element returns to its reset condition. If the delay period is set to some value in seconds, then an intentional delay is added to the reset period. If the energising voltage is below the undervoltage setting for a transient period without causing tripping, then resetting is delayed for a user-definable period. When the energising voltage rises above the reset threshold, the integral state (the point towards operation that it has travelled) of the timing function (IDMT) is held for that period. 12 6 F 2 T 0 1 7 6 This does not apply following a trip operation, in which case resetting is always instantaneous. Undervoltage Inverse Time Curves 1000.000 Operating Time (secs) 100.000 TMS = 10 10.000 TMS = 5 TMS = 2 TMS = 1 1.000 0 0.2 0.4 0.6 0.8 1 Applied Voltage (x Vs) Figure 2.1.8 IDMT Characteristic Scheme Logic Figures 2.1.9 to 2.1.11 show the scheme logic of the undervoltage protection UV1 to UV3. The UV1 protection provides a selective definite time or inverse time characteristic as shown in Figure 2.1.8. The definite time protection is enabled by setting [UV1EN] to “DT”, and trip signal UV1_TRIP is given through the delayed pick-up timer TUV1. The inverse time protection is enabled by setting [UV1EN] to “IDMT”, and trip signal UV1_TRIP is given. The UV2 protection also provides a selective definite time or inverse time characteristic as shown in Figure 2.1.10. The scheme logic of UV2 is the same as that of the UV1. Figure 2.1.11 shows the scheme logic of the definite time undervoltage protection UV3. The UV3 gives alarm signal UV3_ALARM through the delayed pick-up timers TUV3. The UV1 to UV3 protection can be disabled by the scheme switches [UV1EN] to [UV3EN]. In addition, there is a user programmable voltage threshold VBLK. If all measured phase voltages drop below this setting, then both UV1 to UV3 are prevented from operating. This function can be blocked by the scheme switch [VBLKEN]. The [VBLKEN] should be set to “OFF” (not used) when the UV elements are used as fault detectors, and set to “ON” (used) when used for load shedding. Note: The VBLK must be set lower than any other UV setting values. 13 6 F 2 T 0 1 7 6 & & t TUV1 0 & & t 0 & & t 72 1(∗) UV1 2(∗) 73 74 3(∗) 157 1(∗) 123 ≥1 124 ≥1 0 125 ≥1 UV1 2(∗) 158 INST 3(∗) 159 UV1-A_TRIP UV1-B_TRIP UV1-C_TRIP 0.00 - 300.00s UVBLK ≥1 97 VBLK 1 & 122 UV1_TRIP & NON UVBLK & [VBLKEN] + "ON" [UVTST] & "OFF" [UV1EN] "DT" ≥1 + "IDMT" 18 UV1_BLOCK 1 Figure 2.1.9 UV1 Undervoltage Protection & & t TUV2 0 & & t 0 & & t 75 1(∗) UV2 2(∗) 76 3(∗) 1(∗) UV2 2(∗) INST 3(∗) 77 177 178 127 ≥1 128 ≥1 0 129 ≥1 NON UVBLK UV2-A_TRIP UV2-B_TRIP UV2-C_TRIP 0.00 - 300.00s 179 [UV2EN] "DT" ≥1 ≥1 + & "IDMT" 19 UV2_BLOCK & 1 & Figure 2.1.10 UV2 Undervoltage Protection TUV3 78 1(∗) UV3 2(∗) 79 3(∗) 80 & & t 0 131 & & t 0 132 & & t 0 133 [UV3EN] + UV3-A_ALARM UV3-B_ALARM UV3-C_ALARM "ON" 0.00 - 300.00s NON BLK UV3_BLOCK 20 ≥1 1 Figure 2.1.11 130 UV3_ALARM UV3 Undervoltage Protection (∗)Note : Phases 1, 2 and 3 are replaced with the followings: 14 126 UV2_TRIP 6 F 2 T 0 1 7 6 Phase [APPL] setting 1PP 1PN 2PP / 2PZ 3PN / 3PV 3PP 1 phase-to-phase phase-to-neutral A - B phase A phase A - B phase 2 - - B - C phase B phase B - C phase 3 - - - C phase C - A phase Setting The table shows the setting elements necessary for the undervoltage protection and their setting ranges. Element Range Step Default Remarks UV1 5.0 – 130.0 V 0.1 V 60.0 V UV1 threshold setting TUV1M 0.05– 100.00 0.01 1.00 UVI time multiplier setting. Required if [UV1EN] = IDMT. TUV1 0.00 – 300.00 s 0.01 s 1.00 s UV1 definite time setting. Required if [UV1EN] = DT. TUV1R 0.0 – 300.0 s 0.1 s 0.0 s UV1 definite time delayed reset. UV2 5.0 – 130.0 V 0.1 V 40.0 V UV1 threshold setting TUV2M 0.05– 100.00 0.01 1.00 UVI time multiplier setting. Required if [UV2EN] = IDMT. TUV2 0.00 – 300.00 s 0.01 s 1.00 s UV1 definite time setting. Required if [UV2EN] = DT. TUV2R 0.0 – 300.0 s 0.1 s 0.0 s UV1 definite time delayed reset. UV3 5.0 – 130.0 V 0.1 V 40.0 V UV3 threshold setting. TUV3 0.00 – 300.00 s 0.01 s 1.00 s UV3 definite time setting. VBLK 5.0 - 20.0 V 0.1 V 10.0 V Undervoltage block threshold setting. [UV1EN] Off/ DT/ IDMT/ C DT UV1 Enable [VBLKEN] Off / On Off UV block Enable [UV2EN] Off/ DT/ IDMT/ C DT UV2 Enable [UV3EN] Off / On Off UV3 Enable 15 6 F 2 T 0 1 7 6 2.1.3 Zero Phase Sequence Overvoltage Protection The zero phase sequence overvoltage protection (ZPS) is applied to earth fault detection on unearthed, resistance-earthed system or on ac generators. The low voltage settings which may be applied make the ZPS element susceptible to any 3rd harmonic component which may be superimposed on the input signal. Therefore, a 3rd harmonic filter is provided to suppress such superimposed components. For earth fault detection, the following two methods are in general use. • Measuring the zero sequence voltage produced by a VT residual connection (broken-delta connection) as shown in Figure 2.1.13. • Measuring the residual voltage across an earthing transformer as shown in Figure 2.114. A B C GRE130 V0 Figure 2.1.13 A Earth Fault Detection on Unearthed System B G GRE130 V0 Resistor Figure 2.1.14 Earth Fault Detection on Generator Two independent elements ZPS1 and ZPS2 are provided. These elements are programmable for definite time delayed or inverse time delayed (IDMT) operation. The inverse time characteristic is defined by equation (3) following the form described in IEC 60255-127: 16 6 F 2 T 0 1 7 6 k + c t (G ) = TMS × α V0 − 1 V S (3) where: t = operating time for constant voltage V0 (seconds), V0 = Zero sequence voltage (V), Vs = Zero sequence overvoltage setting (V), TMS = time multiplier setting. k, a, c = constants defining curve. The IDMT characteristic is illustrated in Figure 2.1.15. In addition to the IDMT curve in Figure 2.1.15, a user configurable curve is available via scheme switches [ZPS1EN] and [ZPS2EN]. If required, set the scheme switch [ZPS∗EN] to “C” and set the curve defining constants k, a, c. These curves are defined in Table 2.1.1. ZPS Overvoltage Inverse Time Curves 1000.000 Operating Time (secs) 100.000 10.000 1.000 TMS = 10 TMS = 5 TMS = 2 0.100 TMS = 1 0.010 0 5 10 15 20 Applied Voltage (x Vs) Figure 2.1.15 IDMT Characteristic for ZPS 17 6 F 2 T 0 1 7 6 Definite time reset A definite time reset characteristic is applied when the inverse time delay is used. Its operation is identical to that for the phase overvoltage protection. Scheme Logic Figures 2.1.16 and 2.1.17 show the scheme logic of the zero-phase sequence overvoltage protection. Two zero-phase sequence overvoltage elements ZPS1 and ZPS2 with independent thresholds output trip signals ZPS1 TRIP and ZPS2 TRIP through delayed pick-up timers TZOV1 and TZPS2. The tripping can be disabled by the scheme switches [ZPS1EN] and [ZPS2EN]. ZPS1 ZPS1 INST [ZPS1EN] TZPS1 93 0 t & & ≥1 197 134 ZPS1 TRIP 0.00 - 300.00s "DT" ≥1 & + "IDMT" 21 ZPS1_BLOCK 1 Figure 2.1.16 ZPS2 ZPS2 INST [ZPS2EN] ZPS1 Overvoltage Protection TZPS2 94 & & 0 t ≥1 198 135 ZPS2_ALARM 0.00 - 300.00s "DT" ≥1 & + "IDMT" ZPS2_BLOCK 22 1 Figure 2.1.17 ZPS2 Overvoltage Protection Setting The table below shows the setting elements necessary for the zero sequence overvoltage protection and their setting ranges. Element Range Step Default Remarks ZPS1 1.0 - 130.0 V 0.1V 20.0 V ZPS1 threshold setting (V0) for tripping. TZPS1M 0.05 – 100.00 0.01 1.00 ZPS1 time multiplier setting. Required if [ZPS1EN]=IDMT. TZPS1 0.00 – 300.00 s 0.01 s 1.00 s ZPS1 definite time setting. Required if [ZPS1EN]=DT. TZPS1R 0.0 – 300.0 s 0.1 s 0.0 s ZPS1 definite time delayed reset. ZPS2 1.0 - 130.0 V 0.1V 40.0 V ZPS2 threshold setting (V0) for alarming. TZPS2M 0.05 – 100.00 0.01 1.00 ZPS2 time multiplier setting. Required if [ZPS2EN]=IDMT. TZPS2 0.00 – 300.00 s 0.01 s 1.00 s ZPS2 definite time setting. Required if [ZPS2EN]=DT. TZPS2R 0.0 – 300.0 s 0.1 s 0.0 s ZPS2 definite time delayed reset. [ZPS1EN] Off /DT/ IDMT/ C DT ZPS1 Enable [ZPS2EN] Off / On Off ZPS2 Enable 18 6 F 2 T 0 1 7 6 2.1.4 Negative Phase Sequence Overvoltage Protection The negative phase sequence overvoltage protection (NPS) is used to detect voltage unbalance conditions such as reverse-phase rotation, unbalanced voltage supply etc. The NPS protection is applied to protect three-phase motors from the damage which may be caused by the voltage unbalance. Unbalanced voltage supply to motors due to a phase loss can lead to increases in the negative sequence voltage. The NPS protection is also applied to prevent the starting of the motor in the wrong direction, if the phase sequence is reversed. Two independent elements NPS1 and NPS2 are provided. The elements are programmable for definite time delayed or inverse time delayed (IDMT) operation. The inverse time characteristic is defined by equation (4) following the form described in IEC 60255-127. k + c t (G ) = TMS × α V 2 − 1 V S (4) where: t = operating time for constant voltage V2 (seconds), V2 = Negative sequence voltage (V), Vs = Negative sequence overvoltage setting (V), TMS = time multiplier setting. k, a, c = constants defining curve. The IDMT characteristic is illustrated in Figure 2.1.18. In addition to the IDMT curve in Figure 2.1.18, a user configurable curve is available via scheme switches [NPS1EN] and [NPS2EN]. If required, set the scheme switch [NPS∗EN] to “C” and set the curve defining constants k, a, c. These curves are defined in Table 2.1.1. 19 6 F 2 T 0 1 7 6 NPS Overvoltage Inverse Time Curves 1000.000 Operating Time (secs) 100.000 10.000 1.000 TMS = 10 TMS = 5 TMS = 2 0.100 TMS = 1 0.010 0 5 10 15 20 Applied Voltage (x Vs) Figure 2.1.18 IDMT Characteristic for NPS Definite time reset A definite time reset characteristic is applied to the NPS1 element when the inverse time delay is used. Its operation is identical to that for the phase overvoltage protection. Scheme Logic Figures 2.1.19 and 2.1.20 show the scheme logic of the negative sequence overvoltage protection. Two negative sequence overvoltage elements NPS1 and NPS2 with independent thresholds output trip signals NPS1 TRIP and NPS2 TRIP through delayed pick-up timers TNPS1 and TNPS2. The tripping can be disabled using scheme switches [NPS1EN] and [NPS2EN]. NPS1 NPS1 INST [NPS1EN] TNPS1 95 & & 0 t ≥1 199 136 0.00 - 300.00s "DT" ≥1 & + "IDMT" NPS1_BLOCK 23 1 Figure 2.1.19 NPS1 Overvoltage Protection 20 NPS1 TRIP 6 F 2 T 0 1 7 6 NPS2 NPS2 INST [NPS2EN] TNPS2 96 & & 0 t ≥1 200 137 NPS2_ALARM 0.00 - 300.00s "DT" ≥1 & + "IDMT" NPS2_BLOCK 24 1 Figure 2.1.20 NPS2 Overvoltage Protection Setting The table below shows the setting elements necessary for the negative sequence overvoltage protection and their setting ranges. The delay time setting TNPS1 and TNPS2 is added to the inherent delay of the measuring elements NPS1 and NPS2. The minimum operating time of the NPS elements is approximately 200ms. Element Range Step Default Remarks NPS1 1.0 - 130.0 V 0.1V 20.0 V NPS1 threshold setting for tripping. TNPS1M 0.05 – 100.00 0.01 1.00 NPS1 time multiplier setting. Required if [NPS1EN]=IDMT. TNPS1 0.00 – 300.00 s 0.01 s 1.00 s NPS1 definite time setting. Required if [NPS1EN]=DT. TNPS1R 0.0 – 300.0 s 0.1 s 0.0 s NPS1 definite time delayed reset. NPS2 1.0 - 130.0 V 0.1V 40.0 V NPS2 threshold setting for alarming. TNPS2M 0.05 – 100.00 0.01 1.00 NPS2 time multiplier setting. Required if [NPS2EN]=IDMT. TNPS2 0.00 – 300.00 s 0.01 s 1.00 s NPS2 definite time setting. Required if [NPS2EN]=DT. TNPS2R 0.0 – 300.0 s 0.1 s 0.0 s NPS2 definite time delayed reset. [NPS1EN] Off /DT/ IDMT/ C Off NPS1 Enable [NPS2EN] Off / On Off NPS2 Enable 21 6 F 2 T 0 1 7 6 2.2 Frequency Protection For a four-stage frequency protection, GRE130 incorporates dedicated frequency measuring elements and scheme logic for each stage. Each stage is programmable for underfrequency, overfrequency or frequency rate-of-change protection. Underfrequency protection is provided to maintain the balance between the power generation capability and the loads. It is also used to maintain the frequency within the normal range by load shedding. Overfrequency protection is typically applied to protect synchronous machines from possible damage due to overfrequency conditions. Frequency rate-of-change protection is applied to ensure that load shedding occurs very quickly when the frequency change is very rapid. A-phase to B-phase voltage is used to detect frequency. 2.2.1 Frequency element Underfrequency element UF operates when the power system frequency falls under the setting value. Overfrequency element OF operates when the power system frequency rises over the setting value. These elements measure the frequency and check for underfrequency or overfrequency every 5 ms. They operate when the underfrequency or overfrequency condition is detected 16 consecutive times. The outputs of both the UF and OF elements is invalidated by undervoltage block element (FRQBLK) operation during an undervoltage condition. Figure 2.2.1 shows the characteristics of the UF and OF elements. Figure 2.2.1 2.2.2 Underfrequency and Overfrequency Elements Frequency rate-of-change element The frequency rate-of-change element calculates the gradient of frequency change (df/dt). GRE130 provides two rate-of-change elements, a frequency decay rate element (D) and a frequency rise rate element (R). These elements measure the change in frequency (Δf) over a time interval (Δt=100ms), as shown Figure 2.2.2 and calculate the Δf/Δt every 5 ms. They operate when the frequency change exceeds the setting value 50 consecutive times. The output of both the D and R elements is invalidated by undervoltage block element (FRQBLK) operation during undervoltage condition. 22 6 F 2 T 0 1 7 6 Hz Δf Δt sec Figure 2.2.2 Frequency Rate-of-Change Element Scheme Logic Figure 2.2.3 shows the scheme logic of the frequency protection for stage 1. The first frequency element F11, the second F12, the frequency rise rate-of-change element DFR1 and frequency decay rate-of-change element DFD1 can all output a trip command independently under the condition that the system voltage is higher than the setting of the undervoltage element FVBLK. F11 F12 DF-R1 DF-D1 & & 231 t 0 0.00 – 100.00S & & 232 t 0 0.00 – 100.00S 211 212 + 213 O U B OO UU OFF [FT1] ≥1 ≥1 & 214 R FVBLK + FRQ1 BLOCK [DFT1] 42 D BOTH OFF E 235 F RQ1 TRIP F2 Scheme Logic Selection : [Logic1] & & F1 ≥1 & 233 234 DFR DFD ≥1 1 Figure 2.2.3 FRQ1 Frequency Protection Logic To apply the various types of frequency protection, the GRE130 has the following three scheme switches for each stage. For stage 1, [FT1]: This switch selects the frequency protection to apply as well as provide the measuring elements F11 and F12 with an overfrequency or underfrequency characteristic. 23 6 F 2 T 0 1 7 6 [FT1] F11 / F12 characteristic Protection selected setting F11 F12 O OF(*) Overfrequency protection only with F11 element U UF(**) Underfrequency protection only with F11 element B OF UF Overfrequency protection with F11 element and underfrequency protection with F12 element OO OF OF Overfrequency protection both with F11 and F12 elements UU UF UF Underfrequency protection both with F11 and F12 elements Off OF OF To block frequency protection (*) OF: Overfrequency characteristic (**)UF: Underfrequency characteristic [DFT1]: This switch selects which frequency rate-of-change protection to apply. The following protections can be selected by the [DFT1] settings. [DFT1] setting R D BOTH Off Protection selected Frequency rise rate-of-change protection only Frequency decay rate-of-change protection only Both of frequency rise rate-of-change and decay rate-of-change protections To block frequency rate-of-change protection [LOGIC1]: This switch is provided in the scheme logic selection circuit in Table 2.2.1 and determines the trip command combination of frequency element output and frequency rate-of-change element output. The following table shows the [Logic1] setting and corresponding combinations. Table 2.2.1 Frequency protection logic [Logic1] Setting Scheme Logic F1 L1 E F2 ≥1 E = F1 + F2 + DFR + DFD DFR DFD & F1 L2 Trip Command Logic ( +:OR, x : AND ) ≥1 E E = F1 x (DFR + DFD) + F2 ≥1 E E = F1 + F2 x (DFR + DFD) ≥1 E E = (F1 + F2) x (DFR + DFD) F2 DFR ≥1 DFD F1 L3 & F2 DFR ≥1 DFD L4 F1 & F2 & DFR DFD ≥1 24 6 F 2 T 0 1 7 6 L5 F1 & F2 & ≥1 E E = F1 x DFR + F2 x DFD DFR DFD The individual scheme logic for stages 2 to 4 are similar to that of stage 1 except that the device names of the measuring elements, timers, scheme switches and binary input signals change and the logic described above is applied to stages 2 to 4. F21 F22 DF-R2 DF-D2 & & 236 t 0 0.00 – 100.00S & & 237 t 0 0.00 – 100.00S 215 216 + 217 [FT2] O U B OO UU OFF ≥1 ≥1 & & & 218 FVBLK ≥1 + [DFT2] 43 FRQ2 BLOCK D BOTH OFF E 240 F RQ2 TRIP F2 Scheme Logic Selection : [Logic2] & R F1 238 239 DFR DFD ≥1 1 Figure 2.2.4 FRQ2 Frequency Protection Logic F31 F32 DF-R3 DF-D3 & & 241 t 0 0.00 – 100.00S & & 242 t 0 0.00 – 100.00S 219 220 + 221 [FT3] O U B OO UU OFF ≥1 ≥1 & 222 R FVBLK + FRQ3 BLOCK [DFT3] 44 D BOTH OFF F2 Scheme Logic Selection : [Logic3] & & F1 ≥1 & 243 244 DFR DFD ≥1 1 Figure 2.2.5 FRQ3 Frequency Protection Logic 25 E 245 F RQ3 TRIP 6 F 2 T 0 1 7 6 F41 F42 DF-R4 DF-D4 & & 246 t 0 0.00 – 100.00S & & 247 t 0 0.00 – 100.00S 223 224 + 225 [FT4] O U B OO UU OFF ≥1 ≥1 & & & 248 226 R FVBLK + FRQ4 BLOCK [DFT4] 45 E 250 F RQ4 TRIP F2 Scheme Logic Selection : [Logic4] & D BOTH OFF F1 ≥1 249 DFR DFD ≥1 1 Figure 2.2.6 FRQ4 Frequency Protection Logic Setting The setting elements necessary for the frequency protection and their setting ranges are shown in the table below. Element F1 (*) F2 DF (**) FVBLK(***) TF1 TF2 FT DFT Logic Range 45.00 – 55.00 Hz ( 54.00 – 66.00 Hz 45.00 – 55.00 Hz ( 54.00 – 66.00 Hz 0.1 – 9.9 Hz/s 40 –100 V 0.00 – 100.00 s 0.00 – 100.00 s Off / O / U / B / OO / UU Off / R / D / Both L1 / L2 / L3 / L4 / L5 Step 0.01 Hz 0.01 Hz 0.01 Hz 0.01 Hz 0.1 Hz/s 1V 0.01 s 0.01 s Default 51.00 Hz 61.00 Hz ) 49.00 Hz 59.00 Hz ) 0.5 Hz/s 40 V 1.00 s 1.00 s B Both L1 Remarks First frequency element setting Second frequency element setting Frequency rate-of-change (**) Undervoltage block Timer setting of first frequency element Timer setting of second frequency element Frequency protection selection Frequency rate-of-change protection selection Scheme logic selection (*): Number 1 to 4 enter into for stages 1 to 4 respectively. (**): DF is a common setting element name for DFR and DFD. (***): FVBLK is common to stage 1 to 4. 26 6 F 2 T 0 1 7 6 2.3 Trip and Alarm Signal Output GRE130 provides various trip and alarm signal outputs such as three-phase and single-phase trip and alarm for each protection. Figure 2.4.1 shows the trip and alarm signals grouped for each protection. GRE130 provides 4 or 8 auxiliary relays for binary outputs as described in Section 3.2.3. After the trip signal has disappeared, following the clearance of the fault, the reset time of the tripping output relay can be programmed. The setting is respective for each output relay. When the relay is latched, it can be reset with the RESET key on the relay front panel or via a binary input. This resetting resets all of the output relays collectively. For the tripping output relay, a check must be made to ensure that the tripping circuit is open by monitoring the status of a circuit breaker auxiliary contact prior to the tripping output relay resetting, in order to prevent the tripping output relay from directly interrupting the circuit breaker tripping coil current. OV1 TRIP OV2 TRIP UV1 TRIP UV2 TRIP 141 ≥1 GEN_TRIP ZPS1 TRIP NPS1 TRIP FRQ1 TRIP FRQ2 TRIP FRQ3 TRIP FRQ4 TRIP OV1-A TRIP OV2-A TRIP ≥1 372 ≥1 373 ≥1 374 GEN_TRIP-A UV1-A TRIP UV2-A TRIP OV1-B TRIP OV2-B TRIP GEN_TRIP-B UV1-B TRIP UV2-B TRIP OV1-C TRIP OV2-C TRIP UV1-C TRIP GEN_TRIP-C UV2-C TRIP 375 ZPS1_TRIP Figure 2.4.1 Tripping and Alarm Outputs 27 GEN. TRIP-N 6 F 2 T 0 1 7 6 OV3 ALARM ≥1 UV3 ALARM 380 GEN_ALARM ZPS2 ALARM NPS2 ALARM OV3-A ALARM ≥1 381 ≥1 382 ≥1 383 UV3-A ALARM OV3-B ALARM UV3-B ALARM OV3-C ALARM UV3-C ALARM 384 ZPS2 ALARM GEN_ALARM-A GEN_ALARM-B GEN_ALARM-C GEN_ALARM-N Figure 2.4.1 Tripping and Alarm Outputs (cont’d) Pick-up signals GRE130 provides various pick-up signal outputs to select the signal No. for pick-up. The pick-up signal of IDMT elements are output from ***-INST shown as each scheme logic. When the DT elements operate, the ***-INST element is NOT output. 28 6 F 2 T 0 1 7 6 3. Technical Description 3.1 Hardware Description 3.1.1 Outline of Hardware Modules The case outline of GRE130 is shown in Appendix E. As shown in Figure 3.1.1, the human machine interface (HMI) panel has a liquid crystal display (LCD), light emitting diodes (LED), operation keys and a USB type-B connector on the front panel. The LCD consists of 16 columns by 8 rows (128x64dots) with a back-light and displays recording, status and setting data. There are a total of 14 LED indicators and their signal labels and LED colors are defined as follows: Label Color Remarks IN SERVICE Green Lit when the relay is in service and flashing when the relay is in “Test” menu. TRIP Red Lit when a trip command is issued. ALARM Yellow Lit when relay alarm is detected. Relay Fail Red Lit when a relay failure is detected. CB CLOSED Red/Green/ Lit when CB is closed. Yellow CB OPEN Green Lit when CB is open. LOCAL Yellow Lit when Local Control is enabled REMOTE Yellow Lit when Remote Control is enabled (LED1) Red/Green/ Yellow User-configurable (LED2) Red/Green/ Yellow User-configurable (LED3) Red/Green/ Yellow User-configurable (LED4) Red/Green/ Yellow User-configurable (LED5) Red/Green/ Yellow User-configurable (LED6) Red/Green/ Yellow User-configurable LED1 to LED6 are user-configurable. Each is driven via a logic gate which can be programmed for OR gate or AND gate operation. Further, each LED has a programmable reset characteristic, settable for instantaneous drop-off, or for latched operation. A configurable LED can be programmed to indicate the OR combination of a maximum of 4 elements, and the LED color can be changed to one of three colors- (Red / Green / Yellow) , the individual status of which can be viewed on the LCD screen as “Virtual LEDs.” For the setting, see Section 4.2.6.10. For the operation, see Section 4.2.1. The TRIP LED and an operated LED if latching operation is selected, must be reset by the user, 29 6 F 2 T 0 1 7 6 either by pressing the RESET key, by energising a binary input which has been programmed for ‘Remote Reset’ operation, or by a communications command. Other LEDs operate as long as a signal is present. The RESET key is ineffective for these LEDs. Further, the TRIP LED is controlled with the scheme switch [AOLED] whether it is lit or not by the output of an alarm element such as OV4 ALARM, UV4 ALARM, etc.. The CB CLOSED and CB OPEN LEDs indicate CB condition. The CB CLOSED LED color can be changed to one of three colors-(Red / Green / Yellow) . The LOCAL / REMOTE LED indicates the CB control hierarchy. When the LOCAL LED is lit, the CB can be controlled using the ○ and | keys on the front panel. When the REMOTE LED is lit, the CB can be controlled using a binary input signal or via relay communications. When neither of these LEDs are lit , the CB control function is disabled. The ▼ key starts the Digest screen (Metering, Virtual LED) view on the LCD. The ▼ key will scroll the screen through “Virtual LED” → “Metering” →”Indication and back-light off” when the LCD is in the Digest screen mode. The ENTER key starts the Main menu indication on the LCD. The END key clears the LCD indication and turns the LCD back-light off when the LCD is in the “MAIN MENU”. The operation keys are used to display the records, status and setting data on the LCD, to input settings or to change settings. The USB connector is a B-type connector. This connector is used for connection with a local personal computer. Liquid crystal display Light emitting diodes (LED) Light emitting diodes (LED) Control keys Motor status Operation keys To a local PC USB type B connector Figure 3.1.1 Front Panel (model 410, 411) 30 6 F 2 T 0 1 7 6 3.2 Input and Output Signals 3.2.1 AC Input Signals Table 3.2.1 shows the AC input signals necessary for the GRE130 model and their respective input terminal numbers. Their terminal numbers depend on their scheme switch [APPL] setting. Table 3.2.1 AC Input Signals : Scheme switch [APPL] setting Model Term. No. TB1 at 410/411 3.2.2 410, 411, 412 TB2 at 412 1PP 1PN 2PP 2PZ 3PN 3PV 3PP 1-2 Phase-tophase voltage Phase-toneutral voltage A-B phase voltage A-B phase voltage A phase voltage A phase voltage A-B phase voltage 3-4 --- --- B-C phase voltage B-C phase voltage B phase voltage B phase voltage B-C phase voltage 5-6 --- --- --- --- C phase voltage C phase voltage C-A phase voltage 7-8 Ve Ve --- Ve --- Ve Ve Binary Input Signals The GRE130 provides 2 (Model 410) or 6 (Model 411 / 412) programmable binary input circuits. Each binary input circuit is programmable, and provided with the function of Logic level inversion, detection threshold voltage change and function selection. Logic level inversion and detection threshold voltage change The binary input circuit of the GRE130 is provided with a logic level inversion function, a pick-up and drop-off delay timer function and a detection threshold voltage change as shown in Figure 3.2.1. Each input circuit has a binary switch BISNS which can be used to select either normal or inverted operation. This allows the inputs to be driven either by normally open or normally closed contacts. Where the driving contact meets the contact conditions then the BISNS can be set to “Norm” (normal). If not, then “Inv” (inverted) should be selected. The pick-up and drop-off delay times can be set 0.0 to 300.00s respectively. The binary input detection nominal voltage is programmable by the user, and the setting range varies depending on the rated DC power supply voltage. In the case that a 110V / 220Vdc rated model is ordered, the input detection nominal voltage can be set to 48V, 110V or 220V for BI1 and BI2, and to 110V or 220V for BI3-BI6. In the case of a 24 / 48Vdc model, the input detection nominal voltage can be set to 12V, 24V or 48V for BI1 and BI2, and to 24V or 48V for BI3-BI6. The binary input detection threshold voltage (i.e. minimum operating voltage) is normally set at 77V and 154V for supply voltages of 110V and 220V respectively. In the case of 24V and 48V supplies, the normal thresholds are 16.8V and 33.6V respectively. Binary inputs can be configured for operation in a Trip Circuit Supervision (TCS) scheme by setting the [TCSPEN] switch to “Enable”. For the case where TCS using 2 binary inputs is to be applied (refer to Section 3.3.3), then the binary input detection threshold of BI1 and BI2 should be set to less than half of the rated dc supply 31 6 F 2 T 0 1 7 6 voltage. The logic level inversion function, pick-up and drop-off delay timer and detection voltage change settings are as follow: Element Contents Range BI1SNS – BI6SNS Binary switch Norm/ Inv Norm BITHR1 * BI1-2 nominal voltage 48 / 110 / 220 110 (12 / 24 / 48 ) (24) (24 / 48 / 110 ) (48) 110 / 220 110 (24 / 48) (24) (48 / 110) (110) Off BITHR2 * BI3-6 nominal voltage Step Default TCSPEN TCS enable Off / On / Opt-On BI1PUD – BI6PUD Delayed pick-up timer 0.00 - 300.00s 0.01s 0.00 BI1DOD – BI6DOD Delayed drop-off timer 0.00 - 300.00s 0.01s 0.00 *At the PC interface software RSM100 (Relay Setting and Monitoring system), BI threshold voltage settings are indicated by V1, V2 and V3. The V1, V2 and V3 are distinguished with 11th digit of ordering code for supply voltage, as shown below,: Supply voltage (11th digt of ordering cord) V1 V2 V3 110 - 220V (-1x-xx) 48V 110V 24V 48V 12V 24V 110V 220V 48V 110V 24V 48V 220 110V 48V - 48 - 110V (-2x-xx) 12 - 48V (-Ax-xx) BITH1 BITH2 BITH1 BITH2 BITH1 BITH2 Four alarm messages (Alarm1 to Alarm4) can be set. The user can define a text message within 16 characters for each alarm. The messages are valid for any of the input signals BI1 to BI2 or BI6 by setting. Then when inputs associated with that alarm are raised, the defined text is displayed on the LCD. The binary input detection threshold of BI1 and BI2 should be set to less than half of the rated dc supply voltage. The logic level inversion function, pick-up and drop-off delay timer and detection voltage change settings are as follow: 32 6 F 2 T 0 1 7 6 GRE130 (+) (−) BI1 BI1PUD BI1DOD t 0 0 [BI1SNS] t BI1 BI1 command "Norm" 1 "Inv" BI2 BI2PUD BI2DOD t 0 0 t BI2 BI2 command "Norm" [BITHR1] 1 + "220V" BI3 [BI2SNS] "Inv" + "110V" + "48V" BI6PUD BI6 t 0 BI6DOD 0 t [BI6SNS] BI6 command BI6 "Norm" [BITHR2] "220V" "110V" 1 "Inv" + + 1 0V Figure 3.2.1 Logic Level Inversion Function selection The input signals BI1 COMMAND to BI6 COMMAND are used for the functions listed in Table 3.2.2. Each input signal can be allocated for one or some of those functions by setting. For the setting, refer to Section 4.2.6.8. The Table also shows the signal name corresponding to each function used in the scheme logic and the LCD indication and driving contact condition required for each function. [OV1BLK] BI1 COMMAND OV1 BLOCK "ON" [OV2BLK] OV2 BLOCK "ON" [OV3BLK] OV3 BLOCK "ON" [Alarm4] Alarm 4 "ON" Figure 3.2.2 Function Scheme Logic The logic of BI2 COMMAND to BI6 COMMAND are the same as that of BI1 COMMAND as shown in Figure 3.2.2. 33 6 F 2 T 0 1 7 6 Table 3.2.2 Function of Binary Input Signals Functions Signal Names (*1) Driving Contact Condition Overvoltage protection1 block OV1 BLOCK / OV 1BLK Closed to block Overvoltage protection2 block OV2 BLOCK / OV 2BLK Closed to block Overvoltage protection3 block OV3 BLOCK / OV 3BLK Closed to block Undervoltage protection1 block UV1 BLOCK / UV 1BLK Closed to block Undervoltage protection2 block UV 2 BLOCK / UV 2BLK Closed to block Undervoltage protection3 block UV 3 BLOCK / UV 3BLK Closed to block Zero phase sequence OV1 block ZPS1 BLOCK / ZP1BLK Closed to block Zero phase sequence OV2 block ZPS2 BLOCK / ZP2BLK Closed to block Negative phase sequenceOV1 block NPS1 BLOCK / NP1BLK Closed to block Negative phase sequenceOV2 block NPS2 BLOCK / NP2BLK Closed to block Frequency protection1 block FRQ1 BLOCK / FRQ1BLK Closed to block Frequency protection2 block FRQ2 BLOCK / FRQ2BLK Closed to block Frequency protection3 block FRQ3 BLOCK / FRQ3BLK Closed to block Frequency protection4 block FRQ4 BLOCK / FRQ4BLK Closed to block Trip circuit supervision TC FAIL / TCFALM Trip supply State transition for cold load protection, trip supervision and CB monitoring CB CONT OPN / CBOPN CB normally open contact closed. CB monitoring CB CONT CLS / CBCLS CB normally closed contactclosed. Indication remote reset REMOTE RESET / RMTRST Closed to reset TRIP LED indication and latch of binary output relays Synchronize clock SYNC CLOCK / SYNCLK Synchronize clock Disturbance record store STORE RECORD / STORCD Closed to store the record Alarm 1 Alarm 1 / Alarm1 Closed to display Alarm 1 text. Alarm 2 Alarm 2 / Alarm2 Closed to display Alarm 2 text. Alarm 3 Alarm 3 / Alarm3 Closed to display Alarm 3 text. Alarm 4 Alarm 4 / Alarm4 Closed to display Alarm 4 text. Remote Open Remote OPEN / RMTOPN CB normally open contact. Remote Close Remote CLOSE / RMTCLS CB normally close contact. Control Lock Control Lock / CNTLCK Closed to block (*1) : Signal names are those used in the scheme logic / LCD indication. The binary input signals can be programmed to switch between four settings groups. Element Contents Range BI1SGS – BI6SGS Setting group selection OFF / 1 / 2 Step Default OFF Four alarm messages can be set. The user can define a text message using up to 22 characters for each alarm. The messages are valid for any of the input signals BI1 to BI6 by setting. Then when inputs associated with that alarm are raised, the defined text is displayed on the LCD. 34 6 F 2 T 0 1 7 6 3.2.3 Binary Output Signals The number of binary output signals and their output terminals are as shown in Appendix E. All outputs, except the relay failure signal, can be configured. GRE130 provides 5 auxiliary relays which is composed of one auxiliary relay FAIL for the relay fail output and four programmable auxiliary relays BO1 to BO4. The reset time of the tripping output relay following fault clearance can be programmed. The setting is respective for each output relay. The signals shown in the signal list in Appendix A can be assigned to output relays BO1 to BO4 individually or in arbitrary combinations. The output relays BO1 and BO2 connect to CB OPEN / CLOSE for CB control. The CB close control switch | is linked to BO1 and the CB open control switch ○ is linked to BO2, when the control function is enabled. Signals can be combined using either an AND circuit or OR circuit with 4 gates each as shown in Figure 3.2.3. The output circuit can be configured according to the setting menu. Appendix G shows the factory default settings. Further, each BO has a programmable reset characteristic, settable for instantaneous drop-off “Ins”, for delayed drop-off “Dl”, for dwell operation “Dw” or for latching operation “Lat” by the scheme switch [RESET]. The time of the delayed drop-off “Dl” or dwell operation “Dw” can be set by TBO. When “Dw” is selected, the BO outputs for the TBO set time if the input signal does not continue on the TBO set time. If the input signal continues, the BO output is continuous for the time duration of the input signal. When the relay is latched, it can be reset with the RESET key on the relay front panel or a binary input. This resetting resets all the output relays collectively. The relay failure contact closes when a relay defect or abnormality in the power supply circuit is detected. Signal List & Appendix A Auxiliary relay 4 GATES ≥1 or ≥1 4 GATES & TBO & [RESET] "Dw" t 0.00 – 10.00s "Dl" + 0 & S F/F "Lat" R Reset button + BI1_COMMAND ≥ RMTRST Figure 3.2.3 Configurable Output 35 6 F 2 T 0 1 7 6 Settings The setting elements necessary for binary output relays and their setting ranges are as follows: Element [RESET] Range Ins Dl / Dw /Lat Step Default See Appendix A TBO 0.00 – 10.00s 0.01s See Appendix A Remarks Output relay reset time. Instantaneous, delayed, dwell or latched. 3.2.4 PLC (Programmable Logic Controller) Function GRE130 is provided with a PLC function which enables user-configurable sequence logic based upon binary signals. The sequence logic with timers, flip-flops, AND, OR, XOR, NOT logic, etc. can be produced by using the PC software “PLC tool” and linked to signals corresponding to relay elements or binary circuits. Configurable binary inputs and the initiation of fault and disturbance records can be programmed using the PLC function. Temporary signals are provided for complicated logic or for using a user-configured signal in many logic sequences. PLC logic is assigned to protection signals by using the PLC tool. For details of the PLC tool, refer to the PLC tool instruction manual. (see 6F2S0810 Instruction manual – PLC TOOL) Figure 3.2.4.1 Sample Screen for PLC Tool 36 6 F 2 T 0 1 7 6 3.3 Automatic Supervision 3.3.1 Basic Concept of Supervision Although the protection system is in a non-operating state under normal conditions, it continuously monitors the power system in order to detect a fault which may occur at any time, and must operate for the fault without fail. Therefore, the automatic supervision function, which checks the health of the protection system during normal operation, plays an important role. The GRE130 implements an automatic supervision function, based on the following concepts: • The supervising function should not affect the protection performance. • Perform supervision with no omissions wherever possible. • When a failure occurs, it is recorded as an Alarm record, the user should be easily able to identify the location of the failure. • Under relay failure detection , CB open control is enabled, but CB close control is disabled. 3.3.2 Relay Monitoring The relay is supervised by the following functions. AC input imbalance monitoring The AC current input is monitored to check that the following equation is satisfied and the health of the AC input circuit is verified. • Zero sequence voltage monitoring for [APPL]= “3PN” setting |Va + Vb + Vc| / 3 ≤ 6.35 (V) • Negative sequence voltage monitoring for [APPL]≠ “1PN” or “1PP” setting |Va + a2Vb + aVc| / 3 ≤ 6.35 (V) where, a = Phase shift operator of 120°, a2 = Phase shift operator of 240° The zero sequence monitoring and negative sequence monitoring allow high sensitivity detection of failures that have occurred in the AC input circuits. The negative sequence voltage monitoring allows high sensitivity detection of failures in the voltage input circuit, and it is effective for detection particularly when cables have been connected with the incorrect phase sequence. A/D accuracy checking An analog reference voltage is applied to a prescribed channel in the analog-to-digital (A/D) converter, and a check is made to ensure that the data after A/D conversion is within a prescribed range, and that the A/D conversion characteristics are correct. Memory monitoring Memory is monitored as follows, depending on the type of memory, and checks are done to verify that memory circuits are healthy: • Random access memory monitoring: Writes/reads prescribed data and checks the storage function. • Program memory monitoring: Checks the checksum value of the written data. • Setting value monitoring: Checks discrepancies between the setting values stored in duplicate. 37 6 F 2 T 0 1 7 6 Watchdog Timer A hardware timer that is cleared periodically by the relay software is provided, to check that the relay software is running normally. Power supply Monitoring The secondary voltage level is monitored, and a check is made to ensure that the DC voltage is within a prescribed range. Issuing of Alarms The alarms are issued when the failure continues for a predetermined time. The times for each monitoring item are as follows; • A/D accuracy checking, memory monitoring, Watch Dog Timer, DC supply monitoring: less than 1s • AC input imbalance monitoring, sampling synchronization monitoring : 15s 3.3.3 Trip Circuit Supervision The circuit breaker tripping control circuit can be monitored by either one or two binary inputs, as described below. Trip Circuit Supervision using 1 binary input The circuit breaker tripping control circuit can be monitored using a binary input. Figure 3.3.1 shows a typical scheme. When the trip circuit is intact , a small current flows through the binary input, the circuit breaker auxiliary contacts and the trip coil. This current flows for both the breaker open and closed conditions. Then the logic signal output of the binary input circuit TC FAIL is "1" under healthy conditions. If the trip supply is lost or if a connection becomes open circuit, then the binary input resets and TC FAIL becomes "0". Figure 3.3.2 shows the scheme logic. A trip circuit fail alarm TCSV is output when the TC FAIL output is "0". If the trip circuit failure is detected, then “ALARM” LED is lit and “Err: TC” is displayed in LCD message. Monitoring is enabled by setting the scheme switch [TCSPEN] to "ON" or "OPT-ON" and one BI is selected for "TCFAIL". When "OPT-ON" is selected, monitoring is enabled only while the CB is closed. GRE130 +ve Trip Supply Circuit Breaker CB Trip Coil Trip Output Binary Input CB Aux. Contacts Figure 3.3.1 Trip Circuit Supervision by 1 binary input 38 -ve Trip Supply 6 F 2 T 0 1 7 6 t TC FAIL ≥1 1 0 0 t & (BI command) 0.4s TCSV 0.4s TC FAIL (BI command) CB status “closed” & ≥1 "OPT-ON" [TCSPEN] "ON" + Figure 3.3.2 Supervision Scheme Logic Trip Circuit Supervision using 2 binary inputs The circuit breaker tripping control circuit can be monitored using two binary inputs. Figure 3.3.3 shows a typical scheme. When the trip circuit is intact a small current flows in the photo-couplers, the circuit breaker auxiliary contacts and the trip coil. This current flows for both the breaker open and breaker closed conditions. If the trip circuit supply is lost or if a connection becomes open circuit then the TCS issues a Trip Circuit Fail alarm. Monitoring is enabled by setting scheme switch [TCSPEN] to "ON" or "OPT-ON" and the two BIs selected for " TCFAIL". When "OPT-ON" is selected, monitoring is enabled only while the CB is closed. TCS using 2BIs should be applied using BI1 and BI2 for the BI inputs. For TCS using 2BIs the BI nominal operating voltage ([BITHR1]) should be set to a value of approximately half that of the trip supply voltage. If the trip supply voltage is 110V (or 24V) , [BITHR1] can be set at "48" (or "12"). GRE130 Circuit Breaker CB Aux. Contacts Trip Output +ve Trip Supply CB Trip Coil -ve Trip Supply Resistor Binary Input (BI1) Binary Input (BI2) Figure 3.3.3 Trip Circuit Supervision by 2 binary inputs The resistors connected in series with the binary inputs are to prevent unnecessary tripping of the circuit breaker if any one component suffers a short-circuit condition. The value of resistance should be chosen to limit the current flowing through the circuit breaker trip coil to 60mA in the event of a short circuit of BI1 with the circuit breaker closed. A typical value for a 110V dc rated circuit is 3.3kΩ. 39 6 F 2 T 0 1 7 6 3.3.4 Circuit Breaker Monitoring The relay provides the following circuit breaker monitoring functions. Circuit Breaker State Monitoring Circuit breaker state monitoring is provided for checking the health of the circuit breaker (CB). If two binary inputs are programmed to the functions ‘CB_N/O_CONT’ and ‘CB_N/C_CONT’, then the CB state monitoring function becomes active. Under normal circumstances these inputs are in opposite states. Figure 3.3.4 shows the scheme logic. If both show the same state for a period of five seconds, then a CB state alarm CBSV operates and “Err:CB” and “CB err” are displayed in an LCD message and event record message respectively. The monitoring can be enabled or disabled by setting the scheme switch [CBSMEN]. Normally open and normally closed contacts of the CB are connected to binary inputs BIm and BIn respectively, and the functions of BIm and BIn are set to “CBOPN=ON” and “CBCLS=ON” respectively. (Refer to Section 4.2.6.8.) CB CONT_OPN =1 1 t 0 & 1271 CBSV 5.0s CB CONT_CLS [CBSMEN] + "ON" Figure 3.3.4 CB State Monitoring Scheme Logic Circuit Breaker Condition Monitoring Periodic maintenance of a CB is required in order to check the trip circuit, the operating mechanism and the interrupting capability. Generally, maintenance is based on a time interval or a number of fault current interruptions. The following CB condition monitoring functions are provided to determine the time for maintenance of a CB: • The number of trip operations are counted for maintenance of the trip circuit and CB operating mechanism. The trip counter increments the number of tripping operations performed. An alarm is issued and informs the user of the time for maintenance when the count exceeds a user-defined setting TCALM. The trip count alarm can be enabled or disabled by setting the scheme switch [TCAEN]. • Operating time monitoring is provided for CB mechanism maintenance. It checks the CB operating time and the need for mechanism maintenance is advised if the CB operation is slow. The operating time monitor records the time between issuing the tripping signal and the phase currents falling to zero. An alarm is issued when the operating time for any phase exceeds a user-defined setting OPTALM. The operating time is set in relation to the specified interrupting time of the CB. The operating time alarm can be enabled or disabled by setting the scheme switch [OPTAEN]. The maintenance program should comply with the switchgear manufacturer’s instructions. 3.3.5 Failure Alarms When a failure is detected by the automatic supervision, it is followed with an LCD message, LED indication, external alarm and event recording. Table 3.3.1 summarizes the supervision items and alarms. 40 6 F 2 T 0 1 7 6 The LCD messages are shown on the "Auto-supervision" screen, which is displayed automatically when a failure is detected or displayed by pressing ▼ key. The event record messages are shown on the "Event record" screen by opening the "Record" sub-menu. The alarms are retained until the failure is recovered. The alarms can be disabled collectively by setting the scheme switch [AMF] to "OFF". The setting is used to block unnecessary alarms during commissioning, test or maintenance. When the Watchdog Timer detects that the software is not running normally, LCD display and event recording of the failure may not function normally. Table 3.3.1 Supervision Items and Alarms Supervision Item LED "IN SERVICE" LED "ALARM" LED "Relay fail" Err:V0, Err:V2 (1) On/Off (2) On (4) V0 err, V2 err, Relay fail or Relay fail-A (2) (1) Off On (4) Relay fail ---- Off On (4) ---- Power supply monitoring Err:DC Off (3) Off Relay fail-A Trip circuit supervision Err:TC On On Off TC err, Relay fail-A CB state monitoring CB condition monitoring Trip count alarm Err:CB On On Off CB err, Relay fail-A ALM: TP COUNT On On Off TP COUNT ALM, Relay fail-A ALM: OP time On On Off OP time ALM, Relay fail-A AC input imbalance monitoring LCD Message A/D accuracy check Memory monitoring Watchdog Timer Operating time alarm Alarm record Message (1): Various messages are provided as expressed with "Err:---" in the table in Section 6.7.2. (2): The LED is on when the scheme switch [SVCNT] is set to "ALM" and off when set to "ALM & BLK" (refer to Section 3.3.5). The message "Relay fail-A" is recorded when the scheme switch [SVCNT] is set to "ALM". (3): Whether the LED is lit or not depends on the degree of the voltage drop. (4): The binary output relay "FAIL" operates. The failure alarm and the relationship between the LCD message and the location of the failure is shown in Table 6.7.1 in Section 6.7.2. 3.3.6 Trip Blocking When a failure is detected by the following supervision items, the trip function is blocked for as long as the failure exists, and is restored when the failure is removed. • A/D accuracy check • Memory monitoring • Watchdog Timer When a fault is detected by the AC input imbalance monitoring, the scheme switch [SVCNT] setting can be used to determine if both tripping is blocked and an alarm is output(ALM&BLK), or if only an alarm is output (ALM). 41 6 F 2 T 0 1 7 6 3.3.7 Setting The setting element necessary for the automatic supervision and its setting range are shown in the table below. Element [SVCNT] Range ALM&BLK/ALM Step [TCSPEN] [CBSMEN] Off/On Off/On Off Off Remarks Automatic supervision and input imbalance supervision Trip circuit supervision CB condition supervision [TCAEN] OFF/ON OFF Trip count alarm TCALM 1 - 10000 10000 Trip count alarm threshold setting 1 Default Off AC The scheme switch [SVCNT] is set in the "Application" sub-menu. Other scheme switches are set in the "Scheme sw" sub-menu. 3.4 Recording Function The GRE130 is provided with the following recording functions: Fault recording Event recording Disturbance recording These records are displayed on the LCD screen of the relay front panel or on a local or remote PC. 3.4.1 Fault Recording Fault recording is initiated by a tripping command from the GRE130 and the following items are recorded for one fault: Date and time Trip mode Operating phase Power system quantities Up to the 4 most-recent faults are stored as fault records. If a new fault occurs when 4 faults have been stored, the record of the oldest fault is deleted and the record of the latest fault is then stored. Date and time occurrence This is the time at which a tripping command has been initiated. The time resolution is 1 ms using the relay internal clock. Trip mode This shows the protection scheme such as OV1, UV1 etc. that output the tripping command. Faulted phase This is the phase to which a tripping command is output. 42 6 F 2 T 0 1 7 6 Power system quantities The following power system quantities are recorded both pre-fault and post-fault. 3.4.2 - Magnitude and phase angle of phase voltages (Va, Vb, Vc) - Magnitude and phase angle of phase-to-phase voltages (Vab, Vbc, Vca) - Magnitude and phase angle of zero sequence voltage which is measured directly in the form of the system residual voltage (Ve) - Magnitude and phase angle of symmetrical component voltages (V1, V2, V0) - Frequency (f) Event Recording The events shown in Appendix B are recorded with a 1 ms resolution time-tag when the status changes. For BI1 to BI6 commands, the user can select the items to be recorded and their status change mode to initiate recording as below. One of the following four modes is selectable. Modes Setting Not to record the event. N To record the event when the status changes to "operate". O To record the event when the status changes to "reset". R To record the event when the status changes both to "operate" and "reset". B For the setting, see Section 4.2.6.5. The default setting is "B" Up to 200 records can be stored. If an additional event occurs after 200 records have been stored, the oldest event record is overwritten. The LCD display only shows 100 records. All event records (200 records) can be displayed on a PC. For how to download all of the event records onto a PC refer to the RSM100 instruction manual. 3.4.3 Disturbance Recording Disturbance recording is initiated when the overvoltage or undervoltage starter element operates or a tripping command is initiated. Further, disturbance recording is initiated when a start command is initiated. The user can configure four disturbance record triggers. The records include a maximum of 8 analogue signals as shown in Table 3.4.1, 32 binary signals and the dates and times at which recording started. Any binary signal shown in Appendix B can be assigned using the binary signal setting of a disturbance record. Table 3.4.1 Analog Signals for Disturbance Recording Model APPL setting Model 410 , 411, 412 1PP 1PN 2PP 2PV 3PN 3PZ 3PP Vph Vph Vab Vab Va Va Vab Vbc Vbc Vb Vb Vbc Vc Vc Vca Ve Ve Analog signals Ve Ve 43 Ve 6 F 2 T 0 1 7 6 The LCD display only shows the dates and times of the disturbance records stored. Details can be displayed on a PC. For how to obtain disturbance records on a PC, see the RSM software instruction manual. The pre-fault recording time can be set between 0.1 and 4.9s and the post-fault recording time can be set between 0.1 and 3.0s. But the combined duration for the pre-fault and post-fault recording times is 5.0s or less. The number of records stored depends on the post-fault recording time. The approximate relationship between the post-fault recording time and the number of records stored is shown in Table 3.4.2. (Recording time = pre-fault recording time + post-fault recording time) Note: If the recording time setting is changed, the records stored so far are deleted. Table 3.4.2 Post Fault Recording Time and Number of Disturbance Records Stored Recording time 0.2s 1.0s 1.5s 2.0s 3.0s 4.0s 5.0s 50Hz 40 29 19 14 9 7 5 60Hz 40 24 16 12 8 6 5 Settings The elements necessary for initiating a disturbance recording and their setting ranges are shown in the table below. Element Range Step Default Remarks Time1 0.1-4.9 s 0.1 s 0.3 s Pre--fault recording time Time2 0.1-4.9 s 0.1 s 3.0 s Post--fault recording time OV 10.0-200.0 V 0.1 V 120.0 V Overvoltage detection UV 5.0-130.0 V 0.1 V 60.0 V Undervoltage detection ZPS 1.0-130.0 V 0.1 V 20.0 V Zero sequence overvoltage detection NPS 1.0-130.0 V 0.1 V 20.0 V Negative sequence overvoltage detection Starting disturbance recording using a tripping command or the starter element listed above is enabled or disabled by setting the following scheme switches. Element Range [Trip] Step Default Remarks OFF/ON ON Start by tripping command [OV] OFF/ON ON Start by OV operation [UV] OFF/ON ON Start by UV operation [ZPS] OFF/ON ON Start by ZPS operation [NPS] OFF/ON ON Start by NPS operation 44 6 F 2 T 0 1 7 6 3.5 Metering Function The GRE130 relay measures current and demand values of phase and phase-to-phase voltages, residual voltage, symmetrical component voltages and frequency. The measurement data shown below is displayed on the LCD of the relay front panel or on a local or remote PC. The following quantities are measured and updated every second. - Magnitude and phase angle of phase voltage (Va, Vb, Vc) - Magnitude and phase angle of phase-to-phase voltage (Vab, Vbc, Vca) - Magnitude and phase angle of symmetrical component voltage (V1, V2, V0) - Frequency (f) Maximum and minimum of frequency (f: max, min) - Frequency rate-of-change (df / dt) The above system quantities are displayed in values on the primary side or on the secondary side as determined by a setting. To display accurate values, it is necessary to set the VT ratio as well. For the setting method, see "Setting the metering" in 4.2.6.6 and "Setting the parameter" in 4.2.6.7. In the case of the maximum and minimum values display above, the measured quantity is averaged over a rolling 15 minute time window, and the maximum and minimum recorded average values are shown on the display screen. The displayed quantities depend on [APPL] settings and relay model as shown in Table 3.5.1. Input voltage greater than 0.06V at the secondary side are required for measurement. Phase angles above are expressed taking the positive sequence voltage as a reference phase angle, where leading phase angles are expressed as positive, (+). Table 3.5.1 Model APPL Displayed Quantity Model 410 1PP 1PN 2PP 2PV 3PN Van Vbn Vcn Vph 3PZ 3PP Vab Vbc Vcb V1 V2 V0 f f max f min df / dt 45 6 F 2 T 0 1 7 6 3.6 Control Function The relay is provided with the following control functions: • CB control • Interlocking • Change of CB control hierarchy The CB control function operates the CB by using the open command key ○ or close command key | on the front panel of the relay, a BI command from remote state or by using the communication function. The interlock function blocks the CB close command using the control lock signal of the BI command.The change of CB control hierarchy changes the CB control state to Local or Remote. The Local mode is controled at the front panel of the relay (see chapter 4.2.7). The Remote mode is controlled by BI command or by a communication function of Modbus (see Appendix M) or IEC 61850 (see Appendix P). 46 6 F 2 T 0 1 7 6 4. User Interface 4.1 Outline of User Interface The user can access the relay from the front or rear panel. Local communication with the relay is also possible using RSM (Relay Setting and Monitoring) via a USB port. Furthermore, remote communication is also possible using MODBUS communication via an RS485 port. This section describes the front panel configuration and the basic configuration of the menu tree for the local human machine communication ports and HMI (Human Machine Interface). 4.1.1 Front Panel As shown in Figure 3.1.1, the front panel is provided with a liquid crystal display (LCD), light emitting diodes (LED), operation keys, and USB type B connector. (a) Model 410, 411 (b) Model 412 Figure 4.1.1 Front Panel of GRE130 (without cover) LCD The LCD screen, provided with an 8-line, 16-character display and back-light, provides the user with information such as records, statuses and settings. The LCD screen is normally unlit, but pressing ▼ key will display the digest screen and pressing ENTER key will display the mainmenu screen. These screens are turned off by pressing the END key when viewing the LCD display at the top of the main-menu. If any display is left for approximately 5 minutes without operation, the back-light will go off. LED There are 14 LED displays. The signal labels and LED colors are defined as follows: 47 6 F 2 T 0 1 7 6 Label Color Remarks IN SERVICE Green Lit when the relay is in service and flashing when the relay is in “Test” menu. TRIP Red Lit when a trip command is issued. ALARM Yellow Lit when an alarm command is issued or a relay alarm is detected. Relay Fail Red Lit when a relay failure is detected. CB CLOSED R /G / Y Lit when CB is closed. CB OPEN Green Lit when CB is open. Local Yellow Lit when Local Control is enabled Remote Yellow Lit when Remote Control is enabled (LED1) R/G/Y user-configurable (LED2) R/G/Y user-configurable (LED3) R/G/Y user-configurable (LED4) R/G/Y user-configurable (LED5) R/G/Y user-configurable (LED6) R/G/Y user-configurable LED1-6 are configurable. For setting, see Section 4.2.6.10. The TRIP LED illuminates when the relay operates and remains lit even after the trip command releases . The TRIP LED can be extinguished by pressing the RESET key. Other LEDs are lit as long as a signal is present and the RESET key is invalid while the signal is maintained. Operation keys , ▼ ▼, ▲, ▲ The operation keys are used to display records, status, and set values on the LCD, as well as to input or change set values. The function of each operation key is as follows: : Used to move between lines displayed on a screen and to enter numerical values and text strings. CANCEL : Used to cancel entries and return to the upper screen. END : Used to end the entering operation, return to the upper screen or turn off the display. ENTER : Used to store or establish entries. RESET key Pressing the RESET key causes the Trip LED to turn off and latched output relays to be released. Control keys The control keys are used for CB control. When the LCD display cursor is not at the CB control position-(CB close/open , Local / Remote), the Control keys will not function. ○ : Used for CB open operation. When the CB is in the open position, the ○ key does not function. 48 6 F 2 T 0 1 7 6 ② | : Used for CB close operation. When the CB is in the closed position, the | key does not function ③ L/R : Used for CB control hierarchy (local / remote) change. CAUTION The CB close control key | is linked to BO1 and the CB open control key ○ is linked to BO2, when the control function is enabled. USB connector The USB connector is a B-type connector for connection with a local personal computer. 4.1.2 Communication Ports The following three interfaces are provided as communication ports: • USB port • RS485 port • Optional Communication Unit port USB port This connector is a standard B-type connector for USB transmission and is mounted on the front panel. By connecting a personal computer (PC) to this connector, setting operation and display functions can be performed. RS485 port The RS485 port is used for MODBUS communication to connect between relays and to construct a network communication system. The RS485 port is provided on the rear of the relay as shown in Figure 4.1.2. TB2 TB1 RS485 Port Figure 4.1.2 Location of RS485 Port 49 6 F 2 T 0 1 7 6 Optional Fibre or Ethernet LAN port for model 412A An optional Ethernet LAN port can be connected to substation automation system via an Ethernet communication networks using the IEC 61850 protocol. 100Base-TX (T1: RJ-45 connector) for Ethernet LAN is provided at the rear of the relay, as shown in Figure 4.1.3. TB2 TB3 TB1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 3 5 7 9 11 2 4 6 8 10 12 for Optional Communication Port Figure 4.1.3 Location of Optional Communication Port 4.2 Operation of the User Interface The user can access such functions as recording, measurement, relay setting and testing with the LCD display and operation keys. Note: LCD screens depend on the relay model and the scheme switch setting. Therefore, LCD screens described in this section are samples for a typical model. 4.2.1 LCD and LED Displays Displays during normal operation When the GRE130 is operating normally, the green "IN SERVICE" LED is lit and the LCD is off. Press the ▼ key when the LCD is off to display the digest screens which are the "Indication", "Metering", "Latest fault", "Auto-supervision" and "Alarm Display" screens in turn. "Latest fault", "Auto-supervision" and "Alarm Display" screens are displayed only when there is some data. The following are the digest screens and can be displayed without entering the menu screens. Indication I N D 1 [ 0 0 0 0 0 0 0 0 ] I N D 2 [ 0 0 0 0 0 0 0 0 ] 50 6 F 2 T 0 1 7 6 Metering V a n * * . * * V V b n * * . * * V V c n * * . * * V V 0 * * . * * V V 1 * * . * * V V 2 * * . * * V f * * . * * H z * * . * * H z f / t / s To clear the latched indications (LEDs, LCD screen of Latest fault) of the latest fault indication, press RESET key for 3 seconds or more. For any display, the back-light is automatically turned off after five minutes. Indication This screen shows the status of elements assigned as a virtual LED. I N D 1 [ 0 0 0 0 0 0 0 0 ] I N D 2 [ 0 0 0 0 0 0 0 0 ] Status of element, Elements depend on user setting. 1: Operate, 0: Not operate (Reset) Displays in tripping Latest fault P h a s e : Faulted phases. A B C : Tripping element O V 1 If a fault occurs and a tripping command is output when the LCD is off, the red "TRIP" LED is lit as well as other configurable LEDs if assigned to trigger by tripping. Press the ▼ to scroll the LCD screen to read the rest of the messages. Press the RESET key for more than 3s to reset the LEDs; the Trip LED and configurable LEDs (LED1 through LED6) are assigned to a latched signal if triggered by tripping. To return from the menu screen to the digest "Latest fault" screen, do the following: • Return to the top screen of the menu by repeatedly pressing the END or CANCEL key. 51 6 F 2 T 0 1 7 6 • Press the END key to turn off the LCD when the LCD is displaying the top menu. • Press the ▼ key to display the digest screens. Displays in automatic supervision operation Auto-supervision E r r : R O M , A / D If the automatic supervision function detects a failure when the LCD is off, the "Auto-supervision" screen is displayed automatically, showing the location of the failure, and the "ALARM" LED lights. Press the ▼ to display other digest screens in turn including the "Metering" and "Latest fault" screens. Press the RESET key to turn off the LEDs. However, if the failure continues, the "ALARM" LED remains lit. After recovery from a failure, the "ALARM" LED and "Auto-supervision" display turn off automatically. If a failure is detected when any of the screens is displayed, the current screen remains displayed and the "ALARM" LED lights. When any of the menu screens is displayed, the RESET key is available. To return to the digest "Auto-supervision" screen, do the following: • Return to the top screen of the menu by repeatedly pressing the END or CANCEL key. • Press the END key to turn off the LCD. • Press the ▼ key to display the digest screens. Alarm Display Alarm Display (ALM1 to ALM4) * * * * * * * * * * * * * * * * * * * * * * : A L M 1 The four alarm screens can be provided, and their text messages are defined by the user. (For setting, see Section 4.2.6.8) These alarms are raised by associated binary inputs. Press the ▼ to display other digest screens in turn including the "Metering" and "Latest fault" screens. To clear the Alarm Display, press RESET key. Clearing is available after displaying up to ALM4. 4.2.2 Relay Menu Figure 4.2.1 shows the menu hierarchy for the GRE130. The menu has some sub-menus, "Record", "Status", "Set. (view)", "Set. (change)", and "Test". For details of the menu hierarchy, see Appendix D. 52 6 F 2 T 0 1 7 6 Menu Fault Record Event Disturbance Counter Status Metering Binary I/O Relay element Time sync. Clock adjust. LCD contrast Set. (view) Version Description Comms Record Status Protection Binary I/P Binary O/P LED Control Frequency Set. (change) Password Description Comms Record Status Protection Binary I/P Binary O/P LED Control Frequency Control Password(Ctrl) Local / Remote CB close/open Test Password(test) Switch Binary O/P Figure 4.2.1 Relay Menu Record In the "Record" menu, the fault records, event records, disturbance records and counts such as trip count can be accessed. 53 6 F 2 T 0 1 7 6 Status The "Status" menu displays the power system quantities, binary input and output status, relay measuring element status, signal source for time synchronisation (BI or RSM), adjusts clock and LCD contrast. Set. (view) The "Set. (view)" menu displays the relay version, description, relay address and baud rate for RSM, the current settings of record, status, protection, binary inputs, configurable binary outputs and configurable LEDs. Set. (change) The "Set. (change)" menu is used to change the settings for password, description, relay address and baud rate for Modbus communication, record, status, protection, binary inputs, configurable binary outputs and configurable LEDs. Since this is an important menu and is used to change settings related to relay tripping, it has password security protection. Control The "Control" menu is used to operate the CB. When the cursor (>) is in the Local / Remote position, the CB control hierarchy change over key L/R is enabled. When the cursor (>) is in the CB close/open position, the CB control keys ○ and | are enabled. Since this is an important menu and is related to relay tripping, it has password security protection. Test The "Test" menu is used to set test switches and to forcibly operate binary output relays. When the LCD is off, press the ENTER key to display the top "MAIN MENU" screen and then proceed to the relay menus. > R e M A I N c d o r M E N U S t a t u s S e t . ( v i S e t . ( c h a n g C o n t o l T e s r e w ) e ) t To display the "MAIN MENU" screen when the digest screen is displayed, press the ▼ key to turn off the LCD, then press the ENTER key. Press the END key when the top screen is displayed to turn off the LCD. An example of the sub-menu screen is shown below. The top line shows the hierarchical layer. The 8th line under some items is not displayed for all of the screens. " ",or " " or " " displayed on the far right shows that lower or upper lines exist. To move the cursor downward or upward for setting or for viewing other lines not displayed on the window, use the ▼ and ▲ keys. 54 6 F 2 T 0 1 7 6 / 4 T r S c i p > T r i p O f f / h e m e s w _ 1 O n B I O f 1 f / O n O V O f 1 f / O n U V O f 1 f / O n Z P S O f 1 F / O n N P S O f f 1 / O n F R Q O f f 1 / O n To return to the higher screen or move from the right side screen to the left side screen in Appendix D press the END or CANCEL key. The CANCEL key can also be used to return to the higher screen but it must be used carefully because it may cancel entries made so far. To move between screens of the same hierarchical depth, first return to the higher screen and then move to the lower screen. 4.2.3 Displaying Records The sub-menu of "Record" is used to display fault records, event records, disturbance records and counts such as trip count. 4.2.3.1 Displaying Fault Records To display fault records, do the following: • Open the top "MAIN MENU" screen by pressing the ENTER key. • Select "Record" to display the "Record" sub-menu. / 1 R e c o r d > F a u l t u r b a E v e n t D i s t C o u n t e n c r • Select "Fault" to display the "Fault" screen. 55 e 6 F 2 T 0 1 7 6 / 2 F a > V i e w C l e a u l t r e c o r d r • Select "View record" to display the dates and times of the fault records stored in the relay from the top in new-to-old sequence. / 3 F a u l t > ♯ 1 0 1 / J a n / 2 0 1 0 0 : 0 0 : . 0 1 0 0 1 / J a n / 2 0 1 0 0 : 0 0 : . 0 0 0 0 1 / J a n / 2 0 1 0 0 : 0 0 : . 0 0 ♯ 2 0 ♯ 3 0 0 0 0 0 0 0 0 0 • Move the cursor to the fault record line to be displayed using the ▲ and ▼ keys and press the ENTER key to display the details of the fault record. The lines which are not displayed in the window can be displayed by pressing the ▲ and ▼ keys. / 4 P r e F a u l t f a u l t * * * ♯ 1 v a l u e . * * k V * * . * ° * * . * * k * * * . * ° * * . * * k * * * . * ° * * . * * k * * * . * ° * * . * * k * * * . * ° * * . * * k * * * . * ° V p h * * . * * k V V 0 * * . * * k V * * * . * ° * * . * * k * * * . * ° * * . * * k * * * . * ° * * . * * H z * * . * * H z V a n V b n V c n V a b V b c V c a V 1 V 2 f f / t 56 s V V V V V V V / s 6 F 2 T 0 1 7 6 Note: Phase angles above are expressed taking that of positive sequence voltage (V1) as a reference phase angle. When the V1 is not available, phase angles are not displayed. Frequency above is displayed as "0Hz" when only residual voltage (zero sequence voltage) is input to the relay To clear all the fault records, do the following: • Open the "Record" sub-menu. • Select "Fault" to display the "Fault" screen. • Select "Clear" to display the following confirmation screen. C l e a r r e E N D = Y c o r d s C A N C E L = N • Press the END (= Y) key to clear all the fault records stored in non-volatile memory. If all fault records have been cleared, the "Latest fault" screen of the digest screens is not displayed. 4.2.3.2 Displaying Event Records To display event records, do the following: • Open the top "MAIN MENU" screen by pressing the ENTER key. • Select "Record" to display the "Record" sub-menu. • Select "Event" to display the "Event" screen. / 2 E v > V i e w C l e a e n t r e c o r d r • Select "View record" to display the events with date from the top in new-to-old sequence. / 3 E v e n t 2 4 / A u g / 2 0 1 O V 1 ・ A t r i P 2 4 / A u g / 2 0 1 O V 1 ・ A t r i p 2 4 / A u g / 2 0 1 O V 1 ・ A t r i p 2 4 / A u g / 2 0 1 O V 1 ・ A t r i p 2 4 / A u g / 2 0 1 O V 1 ・ A t r p i 57 0 1 0 0 O n 0 0 9 9 O N 0 9 8 O n 0 0 0 2 O n 0 0 0 1 O n The time is displayed by pressing the Press the ▲ / 3 ▼ 6 F 2 T 0 1 7 6 key. E v e n t 1 3 : 2 2 : 4 5 . 2 O V 1 ・ A t r i p 1 3 : 2 2 : 4 5 . 2 O V 1 ・ A t r i p 1 3 : 2 2 : 4 5 . 1 O V 1 ・ A t r i p 1 3 : 2 2 : 4 4 . 1 O V 1 ・ A t r i p 1 3 : 2 2 : 4 4 . 1 O V 1 ・ A t r p i 1 1 O n 0 0 O N 1 1 O n 1 1 O n 0 0 O n key to return the screen with date. The lines which are not displayed in the window can be displayed by pressing the ▲ and ▼ keys. To clear all the event records, do the following: • Open the "Record" sub-menu. • Select "Event" to display the "Event" screen. • Select "Clear" to display the following confirmation screen. C l e a r E N D = Y r e c o r d s C A N C E L = N • Press the END (= Y) key to clear all the event records stored in non-volatile memory. "Data lost" or "E.record CLR" and "F.record CLR" are displayed at the initial setting. 4.2.3.3 Displaying Disturbance Records Details of disturbance records can be displayed on the PC screen only (*); the LCD displays only the recorded date and time for all disturbances stored in the relay. They are displayed in the following sequence. (*) For the display on the PC screen, refer to the RSM100 manual. • Open the top "MAIN MENU" screen by pressing the ENTER key. • Select "Record" to display the "Record" sub-menu. • Select "Disturbance" to display the "Disturbance" screen. 58 6 F 2 T 0 1 7 6 / 2 D i > V i e w C l e a s t u r b a n c r e o d c r e r • Select "View record" to display the date and time of the disturbance records from the top in new-to-old sequence. / 3 D i ♯ 1 0 ♯ 2 0 ♯ 3 0 s t u r b a n c 0 1 / J a n / 0 : 0 0 : 0 0 1 / J a n / 0 : 0 0 : 0 0 1 / J a n / 0 : 0 0 : 0 e 2 0 0 9 0 . 0 0 0 2 0 0 9 0 . 0 0 0 2 0 0 9 0 . 0 0 0 The lines which are not displayed in the window can be displayed by pressing the ▲ and ▼ keys. To clear all the disturbance records, do the following: • Open the "Record" sub-menu. • Select "Disturbance" to display the "Disturbance" screen. • Select "Clear" to display the following confirmation screen. C l e a r r e E N D = Y c o r d s C A N C E L = N • Press the END (= Y) key to clear all the disturbance records stored in non-volatile memory. 4.2.3.4 Displaying Counter • Open the top "MAIN MENU" screen by pressing the ENTER key. • Select "Record" to display the "Record" sub-menu. • Select "Counter" to display the "Counter" screen. / 2 C o u n t c o e r > V i e w u n t e r C l e a r T r i p s C l e a r T r i p s A (*) C l e a r T r i p s B (*) C l e a r T r i p s C (*) (*) Note: These settings are only available when single phase External Trip BI functions 59 6 F 2 T 0 1 7 6 are used. In this case, the main "Clear Trips" option is not available. • Select "Display" to display the counts stored in the relay. / 3 C o u n t e r * * * * * * T r i p s T r i p s A * * * * * * (*) T r i p s B * * * * * * (*) T r i p s C * * * * * * (*) (*) Note: These settings are only available when single phase External Trip BI functions are used. In this case, the main "Trips" option is not available. The lines which are not displayed in the window can be displayed by pressing the ▲ and ▼ keys. To clear each count, do the following: • Open the "Record" sub-menu. • Select "Counter" to display the "Counter" screen. • Select "Clear Trips" to display the following confirmation screen. C l e a r T r E N D = Y i p s ? C A N C E L = N • Select "Clear Trips A" to display the following confirmation screen. C l e a r T r E N D = Y i p s A ? C A N C E L = N • Select "Clear Trips B" to display the following confirmation screen. C l e a r T r E N D = Y • i p s B ? C A N C E L = N Select "Clear Trips C" to display the following confirmation screen. C l e a r E N D = Y T r i p s C ? C A N C E L = N • Press the END (= Y) key to clear the count stored in non-volatile memory. 60 6 F 2 T 0 1 7 6 4.2.4 Status Display From the sub-menu "Status", the following status condition can be displayed on the LCD: Metering data of the protected line, apparatus, etc. Status of binary inputs and outputs Status of measuring elements output Status of time synchronisation source Status of clock adjustment Status of LCD contrast The data is updated every second. 4.2.4.1 Displaying Metering Data To display metering data on the LCD, do the following: • Select "Status" on the top "MAIN MENU" screen to display the "Status" screen. / 1 S t a t u s t e r i n g B i n a r y I / O R e l y e l e m e T i m e y n c . C l o a d j u s t n t r a t > M e a s c k L C D c o s n t . . • Select "Metering" to display the "Metering" screen. / 4 M e V a n V b n V c n V a b V b c V c a V p h t e r i n g * * . * * k * * * . * ° * * . * * k * * * . * ° * * . * * k * * * . * ° * * . * * k * * * . * ° * * . * * k * * * . * ° * * . * * k * * * . * ° * * . * * k 61 V APPL = 3PP V V V APPL = 3PN V V V APPL = 1PP 6 F 2 T 0 1 7 6 V 0 V 1 V 2 f * * . * * k V * * * . * ° * * . * * k * * * . * ° * * . * * k * * * . * ° * * . * * H z V V f m a x * * . * * H z f m i n * * . * * H z f / t * * . * * H z / s f / t x * * . * * H z / s f / t n * * . * * H z / s Note: Phase angles above are expressed taking that of positive sequence voltage (V1) as a reference phase angle. When the V1 is not available, phase angles are not displayed. Frequency above is displayed as "0Hz" when only residual voltage (zero sequence voltage) is input to the relay 4.2.4.2 Displaying the Status of Binary Inputs and Outputs To display the binary input and output status, do the following: • Select "Status" on the top "MAIN MENU" screen to display the "Status" screen. • Select "Binary I/O" to display the binary input and output status. / 2 B i n a r I P [ 0 0 0 0 0 O P [ 0 0 0 0 0 O P [ 0 0 0 0 2 y I / 0 O ] ] ] The display format is shown below. [ Input (IP) BI1 BI2 BI3 BI4 BI5 BI6 Output (OP) BO1 BO2 BO3 BO4 FAIL Output (OP2) BO5 BO6 BO7 BO8 ] Line 1 shows the binary input status. BI1 to BI6 correspond to each binary input signal. For the binary input signal, see Appendix B and G. The status is expressed with logical level "1" or "0" at the photo-coupler output circuit. BI3 to BI6 are not available for model 410. Line 2 shows the binary output status. All binary outputs BO1 to BO4 and FAIL are configurable. The status of these outputs is expressed with logical level "1" or "0" at the input circuit of the output relay driver. That is, the output relay is energised when the status is "1". FAIL is a normally closed contact for detection of a relay fail condition. Line 3 shows the binary output status for model 412. BO5-8 (OP2) are available only at model 412 62 6 F 2 T 0 1 7 6 4.2.4.3 Displaying the Status of Measuring Elements To display the status of measuring elements on the LCD, do the following: • Select "Status" on the top "MAIN MENU" screen to display the "Status" screen. • Select 3 "Ry element" to display the status of the relay elements. / 2 R y e l A N O V 1 - 3 [ 0 0 0 ] B N O V 1 - 3 [ 0 0 0 ] C N O V 1 - 3 [ 0 0 0 ] A B O V 1 - 3 [ 0 0 0 ] B C O V 1 - 3 [ 0 0 0 ] C A O V 1 - 3 [ 0 0 0 ] O V 1 - [ 0 0 0 ] A N U V 1 - 3 [ 0 0 0 ] B N U V 1 - 3 [ 0 0 0 ] C N U V 1 - 3 [ 0 0 0 ] A B U V 1 - 3 [ 0 0 0 ] B C U V 1 - 3 [ 0 0 0 ] C A U V 1 - 3 [ 0 0 0 ] U V 1 - [ 0 0 0 ] 3 3 e m e n t V Z P S 1 - 2 [ 0 0 ] V N P S 1 - 2 [ 0 0 ] [ 0 0 0 F R Q 1 - 4 0 ] The operation status of phase and residual overcurrent elements are shown as below. [ AN OV1-3 OV1 OV2 OV3 A phase OV elements BN OV1-3 OV1 OV2 OV3 B phase OV element CN OV1-3 OV1 OV2 OV3 C phase OV element AB OV1-3 OV1 OV2 OV3 A to B phase OV elements BC OV1-3 OV1 OV2 OV3 B to C phase OV element CA OV1-3 OV1 OV2 OV3 C to A phase OV element OV1-3 OV1 OV2 OV3 OV elements AN UV1-3 UV1 UV2 UV3 A phase UV element BN UV1-3 UV1 UV2 UV3 B phase UV element CN UV1-3 UV1 UV2 UV3 C phase UV element AB UV1-3 UV1 UV2 UV3 A to B phase UV element BC UV1-3 UV1 UV2 UV3 B to C phase UV element CA UV1-3 UV1 UV2 UV3 C to A phase UV element ZPS1-2 NPS1-2 FRQ1-4 ZPS1 NPS1 FRQ1 ZPS2 NPS2 FRQ2 FRQ3 Zero Phase Sequence element Negative Phase Sequence element Frequency element FRQ4 63 ] 6 F 2 T 0 1 7 6 The status of each element is expressed with logical level "1" or "0". Status "1" means the element is in operation. 4.2.4.4 Displaying the Status of the Time Synchronisation Source The internal clock of the GRE130 can be synchronised with external clocks such as the binary input signal clock, Modbus or IEC60870-5-103 or SNTP(IEC61850). To display on the LCD whether these clocks are active (=Act.) or inactive (=Inact.) and which clock the relay is synchronised with, do the following: • Select "Status" on the top "MAIN MENU" screen to display the "Status" screen. • Select "Time sync." to display the status of time synchronisation sources. / 2 T * B I M o d I E C S N T i b m u e s s y n c . : A C T . : I n a c t I n a c t I n a c t P . The asterisk on the far left shows that the internal clock is synchronised with the marked source clock. If the marked source clock is inactive, the internal clock runs locally. Note: If the Binary input signal has not been detected for one hour or more after the last detection, the status becomes "inactive". For details of the setting time synchronisation, see Section 4.2.6.6. 4.2.4.5 Clock Adjustment To adjust the clock when the internal clock is running locally, do the following: • Select "Status" on the "MAIN MENU" screen to display the "Status" screen. • Select "Clock adjust." to display the setting screen. / 2 > M i H o D a 2 6 / A u g / 0 0 : 0 0 0 0 n u t e Y e 0 _ 0 _ 6 _ 8 _ 0 _ u r y 2 M o : n t h a r 2 0 1 64 2 0 1 0 [ L ] 6 F 2 T 0 1 7 6 Lines 1 and 2 show the current date and time. The time can be adjusted only when the clock is running locally. When[BI], [M] or [S] is active, the adjustment is invalid. • Enter a numerical value for each item and press the ENTER key. For details on how to enter a numerical value, see 4.2.6.1. • Press the END key to adjust the internal clock to the set hours without fractions and return to the previous screen. If a date which does not exist in the calendar is set and END is pressed, "**** Error ****" is displayed on the top line and the adjustment is discarded. Return to the normal screen by pressing the CANCEL key and adjust again. 4.2.4.6 LCD Contrast To adjust the contrast of LCD screen, do the following: • Select "Status" on the "MAIN MENU" screen to display the "Status" screen. • Select "LCD contrast" to display the setting screen. / 2 L C D C o n t r a s t ■ ■ ■ ■ 4.2.5 ▼ ▼ ▲ ▲ • Press the or key to adjust the contrast. The characters on the screen become thinner by pressing the key. key and thicker by pressing the Viewing the Settings The sub-menu "Set. (view)" is used to view the settings made using the sub-menu "Set. (change)". The following items are displayed: Relay version Description Relay address and baud rate for Modbus communication or optional communication. Record setting Status setting Protection setting Binary input setting Binary output setting LED setting Control setting Frequency setting Enter an item on the LCD to display each item as described in the previous sections. 65 6 F 2 T 0 1 7 6 4.2.5.1 Relay Version To view the relay version, do the following. • Press the "Set.(view)" on the main menu. / 1 S e t . ( v i e w ) > V e r s i o n D e s c r i p t i o n C o m m s R e c o r S t a t u s P r o t e c t i o n B i n a r y I / P B i n a r y O / P r o d L E D C o n t l • Press the "Version" on the "Set.(view)" menu. / 2 V e r > R e l a y S o f t s i o n t y p e w a r e . • Select "Relay type" to display the relay type form and model number. (ex.;GRE130-411A-10-10) G R E 1 3 - 1 0 - 4 1 1 A - 1 0 0 •Select "Software" to display the relay software type form and version. (ex.;GS1EM1-03-A) ■ S o f t w a r e G S 1 E M 1 - 0 ■ P L C d a t a P G R E 1 3 0 ( * * * * * * 3 - * A * * * * * ) 66 6 F 2 T 0 1 7 6 4.2.5.2 Settings The "Description","Comms","Record", "Status","Protection","Binary I/P","Binary O/P" ,"LED" , "Control" and "Frequency" screens display the current settings input using the "Set. (change)" sub-menu. 4.2.6 Changing the Settings The "Set. (change)" sub-menu is used to make or change settings for the following items: Password Description Relay address and IP address Baud rate in IEC60870-103 or Modbus IEC 61850 setting Recording setting Status setting Protection setting Binary input setting Binary output setting LED setting Control setting Frequency setting All of the above settings except the password can be seen using the "Set. (view)" sub-menu. CAUTION Modification of settings : Care should be taken when modifying settings for "active group", "scheme switch" and "protection element" in the "Protection" menu. Dependencies exist between the settings in the various menus, with settings in one menu becoming active (or inactive) depending on the selection made in another menu. Therefore, it is recommended that all necessary settings changes be made while the circuit breaker tripping circuit is disconnected. Alternatively, if it is necessary to make settings changes with the tripping circuit active, then it is recommended to enter the new settings into a different settings group, and then change the "active group" setting, thus ensuring that all new settings become valid simultaneously. 4.2.6.1 Setting Method There are three setting methods as follows: - To enter a selected item - To enter a text string - To enter numerical values To enter a selected item When the screen shown below is displayed, setting of the relay can be performed as follows. 67 6 F 2 T 0 1 7 6 The cursor can be moved to the upper or lower lines within the screen by pressing the ▲ and ▼ keys. If a setting (change) is not required, skip the line with the ▲ and ▼ keys. / 1 S e t . ( c > P a s s w o r d D e s c r p C o m m s R e c S t a t u s P r o t e c t B i n a r B i n a o h a n g t i o n i o n y I / P r y O / P o r i e ) d L E D C o n t r F r e u e q l n c y • Move the cursor to a setting item. • Press the ENTER key. To enter a text string Texts strings are entered under "Plant name" or "Description" screen. / 2 D e > P l D e s c a n t s c r i r i p t n a m e p i t o i o n n ▼ ▲ and to move the blinking cursor down, up, left and To select a character, use keys ▼ , ▲ , right. "→" and "←" on the final line indicate a space and backspace, respectively. A maximum of 22 characters can be entered. _ A B C D E F G H I J K L M N O P Q R S T U V W X Y Z a b c d e g h i j K l m n o p q r s t u v w x y z 0 1 2 3 4 5 6 7 8 9 ( ) [ @ _ { } * / + - < = > ! “ ♯ $ % & ‘ : ; , . ^ ` ] f • Set the cursor position in the bracket by selecting "→" or "←" and pressing the ENTER key. • Move the blinking cursor to select a character. • Press the ENTER key to enter the blinking character at the cursor position in the brackets. • Press the END key to confirm the entry and return to the upper screen. 68 6 F 2 T 0 1 7 6 To correct the entered character, do either of the following: • Discard the character by selecting "←" and pressing the ENTER key and enter the new character. • Discard the whole entry by pressing the CANCEL key and restart the entry from the beginning. To enter numerical values When the screen shown below is displayed, setting can be performed as follows: The number to the left of the cursor shows the current setting or default setting set at shipment. The cursor can be moved to the upper or lower lines within the screen by pressing the ▲ and ▼ keys. If a setting (change) is not required, skip the line with the ▲ and ▼ keys. / 4 T i T i m e m e / S t 1 a r t _ e s > T i m e 1 2 . 0 s T i m e 2 2 . 0 s 2 0 . 0 V U V 6 0 . 0 V Z P S 2 0 . 0 V N P S 2 0 . 0 V O V 1 r ▼▲ ▲ • Press the or the ▼ • Move the cursor to a setting line. or key to set a desired value. The value can be raised or lowered by pressing key. , • Press the ENTER key to enter the value. • After completing the setting on the screen, press the END key to return to the upper screen. To correct the entered numerical value, do the following. • If it is before pressing the ENTER key, press the CANCEL key and enter the new numerical value. • If it is after pressing the ENTER key, move the cursor to the line that is to be corrected by pressing the ▲ and ▼ keys and enter the new numerical value. Note: If the CANCEL key is pressed after any entry is confirmed by pressing the ENTER key, all the entries made so far on the screen concerned are canceled and screen returns to the upper one. To complete the setting Enter after making entries on each setting screen by pressing the ENTER key, the new settings are not yet used for operation, although they are stored in memory. To validate the new settings, take the following steps. • Press the END key to return to the upper screen. Repeat this until the confirmation screen shown below is displayed. The confirmation screen is displayed just before returning to the "Set. (change)" sub-menu. 69 6 F 2 T 0 1 7 6 C h a n g e s E N T E R = Y e t t i n g s ? C A N C E L = N • When the screen is displayed, press the ENTER key to commence operation using the new settings, or press the CANCEL key to correct or cancel entries. In the latter case, the screen will return to the setting screen to enable re-entries. Press the CANCEL key to cancel entries that have been made so far and to return to the "Set. (change)" sub-menu. 4.2.6.2 Password For the sake of security of Setting changes and Testing, password protection can be set as follows: • Select "Set. (change)" on the "MAIN MENU" screen to display the "Setting change" screen. • Select "Password" to display the "Password" screen. • Enter a 4-digit number within the brackets after "Input" and press the ENTER key. S e I t . ( c h a n g n p u t 1 2 3 4 5 [ 6 7 8 9 e ) _ ] 0 < • For confirmation, enter the same 4-digit number in the brackets after "Retype". S e t . R e t y p e 1 2 3 4 5 ( c h a n g [ 6 7 8 9 _ e ) ] 0 < • Press the END key to display the confirmation screen. If the retyped number is different from that first entered, the following message is displayed on the bottom of the "Password" screen before returning to the upper screen. "Unmatch passwd!" Re-entry is then requested. • Select "Test" to set the password for the test. Set the password in the same manner as that of "Setting" above. Password trap After the password has been set, the password must be entered in order to enter the setting change screens. If "Set. (change)" or "Test" is entered on the top "MAIN MENU" screen, the password trap screen "Password" is displayed. If the password is not entered correctly, it is not possible to move to the "Setting (change)" or "Test" sub-menu screens. 70 6 F 2 T 0 1 7 6 S e t ( c P a s w o r d 1 2 3 4 5 8 s . 6 7 h a n g [ 9 e ) _ ] 0 < Canceling or changing the password To cancel the password protection, enter "0000" in the two brackets on the "Password" screen. The "Set. (change)" screen is then displayed without having to enter a password. The password can be changed by entering a new 4-digit number on the "Password" screen in the same way as the first password setting. If you forget the password Press CANCEL and RESET keys together for one second on the top "MAIN MENU" screen. The screen goes off, and the password protection of the GRE130 is canceled. Set the password again. 4.2.6.3 Plant Name To enter the plant name and other data, do the following. The data will be attached to records. • Select "Set. (change)" on the "MAIN MENU" screen to display the " Set. (change)" screen. • Select "Description" to display the "Description" screen. / 2 D e > P l D e s c a n t s c r i r i p t n a m e p i t o i o n n • To enter the plant name, select "Plant name" on the "Description" screen. • To enter special items, select "Description" on the "Description" screen. • To enter the name for Alarm∗, select "Alarm∗" on the "Description" screen. _ A B C D E F G H I J K L M N O P Q R S T U V W X Y Z a b c d e g h i j k l m n o p q r s t u v w x y z 0 1 2 3 4 5 6 7 8 9 [ @ _ { } * / + - $ % & ‘ : ; , . ^ ` ] • Enter the text string. 71 < = > ! f ( ) “ ♯ 6 F 2 T 0 1 7 6 4.2.6.4 Communication If the relay is linked with Modbus or optional communication, the relay address must be set. Do this as follows: • Select "Set.(change)" on the main "MAIN MENU" screen to display the "Set.(change)" screen. • Select "Comms" to display the "Comms" screen. / 2 C o m m s > A d d r . / c h S w i t P a r a m . • Select "Addr./Param." on the "Comms" screen to enter the relay address number. / 3 A d d M o > r . / P a r a m . d b u s M o d b u I E C I P 1 ‐ 1 0 I P 1 ‐ 2 0 I P 1 ‐ 3 0 I P 1 ‐ 4 0 S M 1 ‐ 1 0 This setting is displayed if submodel of S M 1 ‐ 2 0 communication type is A-D. S M 1 ‐ 3 0 S M 1 ‐ 4 0 G W 1 ‐ 1 0 G W 1 ‐ 2 0 G W 1 ‐ 3 0 G W 1 ‐ 4 0 I P 2 ‐ 1 0 I P 2 ‐ 2 0 I P 2 ‐ 3 0 I P 2 ‐ 4 0 S M 2 ‐ 1 0 This setting is displayed if submodel of S M 2 ‐ 2 0 communication type is B or D. S M 2 ‐ 3 0 S M 2 ‐ 4 0 G W 2 ‐ 1 0 G W 2 ‐ 2 0 G W 2 ‐ 3 0 G W 2 ‐ 4 0 _ s 1 This setting is displayed if “RS485P” in 1 comms switch settimg is ”IEC103”. 72 6 F 2 T 0 1 7 6 I E C B 1 1 I E C B 2 2 I E C B 3 3 I E C B 4 4 I E C G T 1 I E C A T 1 I E C B T 1 I E C C T 1 I E C E 1 0 I E C E 2 0 I E C E 3 0 I E C E 4 0 I E C E 5 0 I E C E 6 0 I E C E 7 0 I E C E 8 0 I E C I 1 0 I E C I 2 0 I E C I 3 0 I E C I 4 0 I E C I 5 0 I E C I 6 0 I E C I 7 0 I E C I 8 0 I E C 2 B 1 1 I E C 2 B 2 2 I E C 2 B 3 3 I E C 2 B 4 4 I E C 2 G T 1 I E C 2 A T 1 This communication type is 2 and “RS485P” in comms I E C 2 B T 1 I E C 2 C T 1 I E C 2 E 1 0 I E C 2 E 2 0 I E C 2 E 3 0 I E C 2 E 4 0 I E C 2 E 5 0 I E C 2 E 6 0 I E C 2 E 7 0 I E C 2 E 8 0 I E C 2 I 1 0 I E C 2 I 2 0 This setting is displayed if “RS485P” in comms switch settimg is ”IEC103”. setting is displayed switch settimg is ”IEC103”. 73 if submodel of 6 F 2 T 0 1 7 6 I E C 2 I 3 0 I E C 2 I 4 0 This setting is displayed if submodel of communication I E C 2 I 5 0 type is 2 and “RS485P” in comms switch settimg I E C 2 I 6 0 I E C 2 I 7 0 I E C 2 I 8 0 S M O D E 0 G O I N T 1 s D E A D T 1 s is ”IEC103”. This setting is displayed if submodel of communication type is A-D. This setting is displayed if submodel of communication type is A-D and “RS485P” in comms switch settimg is ”off”. • Enter the relay address number on the "Modbus" line for Modbus or the "IEC" line for IEC60870-5-103 and press the ENTER key. • Enter IP address for IP1-1 to IP1-4, Subnet mask for SM1-1 to SM1-4, Default gateway for GW1-1 to GW1-4, and SNTP server address for SI1-1 to SI2-4. two SNTP servers are available. Enter "0" or "1" on "SMODE" column to set the standard time synchronized mode for SNTP server. Using low accuracy level of time server, synchronized compensation to maintain synchronization accuracy may not be done automatically. Therefore enter "1", and synchronized compensation is done forcibly. The default setting is "0". Enter the IP address of the device for PG1-1 to PG2-4 if Ping response is checked. IP address: ∗∗∗. ∗∗∗. ∗∗∗. ∗∗∗ (IP1-1. IP1-2. IP1-3. IP1-4) and (IP2-1. IP2-2. IP2-3. IP2-4) SM1-1 to SM2-4, GW1-1 to GW2-4, SI1-1 to SI2-4: same as above. • Press the ENTER key. CAUTION: Do not duplicate the relay address number. Settings for IEC60870-5-103 communication The lines "IECB1" to "IECB4" are used for auxiliary inputs for IEC103 events INF27 to INF30 in Appendix N. Assign signals to the columns "IECB1" to "IECB4" by entering the number corresponding to each signal referring to Appendix B. The lines "IECGT" to "IECCT" are used for fault indications for IEC103 events INF68 to INF71 in Appendix N. Assign signals to the columns "IECGT" to "IECCT" by entering the BO numbers (1 to 8) corresponding to the binary output settings. The lines "IECE1" to "IECE8" are used to assign the signals for user customization. Assign signals to the columns "IECE1" to "IECE8" by entering the number corresponding to each signal referring to Appendix B. Note: Assign "0" to the column when the function is not used. The lines "IECI1" to "IECI8" are used to assign the above signals from "IECE1" to "IECE8" to each INF number. Enter the INF number to the columns "IECI1" to "IECI8". Settings for IEC61850 communication Enter the time on "GOINT" to set the maximum GOOSE message publishing term if GOOSE message receive checked. Enter the time on "DEADT" to set the Keep Alive time of IEC 16850 communication. Setting for Modbus communication 74 6 F 2 T 0 1 7 6 • Select "Switch" on the "Comms" screen to select the protocol and transmission speed (baud rate), etc., for Modbus, IEC60870-5-103 and IEC61850. / 3 S w i t R S > c h 4 8 5 B R R S 4 8 5 B R 9 . 6 / 1 9 . I E C B L K N o r m a l R S 4 8 5 P O f f / M o E t h e r P O f f / I E C 6 6 1 8 5 0 B L K N o r m a l / B T S T M O D O f f / O n G S E C H K O f f / O n P I N G C H O f f / O n I E C G I 1 N o / Y e s I E C G I 2 N o / Y e s I E C G I 3 N o / Y e s I E C G I 4 N o / Y e s I E C G I 5 N o / Y e s I E C G I 6 N o / Y e s I E C G I 7 N o / Y e s I E C G I 8 N o / Y e s I E C 2 G I N o / Y e s I E C 2 G I N o / Y e s 2 This setting is displayed if “RS485P” in comms 0 / B l o c k e d 0 3 switch settimg is ”IEC103”. 0 d / I E C 1 0 1 8 5 0 This setting is displayed if submodel of communication type is A-D and “RS485P” in comms switch settimg is ”off”. 0 l o c k e d 0 0 K This setting is displayed if submodel of communication 0 type is A0-D0. 0 This setting is displayed if “RS485P” in 0 comms switch settimg is ”IEC103”. 0 0 0 This setting is displayed if “RS485P” in 0 comms switch settimg is ”IEC103”. 0 0 1 0 2 0 This setting is displayed if submodel of communication type is 2 and “RS485P” in comms switch settimg is ”IEC103”. 75 6 F 2 T 0 1 7 6 I E C 2 G I N o / Y e s I E C 2 G I N o / Y e s I E C 2 G I N o / Y e s I E C 2 G I N o / Y e s I E C 2 G I N o / Y e s I E C 2 G I N o / Y e s I E C N F I 1 . 2 / 2 . 3 0 4 0 5 0 This setting is displayed if submodel of communication type is 2 and “RS485P” in comms 6 0 7 0 8 0 switch settimg is ”IEC103”. This setting is displayed if “RS485P” in comms 0 switch settimg is ”IEC103”. 4 <RS485BR> This line is to select the baud rate when the Modbus or IEC60870-5-103 protocols are applied. <IECBLK> Enter 1(=Blocked) to block the monitor direction in the IEC60870-5-103 communication. <IECNFI > This line is to select the normalized factor (1.2 or 2.4) of the current measurand. <IECGI1 - 8 > These lines are to use the GI (General Interrogation) or not for user customized signals. If GI is to be used , enter 1(=Yes). <RS485P> This line is to select the communication protocol when the MODBUS or IEC60850-5-103 system applied. <EtherP> This line is to select the communication protocol when the IEC61850 system applied. <61850BLK> Select 1 (=Blocked) to block transmission from relay to BCU for IEC61850 communication. When using the IEC61850 communication, select 0 (=Normal). <TSTMOD> Select 1 (=On) to set the test mode in IEC61850 communication. <GSECHK> This function is to alarm if any one of the GOOSE messages written in a GOOSE subscribe file cannot be received. Select 1 (=On) to execute a GOOSE receive check for IEC61850 communication. <PINGCHK> This function is to check the health of the network by regularly sending a ‘Ping’ to IP address which is set on PG∗-∗. Select 1 (=On) to execute a ‘Ping’ response check. 76 6 F 2 T 0 1 7 6 • Select the number and press the ENTER key. 4.2.6.5 Setting the Recording function To set the recording function as described in Section 4.2.3, do the following: • Select "Set. (change)" on the main "MAIN MENU" screen to display the "Set. (change)" screen. • Select "Record" to display the "Record " screen. / 2 R e c o r d u r b a > E v e n t D i s t C o u n t e n c e r Setting the event recording • Select "Event" to display the "Event" screen. / 3 E v e n t c o m m . _ 1 c o 3 N / O / R / B B I 2 c m m . N / O / R / B B I 3 c m m . N / O / R / B B I 4 c m m . N / O / R / B B I 5 c m m . N / O / R / B B I 6 c m m . N / O / R / B I 1 > B I o o o o o m m . 3 3 3 3 3 B • Enter 0(=None) or 1(=Operate) or 2(=Reset) or 3(=Both) for BI command trigger setting and press the ENTER key. Setting the disturbance recording • Select "Disturbance" to display the "Disturbance" screen. / 3 D i s t b a n c > T i m e / S t a r t e S c h e m e s w B i n a r s i g . y u r e r • Select "Time/starter" to display the "Time/starter" screen. 77 6 F 2 T 0 1 7 6 / 4 T i T i m e m e / S t 1 a r t _ e s > T i m e 1 2 . 0 s T i m e 2 2 . 0 s 2 0 . 0 V U V 6 0 . 0 V Z P S 2 0 . 0 V N P S 2 0 . 0 V O V 1 r • Enter the recording time and starter element settings. To set each starter to either used or not used, do the following: • Select "Scheme sw" on the "Disturbance" screen to display the "Scheme sw" screen. / 4 T r S c i p > T r i p O f f / h e m e s w _ 1 O n B I O f 1 f / O n O V O f 1 f / O n U V O f 1 f / O n Z P S O f f 1 / O n N P S O f f 1 / O n F R Q O f f 1 / O n D F R Q O f f / 1 O n • Enter 1 to use as a starter. If not to be used as a starter, enter 0. To set each signal number to record binary signals, do the following: • Select "Binary sig." on the "Disturbance" screen to display the "Binary sig." screen. / 4 S I B i n a r y s i G 1 g _ > S I G 1 5 1 S I G 2 5 1 S I G 3 5 1 S I G 4 5 1 78 . 6 F 2 T 0 1 7 6 S I G 3 2 5 1 • Enter the signal number to record binary signals in Appendix A. Setting the counter • Select "Counter" to display the "Counter" screen. / 3 C o u n t e r > S c h e m e s w A l a r m e t s To set each counter to either used or not used , do the following: • Select "Scheme sw" on the "Counter" screen to display the "Scheme sw" screen. / 4 S c h e m e s w T C S P E N _ > T C S P E N 1 O f f / O n / O p t - C B S M E N O f f / 1 O n T C A E N O f f / O n 1 O n • Enter 1 to use as a counter. If not to be used as a counter, enter 0. To set the threshold setting, do the following: • Select "Alarm set" on the "Counter" screen to display the "Alarm set" screen. / 4 A l a r m s e t T C A L M _ > T C A L M 1 0 0 0 0 • Enter the threshold settings. 4.2.6.6 Status To set the status display described in Section 4.2.4, do the following: Select "Status" on the "Set. (change)" sub-menu to display the "Status" screen. / 2 > M e S t a t u s t r i n g e T i m e s y n c T i m e z o n e . This setting is displayed if submodel of communication type is A-D. 79 6 F 2 T 0 1 7 6 Setting the metering • Select "Metering" to display the "Metering" screen. / 3 M e t e p l a y _ > D i s p l a y 1 P r i / S e D i s r i n g c • Enter 0 or 1 or 2 for Display. Enter 0(=Pri.) to display the primary side voltage in kilo-volts(kV). Enter 1(=Sec.) to display the secondary side voltage. Setting the time synchronization The calendar clock can run locally or be synchronised with the binary input signal or Modbus or IEC103 or SNTP. This is selected by setting as follows. • Select "Time sync." to display the "Time sync" screen. / 3 T i m e > T i m e O f f / N T P S T i m e s y B s y n n c . s y n c . I / M o d c . _ 1 / 1 0 3 / • Enter 0, 1, 2, 3 or 4 and press the ENTER key. Enter 0(=off) not to be synchronised with any external signals. Enter 1(=BI) to be synchronised with the binary input signal. Enter 2(=Mod) to be synchronised with the Modbus. Enter 3(=103) to be synchronised with the IEC103. Enter 4(=SNTP) to be synchronised with the SNTP. Note: When selecting BI or Modbus, check that they are active on the "Status" screen in "Status" sub-menu. If BI is selected, the BI command trigger setting should be “None” because event records will become full soon. (See Section 4.2.6.5.) If it is set to an inactive BI or Modbus, the calendar clock runs locally. Setting the time zone When the calendar clock is synchronized with the SNTP time standard, it is possible to transform GMT to the local time. • Select "Time zone" to display the "Time zone" screen. • Enter the difference between GMT and local time. Enter numerical values to GMT (hours) and 80 6 F 2 T 0 1 7 6 GMTm (minutes), and press the ENTER key. / 3 T G M T > G M T G M T i m e z o n e . _ m + 0 h r s + 0 m i n 4.2.6.7 Protection The GRE130 can have 2 setting groups for protection in order to accommodate changes in the operation of the power system, one setting group is assigned active. To set the protection, do the following: • Select "Protection" on the "Set. (change)" screen to display the "Protection" screen. / 2 P r o t > C h a n g c t i o n e a c t . g C h a n g e s e t C o g p y e p p . . Changing the active group • Select "Change act. gp." to display the "Change act. gp." screen. / 3 C h a g p . t i v e > A c t i v A c n g e g p . _ g p . 1 e a c t . • Enter the group number and press the ENTER key. Changing the settings Almost all the setting items have default values that are set when the product is shipped. For the default values, see Appendix G. To change the settings, do the following: • Select "Change set." to display the "Act gp.= *" screen. / 3 > C o A c t g m m o n G r o u p 1 G r o u p 2 p . 81 = 1 6 F 2 T 0 1 7 6 Changing the Common settings • Select "Common" to set the voltage input state and input imbalance monitoring and press the ENTER key. / 4 C o m m o n A P P L _ > A P P L 1 1 P P / 1 P N / 2 P P / 3 P N / 3 P V / 3 P P 2 P Z A O L E D O f f / O n <APPL> • Enter 0(=1PP), 1(=1PN), 3(=2PP), 4(=2PZ), 5(=3PN), 6(=3PV) or 7(=3PP) to set the voltage input state and press the ENTER key. <AOLED> This switch is used to control the “TRIP” LED light when an alarm element is output. • Enter 1 (=On) to illuminate the “TRIP” LED when an alarm element outputs, and press the ENTER key. If not, enter 0 (=Off) and press the ENTER key. Changing the Group settings • Select the "Group∗" on the "Act gp.= *" screen to change the settings and press the ENTER key. / 4 G r > P a r a T r p i o u p m e t * e r Setting the parameter Enter the line name, the VT ratio and the fault locator as follows: • Select "Parameter" on the "Group ∗" screen to display the "Parameter" screen. / 5 P a > L i n e V T r r a a m e t n a m e t o i e r • Select "Line name" to display the "Line name" screen. • Enter the line name as a text string and press the END key. • Select "VT ratio" to display the "VT ratio" screen. 82 6 F 2 T 0 1 7 6 / 6 V T r a t i o P V T _ > P V T 1 0 0 R V T 1 0 0 • Enter the VT ratio and press the ENTER key. Setting the trip function To set the scheme switches and protection elements, do the following. • Select "Trip" on the "Group ∗" screen to display the "Trip" screen. / 5 T r i > S c h e m e o . P r t p e s w l e m e n t Setting the scheme switch • Select "Scheme sw" on the "Trip" screen to display the "Scheme sw" screen. / 6 S c > A p p l h e m e i c a t i s w o n O V p r o t . U V p r o t . Z P S p r o t N P S p r o t . F R Q p r o t . . Setting the application To set the application setting, do the following. • Select "Application" on the " Scheme sw" screen to display the "Application" screen. / 7 A p p l i c a t i o S V C N T _ > S V C N T 1 A L M & B L K / n A L M <SVCNT> Set the alarming and tripping block, or only alarming when a failure is detected by the automatic supervision and AC input imbalance supervision. • Enter 0(=ALM&BLK, alarming and tripping block) or 1(=ALM, only alarming) and press the ENTER key. 83 6 F 2 T 0 1 7 6 Setting the OV protection The settings for the OV protection are as follows: • Select "OV" on the "Scheme sw" screen to display the "OV" screen. / 7 O V O V 1 E N p r o t . _ > O V 1 E N O f f / 1 D T / I M D T / O V 2 E N O f f / 1 D T / I M D T / O V 3 E N O f f / C C 1 O n <OV1EN>, <OV2EN> To set the OV1 and OV2 delay type, do the following. • Enter 1 (=DT) or 2 (=IDMT) or 3 (=C: configurable curve) and press the ENTER key. If disabling the OV1 or OV2, enter 0 (=Off) and press the ENTER key. <OV3EN> • Enter 1 (=On) to enable the OV3, and press the ENTER key. If disabling the OV3, enter 0 (=Off) and press the ENTER key. • After setting, press the END key to display the following confirmation screen. C h a n g e s E N T E R = Y e t t i n g s ? C A N C E L = N • Press the ENTER (= Y) key to change settings and return to the "Scheme sw" screen. Setting the UV protection The settings for the UV protection are as follows: • Select "UV" on the "Scheme sw" screen to display the "UV" screen. / 7 U V U V 1 E N p r o t _ > U V 1 E N O f f / 1 D T / I M D T / U V 2 E N O f f / f / D T / I M D T / 1 O n V B L K E N O f f / C 1 U V 3 E N O f . O n 84 1 C 6 F 2 T 0 1 7 6 <UV1EN>, <UV2EN> To set the UV1 and UV2 delay type, do the following. • Enter 1 (=DT) or 2 (=IDMT) or 3 (=C: configurable curve) and press the ENTER key. If disabling the UV1 or UV2, enter 0 (=Off) and press the ENTER key. <UV3EN> • Enter 1 (=On) to enable the UV3, and press the ENTER key. If disabling the UV3, enter 0 (=Off) and press the ENTER key. • After setting, press the END key to display the following confirmation screen. C h a n g e s E N T E R = Y e t t i n g s ? C A N C E L = N • Press the ENTER (= Y) key to change settings and return to the "Scheme sw" screen. <VBLKEN> • Enter 1 (=On) to enable the UV blocking and press the ENTER key. If disabling the UV blocking, enter 0 (=Off) and press the ENTER key. Setting the ZPS Protection The settings for the ZPS protection are as follows: • Select "ZPS" on the "Scheme sw" screen to display the "ZPS" screen. / 7 Z P S p r o t Z P S 1 E N _ > Z P S 1 1 O f f / E N D T / Z P S 2 E N O f D T / f / I D M T / C 1 I D M T / C <ZPS1EN>, <ZPS2EN> To set the ZPS1 and ZPS2 time delayed type, do the following. • Enter 1 (=DT) or 2 (=IDMT) or 3 (=C: configurable curve) and press the ENTER key. If disabling the ZPS1 or ZPS2, enter 0(=Off) and press the ENTER key. • After setting, press the END key to display the following confirmation screen. C h a n g e s E N T E R = Y e t t i n g s ? C A N C E L = N • Press the ENTER (= Y) key to change settings and return to the "Scheme sw" screen. 85 6 F 2 T 0 1 7 6 Setting the NPS protection The settings for the NPS protection are as follows: • Select "NPS" on the "Scheme sw" screen to display the "NPS" screen. / 7 N P S p r o t N P S 1 E N _ > N P S 1 1 O f f / E N D T / N P S 2 E N O f D T / f / I D M T / C 1 I D M T / C <NPS1EN>, <NPS2EN> To set the NPS1 and NPS2 time delayed type, do the following. • Enter 1 (=DT) or 2 (=IDMT) or 3 (=C: configurable curve) and press the ENTER key. If disabling the NPS1 or NPS2, enter 0(=Off) and press the ENTER key. • After setting, press the END key to display the following confirmation screen. C h a n g e s E N T E R = Y e t t i n g s ? C A N C E L = N • Press the ENTER (= Y) key to change settings and return to the "Scheme sw" screen. Setting the FRQ protection The settings for the FRQ (over/under frequency) protection are as follows: • Select "FRQ" on the "Scheme sw" screen to display the "FRQ" screen. / 7 F R Q p r o t F T 1 _ > F T 1 1 O f f / O / U / B / O O / D F T 1 O f f / L o g i L 1 / 1 R / c 1 L 2 / D / B o L 3 / t L 4 F T 2 O f f U U h / L 5 0 / O / U / B / O O / D F T 2 O f f / L o g i L 1 / U U 0 R / c 2 L 2 / D / B o L 3 / F T 3 t L 4 h / 0 86 L 5 6 F 2 T 0 1 7 6 O f f / O / U / B / O O / D F T 3 O f f / L o g i L 1 / 0 R / c 3 L 2 / D / B o L 3 / t L 4 F T 4 O f f U U h / L 5 0 / O / U / B / O O / D F T 4 O f f / L o g i L 1 / U U 0 R / c 4 L 2 / D / B o L 3 / t L 4 h / L 5 <FT1>,<FT2>,<FT3>,<FT4> FT1, FT2, FT3 and FT4 select the frequency protection. • Enter 0 or 1 or 2 or 3 or 4 or 5 and press the ENTER key. Enter 0 (=Off) not to use the frequency protection. Enter 1 (=O) to use the F11 element for overfrequency protection. The F12 element is not used. Enter 2 (=U) to use the F11 element for underfrequency protection. The F12 element is not used Enter 3 (=B) to use the F11 element for overfrequency protection and the F12 element for underfrequency protection. Enter 4 (=OO) to use the F11 and F12 elements for overfrequency protection. Enter 5 (=UU) to use the F11 and F12 elements for underfrequency protection. <DFT1>, <DFT2>, <DFT3>, <DFT4> DFT1, DFT2, DFT3 and DFT4 select the frequency rate-of-change protection. • Enter 0 or 1 or 2 or 3 and press the ENTER key. Enter 0 (= Off) not to use the frequency rise rate nor frequency decay rate protection. Enter 1 (= R) to use only the frequency rise rate protection. Enter 2 (= D) to use only the frequency decay rate protection. Enter 3 (= Both) to use both the frequency rise rate and frequency decay rate protections. <Logic 1>, <Logic 2>, <Logic3>, <Logic 4> Logic 1, Logic 2, Logic 3 and Logic 4 select the tripping combination of the frequency protection and the frequency rate-of-change protection. • Enter 0 (=L1) or 1 (=L2) or 2 (=L3) or 3 (=L4) or 4 (=L5) and press the ENTER key. Refer to Table 2.2.1 for setting. Setting the protection elements To set the protection elements, do the following. • Select "Prot. element" on the "Trip" screen to display the "Prot. element" screen. 87 6 F 2 T 0 1 7 6 / 6 P r o t . e > O V p r o t . U V p r o t . Z P S p r o t N P S p r o t F R Q p r o t l e m e n t Setting the OV elements • Select "OV" on the "Prot. element" screen to display the "OV" screen. / 7 O V p r o t . O V 1 _ > O V 1 1 0 . 0 V OV1 Threshold setting. 1 . 0 0 S OV1 Definite time delay. 1 . 0 0 0 . T O V 1 T O V 1 M T O V 1 R V O V 1 D P R 0 OV1 Inverse time multiplier setting. s OV1 Definite time reset delay. 9 5 % OV1 DO/PU ratio O V 2 1 0 . 0 V OV2 Threshold setting. T O V 2 1 . 0 0 S OV2 Definite time delay. 1 . 0 0 0 . T O V 2 M T O V 2 R O V 2 D P R 0 OV2 Inverse time multiplier setting. s OV2 Definite time reset delay. 9 5 % OV2 DO/PU ratio O V 3 1 0 . 0 V OV3 Threshold setting. T O V 3 1 . 0 0 S OV3 Definite time delay. O V 1 - k 1 . 0 0 OV1 User configurable IDMT curve setting O V 1 - a 1 . 0 0 ditto O V 1 - C 0 . 0 0 ditto O V 2 - k 1 . 0 0 OV2 User configurable IDMT curve setting O V 2 - a 1 . 0 0 ditto O V 2 - c 0 . 0 0 ditto • Enter the numerical value and press the ENTER key. • After setting, press the END key to display the following confirmation screen. C h a n g e s E N T E R = Y e t t i n g s ? C A N C E L = N • Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen. 88 6 F 2 T 0 1 7 6 Setting the UV elements • Select "UV" on the "Prot. element" screen to display the "UV" screen. / 7 U V p r o U V 1 t . _ > U V 1 T U V 1 V 5 . 0 V UV1 Threshold setting. 0 . 0 5 S UV1 Definite time delay. T U V 1 M 0 . 0 5 T U V 1 R 1 0 0 . 0 s UV1 Definite time reset delay. U V 2 4 0 . 0 V UV2 Threshold setting. T U V 2 0 . 0 5 S UV2 Definite time delay. UV1 Inverse time multiplier setting. T U V 2 M 0 . 0 5 T U V 2 R 1 0 0 . 0 s UV2 Definite time reset delay. U V 3 1 0 . 0 V UV3 Threshold setting. T U V 3 1 . 0 0 S UV3 Definite time delay. V B L K 1 0 . V UV Blocking threshold 0 UV2 Inverse time multiplier setting. U V 1 - k 1 . 0 0 UV1 User configurable IDMT curve setting U V 1 - a 1 . 0 0 ditto U V 1 - c 0 . 0 0 ditto U V 2 - k 1 . 0 0 UV2 User configurable IDMT curve setting U V 2 - a 1 . 0 0 ditto U V 2 - c 0 . 0 0 ditto • Enter the numerical value and press the ENTER key. • After setting, press the END key to display the following confirmation screen. C h a n g e s E N T E R = Y e t t i n g s ? C A N C E L = N • Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen. Setting the ZPS elements • Select "ZPS" on the "Prot. element" screen to display the "ZPS" screen. / 7 Z P S Z P S p r 1 o _ > Z P S 1 T Z P S 1 T Z P S 1 M T Z P S 1 R Z P S 2 t 1 V 5 . 0 V ZPS1 Threshold setting. 0 . 0 5 S ZPS 1 Definite time delay. 0 . 0 5 0 0 . 0 s ZPS 1 Definite time reset delay. 4 0 . 0 V ZPS 2 Threshold setting. ZPS 1 Inverse time multiplier setting. 89 6 F 2 T 0 1 7 6 T Z P S 2 0 . 0 5 T Z P S 2 M T Z P S 2 R 0 . 0 5 0 0 . 0 Z P S 1 - k 1 . 0 0 ZPS 1 User configurable IDMT curve setting Z P S 1 - a 1 . 0 0 ditto Z P S 1 - c 0 . 0 0 ditto Z P S 2 - k 1 . 0 0 ZPS 2 User configurable IDMT curve setting Z P S 2 - a 1 . 0 0 ditto Z P S 2 - c 0 . 0 0 ditto 1 S ZPS 2 Definite time delay. ZPS 2 Inverse time multiplier setting. s ZPS 2 Definite time reset delay. • Enter the numerical value and press the ENTER key. • After setting, press the END key to display the following confirmation screen. C h a n g e s E N T E R = Y e t t i n g s ? C A N C E L = N • Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen. Setting the NPS protection elements • Select "NPS" on the "Prot. element" screen to display the "NPS" screen. / 7 N P S N P S p r 1 o t _ > N P S 1 T N P S 1 T N P S 1 M T N P S 1 R 1 N P S 2 V 5 . 0 V NPS1 Threshold setting. 0 . 0 5 S NPS 1 Definite time delay. 0 . 0 5 NPS 1 Inverse time multiplier setting. 0 0 . 0 s NPS 1 Definite time reset delay. 4 0 . 0 V NPS 2 Threshold setting. 0 . 0 5 S NPS 2 Definite time delay. 0 . 0 5 NPS 2 Inverse time multiplier setting. 0 0 . 0 s NPS 2 Definite time reset delay. T N P S 2 T N P S 2 M T N P S 2 R N P S 1 - k 1 . 0 0 NPS 1 User configurable IDMT curve setting N P S 1 - a 1 . 0 0 ditto N P S 1 - c 0 . 0 0 ditto N P S 2 - k 1 . 0 0 NPS 2 User configurable IDMT curve setting N P S 2 - a 1 . 0 0 ditto N P S 2 - c 0 . 0 0 ditto 1 • Enter the numerical value and press the ENTER key. 90 6 F 2 T 0 1 7 6 • After setting, press the END key to display the following confirmation screen. C h a n g e s E N T E R = Y e t t i n g s ? C A N C E L = N • Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen. Setting the FRQ elements • Select "FRQ" on the "Prot. element" screen to display the "FRQ" screen. / 7 F R Q p r F 1 1 > F 1 1 D F 1 0 F 2 D F 2 0 D F 3 0 0 5 S F11 Definite time delay. 5 . 0 H z F12 for FRQ1 Threshold setting. 0 . 0 5 S F12 Definite time delay. . 5 H z 5 . 0 H z F21 for FRQ2 threshold setting. 0 . 0 5 S F21 Definite time delay. 5 . 0 H z F22 for FRQ2 Threshold setting. 0 . 0 5 S F22 Definite time delay. . 5 H z 5 . 0 H z F31 for FRQ3 threshold setting. 0 . 0 5 S F31 Definite time delay. 5 . 0 H z F32 for FRQ3 Threshold setting. 0 . 0 5 S F32 Definite time delay. . 5 H z 5 . 0 H z F41 for FRQ4 threshold setting. 0 . 0 5 S F41 Definite time delay. 5 . 0 H z F42 for FRQ4 Threshold setting. 0 . 0 5 S F42 Definite time delay. . H z 1 T F 4 1 F 4 0 . 2 T F 3 2 F 4 F11 for FRQ1 threshold setting. 1 T F 3 1 F 3 0 H z 2 T F 2 2 F 3 . 1 T F 2 1 2 T F 4 2 D F 4 0 H z 5 2 T F 1 2 F 2 t _ T F 1 1 F 1 o 5 / / / / s DF1 for FRQ1 of DFRQ1 Threshold setting. s DF2 for FRQ2 of DFRQ2 Threshold setting. s DF3 for FRQ3 of DFRQ3 Threshold setting. s DF4 for FRQ4 of DFRQ4 Threshold setting. • Enter the numerical value and press the ENTER key. • After setting, press the END key to display the following confirmation screen. C h a n g e s E N T E R = Y e t t i n g s ? C A N C E L = N 91 6 F 2 T 0 1 7 6 • Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen. Setting group copy To copy the settings from one settings group and overwrite them to another group, do the following: • Select "Copy gp." on the "Protection" screen to display the "Copy A to B" screen. / 3 C o p y A t o B > A _ B _ • Enter the group number to be copied in line A and press the ENTER key. • Enter the group number to be overwritten by the copy in line B and press the ENTER key. 4.2.6.8 Binary Input The logic level of binary input signals can be inverted by setting before entering the scheme logic. Inversion is used when the input contact cannot meet the requirements described in Table 3.2.2. • Select "Binary I/P" on the "Set. (change)" sub-menu to display the "Binary I/P" screen. / 2 B i > B I n a r S t a t y I / P u s B I 1 B I 2 B I 3 B I 4 B I 5 B I 6 A l a r m 1 T e x t A l a r m 2 T e x t A l a r m 3 T e x t A l a r m 4 T e x t Setting Binary Input Status The binary input nominal operating voltage can be selected in GRE130. Control voltages of 24V, 48V, 110V and 220V are supported. BI1 and BI2 can be set to one of three nominal voltages - 48 / 110 / 220V ( or 12 / 24 / 48V) BI3 to BI6 can be set to one of two nominal voltages – 110 / 220V (or 24 / 48V) Note: The nominal voltage 48V (or 12V) of BI1 and BI2 is used for Trip Circuit Supervision using 2 Binary inputs. See section 3.3.3. The threshold voltage options of 48-220V and 12-48V correspond to the dc auxiliary voltage supply rating of the relay models. To set the binary inputs threshold voltage, do the following: • Select "BI Status" on the "Binary I/P" screen to display the "BI Status" screen. 92 6 F 2 T 0 1 7 6 / 3 B I B I a t u s T H R 1 > B I 4 S t 8 T H R 1 / 1 1 0 / B I T H R 2 1 0 / 1 2 1 2 2 0 0 2 0 <BITHR1> To set the threshold voltage for Binary Inputs 1 and 2 , do the following. • Enter 0(=48V) or 1(=110V) or 2(=220V) and press the ENTER key. <BITHR2> To set the threshold voltage for Binary Inputs 3 to 6 , do the following. • Enter 0(=110V) or 1(=220V) and press the ENTER key. Selection of Binary Input • Select the input number (BI number) on the "Binary I/P" screen. After setting, press the ENTER key to display the "BI∗" screen. / 3 B I 1 > T i m e r s F u n c t i o n s Setting Alarm ∗ Text If the BI selected is used for an alarm, an alarm message can be set. • Select the Alarm∗ text and press the ENTER key to display the text input screen. _ A B C D E F G H I J K L M N O P Q R S T U V W X Y Z a b c d e g h i j k l m n o p q r s t u v w x y z 0 1 2 3 4 5 6 7 8 9 [ @ _ { } * / + - $ % & ‘ : ; , . ^ ` ] < = > ! f ( ) “ ♯ • Enter the characters (up to 22 characters) according to the text setting method. After setting, press the ENTER key to display the "BI∗" screen. 93 6 F 2 T 0 1 7 6 Setting timers • Select "Timers" on the "BI" screen to display the "Timers" screen. / 4 B I T i m e r s 1 P U D _ s > B I 1 P U D 0 . 0 0 s Pick-up delay setting B I 1 D O D 0 . 0 0 s Drop-off delay setting • Enter the numerical value and press the ENTER key. • After setting, press the END key to return to the "BI∗" screen. Setting Functions • Select "Functions" on the "BI" screen to display the "Functions" screen. / 4 B I F u n c 1 > B I t i o S N S _ 1 S N S 0 N o r B I 1 S G S O f f m / / 1 I / n v 0 2 O V 1 B L K O f f / f / f / f / f / f / f / f / f / 0 O n F R Q B L K O f 0 O n N P S B L K O f 0 O n Z P S B L K O f 0 O n U V 3 B L K O f 0 O n U V 2 B L K O f 0 O n U V 1 B L K O f 0 O n O V 3 B L K O f 0 O n O V 2 B L K O f n 0 O n • To set the Binary Input Sense, enter 0(=Normal) or 1(=Inverted) and press the ENTER key. • After setting, press the END key to return to the "BI∗" screen. 94 6 F 2 T 0 1 7 6 <BI1SNS> To set the Binary Input 1 Sense, do the following. • Enter 0(=Normal) or 1(=Inverted) and press the ENTER key. <BI1SGS> To set the Binary Input 1 Settings Group Select, do the following. • Enter 0(=Off) or 1(=1) or 2(=2) and press the ENTER key. <Others> • Enter 1(=On) to set the function and press the ENTER key. If not setting the function, enter 0(=Off) and press the ENTER key. • After setting, press the END key to return to the "BI∗" screen. 4.2.6.9 Binary Output All the binary outputs of the GRE130 except the relay failure signal are user-configurable. It is possible to assign one signal or up to four ANDing or ORing signals to one output relay. Available signals are listed in Appendix C. It is also possible to attach Instantaneous or delayed or latched reset timing to these signals. Appendix G shows the factory default settings. CAUTION When having changed the binary output settings, release the latch state on the digest screen by pressing the RESET key for more than 3 seconds. To configure the binary output signals, do the following: Selection of output relay • Select "Binary O/P" on the "Set. (change)" screen to display the "Binary O/P" screen. 2 > B i n a r y O / P B O 1 B O 2 B O 3 B O 4 B O 5 Available for model 412. B O 6 Available for model 412. B O 7 Available for model 412. B O 8 Available for model 412. Note: The setting is required for all the binary outputs. If any of the binary outputs are not used, enter 0 to logic gates #1 to #4 in assigning signals. 95 6 F 2 T 0 1 7 6 • Select the output relay number (BO number) and press the ENTER key to display the "BO∗" screen. / 3 B O ∗ > L o g i c / R e F u n c t i o s e t n s Setting the logic gate type and timer • Select "Logic/Reset" to display the "Logic/Reset" screen. / 4 L o L o g > L o i g i / R e s c g i e t _ c 0 O R / A N D R e s e t n s / D I I c 0 / D w / L a t • Enter 0(=OR) or 1(=AND) to use an OR gate or AND gate and press the ENTER key. • Enter 0(=Instantaneous) or 1(=Delayed) or 2(=Dwell) or 3(=Latched) to select the reset timing and press the ENTER key. • Press the END key to return to the "BO∗" screen. Note: To release the latch state, push the [RESET] key for more than 3 seconds. Assigning signals • Select "Functions" on the "BO∗" screen to display the "Functions" screen. / 4 F u I n ♯ 1 n c t i o n s _ > I n ♯ 1 - - - I n ♯ 2 - - - I n ♯ 3 - - - I n ♯ 4 - - - T B O 0 . 2 0 s • Assign signals to gates (In #1 to #4 of “---”) by entering the number corresponding to each signal referring to Appendix A. Do not assign the signal numbers 170 to 176 (signal names: "BO1 OP" to "BO8 OP"). And set the delay time of timer TBO. Note: If signals are not assigned to all the gates #1 to #6, enter 0 for the unassigned gate(s). Repeat this process for the outputs to be configured. 96 6 F 2 T 0 1 7 6 CAUTION The CB close control key | is linked to BO1 and the CB open control key ○ is linked to BO2, when the control function is enabled. 4.2.6.10 LEDs Six of the LEDs provided by the GRE130 are user-configurable. A configurable LED can be programmed to indicate an OR combination of a maximum of 4 elements, the individual status of which can be viewed on the LED screen as “Virtual LEDs.” The signals listed in Appendix A can be assigned to each LED as follows. CAUTION When having changed the LED settings, release the latch state on the digest screen by pressing the RESET key for more than 3 seconds. Selection of LEDs • Select "LED" on the "Set. (change)" screen to display the "LED" screen. / 2 L E D > L E D V i r t u a l L E D Selection of real LEDs • Select "LED" on the "/2 LED" screen to display the "/3 LED" screen. / 3 L E D > L E D 1 L E D 2 L E D 3 L E D 4 L E D 5 L E D 6 C B C L O S E D Note: The setting is required for all the LEDs. If any of the LEDs are not used, enter 0 to logic gates #1 to #4 in assigning signals. • Select the LED number and press the ENTER key to display the "LED∗" screen. / 4 > L o L E D ∗ g i c / R e s F u n c t i o n s L E D C o l o r 97 e t 6 F 2 T 0 1 7 6 Setting the logic gate type and reset type • Select "Logic/Reset" to display the "Logic/Reset" screen. / 5 L o L o g > L o i g c / R e c g i s e t _ c 0 O R / A N D R e s e t n s t / I i 0 L a t c h • Enter 0(=OR) or 1(=AND) to use an OR gate or AND gate and press the ENTER key. • Enter 0(=Instantaneous) or 1(=Latched) to select the reset timing and press the ENTER key. • Press the END key to return to the "LED∗" screen. Note: To release the latch state, push the [RESET] key for more than 3 seconds. Assigning signals • Select "Functions" on the "LED∗" screen to display the "Functions" screen. / 5 F u I n # 1 n c t i o n s _ > I n # 1 - - - I n # 2 - - - I n # 3 - - - I n # 4 - - - • Assign signals to gates (In #1 to #4 of “---”) by entering the number corresponding to each signal referring to Appendix A. Note: If signals are not assigned to all the gates #1 to #4, enter 0 for the unassigned gate(s). • Press the END key to return to the "LED∗" screen. Repeat this process for the outputs to be configured. Setting the LED color • Select "LED color" on the "LED∗ " screen or on the "CB CLOSED" screen to display the "LED color" screen. / 5 C o L E D l > C o R / C o l o r l o r _ o r G / Y 0 98 6 F 2 T 0 1 7 6 • Select the LED color from red, green or yellow. • Press the END key to return to the "LED∗" screen. Repeat this process for the LED colors to be configured. Selection of virtual LEDs • Select "Virtual LED" on the "/2 LED" screen to display the "Virtual LED" screen. / 3 V i > I N D 1 I N D 2 r t u a l L E D • Select the IND number and press the ENTER key to display the "IND∗" screen. / 4 I N D 1 > R e s e t F u n c t i o n s Setting the reset timing • Select "Reset" to display the "Reset" screen. / 5 R e R e s > R e I s e t e t _ s e t n s t / 0 L a t c h • Enter 0(=Instantaneous) or 1(=Latched) to select the reset timing and press the ENTER key. • Press the END key to return to the "IND∗" screen. Note: To release the latch state, push the [RESET] key for more than 3 seconds. Assigning signals • Select "Functions" on the "IND∗" screen to display the "Functions" screen. / 5 B I F n c t i o n s T 1 _ > B I T 1 - - - B I T 2 - - - B I T 3 - - - B I T 4 - - - B I T 5 - - - B I T 6 - - - B I T 7 - - - B I T 8 - - - 99 6 F 2 T 0 1 7 6 • Assign signals to bits (1 to 8) by entering the number corresponding to each signal referring to Appendix A. Note: If signals are not assigned to all the bits 1 to 8, enter 0 for the unassigned bit(s). • Press the END key to return to the "IND∗" screen. Repeat this process for the outputs to be configured. 4.2.6.11 Control The GRE130 can control the Circuit Breaker(CB) open / close by using the front panel keys. The interlock function can be used to block the Circuit Breaker(CB) close command with interlock signals from binary inputs or from a communication command. To set the control function and interlock function, do the following: • Select "Control" on the "Set. (change)" screen to display the "Control" screen. / 2 C o C o n t > C o n t o r o l l _ n t r o l s a b l e / E n a b l n t e r l o c k 0 a b l e / E n a b l D i I r D i s 0 e e • Enter 0(=Disable) or 1(=Enable) to select the control function to be in use or not in use and press the ENTER key. • Enter 0(=Disable) or 1(=Enable) to select the interlock function to be in use or not in use and press the ENTER key. Note: When the Control function is disabled, both the "Local" LED and the "Remote" LED are not lit, and the sub-menu "Control" on the LCD is not displayed. 4.2.6.12 Frequency Setting of the system frequency for the GRE130 relay for 50Hz or 60Hz. To change the system frequency, do the following: • Select "Frequency" on the "Set. (change)" screen to display the "Frequency" screen. / 2 F r F r e > F r 5 0 e q u e e q H z q u e n c u e / y n c 6 0 n c y _ y 0 H z • Enter 0(=50Hz) or 1(=60Hz) to select the system frequency setting 50Hz or 60Hz and press the ENTER key. 100 6 F 2 T 0 1 7 6 CAUTION When having changed the system frequency settings, the GRE130 must reboot to enable the setting change. When having changed the system frequency, the frequency protection setting value must be changed for the system frequency. 4.2.7 Control The sub-menu "Control" enables the Circuit Breaker(CB) control function from the front panel keys - ○ , | and L/R . Note: When the Control function is disabled, both the "Local" LED and the "Remote" LED are not lit, and the sub-menu "Control" on the LCD is not displayed. 4.2.7.1 Local / Remote Control The "Local/Remote" function provides for change of CB control hierarchy. • Select "Control" on the "MAIN MENU" screen to display the "Control" screen. / 1 C o n t r o l > P a s s w o r d ( L o c a l / R e m o t e c l o s / p e n C t r l C B e C t o r l ) • Move the cursor to "Local/Remote" on the LCD. / 1 C o n t r o l P a s s w o r d ( > L o c a l / R e m o t e c l o s / p e C B e o ) n • The L/R key is enabled to change the CB control hierarchy. 4.2.7.2 CB close / open Control The "CB close/open" function provides CB control. • Move the cursor to "CB close/open" on the LCD. / 1 C o n t r o l P a s w o r d ( L o c > C B s C t r a l / R e m o t e c l o s / p e e o l ) n • The | and ○ keys are enabled to control the CB – close / open. 101 6 F 2 T 0 1 7 6 4.2.7.3 Password For the sake of security of control password protection can be set as follows: • Select "Control" on the "MAIN MENU" screen to display the "Control" screen. • Select "Password" to display the "Password" screen. • Enter a 4-digit number within the brackets after "Input" and press the ENTER key. C o I n t r o n p u t 1 2 3 4 5 l [ 6 7 8 9 _ ] 0 < • For confirmation, enter the same 4-digit number in the brackets after "Retype". C o n t e R e t y 1 2 3 4 5 p r o l 8 9 0 < [ 6 7 _ ] • Press the END key to display the confirmation screen. If the retyped number is different from that first entered, the following message is displayed on the bottom of the "Password" screen before returning to the upper screen. "Unmatch passwd!" Re-entry is then requested. Password trap After the password has been set, the password must be entered in order to enter the control screens. If "Control" is entered on the "MAIN MENU" screen, the password trap screen "Password" is displayed. If the password is not entered correctly, it is not possible to move to the "Control" sub-menu screens. C o n t r w o r d P a s s 1 2 3 4 5 6 7 8 o l [ 9 _ ] 0 < Canceling or changing the password To cancel the password protection, enter "0000" in the two brackets on the "Password" screen. The "Test" screen is then displayed without having to enter a password. The password can be changed by entering a new 4-digit number on the "Password" screen in the same way as the first password setting. 102 6 F 2 T 0 1 7 6 If you forget the password Press the CANCEL and RESET keys together for one second on the "MAIN MENU" screen. The password protection for the GRE130 is canceled. Set the password again. 4.2.8 Testing The sub-menu "Test" provides such functions as disabling the automatic monitoring function and forced operation of binary outputs. Note: When operating the "Test" menu, the "IN SERVICE" LED is flickering. But if an alarm occurs during the test, the flickering stops. The "IN SERVICE" LED flickers only in a testing state. 4.2.8.1 Scheme Switch The automatic monitor function (A.M.F.) can be disabled by setting the switch [A.M.F] to "OFF". Disabling the A.M.F. inhibits trip blocking even in the event of a failure of the items that are being monitored by this function. It also prevents failures from being displayed on the "ALARM" LED and LCD described in Section 4.2.1. No events related to A.M.F. are recorded, either. Disabling A.M.F. is useful for blocking the output of unnecessary alarms during testing. • Select "Test" on the top "MAIN MENU" screen to display the "Test" screen. / 1 T e s s s w o S w i t c h n a r y > P a B i t r d ( O / T e s t ) P • Select "Switch" to display the "Switch" screen. / 2 A . S w i M . > A . O f t h F _ M . F f O n / 1 U V T S T O f f / 0 O n • Enter 0(=Off) to disable the A.M.F. and press the ENTER key. • Enter 1(=On) for UVTST to disable the UV block when testing UV elements and press the ENTER key. • Press the END key to return to the "Test" screen. 4.2.8.2 Binary Output Relay It is possible to forcibly operate all binary output relays for checking connections to external 103 6 F 2 T 0 1 7 6 devices. Forced operation can be performed on one or more binary outputs at a time. • Select "Binary O/P" on the "Test" screen to display the "Binary O/P" screen. Then the LCD displays the name of the output relay. / 2 B i n a r y O / P B O 1 _ > B O 1 0 D i s a b l e / E n a B O 2 D i s s a b l e / E n a a e b l e / E n a b l e 0 s a F A I L D i a s b l 0 B O 4 D i e 0 B O 3 D i b l b l e / E n a b l e 0 b l e / E n a b l e • Enter 1(=Enable) and press the ENTER key to forcibly operate the output relays. • After completing the entries, press the END key. Then the LCD displays the screen shown below. O p e r a t e ? E N T E R = Y C A N C E L = N • Keep pressing the ENTER key to operate the assigned output relays. • Release pressing the ENTER key to reset the operation. • Press the CANCEL key to return to the upper "Binary O/P" screen. 4.2.8.3 Password For the sake of security during testing, password protection can be set as follows: • Select "Test" on the "MAIN MENU" screen to display the "Test" screen. • Select "Password" to display the "Password" screen. • Enter a 4-digit number within the brackets after "Input" and press the ENTER key. T e I s t n p u t 1 2 3 4 5 [ 6 7 8 9 _ ] 0 < • For confirmation, enter the same 4-digit number in the brackets after "Retype". 104 6 F 2 T 0 1 7 6 T e s t R e t y p e 1 2 3 4 5 [ 6 7 8 9 _ ] 0 < • Press the END key to display the confirmation screen. If the retyped number is different from that first entered, the following message is displayed on the bottom of the "Password" screen before returning to the upper screen. "Unmatch passwd!" Re-entry is then requested. Password trap After the password has been set, the password must be entered in order to enter the setting change screens. If "Test" is entered on the "MAIN MENU" screen, the password trap screen "Password" is displayed. If the password is not entered correctly, it is not possible to move to the "Test" sub-menu screens. T e s t P a s s w o r 1 2 3 4 5 6 7 d 8 [ 9 _ ] 0 < Canceling or changing the password To cancel the password protection, enter "0000" in the two brackets on the "Password" screen. The "Test" screen is then displayed without having to enter a password. The password can be changed by entering a new 4-digit number on the "Password" screen in the same way as the first password setting. If you forget the password Press the CANCEL and RESET keys together for one second on the "MAIN MENU" screen. The screen will go off, and the password protection of the GRE130 is cancelled. Set the password again. 105 6 F 2 T 0 1 7 6 4.3 Personal Computer Interface The relay can be operated from a personal computer using a USB port on the front panel. Using a personal computer, the following analysis and display of fault currents are available in addition to the items available on the LCD screen. • Display of current waveform: Oscillograph display • Symmetrical component analysis: On arbitrary time span • Harmonic analysis: On arbitrary time span • Frequency analysis: On arbitrary time span For details, see the separate instruction manual "PC INTERFACE RSM100". 4.4 Modbus Interface GRE130 supports the Modbus communication protocol. This protocol is mainly used when the relay communicates with a control system and is used to transfer the following measurement and status data from the relay to the control system. (For details, see Appendix L.) • Measurement data: current • Status data: events, fault indications, counters, etc. • Setting data • Remote CB operation: Open / Close • Time setting / synchronization The protocol can be used via the RS-485 port on the relay rear panel. The relay supports two baud-rates 9.6kbps and 19.2kbps. These are selected by setting. See Section 4.2.6.4. 4.5 IEC 60870-5-103 Interface The GRE130 supports the IEC60870-5-103 communication protocol. This protocol is mainly used when the relay communicates with a control system and is used to transfer the following measurand and status data from the relay to the control system. (For details, see Appendix N.) • Measurand data: current • Status data: events, fault indications, etc. The protocol can be used through the RS-485 port on the relay rear panel. The relay supports two baud-rates 9.6kbps and 19.2kbps, and supports two normalizing factors 1.2 and 2.4 for measurand. These are selected by setting. See Section 4.2.6.4. The data transfer from the relay can be blocked by the setting. For the settings, see the Section 4.2.6. 4.6 IEC 61850 Communication GRE130 can also support data communication according to the IEC 61850 standard with the provision of an optional communication board. Station bus communication as specified in IEC 61850-8-1 facilitates integration of the relays within a substation control and automation system via Ethernet LAN. 106 6 F 2 T 0 1 7 6 Figure 4.6.1 shows an example of a substation automation system using Ethernet-based IEC 61850 communication. or TX Figure 4.6.1 IEC 61850 Communication Network 4.7 Clock Function The clock function (Calendar clock) is used for time-tagging for the following purposes: • Event records • Disturbance records • Fault records The calendar clock can run locally or be synchronised with an external clock such as the binary time standard input signal or Modbus. This can be selected by setting. The “clock synchronise” function synchronises the relay internal clock to the binary input signal by the following method. Since the BI signal is an “ON” or “OFF” signal which cannot express year-month-day and hour-minute-second etc, synchronising is achieved by setting the number of milliseconds to zero. This method will give accurate timing if the synchronising BI signal is input every second. Synchronisation is triggered by an “OFF” to “ON” (rising edge) transition of the BI signal. When the trigger is detected, the millisecond value of the internal clock is checked, and if the value is between 0~500ms then it is rounded down. If it is between 500~999ms then it is rounded up (ie the number of seconds is incremented). n sec (n+1) sec 500ms corrected to (n+1) sec corrected to n sec t When the relays are connected with the RSM system as shown in separate volume "PC INTERFACE RSM100" and "RSM" is selected in the time synchronisation setting, the calendar clock of each relay is synchronised with the RSM clock. If the RSM clock is synchronised with an external time standard, then all the relay clocks are synchronised with the external time standard. 107 6 F 2 T 0 1 7 6 Special Mode The GRE130 will enter the following special mode using a specific key operation. • LCD contrast adjustment mode • Light check mode LCD contrast adjustment mode When the LCD is not evident or not displayed clearly, it may be that the contrast adjustment for the LCD may not be appropriate. To adjust the contrast of the LCD screen on any of the screens, do the following: • Press ▼ and ▲ ,at same time for 3 seconds or more to shift to the LCD contrast adjustment mode. L C D C o n t r a s t or ▼ • Press the ▲ ■ ■ ■ ■ key to adjust the contrast. LCD and LED check mode key for 3 seconds or more when the LCD is off. • While pressing ▲ • Press ▲ To exercise the LCD and LED check , do the following. key all LEDs are lit and white dots will appear on the whole LCD screen. The colors of the configurable LEDs (LED1-6) can be chosen in the user setting color. CB CLOSED CB OPEN LOCAL REMOTE IN SERVICE TRIP User configurable LEDs (LED1-6) ALARM RELAY FAIL • Release ▲ 4.8 key , to finish the LCD and LED check mode. 108 6 F 2 T 0 1 7 6 5. Installation 5.1 Receipt of Relays When relays are received, carry out an acceptance inspection immediately. In particular, check for damage during transportation, and if any is found, contact the vendor. Always store the relays in a clean, dry environment. Relay Mounting The relay case is designed for flush mounting using two mounting attachment kits. Appendix E shows the case outlines. 5 127 14 5.2 117 13 5 Fig. 5.2.1 Outline of attachment kit The attachment kits can be mounted on a panel thickness of 1 – 2.5mm when the M4x8 screws included with the kit are used. When mounted on a panel thickness of 2.5-4.5mm, M4x10 screws together with some spacing washers should be used. 5.2.1 Flush Mounting For flush mounting in a panel cut-out; ・Mount the case in the panel cut-out from the front of the panel. ; See Fig.5.2.2. ・Use the mounting attachment kits set ; See Fig.5.2.3. ・Tighten the M4 screws from the attachment kits ; see Fig.5.2.4. The allowed range for the fixing screw tightening torque is 1.0…1.4Nm. Do not tighten the screws too tightly. 109 6 F 2 T 0 1 7 6 (a) model 410A and 411A +0.2 160 +0.2 -0.2 217 -0.2 (b) model 412A Fig. 5.2.2 Flush mounting the case into a panel cut-out 110 6 F 2 T 0 1 7 6 Fig. 5.2.3 Side view of GRE130 showing the positions of the mounting attachment kit (a) model 410A, 411A (b) model 412A Fig. 5.2.4 Rear view of GRE130 showing the screw location for the mounting attachment kits 5.2.2 Dimensions 5.2.2.1 Power Supply The power supply for the relay can be either DC (range 24-48Vdc, 48-110Vdc, 110-250Vdc) or AC (110-220Vac-50/60Hz). The voltage range is specified on the relay indicator plate on the front face. On models 410A and 411A, the power supply should be connected to terminals 13 and 14 of TB1 and the earthing should be connected to terminal 12 of TB1. On model 412A, the power supply should be connected to terminals 13 and 14 of TB2 and the 111 6 F 2 T 0 1 7 6 earthing should be connected to terminal 12 of TB2. A minimum 1.25mm2 wire size recommended. 5.2.2.2 Analogue inputs GRE130-410A, 411A and 412A have 4 analogue inputs for phase and earth voltage. On models 410A and 411A, the voltage inputs should be connected to terminals 1 to 8 of TB1. A minimum 2.5 mm2 wire size recommended. The voltage input and power supply terminals (TB1 or TB2) can be connected from both sides. 5.2.2.3 Binary inputs The relay has 2 (or 6) opto-insulated logic inputs. Each input has is separately powered with a dc voltage. On models 410A and 411A, the binary inputs should be connected to terminals 13 to 16 (or 22) of TB2. On model 412A, the binary inputs should be connected to terminals 13 to 16 (or 22) of TB3. A minimum 1.25 mm2 wire size is recommended. 5.2.2.4 Binary outputs (Output relays) Five output relays are available on the relay. Four relays are programmable, the last relay being assigned to the signaling of a relay fault. BO3 and BO4 are NOT applicable for direct CB coil connection. On models 410A and 411A, the binary outputs should be connected to terminals 1 to 10 of TB2. On model 412A, the binary outputs should be connected to terminals 1 to 10 of TB3. A minimum 1.25 mm2 wire size is recommended. 5.2.2.5 RS485 port The communication connection (RS485 port) is assigned to terminals 21, 23 and 24 of TB2 at model 410A and 411A or TB3 at model 412A. The total length of twisted pair wires should not exceed 1200 m. The transmission wires should be terminated using a 120Ω resistor at both extreme ends of the cable. The binary input , binary output and RS485 communication terminal is a single side connected terminal block. The relay terminal block size and the clearance between the terminals are shown at Fig 5.2.4. 112 6 F 2 T 0 1 7 6 17 24 17 24 TB2 42 TB2 TB3 TB1 8.7 10.0 6.35 6.35 7.62 (a) model 410A1 and 411A 7.62 8.7 10.0 7.62 6.35 TB1 (b) model 412A Fig. 5.2.4 Rear view of the relay 5.3 Electrostatic Discharge CAUTION Do not remove the relay PCB from the relay case since electronic components on the modules are very sensitive to electrostatic discharge. 5.4 Handling Precautions A person's normal movements can easily generate electrostatic potentials of several thousand volts. Discharge of these voltages into semiconductor devices when handling electronic circuits can cause serious damage. Often, this damage may not be immediately apparent, but the reliability of the circuit will have been reduced. The electronic circuits are completely safe from electrostatic discharge when housed in the case. Do not expose them to risk of damage. The relay unit incorporates the highest practical protection for its semiconductor devices. However, if it becomes necessary to withdraw the relay unit, precautions should be taken to preserve the high reliability and long life for which the equipment has been designed and manufactured. CAUTION • Do not pass the relay unit to another person without first ensuring you are both at the same electrostatic potential. Shaking hands achieves equipotential. • Place the relay unit on an anti-static surface, or on a conducting surface which is at the same potential as yourself. • Do not place the relay unit in polystyrene trays. It is strongly recommended that detailed investigations on electronic circuitry should be carried out in a Special Handling Area. 113 6 F 2 T 0 1 7 6 5.5 External Connections External connections for each relay model are shown in Appendix F. 5.6 Optinal case model S1-GRE130 GRE130 has optional case model S1-GRE130. Details are shown in 6F2T0195. 114 6 F 2 T 0 1 7 6 6. Commissioning and Maintenance 6.1 Outline of Commissioning Tests The GRE130 is fully numerical and the hardware is continuously monitored. Commissioning tests can be kept to a minimum and need only include hardware tests and the conjunctive tests. The function tests are at the user’s discretion. In these tests, user interfaces on the front panel of the relay or local PC can be fully utilised. Test personnel must be familiar with general relay testing practices and safety precautions to avoid personal injuries or equipment damage. Hardware tests These tests are performed for the following hardware to ensure that there is no hardware defect. Defects of hardware circuits other than the following can be detected by monitoring which circuits function when the DC power is supplied. User interfaces Binary input circuits and output circuits AC input circuits Function tests These tests are performed for the following functions that are fully software-based. Measuring elements Metering and recording Conjunctive tests The tests are performed after the relay is connected with the primary equipment and other external equipment. The following tests are included: On load test: phase sequence check and polarity check Tripping circuit test 6.2 Cautions 6.2.1 Safety Precautions CAUTION • When connecting the cable to the rear of the relay, firmly fix it to the terminal block and attach the cover provided for the terminal block . • Before checking the interior of the relay, be sure to turn off the power. Failure to observe any of the precautions above may cause electric shock or malfunction. 115 6 F 2 T 0 1 7 6 6.2.2 Precautions for Testing CAUTION • When the power is on, do not draw out/insert the relay unit. • Before turning the power on, check the following: - Make sure the polarity and voltage of the power supply are correct. - Make sure the VT circuit is not short-circuited. • Be careful to ensure that the relay is not damaged due to an overcurrent or overvoltage. • If settings are changed for testing, remember to reset them to the original settings. Failure to observe any of the precautions above may cause damage or malfunction of the relay. 6.3 Preparations Test equipment The following test equipment is required for the commissioning tests. 1 Single-phase voltage source 1 Three-phase voltage source 1 power supply 3 Phase angle meter 3 AC ammeter 3 AC voltmeter 1 Time counter, precision timer 1 PC (not essential) Relay settings Before starting the tests, it must be specified whether the tests will use the user’s settings or the default settings. For the default settings, see the Appendix G Relay Setting Sheet. Visual inspection After unpacking the product, check for any damage to the relay case. If there is any damage, the internal module might also have been affected. Contact the vendor. Relay ratings Check that the items described on the nameplate on the front of the relay conform to the user’s specification. The items are: relay type and model, AC voltage and frequency ratings, and auxiliary supply voltage rating. Local PC When using a local PC, connect it to the relay via the USB port on the front of the relay. RSM100 software is required to run the PC. For full details, see separate volume "PC INTERFACE RSM100". 116 6 F 2 T 0 1 7 6 Hardware Tests The tests can be performed without external wiring, but a power supply and AC current and voltage sources are required. The testing circuit figures used in this chapter show the circuit diagram for the 410A and 411A models. In the case of the 412A model, TB1 replaces TB2 and TB2 replaces TB3. 6.4.1 User Interfaces This test ensures that the LCD, LEDs and keys function correctly. LCD ・LED display • Apply the rated supply voltage and check that the LCD is off and the "IN SERVICE" LED is lit green. Note: If there is a failure, the LCD will display the "ERR: " screen when the supply voltage is applied. • Press key for 3 seconds or longer and check that white dots appear on the whole screen and that all LEDs are lit. ▲ 6.4 Operation keys • Press the ENTER key when the LCD is off and check that the LCD displays the "MAIN MENU" screen. Press the END key to turn off the LCD. • Press the ENTER key when the LCD is off and check that the LCD displays the "MAIN MENU" screen. Press any keys to check that they operate. 6.4.2 Binary Input Circuits The testing circuit is shown in Figure 6.4.1. GRE130 TB2 -13 -14 - 19 - 20 + power supply TB1 − BI1 BI2 BI3 BI4 BI5 BI6 - 13 - 14 -12 Figure 6.4.1 Testing Binary Input Circuit 117 6 F 2 T 0 1 7 6 • Display the "Binary I/O" screen from the "Status" sub-menu. / 2 B i n a r y I / O I P [ 0 0 0 0 0 0 ] O P [ 0 0 0 0 0 ] • Apply the rated supply voltage to terminals 13-14, 15-16, 17,18,19,20-21 of terminal block TB2. Check that the status display corresponding to the input signal (IP) changes from 0 to 1. (For details of the binary input status display, see Section 4.2.4.2.) The user will be able to perform this test from one terminal to another or for all the terminals at once. 6.4.3 Binary Output Circuits This test can be performed by using the "Test" sub-menu and forcibly operating the relay drivers and output relays. Operation of the output contacts is monitored at the output terminal. The output contact and corresponding terminal number are shown in Appendix G. • Select "Binary O/P" on the "Test" screen to display the "Binary O/P" screen. The LCD displays the name of the output relay. / 2 B i n a r y O / P B O 1 _ > B O 1 0 D i s a b l e / E n a B O 2 D i s s a b l e / E n a a e b l e / E n a b l e 0 s a F A I L D i a s b l 0 B O 4 D i e 0 B O 3 D i b l b l e / E n a b l e 0 b l e / E n a b l e • Enter 1 and press the ENTER key. • After completing the entries, press the END key. The LCD will display the screen shown below. If 1 is entered for all the output relays, the following forcible operation can be performed collectively. 118 6 F 2 T 0 1 7 6 O p e r a t e ? E N T E R = Y C A N C E L = N • Keep pressing the ENTER key to operate the output relays forcibly. • Check that the output contacts operate at the terminal. • Stop pressing the ENTER key to reset the operation 6.4.4 AC Input Circuits This test can be performed by applying check currents to the AC input circuits and verifying that the values applied coincide with the values displayed on the LCD screen. The testing circuit is shown in Figure 6.4.2. GRE130 V TB1 -1 VA -2 Three-phase voltage source -3 -4 VB -5 VC -6 V -7 Single-phase voltage source power supply -8 + TB1 -13 − -14 12 Figure 6.4.2 Testing AC Input Circuit To check the metering data on the "Metering" screen, do the following. "Set. (view)" sub-menu → "Status" screen → "Metering" screen If the setting is 0 ( = Primary), change the setting to 1 (Secondary) in the "Set. (change)" sub-menu. "Set. (change)" sub-menu → "Status" screen → "Metering" screen Remember to reset it to the initial setting after the test is finished. • Open the "Metering" screen in the "Status" sub-menu. "Status" sub-menu → "Metering" screen • Apply AC currents and check that the displayed values are within ±5% of the input values. 119 6 F 2 T 0 1 7 6 6.5 Function Test CAUTION The function test may cause the output relays to operate including the tripping output relays. Therefore, the test must be performed with tripping circuits disconnected. 6.5.1 Measuring Element Measuring element characteristics are realized using software, so it is possible to verify the overall characteristics by checking representative points. Operation of the element under test is observed by assigning the signal number to a configurable LED or a binary output relay. Note: The voltage level at the monitoring jacks is +5V for logic level "1" and less than 0.1V for logic level "0". CAUTION • Use test equipment with more than 1 kΩ of internal impedance when observing the output signal at the monitoring jacks. • Do not apply an external voltage to the monitoring jacks. • Do not leave the A or B terminal shorted to 0V terminal for a long time. In the case of a three-phase element, it is sufficient to test for a representative phase. The A-phase element is selected hereafter. Further, the [APPLCT] settings are selected “3P” and “3PV”. Note: The operating time test for the relay measuring elements at monitoring jacks A or B does not include operation of the binary output. An overall operating time test, if required, should be measured at a binary output relay. Assigning signals to LEDs • Select "LED" on the "Set. (change)" screen to display the "2/ LED" screen. / 2 L E D > L E D V i • r t u a l L E D Select "LED" on the "/2 LED" screen to display the "/3 LED" screen. / 3 L E D > L E D 1 L E D 2 L E D 3 L E D 4 L E D 5 L E D 6 C B C L O S E D Note: The setting is required for all of the LEDs. If any of the LEDs are not used, enter 0 to logic gates #1 to #4 in assigning signals. 120 6 F 2 T 0 1 7 6 • Select the LED number and press the ENTER key to display the "LED∗" screen. / 4 L E D ∗ > L o g i c / R e s F u n c t i o n s L E D C o l o e t r • Select "Logic/Reset" to display the "Logic/Reset" screen. / 5 L o L o g > L o i g c / R e c g i s e t _ c 0 O R / A N D R e s e t n s t / I i 0 L a t c h • Enter 0 (= OR) and press the ENTER key. • Enter 0 (= Instantaneous) and press the ENTER key. • Press the END key to return to the "LED∗" screen. • Select "Functions" on the "LED∗" screen to display the "Functions" screen. / 5 F u I n ♯ 1 n c t i o n s _ > I n ♯ 1 _ _ _ I n ♯ 2 _ _ _ I n ♯ 3 _ _ _ I n ♯ 4 _ _ _ • Assign the gate In #1 the number corresponding to the testing element referring to Appendix B, and assign other gates to “0”. Assigning signals to Binary Output Relays • Select "Binary O/P" on the "Set. (change)" screen to display the "Binary O/P" screen. / 2 B i n a r y > B O 1 B O 2 B O 3 B O 4 121 O / P 6 F 2 T 0 1 7 6 Note: The setting is required for all of the binary outputs. If any of the binary outputs are not used, enter 0 to logic gates In #1 to #4 in assigning signals. • Select the output relay number (BO number) and press the ENTER key to display the "BO∗" screen. / 3 B O ∗ > L o g i c / R e F u n c t i o s e t n s • Select "Logic/Reset" to display the "Logic/Reset" screen. / 4 L o L o g > L o i g i / R e s c g i e t _ c 0 O R / A N D R e s e t n s / D l I c 0 / D w / L a t • Enter 0 (= OR) and press the ENTER key. • Enter 0 (= Instantaneous) and press the ENTER key. • Press the END key to return to the "BO∗" screen. • Select "Functions" on the "BO∗" screen to display the "Functions" screen. / 4 F u I n ♯ 1 n c > I n ♯ 1 I n ♯ 2 I n ♯ 3 I n ♯ 4 T B O t i o n s _ _ _ _ _ _ _ _ _ _ _ _ _ 0 . 2 0 s • Assign the gate In #1 the number corresponding to the testing element referring to Appendix A and assign other gates to “0”. 122 6 F 2 T 0 1 7 6 6.5.1.1 Overvoltage and undervoltage elements The testing circuit is shown in Figure 6.5.1. GRE130 V + Variable- TB 1 − Voltage source -2 + power supply -1 TB1 -13 − -14 -12 (∗ ) :Connect the terminal number corresponding to the testing element. Refer to Table 3.2.1. Figure 6.5.1 Operating Value Test Circuit Overvoltage and undervoltage elements and their output signal numbers are listed below. Element OV1 OV2 OV3 ZPS1 Signal No. 101 108 115 134 Element UV1 UV2 UV3 ZPS2 Signal No. 122 126 130 135 • Enter the signal number to observe the operation at the LED as shown in Section 6.5.1 and press the ENTER key. • Apply a test voltage and change the magnitude of the voltage applied and measure the value at which the element operates. Check that the measured value is within 5% of the setting value. Operating value test of OV1, OV2, OV3, ZPS1, ZPS2 • Apply rated voltage as shown in Figure 6.5.1. • Increase the voltage and measure the value at which the element operates. Check that the measured value is within ± 5% of the setting. Operating value test of UV1, UV2, UV3 • Apply rated voltage and frequency as shown Figure 6.5.1. • Decrease the voltage and measure the value at which the element operates. Check that the measured value is within ± 5% of the setting. Operating time check of OV1, UV1, ZPS1 IDMT curves • Change the voltage from the rated voltage to the test voltage quickly and measure the operating time. • Calculate the theoretical operating time using the characteristic equations shown in Section 2.1.1 and 2.1.2. Check the measured operating time. 123 6 F 2 T 0 1 7 6 6.5.1.2 Negative sequence overvoltage element NPS1 and NPS2 The testing circuit is shown in Figure 6.5.2. GRE130 V Three-phase Voltage source power supply Va TB1 -1 Vb -3 Vc VN -5 -6 + TB1 -13 − -14 -12 Figure 6.5.2 Testing NOV elements The output signal numbers of the elements are as follows: Element Signal No. NPS1 136 NPS2 137 • Apply a three-phase balanced voltage and the check the value of the operating voltage by increasing the magnitude of the voltage applied. Check that the measured value is within 5% of the setting value. Operating time check of NPS1 IDMT curve • Change the voltage from the rated voltage to the test voltage quickly and measure the operating time. • Calculate the theoretical operating time using the characteristic equations shown in Section 2.1.4. Check the measured operating time. 124 6 F 2 T 0 1 7 6 6.5.1.3 Frequency Elements The testing circuit is shown in Figure 6.5.3. GRE130 + VariableFrequency / − Voltage source power supply V f TB1 -1 -2 + TB1 -13 − -14 -12 Figure 6.5.3 Operating Value Test Circuit Frequency elements and their output signal numbers are listed below. Element FRQ1 FRQ2 FRQ3 FRQ4 FVBLK Signal No. 251 252 253 254 255 Overfrequency or underfrequency elements FRQ1 to FRQ4 Note: Each element characteristic, overfrequency or underfrequency, is determined by the scheme switch [FT1] to [FT4] settings. Check the scheme switch setting and characteristic of each element before testing . • Apply rated voltage and frequency as shown in Figure 6.5.3. For the overfrequency characteristic, • Increase the frequency and measure the value at which the element operates. Check that the measured value is within ± 0.005Hz of the setting. For the underfrequency characteristics, • Decrease the frequency and measure the value at which the element operates. Check that the measured value is within ± 0.005Hz of the setting. Undervoltage block test, FVBLK • Apply rated voltage and change the magnitude of the frequency to operate an element. • Maintain the frequency at which the element is operating, and change the magnitude of the voltage applied from the rated voltage to less than the FVBLK setting voltage. And then, check that the element resets. 6.5.2 Protection Scheme In the protection scheme tests, a dynamic test set is required to simulate power system pre-fault, fault and post-fault conditions. Tripping is observed with the tripping command output relays operate after a simulated fault occurs. 125 6 F 2 T 0 1 7 6 6.5.3 Metering and Recording The metering function can be checked while testing the AC input circuit. See Section 6.4.4. Fault recording can be checked while testing the protection schemes. Open the "Fault record" screen and check that the descriptions are correct for the fault concerned. Recording events are listed in Appendix B. There are internal events and external events from binary input commands. Event recording from an external event can be checked by changing the status of binary input command signals. Change the status in the same way as the binary input circuit test (see Section 6.4.2) and check that the description displayed on the "Event record" screen is correct. Some of the internal events can be checked in the protection scheme tests. Disturbance recording can be checked while testing the protection schemes. The LCD display only shows the date and time when a disturbance is recorded. Open the "Disturbance record" screen and check that the descriptions are correct. Details can be displayed on a PC. Check that the descriptions on the PC are correct. For details on how to obtain disturbance records on the PC, see the RSM100 Manual. 6.6 Conjunctive Tests 6.6.1 On Load Test To check the polarity of the current and voltage transformers, check the load current, system voltage and their respective phase angles using the metering displays on the LCD screen. • Open the "Auto-supervision" screen and check that no message appears. • Open the following "Metering" screen from the "Status" sub-menu to check the above. / Note: 6.6.2 2 M e t e r i n g V a * * . * * k V V b * * . * * k V V c * * . * * k V V e s * * . * * k V V a b * * . * * k V V b c * * . * * k V V c a * * . * * k V V 1 * * * . * k V V 2 * * * . * k V V 0 * * . * * k V f * * . * * H z The magnitude of current can be set in values for either the primary side or the secondary side by a setting. (The default setting is the secondary side.) Tripping Circuit Test The tripping circuit, including the circuit breaker, is checked by forcibly operating the output relay and monitoring the circuit breaker to confirm that it has tripped. Forcible operation of the output relay is performed on the "Binary O/P " screen of the "Test" sub-menu as described in Section 6.4.3. 126 6 F 2 T 0 1 7 6 Tripping circuit • Set the breaker to be closed. • Select "Binary O/P" on the "Test" sub-menu screen to display the "Binary O/P" screen. / 2 B i n a r y O / P B O 1 _ > B O 1 0 D i s a b l e / E n a B O 2 D i s s a b l e / E n a a e b l e / E n a b l e 0 s a F A I L D i a s b l 0 B O 4 D i e 0 B O 3 D i b l b l e / E n a b l e 0 b l e / E n a b l e BO1 to BO4 are output relays with one normally open contact. • Enter 1 for BO2 and press the ENTER key. • Press the END key. Then the LCD will display the screen shown below. O p e r a t e E N T E R = Y ? C A N C E L = N • Keep pressing the ENTER key to operate the output relay BO2 and check that the A-phase breaker is tripped. • Stop pressing the ENTER key to reset the operation. • Repeat the above for BO1, BO3 and BO4. 127 6 F 2 T 0 1 7 6 6.7 Maintenance 6.7.1 Regular Testing The relay is almost completely self-supervised. The circuits that can not be supervised are binary input and output circuits and human interfaces. Therefore, regular testing is minimised to checking the unsupervised circuits. The test procedures are the same as described in Sections 6.4.1, 6.4.2 and 6.4.3. 6.7.2 Failure Tracing and Repair Failures will be detected by automatic supervision or regular testing. When a failure is detected by supervision, a remote alarm is issued from the binary output FAIL relay and the failure is indicated on the front panel by the LED indicators or LCD display. It is also recorded in the event record. Failures detected by supervision are traced by checking the "Err: " screen on the LCD. Table 6.7.1 shows LCD messages and failure locations. The locations marked with (1) have a higher probability than locations marked with (2). Table 6.7.1 LCD Message and Failure Location Message Failure location Relay Unit AC cable Err: SUM ×(Flash memory) Err: RAM ×(SRAM) Err: BRAM ×(Backup RAM) Err: EEP ×(EEPROM) Err: A/D ×(A/D converter) Err: V0, Err: V2 × (AC input circuit)(1) Err: DRIVER × (BI,BO circuit)(1) CB or Cable × (2) × (2) ( ): Probable failure location in the relay unit including its peripheral circuits. * ; Error level set in VT supervision function. Alarms detected by the relay self-supervision are traced by checking the "ALM: " screen on the LCD. Table 6.7.2 shows LCD messages and alarm locations. Table 6.7.2 LCD Message and Alarm Location Message Failure location Relay Unit AC cable CB or Cable ALM: VT ×(AC input circuit)(1) ALM: TC ×(Trip circuit)(1) × (2) ALM: CB ×(Circuit breaker)(1) × (2) ALM: TP COUNT ×(Trip count)(1) × (2) × (2) ( ): Probable failure location in the relay unit including peripheral circuits. 128 6 F 2 T 0 1 7 6 If there is no message is shown on the LCD it means that the failure location is either in the power supply circuit or in the microprocessors. If the "ALARM" LED is off, the failure is in the power supply circuit. If the LED is lit, the failure is in the microprocessors. Replace the relay unit in both cases after checking if the correct voltage is applied to the relay. If a failure is detected by the automatic supervision function or regular testing, replace the failed relay unit. Note: When a failure or an abnormality is detected during a regular test, confirm the following first: - Test circuit connections are correct. - Correct power voltage is applied. - Correct AC inputs are applied. - Test procedures comply with those stated in the manual. 6.7.3 Replacing Failed Relay Unit If the failure is identified to be in the relay and the user has a spare relay, the user can recover the protection by replacing the relay. Repairs at site should be limited to relay replacement. Maintenance at component level is not recommended. Check that the replacement relay unit has an identical Model Number and relay version (software type form) as the relay to be replaced. The Model Number is indicated on the front of the relay. For the relay version, see Section 4.2.5.1. Replacing the relay unit CAUTION After replacing the relay unit, check the settings. The procedure for relay withdrawal and insertion is as follows: • Switch off the DC power supply. WARNING Hazardous voltage may remain in the DC circuit when the power supply is de-energized. It will take approximately 30 seconds for the voltage to discharge. • Remove the terminal blocks from the relay leaving the wiring in place. • To remove the relay unit from the panel, the attachment screws must be removed. • Insert the (spare) relay unit following the reverse procedure. CAUTION To avoid risk of damage: • When the attachment kits are removed, support the relay to ensure that it does not fall from panel. • Ensure that the relay front cover panel is closed throughout the operation. 6.7.4 Resumption of Service After replacing the failed relay unit or repairing failed external circuits, take the following procedures to restore the relay to the service. • Switch on the power supply and confirm that the "IN SERVICE" green LED is lit and the "ALARM" red LED is not lit. • Connect the AC inputs and reconnect the trip outputs. 6.7.5 Storage The spare relay should be stored in a dry and clean room. Based on IEC Standard 60255-6 the storage temperature should be −25°C to +70°C, but the temperature of 0°C to +40°C is recommended for long-term storage. 129 6 F 2 T 0 1 7 6 7. Putting Relay into Service The following procedure must be adhered to when putting the relay into service after finishing the commissioning tests or maintenance tests. • Check that all the external connections are correct. • Check the settings of all measuring elements, timers, scheme switches, recordings and clock are correct. In particular, when settings are changed temporarily for testing, be sure to restore them. • Clear any unnecessary records on faults, alarms, events, disturbances and counters which are recorded during the tests. • Press ▼ key and check that no failure message is displayed on the "Auto-supervision" screen. • Check that the green "IN SERVICE" LED is lit and no other LEDs are lit on the front panel. 130 6 F 2 T 0 1 7 6 Appendix A Signal List 131 6 F 2 T 0 1 7 6 No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 SIGNAL Name BI1 COMAND BI2 COMAND BI3 COMAND BI4 COMAND BI5 COMAND BI6 COMAND CONSTANT_0 CONSTANT_1 SET. GROUP1 SET. GROUP2 OV1 BLOCK OV2 BLOCK OV3 BLOCK UV1 BLOCK UV2 BLOCK UV3 BLOCK ZPS1 BLOCK ZPS2 BLOCK NPS1 BLOCK NPS2 BLOCK TC FAIL CB CONT OPN CB CONT CLS EXT TRIP-3PH EXT TRIP-APH EXT TRIP-BPH EXT TRIP-CPH REMOTE RESET SYNC CLOCK STORE RECORD ALARM1 ALARM2 ALARM3 ALARM4 Contents Not in use Binary Input signal of BI1 Binary Input signal of BI2 Binary Input signal of BI3 Binary Input signal of BI4 Binary Input signal of BI5 Binary Input signal of BI6 Not in use Not in use Constant 0 Constant 1 BI command of change active setting group1 BI command of change active setting group2 Not in use Not in use BI command of OV1 protection scheme block BI command of OV2 protection scheme block BI command of OV3 protection scheme block BI command of UV1 protection scheme block BI command of UV2 protection scheme block BI command of UV3 protection scheme block BI command of ZPS1 protection scheme block BI command of ZPS2 protection scheme block BI command of NPS1 protection scheme block BI command of NPS2 protection scheme block BI command of Trip circuit Fail Alarm BI command of CB N/O contact BI command of CB N/C contact BI command of External trip (3 Phase) BI command of External trip (A Phase) BI command of External trip (B Phase) BI command of External trip (C Phase) BI command of Remote reset BI command of Synchronize Clock BI command of Store Disturbance Record BI command of Alarm1 BI command of Alarm2 BI command of Alarm3 BI command of Alarm4 Not in use Not in use 132 6 F 2 T 0 1 7 6 No. 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 SIGNAL Name FRQ1 BLOCK FRQ2 BLOCK FRQ3 BLOCK FRQ4 BLOCK OV1_INST-OR OV1-A INST OV1-B INST OV1-C INST OV2_INST-OR OV2-A INST OV2-B INST OV2-C INST OV1-A OV1-B OV1-C OV2-A OV2-B OV2-C OV3-A OV3-B OV3-C UV1-A UV1-B UV1-C UV2-A UV2-B UV2-C UV3-A UV3-B UV3-C OV1-OR OV1-A pick up OV1-B pick up OV1-C pick up Contents Not in use BI command of FRQ1 protection scheme block BI command of FRQ2 protection scheme block BI command of FRQ3 protection scheme block BI command of FRQ4 protection scheme block Not in use Not in use Not in use Not in use OV1 element start at IDMT setting. OV1-A relay element start at IDMT setting. OV1-B relay element start at IDMT setting. OV1-C relay element start at IDMT setting. Not in use Not in use OV2 element start at IDMT setting.. OV2-A relay element start at IDMT setting. OV2-B relay element start at IDMT setting. OV2-C relay element start at IDMT setting. Not in use Not in use Not in use OV1-A relay element output OV1-B relay element output OV1-C relay element output OV2-A relay element output OV2-B relay element output OV2-C relay element output OV3-A relay element output OV3-B relay element output OV3-C relay element output UV1-A relay element output UV1-B relay element output UV1-C relay element output UV2-A relay element output UV2-B relay element output UV2-C relay element output UV3-A relay element output UV3-B relay element output UV3-C relay element output OV1 element start at DT settings. OV1-A relay element start at DT settings. OV1-B relay element start at DT settings. OV1-C relay element start at DT settings. 133 6 F 2 T 0 1 7 6 No. 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 SIGNAL Name OV2-OR OV2-A pick up OV2-B pick up OV2-C pick up OV3-OR ZPS1 ZPS2 NPS1 NPS2 UVBLK OV1 TRIP OV1-A TRIP OV1-B TRIP OV1-C TRIP OV2 TRIP OV2-A TRIP OV2-B TRIP OV2-C TRIP OV3 TRIP OV3-A TRIP OV3-B TRIP OV3-C TRIP FV BLOCK UV1 TRIP UV1-A TRIP UV1-B TRIP UV1-C TRIP UV2 TRIP UV2-A TRIP UV2-B TRIP UV2-C TRIP Contents OV2 element start at DT settings. OV2-A relay element start at DT settings. OV2-B relay element start at DT settings. OV2-C relay element start at DT settings. OV3 element start at DT settings. Not in use Not in use Not in use ZPS1 relay element output ZPS2 relay element output NPS1 relay element output NPS2 relay element output UV protection scheme block Not in use Not in use Not in use OV1 trip command OV1 trip command (A Phase) OV1 trip command (B Phase) OV1 trip command (C Phase) Not in use Not in use Not in use OV2 trip command OV2 trip command (A Phase) OV2 trip command (B Phase) OV2 trip command (C Phase) Not in use Not in use Not in use OV3 trip command OV3 trip command (A Phase) OV3 trip command (B Phase) OV3 trip command (C Phase) Not in use Not in use FRQ protection scheme block by UV element UV1 trip command UV1 trip command (A Phase) UV1 trip command (B Phase) UV1 trip command (C Phase) UV2 trip command UV2 trip command (A Phase) UV2 trip command (B Phase) UV2 trip command (C Phase) 134 6 F 2 T 0 1 7 6 No. 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 SIGNAL Name UV3 TRIP UV3-A TRIP UV3-B TRIP UV3-C TRIP ZPS1 TRIP ZPS2 ALARM NPS1 TRIP NPS2 ALARM GEN.TRIP GEN.TRIP-A GEN.TRIP-B GEN.TRIP-C GEN.ALARM ZPS1 pick-up ZPS2 pick-up NPS1 pick-up NPS2 pick-up UV1 INST-OR UV2 INST-OR UV1-A INST UV1-B INST UV1-C INST A.M.F.OFF RELAY FAIL RELAY FAIL-A TCSV CBSV TC ALARM V0 ERR V2 ERR BO1OP BO2OP BO3OP BO4OP Contents UV3 trip command UV3 trip command (A Phase) UV3 trip command (B Phase) UV3 trip command (C Phase) ZPS1 trip command ZPS2 alarm command NPS1 trip command NPS2 alarm command Not in use Not in use Not in use General Trip command General Trip command (A Phase) General Trip command (B Phase) General Trip command (C Phase) Not in use Not in use Not in use Not in use Not in use General alarm command ZPS1 element start at DT setting. ZPS2 element start at DT setting. NPS1 element start at DT setting. NPS2 element start at DT setting. UV1 relay element start at IDMT setting UV2 relay element start at IDMT setting UV1-A relay element start at IDMT setting UV1-B relay element start at IDMT setting UV1-C relay element start at IDMT setting Automatic monitoring function off Relay failure & trip blocked alarm Relay failure alarm (Trip not blocked) Trip circuit supervision failure Circuit breaker status monitoring failure Trip counter alarm Not in use Not in use V0 error V2 error Binary Output1 operated Binary Output2 operated Binary Output3 operated Binary Output4 operated 135 6 F 2 T 0 1 7 6 No. 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 SIGNAL Name UV2-A INST UV2-B INST UV2-C INST LCD IND. LCD IND1. LCD IND2. TESTING GEN PICKUP NORM LED ON TRIP LED ON PROT COM ON IECTST IECBLK ZPS1 INST ZPS2 INST NPS1 INST NPS2 INST BI1 COMMAND1 BI2 COMMAND1 BI3 COMMAND1 BI4 COMMAND1 BI5 COMMAND1 BI6 COMMAND1 BO5OP BO6OP BO7OP BO8OP F11 F12 DF-R1 DF-D1 F21 F22 DF-R2 Contents Not in use Not in use Not in use UV2-A relay element start at IDMT setting. UV2-B relay element start at IDMT setting. UV2-C relay element start at IDMT setting. Not in use LCD indication (Virtual LED) command LCD indication1 (Virtual LED) command LCD indication2 (Virtual LED) command Not in use Not in use Testing LED lit output Not in use Not in use Not in use General start / pick-up output In service LED ON TRIP LED ON IEC60870-5-103 protection command IEC60870-5-103 communication test IEC60870-5-103 communication block Not in use ZPS1 relay element start at IDMT setting ZPS2 relay element start at IDMT setting NPS1 relay element start at IDMT setting NPS2 relay element start at IDMT setting Binary Input signal of BI1 after BI1SNS Binary Input signal of BI2 after BI2SNS Binary Input signal of BI3 after BI3SNS Binary Input signal of BI4 after BI4SNS Binary Input signal of BI5 after BI5SNS Binary Input signal of BI6 after BI6SNS Binary Output5 operated Binary Output6 operated Binary Output7 operated Binary Output8 operated FRQ1 relay F11 element output FRQ1 relay F12 element output DFRQ1 relay rise element output DFRQ1 relay decay element output FRQ2 relay F21 element output FRQ2 relay F22 element output DFRQ2 relay rise element output 136 6 F 2 T 0 1 7 6 No. 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 SIGNAL Name DF-D2 F31 F32 DF-R3 DR-D3 F41 F42 DF-R4 DF-D4 F11 TRIP F12 TRIP DF-R1 TRIP DF-D1 TRIP FRQ1 TRIP F21 TRIP F22 TRIP DF-R2 TRIP DF-D2 TRIP FRQ2 TRIP F31 TRIP F32 TRIP DF-R3 TRIP DF-D3 TRIP FRQ3 TRIP F41 TRIP F42 TRIP DF-R4 TRIP DF-D4 TRIP FRQ4 TRIP FRQ STAGE1 TRIP FRQ STAGE2 TRIP FRQ STAGE3 TRIP FRQ STAGE4 TRIP UV1-OR UV1-A pick up UV1-B pick up UV1-C pick up UV2-OR UV2-A pick up UV2-B pick up UV2-C pick up Contents DFRQ2 relay decay element output FRQ3 relay F31 element output FRQ3 relay F32 element output DFRQ3 relay rise element output DFRQ3 relay decay element output FRQ4 relay F41 element output FRQ4 relay F42 element output DFRQ4 relay rise element output DFRQ4 relay decay element output Not in use Not in use Not in use Not in use FRQ1 relay F11 Trip command FRQ1 relay F12 Trip command DFRQ1 relay rise Trip command DFRQ1 relay decay Trip command FRQ1 relay Trip command FRQ2 relay F21 Trip command FRQ2 relay F22 Trip command DFRQ2 relay rise Trip command DFRQ2 relay decay Trip command FRQ2 relay Trip command FRQ3 relay F31 Trip command FRQ3 relay F32 Trip command DFRQ3 relay rise Trip command DFRQ3 relay decay Trip command FRQ3 relay Trip command FRQ4 relay F41 Trip command FRQ4 relay F42 Trip command DFRQ4 relay rise Trip command DFRQ4 relay decay Trip command FRQ4 relay Trip command FRQ1 relay Trip command FRQ2 relay Trip command FRQ3 relay Trip command FRQ4 relay Trip command UV1 element start at DT settings. UV1-A relay element start at DT settings. UV1-B relay element start at DT settings. UV1-C relay element start at DT settings. UV2 element start at DT settings. UV2-A relay element start at DT settings. UV2-B relay element start at DT settings. UV2-C relay element start at DT settings. 137 6 F 2 T 0 1 7 6 No. 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 SIGNAL Name UV3-OR UV3-A pick up UV3-B pick up UV3-C pick up LOCAL REMOTE CB_OPN_L CB_CLS_L CB_OPN_BI CB_CLS_BI CB_OPN_COMM CB_CLC_COMM LOCK_BI LOCK_COMM CB OPOUT CB CLOUT OV1I-A OV1I-B OV1I-C OV2I-A OV2I-B OV2I-C ZPS1I-A NPS1I-B ZPS2I-C NPS2I-A UV1I-A UV1I-B UV1I-C UV2I-A UV2I-B UV2I-C ETH1_LINKUP ETH2_LINKUP IEC61850 RUN GOOSE IN Q1 GOOSE IN Q2 GOOSE IN Q3 GOOSE IN Q4 Contents UV3 element start at DT settings. UV3-A relay element start at DT settings. UV3-B relay element start at DT settings. UV3-C relay element start at DT settings. Not in use Not in use Not in use Circuit Breaker Control hierarchy Local state Circuit Breaker Control hierarchy Remote state Local SW command of Circuit Breaker open Local SW command of Circuit Breaker close BI command of Circuit Breaker open BI command of Circuit Breaker close Communication command of Circuit Breaker open Communication command of Circuit Breaker close BI command of Interlock Communication command of Interlock Circuit Breaker Open output Circuit Breaker Close output Not in use Not in use OV1-A integrated value holding at IDMT setting OV1-B integrated value holding at IDMT setting OV1-C integrated value holding at IDMT setting OV2-A integrated value holding at IDMT setting OV2-B integrated value holding at IDMT setting OV2-C integrated value holding at IDMT setting ZPS1 integrated value holding at IDMT setting NPS1 integrated value holding at IDMT setting ZPS2 integrated value holding at IDMT setting NPS2 integrated value holding at IDMT setting UV1-A integrated value holding at IDMT setting UV1-B integrated value holding at IDMT setting UV1-C integrated value holding at IDMT setting UV2-A integrated value holding at IDMT setting UV2-B integrated value holding at IDMT setting UV2-C integrated value holding at IDMT setting Not in use Ether port 1 LINK-UP Ether port 2 LINK-UP IEC61850 RUN Goose quality#1 Goose quality#2 Goose quality#3 Goose quality#4 138 6 F 2 T 0 1 7 6 No. 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 SIGNAL Name GOOSE IN Q5 GOOSE IN Q6 GOOSE IN Q7 GOOSE IN Q8 GOOSE IN Q9 GOOSE IN Q10 GOOSE IN Q11 GOOSE IN Q12 GOOSE IN Q13 GOOSE IN Q14 GOOSE IN Q15 GOOSE IN Q16 GOOSE IN 1 GOOSE IN 2 GOOSE IN 3 GOOSE IN 4 GOOSE IN 5 GOOSE IN 6 GOOSE IN 7 GOOSE IN 8 GOOSE IN 9 GOOSE IN 10 GOOSE IN 11 GOOSE IN 12 GOOSE IN 13 GOOSE IN 14 GOOSE IN 15 GOOSE IN 16 Contents Goose quality#5 Goose quality#6 Goose quality#7 Goose quality#8 Goose quality#9 Goose quality#10 Goose quality#11 Goose quality#12 Goose quality#13 Goose quality#14 Goose quality#15 Goose quality#16 Goose data#1 Goose data#2 Goose data#3 Goose data#4 Goose data#5 Goose data#6 Goose data#7 Goose data#8 Goose data#9 Goose data#10 Goose data#11 Goose data#12 Goose data#13 Goose data#14 Goose data#15 Goose data#16 350 351 352 353 354 355 356 357 358 359 360 361 TEMP001 TEMP002 TEMP003 TEMP004 TEMP005 TEMP006 TEMP007 TEMP008 TEMP009 TEMP0010 TEMP0011 TEMP0012 Temporally output signal Temporally output signal Temporally output signal Temporally output signal Temporally output signal Temporally output signal Temporally output signal Temporally output signal Temporally output signal Temporally output signal Temporally output signal Temporally output signal 139 6 F 2 T 0 1 7 6 Appendix B Event Record Items 140 6 F 2 T 0 1 7 6 ID. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 LCD indication GEN.trip GEN.trip-A GEN.trip-B GEN.trip-C GEN.trip-AB GEN.trip-BC GEN.trip-CA OV1-A trip OV1-B trip OV1-C trip OV2-A trip OV2-B trip OV2-C trip OV3-A alarm OV3-B alarm OV3-C alarm UV1-A trip UV1-B trip UV1-C trip UV2-A trip UV2-B trip UV2-C trip UV3-A alarm UV3-B alarm UV3-C alarm OV1-AB trip OV1-BC trip OV1-CA trip OV2-AB trip OV2-BC trip OV2-CA trip OV3-AB alarm OV3-BC alarm OV3-CA alarm UV1-AB trip UV1-BC trip UV1-CA trip UV2-AB trip UV2-BC trip UV2-CA trip UV3-AB alarm UV3-BC alarm Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Contents General trip command General trip command (A Phase) General trip command (B Phase) General trip command (C Phase) General trip command (A-B Phase) General trip command (B-C Phase) General trip command (C-A Phase) OV1 trip command (A Phase) OV1 trip command (B Phase) OV1 trip command (C Phase) OV2 trip command (A Phase) OV2 trip command (B Phase) OV2 trip command (C Phase) OV3 alarm command (A Phase) OV3 alarm command (B Phase) OV3 alarm command (C Phase) UV1 trip command (A Phase) UV1 trip command (B Phase) UV1 trip command (C Phase) UV2 trip command (A Phase) UV2 trip command (B Phase) UV2 trip command (C Phase) UV3 alarm command (A Phase) UV3 alarm command (B Phase) UV3 alarm command (C Phase) OV1 trip command (A-B Phase) OV1 trip command (B-C Phase) OV1 trip command (C-A Phase) OV2 trip command (A-B Phase) OV2 trip command (B-C Phase) OV2 trip command (C-A Phase) OV3 alarm command (A-B Phase) OV3 alarm command (B-C Phase) OV3 alarm command (C-A Phase) UV1 trip command (A-B Phase) UV1 trip command (B-C Phase) UV1 trip command(C-A Phase) UV2 trip command (A-B Phase) UV2 trip command (B-C Phase) UV2 trip command(C-A Phase) UV3 alarm command (A-B Phase) UV3 alarm command (B-C Phase) 141 6 F 2 T 0 1 7 6 No. 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 LCD indication UV3-CA alarm OV1 trip OV2 trip OV3 trip UV1 trip UV2 trip UV3 trip ZPS1 trip ZPS2 alarm NPS1 trip NPS2 alarm OV1-A OV1-B OV1-C OV2-A OV2-B OV2-C OV3-A OV3-B OV3-C UV1-A UV1-B UV1-C UV2-A UV2-B UV2-C UV3-A UV3-B UV3-C OV1-AB OV1-BC OV1-CA OV2-AB OV2-BC OV2-CA OV3-AB OV3-BC OV3-CA UV1-AB UV1-BC UV1-CA UV2-AB UV2-BC UV2-CA UV3-AB UV3-BC Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Contents UV3 alarm command (C-A Phase) OV1 trip command OV2 trip command OV3 trip command UV1 trip command UV2 trip command UV3 trip command ZPS1 trip command ZPS2 alarm command NPS1 trip command NPS2 alarm command OV1-A relay element operating OV1-B relay element operating OV1-C relay element operating OV2-A relay element operating OV2-B relay element operating OV2-C relay element operating OV3-A relay element operating OV3-B relay element operating OV3-C relay element operating UV1-A relay element operating UV1-B relay element operating UV1-C relay element operating UV2-A relay element operating UV2-B relay element operating UV2-C relay element operating UV3-A relay element operating UV3-B relay element operating UV3-C relay element operating OV1-AB relay element operating OV1-BC relay element operating OV1-CA relay element operating OV2-AB relay element operating OV2-BC relay element operating OV2-CA relay element operating OV3-AB relay element operating OV3-BC relay element operating OV3-CA relay element operating UV1-AB relay element operating UV1-BC relay element operating UV1-CA relay element operating UV2-AB relay element operating UV2-BC relay element operating UV2-CA relay element operating UV3-AB relay element operating UV3-BC relay element operating 142 6 F 2 T 0 1 7 6 No. 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 LCD indication UV3-CA OV1 OV2 OV3 UV1 UV2 UV3 ZPS1 ZPS2 NPS1 NPS2 UVBLK BI1 command BI2 command BI3 command BI4 command BI5 command BI6 command SET. group1 SET. group2 OV1 block OV2 block OV3 block UV1 block UV2 block UV3 block ZPS1 block ZPS2 block NPS1 block NPS2 block TC fail CB CONT OPN CB CONT CLS EXT trip-3PH EXT trip-APH EXT trip-BPH EXT trip-CPH Remote reset SYNC Store record Alarm1 Alarm2 Alarm3 Alarm4 Relay fail Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Contents UV3-CA relay element operating OV1 relay element operating OV2 relay element operating OV3 relay element operating UV1 relay element operating UV2 relay element operating UV3 relay element operating ZPS1 relay element operating ZPS2 relay element operating NPS1 relay element operating NPS2 relay element operating UVBLK element operating Binary input signal of BI1 Binary input signal of BI2 Binary input signal of BI3 Binary input signal of BI4 Binary input signal of BI5 Binary input signal of BI6 BI command of change active setting group1 BI command of change active setting group2 BI command of OV1 protection scheme block BI command of OV2 protection scheme block BI command of OV3 protection scheme block BI command of UV1 protection scheme block BI command of UV2 protection scheme block BI command of UV3 protection scheme block BI command of ZPS1 protection scheme block BI command of ZPS2 protection scheme block BI command of NPS1 protection scheme block BI command of NPS2 protection scheme block BI command of Trip circuit Fail Alarm BI command of CB N/O contact BI command of CB N/C contact BI command of External trip (3 Phase) BI command of External trip (A Phase) BI command of External trip (B Phase) BI command of External trip (C Phase) BI command of Remote reset BI command of Store Disturbance Record BI command of Alarm1 BI command of Alarm2 BI command of Alarm3 BI command of Alarm4 Relay failure & trip blocked alarm 143 6 F 2 T 0 1 7 6 No. 134 135 136 137 138 139 140 141 142 143 144 LCD indication Relay fail-A TC err CB err V0 err V2 err TP COUNT ALM F.record CLR E.record CLR D.record CLR TP COUNT IND.reset Contents Off / On Off / On Off / On Off / On Off / On Off / On On On On On On 145 Data lost On 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 On On On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Sys.Set Change Rly.Set Change Grp.Set Change OV1-A INST OV1-B INST OV1-C INST OV2-A INST OV2-B INST OV2-C INST UV1-A INST UV1-B INST UV1-C INST UV2-A INST UV2-B INST UV2-C INST OV1-AB INST OV1-BC INST OV1-CA INST OV2-AB INST OV2-BC INST OV2-CA INST UV1-AB INST UV1-BC INST UV1-CA INST UV2-AB INST UV2-BC INST UV2-CA INST OV1 INST OV2 INST UV1 INST UV2 INST ZPS1 INST ZPS2 INST No. Relay failure alarm (Trip not blocked) Trip circuit supervision failure Circuit Breaker failure Zero phase input circuit failure VT circuit supervision failure Trip counter alarm Clear Fault records Clear Event records Clear Disturbance records Clear Trip counter Reset indication for Trip mode, Alarm etc. Record and time for data lost with power supply de-energized for an extended period System setting change command Relay setting change command Group setting change command OV1-A relay element start OV1-B relay element start OV1-C relay element start OV2-A relay element start OV2-B relay element start OV2-C relay element start UV1-A relay element start UV1-B relay element start UV1-C relay element start UV2-A relay element start UV2-B relay element start UV2-C relay element start OV1-AB relay element start OV1-BC relay element start OV1-CA relay element start OV2-AB relay element start OV2-BC relay element start OV2-CA relay element start UV1-AB relay element start UV1-BC relay element start UV1-CA relay element start UV2-AB relay element start UV2-BC relay element start UV2-CA relay element start OV1 relay element start OV2 relay element start UV1 relay element start UV2 relay element start ZPS1 relay element start ZPS2 relay element start 144 6 F 2 T 0 1 7 6 No. 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 LCD indication NPS1 INST NPS2 INST FREQ1 trip FREQ2 trip FREQ3 trip FREQ4 trip FREQ1 block FREQ2 block FREQ3 block FREQ4 block Local Remote CB OPC_L CB CLC_L CB OPC_BI CB CLC_BI CB OPC_COMM CB CLC_COMM LOCK_BI LOCK_COMM CB OPOUT CB CLOUT V0 ALM V2 ALM BO1 operate BO2 operate BO3 operate BO4 operate BO5 operate BO6 operate BO7 operate BO8 operate GEN.pick-up Contents Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On No. NPS1 relay element start NPS2 relay element start FREQ1 relay element operating FREQ2 relay element operating FREQ3 relay element operating FREQ4 relay element operating BI command of FREQ1 protection scheme block BI command of FREQ2 protection scheme block BI command of FREQ3 protection scheme block BI command of FREQ4 protection scheme block CB Control hierarchy Local state CB Control hierarchy Remote state Local SW command of CB Open Local SW command of CB Close BI command of CB Open BI command of CB Close Communication command of CB Open Communication command of CB Close BI command of Interlock Communication command of Interlock CB Open Output CB Close Output Zero phase input circuit alarm VT circuit supervision alarm Binary output1 operating Binary output2 operating Binary output3 operating Binary output4 operating Binary output5 operating Binary output6 operating Binary output7 operating Binary output8 operating General start / pick-up command 145 6 F 2 T 0 1 7 6 Appendix C Binary Output Default Setting List 146 6 F 2 T 0 1 7 6 Relay Model BO No. Terminal No. Signal Name Contents GRE130 BO1 -410 BO2 TB2: 1-2 3–4 BO3 BO4 R.F. 5-6 7-8 9 - 10 Off (Link to CB Close SW) Relay trip (General) (Link to CB Open SW) GENERAL ALARM Relay alarm (General) NON Off Relay fail GRE130 BO1 -411 BO2 TB2: 1-2 3–4 NON GENERAL TRIP BO3 BO4 R.F. 5-6 7-8 9 - 10 Off (Link to CB Close SW) Relay trip (General) (Link to CB Open SW) GENERAL ALARM Relay alarm (General) NON Off Relay fail GRE130 BO1 -412 BO2 TB3: 1-2 3–4 NON GENERAL TRIP BO3 BO4 R.F. BO5 BO6 BO7 BO8 5-6 7-8 9 – 10 TB1 1-2 3-4 5-6 7-8 NON GENERAL TRIP Off (Link to CB Close SW) Relay trip (General) (Link to CB Open SW) GENERAL ALARM Relay alarm (General) NON Off Relay fail NON NON NON NON Off Off Off Off 147 Setting Signal No. Logic (OR:0, AND:1) Reset (Inst:0, Del:1 Latch:2) 0 141 0 0 1 1 150 0 0 0 1 1 0 141 0 0 1 1 150 0 0 0 1 1 0 141 0 0 1 1 150 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1 1 1 6 F 2 T 0 1 7 6 Appendix D Details of Relay Menu and LCD & Button Operation 148 6 F 2 T 0 1 7 6 a-1 b-1 MAIN MENU Record Status Set. (view) Set. (change) Control Test /1 Record Fault Event Disturbance Counter /2 Fault View record Clear Refer to Section 4.2.3.1. /3 Fault #1 16/Jul/2010 18:13:57.031 Clear records? END=Y CANCEL=N /2 Event View record Clear Refer to Section 4.2.3.2. /3 Event 16/Jul/2010 Ext. trip A On Clear records? END=Y CANCEL=N /2 Disturbance View record Clear Refer to Section 4.2.3.3. /3 Disturbance #1 16/Jul/2010 18:13:57.401 Clear records? END=Y CANCEL=N a-1 a-1 b-1 149 /4 Fault #1 16/Jul/2010 6 F 2 T 0 1 7 6 /2 Counter View counter Clear Trips Clear Trips A Clear Trips B Clear Trips C /3 Counter Trips ***** TripsA ***** TripsB ***** TripsC ***** Clear Trips? END=Y CANCEL=N Clear Trips A? END=Y CANCEL=N Clear Trips B? END=Y CANCEL=N Clear Trips C? END=Y CANCEL=N 150 6 F 2 T 0 1 7 6 a-1 /1 Status Metering Binary I/O Relay element Time sync. Clock adjust. LCD contrast /2 Metering Va **.** kV /2 Binary I/O IP [0000 00 ] /2 Ry element AN OV1-4[0000 ] Refer to Section 4.2.4. /2 Time sync. *BI: Act. /2 16/Jul/2010 22:56:19 [L] /2 LCD contrast /1 Set. (view) Version Description Comms Record Status Protection Binary I/P Binary O/P LED Control Frequency Refer to Section 4.2.5 /2 Version Relay type Software /2 Description Plant name Description /2 Comms Addr. Switch GRE130-411A-10 -10 ■Software GS1EM1-03-* ■PLC data /3 Addr. Addr. /3 Switch a-1, b-1 151 * 6 F 2 T 0 1 7 6 a-1 b-1 /2 Record Event Disturbance Counter /3 Event BI1 comm. N/O/R/B : 3 /3 Disturbance Time/Starter Scheme sw Binary sig. /4 Time/starter Time1 2.0s /4 Scheme sw /4 Binary sig. SIG1 51 /3 Counter Scheme sw Alarm set /2 Status Metering Time sync. Time zone /2 Act. gp. =* Common Group1 Group2 /3 Metering /3 Time sync. /3 Time zone. /3 Common APPL /3 Group1 Parameter Trip /4 Parameter Line name VT ratio ∗∗∗∗∗∗∗∗∗∗∗∗∗∗ ∗∗∗∗∗∗ /5 VT ratio VTS 100 a-1 b-1 c-1 d-1 152 /4 Scheme sw /4 Alarm set TCALM 10000 6 F 2 T 0 1 7 6 a-1 b-1 c-1 d-1 /4 Trip Scheme sw Prot.element /6 Application /5 Scheme sw Application OV prot. UV prot. ZPS prot. NPS prot. FRQ prot. /6 OV prot. /6 UV prot. /6 ZPS prot. /6 NPS prot. /6 FRQ prot. /3 Group2 Parameter /2 Binary I/P BI STATUS BI1 BI2 BI3 BI4 BI5 BI6 Alarm1 Text Alarm2 Text Alarm3 Text Alarm4 Text /5 Prot.element OV prot. UV prot. ZPS prot. NPS prot. FRQ prot. /3 BI STATUS /3 BI1 Timers Functions /6 OV prot. OV1 10.0V /6 UV prot. UV1 10.0V /6 ZPS prot. ZPS1 10.0V /6 NPS prot. NPS1 10.0V /6 FRQ prot. FRQ1 10.0Hz /4 Timers BI1PUD 0.00s /4 Functions /3 BI6 Timers Functions ∗∗∗∗∗∗∗∗∗∗∗∗∗∗∗∗∗ Alarm∗ Text a-1 b-1 153 6 F 2 T 0 1 7 6 a-1 b-1 /2 Binary O/P BO1 AND, DL 0, 0, 0, 0 BO4 OR , Lat 141, 1, 2, 3 /2 LED LED Virtual LED /2 Control /2 Frequency /1 Set.(change) Password Description Comms Record Status Protection Binary I/P Binary O/P LED Control Frequency /3 LED /3 Virtual LED IND1 IND2 I,O : Confirmation trap Change settings? ENTER=Y CANCEL=N /2 Description Plant name Description _ Refer to Section 4.2.6.4. /4 IND2 BIT1 Set.(change) Password [_ ] 1234567890← Set.(change) Retype [_ ] 1234567890← /2 Comms Addr. Switch I,O : Password trap Set.(change) Input [_ ] 1234567890← Refer to Section 4.2.6.3. /4 IND1 BIT1 ABCDEFG _ ABCDEFG /3 Addr. Addr /3 Switch RS485 a-1 b-2 154 Refer to Section 4.2.6.2. 6 F 2 T 0 1 7 6 a-1 b-2 /2 Record Event Disturbance Counter Refer to Section 4.2.6.5. /3 Event BI1 comm. BI1 comm. N/O/R/B : : 3 _ /4 Time/starter /3 Disturbance Time/starter Scheme sw Binary sig. /4 Scheme sw /3 Counter Scheme sw Alarm set /4 Scheme sw /4 Binary sig. /4 Alarm set /2 Status Metering Time sync. Time zone Refer to Section 4.2.6.6. /2 Protection Change act. gp. Change set. Copy gp. /3 Metering Display /3 Time sync. Time sync. /3 Time zone GMT _ Refer to Section 4.2.6.7. /3 Change act. gp. /3 Act gp.=1 Common Group1 Group2 /4 Common APPL a-1 b-2 c-2 d-2 155 6 F 2 T 0 1 7 6 a-1 b-2 c-2 d-2 /4 Group1 Parameter Trip /5 Parameter Line name VT ratio _ ABCDEFG /6 VT ratio VTS /5 Trip Scheme sw Prot.element /6 Scheme sw Application OV prot. UV prot. ZPS prot. NPS prot. FRQ prot. /7 Application /7 OV prot. /7 UV prot. /7 ZPS prot. /7 NPS prot. /7 FRQ prot. /6 Prot.element OV prot. UV prot. ZPS prot. NPS prot. FRQ prot. /7 OV prot. /7 UV prot. /7 ZPS prot. /7 NPS prot. /4 Group2 Parameter /7 FRQ prot. a-1, b-2 c-2 156 6 F 2 T 0 1 7 6 a-1 b-2 c-2 /3 Copy A to B A _ B _ /2 Binary I/P BI Status BI1 BI2 BI3 BI4 BI5 BI6 Alarm1 Text Alarm2 Text Alarm3 Text Alarm4 Text Refer to Section 4.2.6.8. /2 Binary O/P BO1 BO2 BO3 BO4 Refer to Section 4.2.6.9. /2 LED LED Virtual LED /3 LED LED1 LED2 LED3 LED4 LED5 LED6 CB CLOSED a-1 b-2 c-3 /3 BI Status BITHR1 /3 BI1 Timers Functions /4 Timers /4 Functions /3 BI6 Timers Functions ∗∗∗∗∗∗∗∗∗∗∗∗∗∗∗∗∗ ABCDEFG Alarm∗ Text /3 BO1 Logic/Reset Functions /4 Logic/Reset /4 Functions /3 BO4 Logic/Reset Functions Refer to Section 4.2.6.10. /4 LED1 Logic/Reset Functions LED Color /4 LED6 Logic/Reset Functions LED Color /4 CB CLOSED LED Color 157 /5 Logic/Reset /5 Functions /5 LED Color /5 LED Color 6 F 2 T 0 1 7 6 a-1 b-2 c-3 /3 Virtual LED IND1 IND2 /4 IND1 Reset Functions /5 Reset /5 Functions /2 Control /4 IND2 Reset Functions /2 Frequency : Password trap Control Password [_ ] 1234567890← /1 Control Password(Ctrl) Local/Remote CB OPEN/CLOSE Refer to Section 4.2.7 /1 Test Password(Test) Switch Binary O/P Refer to Section 4.2.8. Control Input [_ ] 1234567890← Refer to Section 4.2.7.2. Test Input [_ ] 1234567890← Refer to Section 4.2.8.2. Test Retype [_ ] 1234567890← : Password trap Test Password [_ ] 1234567890← /2 Switch A.M.F. 1 _ Off/On UVTST 0 Off/S0/S3 /2 Binary O/P Control Retype [_ ] 1234567890← Operate? ENTER=Y CANCEL=N BO1 0 _ Disable/Enable BO4 0 Disable/Enable 158 6 F 2 T 0 1 7 6 Appendix E Case Outline 159 6 F 2 T 0 1 7 6 Case Outline 160 6 F 2 T 0 1 7 6 Case Outline for model 412 161 6 F 2 T 0 1 7 6 Appendix F Typical External Connection 162 6 F 2 T 0 1 7 6 A B C OUTPUT CONACTS SIGNAL LIST (DEFAULT) BO1 BO2 BO3 BO4 OFF(CB CLOSE) GENERAL TRIP GENERAL ALARM OFF P Control Power Controled CB GRE130-410A APPL ; 1PP TB1 1 Vph 2 3 4 5 6 7 Ve 8 9 N.C. 10 11 12 GND POWER 13 + SUPPLY 14 - P N FG FRONT PANEL TB2 CB CLOSE SW CB OPEN SW CB CLOSE 1 2 CB OPEN/TRIP BO2 3 4 AUXILIARY * AUXILIARY * BO3 5 6 TRIP COIL CLOSE COIL N BO4 7 8 Relay fail BO5 DEFAULT BI1-2; Off 9 10 N.C. 11 12 AUXILIARY Available for TCS (CB CLOSED) Threshold 33.6/77/154V AUXILIARY Available for TCS (CB OPEN) Threshold 33.6/77/154V USB Type B N.C. Rear PANEL Relay fail indicator N BI1 13 14 BI2 15 16 N 17 18 19 20 22 RS485 COM RJ45 BO1 A+ B- N.C. 21 23 24 A+ BCOM COM A+ B- *BO3 and BO4 are NOT applicable for direct CB coil connection. Typical External Connections for the GRE130 - 410A 1PP setting 163 6 F 2 T 0 1 7 6 A B C OUTPUT CONACTS SIGNAL LIST (DEFAULT) BO1 BO2 BO3 BO4 OFF(CB CLOSE) GENERAL TRIP GENERAL ALARM OFF Control Power P Controled CB GRE130-411A APPL ; 1PN TB2 CB CLOSE SW TB1 1 Vph 2 3 4 5 6 7 Ve 8 9 N.C. 10 11 12 GND POWER 13 + SUPPLY 14 - P N CB OPEN SW CB CLOSE 1 2 CB OPEN/TRIP * AUXILIARY * TRIP COIL BO3 5 6 CLOSE COIL N BO4 7 8 Relay fail BO5 DEFAULT BI1-2; Off FG 9 10 N.C. 11 12 Threshold 33.6/77/154V Available for TCS AUXILIARY FRONT PANEL Threshold 33.6/77/154V Available for TCS (CB CLOSED) AUXILIARY (CB OPEN) AUXILIARY Threshold 77/154V AUXILIARY Rear PANEL N 13 14 BI2 15 16 RS485 COM Relay fail indicator BI1 17 18 19 20 22 AUXILIARY RJ45 BO2 3 4 AUXILIARY AUXILIARY USB Type B BO1 N 21 A+ 23 B- 24 N.C. A+ BCOM COM A+ B- *BO3 and BO4 are NOT applicable for direct CB coil connection. Typical External Connections for the GRE130 - 411A 1PN setting 164 6 F 2 T 0 1 7 6 A B C OUTPUT CONACTS SIGNAL LIST (DEFAULT) BO1 BO2 BO3 BO4 OFF(CB CLOSE) GENERAL TRIP GENERAL ALARM OFF Control Power P Controled CB GRE130-410A APPL ; 2PP 2PZ TB1 1 Vab 2 3 Vbc 4 5 6 7 Ve 8 9 N.C. 10 11 12 GND POWER 13 + SUPPLY 14 - P N FG FRONT PANEL TB2 CB CLOSE SW CB OPEN SW CB CLOSE 1 2 CB OPEN/TRIP BO2 3 4 AUXILIARY * AUXILIARY * TRIP COIL BO3 5 6 CLOSE COIL N BO4 7 8 Relay fail BO5 DEFAULT BI1-2; Off 9 10 N.C. 11 12 AUXILIARY Available for TCS (CB CLOSED) Threshold 33.6/77/154V AUXILIARY Available for TCS (CB OPEN) Threshold 33.6/77/154V USB Type B N.C. Rear PANEL Relay fail indicator N BI1 13 14 BI2 15 16 N 17 18 19 20 22 RS485 COM RJ45 BO1 A+ B- N.C. 21 23 24 A+ BCOM COM A+ B- *BO3 and BO4 are NOT applicable for direct CB coil connection. Typical External Connections for the GRE130 - 410A 2PP ( 2PZ ) setting 165 6 F 2 T 0 1 7 6 A B C OUTPUT CONACTS SIGNAL LIST (DEFAULT) BO1 BO2 BO3 BO4 OFF(CB CLOSE) GENERAL TRIP GENERAL ALARM OFF P Control Power Controled CB GRE130-411A APPL ; 3PN TB1 3PV 1 Va 2 3 Vb 4 5 Vc 6 7 Ve 8 9 N.C. 10 11 12 GND POWER 13 + SUPPLY 14 - P N TB2 CB CLOSE SW CB OPEN SW CB CLOSE 1 2 CB OPEN/TRIP * AUXILIARY * TRIP COIL BO3 5 6 CLOSE COIL N BO4 7 8 Relay fail BO5 DEFAULT BI1-2; Off AUXILIARY 9 10 N.C. 11 12 Threshold 33.6/77/154V Available for TCS AUXILIARY FRONT PANEL Threshold 33.6/77/154V Available for TCS (CB CLOSED) AUXILIARY (CB OPEN) AUXILIARY Threshold 77/154V AUXILIARY Rear PANEL BI1 BI2 15 16 RS485 COM A+ B- N.C. Relay fail indicator N 13 14 17 18 19 20 22 AUXILIARY RJ45 BO2 3 4 AUXILIARY FG USB Type B BO1 N 21 23 24 A+ BCOM COM A+ B- *BO3 and BO4 are NOT applicable for direct CB coil connection. Typical External Connections for the GRE130 - 410A 3PN ( 3PV ) setting 166 6 F 2 T 0 1 7 6 A B C OUTPUT CONACTS SIGNAL LIST (DEFAULT) BO1 BO2 BO3 BO4 OFF(CB CLOSE) GENERAL TRIP GENERAL ALARM OFF P Control Power Controled CB GRE130-410A APPL ; 3PP TB1 1 Vab 2 3 Vbc 4 5 Vca 6 7 Ve 8 9 N.C. 10 11 12 GND POWER 13 + SUPPLY 14 - P N FG FRONT PANEL TB2 CB CLOSE SW CB OPEN SW CB CLOSE 1 2 CB OPEN/TRIP BO2 3 4 AUXILIARY * AUXILIARY * TRIP COIL BO3 5 6 CLOSE COIL N BO4 7 8 Relay fail BO5 DEFAULT BI1-2; Off 9 10 N.C. 11 12 AUXILIARY Available for TCS (CB CLOSED) Threshold 33.6/77/154V AUXILIARY Available for TCS (CB OPEN) Threshold 33.6/77/154V Relay fail indicator N BI1 13 14 BI2 15 16 N 17 18 N.C. 19 20 22 USB Type B Rear PANEL RS485 COM RJ45 BO1 A+ B- N.C. 21 23 24 A+ BCOM COM A+ B- *BO3 and BO4 are NOT applicable for direct CB coil connection. Typical External Connections for the GRE130 - 410A 3PP setting 167 6 F 2 T 0 1 7 6 A B C Control Power P Controled CB GRE130-412A APPL ; 3PP TB3 CB CLOSE SW TB2 1 Vab 2 3 Vbc 4 5 Vca 6 7 Ve 8 9 N.C. 10 11 12 GND POWER 13 + SUPPLY 14 - P N CB OPEN SW CB CLOSE 1 2 CB OPEN/TRIP * AUXILIARY * TRIP COIL BO3 5 6 CLOSE COIL N BO4 7 8 Relay fail R.F. DEFAULT BI1-2; Off FG 9 10 N.C. 11 12 Threshold 33.6/77/154V Available for TCS AUXILIARY FRONT PANEL Threshold 33.6/77/154V Available for TCS (CB CLOSED) AUXILIARY (CB OPEN) AUXILIARY Threshold 77/154V AUXILIARY COM A+ B- N.C. BI2 15 16 N 21 23 24 TB1 AUXILIARY N 13 14 RS485 RJ45 Relay fail indicator BI1 17 18 19 20 22 AUXILIARY Rear PANEL BO2 3 4 AUXILIARY AUXILIARY USB Type B BO1 A+ BCOM COM A+ B- Control Power BO5 1 2 OUTPUT CONACTS SIGNAL LIST (DEFAULT) BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 OFF(CB CLOSE) GENERAL TRIP GENERAL ALARM OFF OFF OFF OFF OFF AUXILIARY AUXILIARY 100BASE-TX 1port / 2port BO6 3 4 Optional Communication Port *** * AUXILIARY BO7 5 6 BO8 7 8 9 N.C. 10 11 12 * 100BASE-FX 1port / 2port *BO3, 4, 7 and 8 are NOT applicable for direct CB coil connection. Typical External Connections for the GRE130 - 412A 3PP setting 168 6 F 2 T 0 1 7 6 Appendix G Relay Setting Sheet 1. Relay Identification 2. Line parameter 3. Contacts setting 4. Relay setting sheet 169 6 F 2 T 0 1 7 6 1. Relay Identification Date: Relay type Serial Number Frequency AC voltage Supply voltage Active setting group Password Setting Control Test 2. Line parameter VT ratio PVT: RVT: 3. Contacts setting TB2 BO1 Terminal 1-2 (For model type 412, the terminal block number is TB3 ) BO2 Terminal 3-4 BO3 Terminal 5-6 BO4 Terminal 7-8 BI1 Terminal 13-14 BI2 Terminal 15-16 BI3 Terminal 17-22 BI4 Terminal 18-22 BI5 Terminal 19-22 BI6 Terminal 20-22 TB1 (Only for model type 412) BO5 Terminal 1-2 BO6 Terminal 3-4 BO7 Terminal 5-6 BO8 Terminal 7-8 170 6 F 2 T 0 1 7 6 4. Relay setting sheet Menu Password Description Communi -cation Name Range Password(Set) 0000 – 9999 Password(Ctrl) 0000 – 9999 Password for Control Password(Test) 0000 – 9999 Password for Test Plant name Description Modbus IEC RS485BR PORTTYPE Ether P RS485P IECNFI IECBLK IECB1 IECB2 IECB3 IECB4 IECGT IECAT IECBT IECCT IECE1 IECE2 IECE3 IECE4 IECE5 IECE6 IECE7 IECE8 IECI1 IECI2 IECI3 IECI4 IECI5 IECI6 IECI7 IECI8 IECGI1 IECGI2 IECGI3 IECGI4 IECGI5 IECGI6 IECGI7 IECGI8 Specified by user ditto 1 - 247 0 - 254 9.6 / 19.2 RS485-1 Off / IEC61850 Off/MOD/IEC103 1.2 / 2.4 Normal/Blocked 0 - 361 0 - 361 0 - 361 0 - 361 0-8 0-8 0-8 0-8 0 - 361 0 - 361 0 - 361 0 - 361 0 - 361 0 - 361 0 - 361 0 - 361 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 No / Yes No / Yes No / Yes No / Yes No / Yes No / Yes No / Yes No / Yes Plant name Memorandum for user Relay ID No.for Modbus Relay ID No.for IEC Baud rate for Modbus Switch for communications Switch for communications Switch for communications Switch for communications Switch for communications IEC user specified signal 1 IEC user specified signal 2 IEC user specified signal 3 IEC user specified signal 4 IEC General Trip IEC Trip A phase IEC Trip B phase IEC Trip C phase IEC user event 1 IEC user event 2 IEC user event 3 IEC user event 4 IEC user event 5 IEC user event 6 IEC user event 7 IEC user event 8 IEC user INF 1 IEC user INF 2 IEC user INF 3 IEC user INF 4 IEC user INF 5 IEC user INF 6 IEC user INF 7 IEC user INF 8 IEC event type setting 1 IEC event type setting 2 IEC event type setting 3 IEC event type setting 4 IEC event type setting 5 IEC event type setting 6 IEC event type setting 7 IEC event type setting 8 171 Contents Password for Setting change Default None (0000) None (0000) None (0000) - - 1 1 19.2 RS485-1(0) Off(0) MOD(1) 2.4(1) Normal(0) 1 2 3 4 2 2 2 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 No(0) No(0) No(0) No(0) No(0) No(0) No(0) No(0) 6 F 2 T 0 1 7 6 Menu Name 61850BLK 61850AUT Communi -cation TSTMOD PINGCHK IP1-1 IP1-2 IP1-3 IP1-4 SM1-1 SM1-2 SM1-3 SM1-4 GW1-1 GW1-2 GW1-3 GW1-4 SI1-1 SI1-2 SI1-3 SI1-4 PG1-1 PG1-2 PG1-3 PG1-4 SMODE DEADT GOINT BI1 comm. BI2 comm. Event Record BI3 comm. BI4 comm. BI5 comm. BI6 comm. Disturbance Record Range Normal / Blocked Off / On Off / On Off / On 0 – 254 0 – 254 0 – 254 0 – 254 0 – 255 0 – 255 0 – 255 0 – 255 0 – 254 0 – 254 0 – 254 0 – 254 0 – 254 0 – 254 0 – 254 0 – 254 0 – 254 0 – 254 0 – 254 0 – 254 Off / On 1 – 32400 s 1 – 60 s None/Operate/ Reset/Both None/Operate/ Reset/Both None/Operate/ Reset/Both None/Operate/ Reset/Both None/Operate/ Reset/Both None/Operate/ Reset/Both Time1 0.1 – 4.9 s Time2 0.1 – 4.9 s OV UV NPS ZPS Trip 10.0 – 200.0 V 1.0 – 130.0 V 1.0 – 160.0 V 1.0 – 160.0 V Off / On 172 Contents IEC61850 Block setting IEC61850 Auto negotiation setting IEC61850 Test mode Ping check IP address 1 of ETH 1 IP address 2 of ETH 1 IP address 3 of ETH 1 IP address 4 of ETH 1 Subnet mask 1 of ETH 1 Subnet mask 2 of ETH 1 Subnet mask 3 of ETH 1 Subnet mask 4 of ETH 1 Default gateway of ETH1 Default gateway of ETH1 Default gateway of ETH1 Default gateway of ETH1 SNTP server address 1 SNTP server address 2 SNTP server address 3 SNTP server address 4 Ping check add1 of ETH1 Ping check add2 of ETH1 Ping check add3 of ETH1 Ping check add4 of ETH1 SNTP mode Keep-arrive timeout GOOSE receive check interval BI1 command trigger BI2 command trigger BI3 command trigger BI4 command trigger BI5 command trigger BI6 command trigger Recording period before fault Recording period after fault OV element for disturbance UV element for disturbance NPS element for disturbance ZPS element for disturbance Disturbance trigger Default Normal(0) Off(0) Off(0) Off(0) 192 168 19 173 255 255 255 0 192 168 19 1 0 0 0 0 0 0 0 0 0(Off) 7200 60 Both(3) Both(3) Both(3) Both(3) Both(3) Both(3) 3.0 2.0 On 6 F 2 T 0 1 7 6 Menu Disturbance Record Counter Status Name BI OV UV NPS ZPS SIG1 SIG2 SIG3 SIG4 SIG5 SIG6 SIG7 SIG8 SIG9 SIG10 SIG11 SIG12 SIG13 SIG14 SIG15 SIG16…30 SIG31 SIG32 Range Off / On Off / On Off / On Off / On Off / On 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 0 – 361 TCSPEN Off / On / Opt-On CBSMEN Off / On TCAEN Off / On TCALM 1 – 10000 Display Pri / Sec Off / BI / Modbus / 103 / SNTP 48 / 110 /220 110 / 220 0.00 – 300.00 0.00 – 300.00 Norm / Inv Off / 1 / 2 Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Off / On Time sync. BITHR1 BITHR2 Binary Input BI1 BI1PUD BI1DOD BI1SNS BI1SGS OV1BLK OV2BLK OV3BLK UV1BLK UV2BLK UV3BLK ZP1BLK ZP2BLK NP1BLK NP2BLK TCFALM 173 Contents Disturbance trigger Disturbance trigger Disturbance Trigger Disturbance Trigger Disturbance Trigger Disturbance Trigger Trip Circuit Supervision Enable Circuit Breaker State Monitoring Alarm Enable Trip Count Alarm Enable Trip Count Alarm Threshold Metering Time synch setting BI1,BI2 Threshold BI3-BI6 Threshold BI1 Pick-up delay BI1 Drop-off delay BI1 Trigger BI1 Settings Group OV1 Block OV2 Block OV3 Block UV1 Block UV2 Block UV3 Block ZPS1 Block ZPS2 Block NPS1 Block NPS2 Block Trip Circuit Fail Alarm Default On On On On On 51 52 53 63 102 103 104 117 141 142 143 144 145 0 0 0 0 0 Off Off Off 10000 Pri Off 110 110 0.00 0.00 Norm Off Off Off Off Off Off Off Off Off Off Off Off 6 F 2 T 0 1 7 6 Menu Name BI1 BI2 Binary Input BI3 BI4 BI5 BI6 Binary Output BO1 Range CBOPN Off / On CBCLS Off / On EXT3PH Off / On EXTAPH Off / On EXTBPH Off / On EXTCPH Off / On RMTRST Off / On SYNCLK Off / On STORCD Off / On Alarm1 Off / On Alarm2 Off / On Alarm3 Off / On Alarm4 Off / On RMTOPN Off / On RMTCLS Off / On CNTLCK Off / On FRQ1BLK Off / On FRQ2BLK Off / On FRQ3BLK Off / On FRQ4BLK Off / On BI2PUD 0.00 – 300.00 BI2DOD 0.00 – 300.00 BI2SNS Norm / Inv BI2SGS Off / 1 / 2 The following items are same as BI1 BI3PUD 0.00 – 300.00 BI3DOD 0.00 – 300.00 BI3SNS Norm / Inv BI3SGS Off / 1 / 2 The following items are same as BI1 BI4PUD 0.00 – 300.00 BI4DOD 0.00 – 300.00 BI4SNS Norm / Inv BI4SGS Off / 1 / 2 The following items are same as BI1 BI5PUD 0.00 – 300.00 BI5DOD 0.00 – 300.00 BI5SNS Norm / Inv BI5SGS Off / 1 / 2 The following items are same as BI1 BI6PUD 0.00 – 300.00 BI6DOD 0.00 – 300.00 BI6SNS Norm / Inv BI6SGS Off / 1 / 2 The following items are same as BI1 Logic OR / AND Reset Ins / DI / Dw / Lat In #1 0 – 361 In #2 0 – 361 In #3 0 – 361 174 Contents Circuit Breaker Open Circuit Breaker Closed External Trip 3 Phase External Trip A Phase External Trip B Phase External Trip C Phase Remote Reset Synchronize clock Store Disturbance Record Alarm screen 1 Alarm screen 2 Alarm screen 3 Alarm screen 4 Remote CB Open Control Remote CB Close Control Interlock input FRQ1 Block FRQ2 Block FRQ3 Block FRQ4 Block BI2 Pick-up delay BI2 Drop-off delay BI2 Trigger BI2 Settings Group Default Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off 0.00 0.00 Norm Off BI3 Pick-up delay BI3 Drop-off delay BI3 Trigger BI3 Settings Group 0.00 0.00 Norm Off BI4 Pick-up delay BI4 Drop-off Delay BI4 Trigger BI4 Settings Group 0.00 0.00 Norm Off BI5 Pick-up delay BI5 Drop-off Delay BI5 Trigger BI5 Settings Group 0.00 0.00 Norm Off BI6 Pick-up delay BI6 Drop-off Delay BI6 Trigger BI6 Settings Group 0.00 0.00 Norm Off Logic Gate Type Reset Operation Functions Functions Functions OR DI 141 0 0 6 F 2 T 0 1 7 6 Menu Binary Output Configurable LED Active group / Common Name BO1 Range In #4 0 – 361 TBO 0.00 – 10.00 s BO2 Same as BO1 BO3 Same as BO1 BO4 Same as BO1 BO5 Same as BO1 (for model 412) BO6 Same as BO1 (for model 412) BO7 Same as BO1 (for model 412) BO8 Same as BO1 (for model 412) Logic OR / AND Reset Inst / Latch In #1 0 – 361 LED1 In #2 0 – 361 In #3 0 – 361 In #4 0 – 361 Color R/G/Y LED2 Same as LED1 LED3 Same as LED1 LED4 Same as LED1 LED5 Same as LED1 LED6 Same as LED1 CB CLOSED Color R/G/Y IND1 Reset Inst / Latch IND2 Reset Inst / Latch BIT1 0 – 361 BIT2 0 – 361 BIT3 0 – 361 BIT4 0 – 361 IND1 BIT5 0 – 361 BIT6 0 – 361 BIT7 0 – 361 BIT8 0 – 361 IND2 Same as IND1 Active gp. 1-2 AOLED Off / On Control Interlock Disable / Enable Disable / Enable Control Hierarchy Local / Remote Frequency 50Hz / 60Hz 175 Contents Functions Delay / Pulse width Default 0 0.20 Logic Gate Type Reset Operation Functions Functions Functions Functions LED Color OR Inst 0 0 0 0 R CB CLOSED LED Color IND1 Reset operation IND2 Reset operation Virtual LED Virtual LED Virtual LED Virtual LED Virtual LED Virtual LED Virtual LED Virtual LED R Inst Inst 0 0 0 0 0 0 0 0 Active setting group ALARM LED lighting control at alarm output Control Enable Interlock Enable Control Hierarchy (if Control = Enable) Frequency 1 On Disable Disable -(Local) 50Hz 6 F 2 T 0 1 7 6 Menu Name Line name PVT RVT Range Specified by user 1 – 20000 1 – 20000 Contents Line name VT ratio of Phase VT VT ratio of Earth Fault CT SVCNT ALM&BLK/ALM AC input imbalance OV1 Enable OV2 Enable OV3 Enable UV1 Enable UV2 Enable UV3 Enable UV Block Enable ZPS1 Enable ZPS2 Enable NPS1 Enable NPS2 Enable DFT4 Logic4 OV1 Off / DT/IDMT/C Off / DT/IDMT/C Off / On Off / DT/IDMT/C Off / DT/IDMT/C Off / On Off / On Off / DT/IDMT/C Off / DT/IDMT/C Off / DT/IDMT/C Off / DT/IDMT/C Off/O/U/B/ OO/UU Off/R/D/Both L1/L2/L3/L4/L5 Off/O/U/B/ OO/UU Off/R/D/Both L1/L2/L3/L4/L5 Off/O/U/B/ OO/UU Off/R/D/Both L1/L2/L3/L4/L5 Off/O/U/B/ OO/UU Off/R/D/Both L1/L2/L3/L4/L5 10.0 – 200.0 V TOV1 0.05 – 100.00 TOV1 0.00 – 300.00 s TOV1R OV1DPR OV2 0.0 – 300.0 s 10 – 98 % 10.0 – 200.0 V TOV2 0.05 – 100.00 TOV2 0.00 – 300.00 s TOV2R OV2DPR OV3 TOV3 OV3DPR OV1-k 0.0 – 300.0 s 10 – 98 % 10.0 – 200.0 V 0.00 – 300.00 s 10 – 98 % 0.00 – 300.00 OV UV ZPS NPS OV1EN OV2EN OV3EN UV1EN UV2EN UV3EN VBKEN ZPS1EN ZPS2EN NPS1EN NPS2EN FT1 DFT1 Logic1 FT2 FRQ DFT2 Logic2 FT3 Protection DFT3 Logic3 FT4 OV 176 FRQ1 Enable DFRQ1 Enable FRQ1 logic FRQ2 Enable DFRQ2 Enable FRQ2 logic FRQ3 Enable DFRQ3 Enable FRQ3 logic FRQ4 Enable DFRQ4 Enable FRQ4 logic OV1 Threshold OV1 Time multiplier (if OV1EN = IDMT) OV1 Definite time (if OV1EN = DT) OV1 Definite time reset OV1 DO/PU ratio OV2 Threshold OV2 Time multiplier (if OV2EN = IDMT) OV2 Definite time (if OV2EN = DT) OV2 Definite time reset OV2 DO/PU ratio OV3 Threshold OV3 Definite time OV3 DO/PU ratio Configurable IDMT Default -100 100 ALM& BLK Off Off Off DT Off Off Off DT Off Off Off B Both L1 B Both L1 B Both L1 B Both L1 120.0 V 10.00 0.10 s 0.0 s 95% 140.0 V 10.00 0.10 s 0.0 s 95% 160.0 V 0.10 s 95% 1.00 6 F 2 T 0 1 7 6 Menu Name OV UV Protection OV1-α OV1-C OV2-k OV2-α OV2-C UV1 Range 0.00 – 5.00 0.000 – 5.000 0.00 – 300.00 0.00 – 5.00 0.000 – 5.000 5.0 – 130.0 V TUV1 0.05 – 100.00 TUV1 0.00 – 300.00 s TUV1R UV2 0.0 – 300.0 s 5.0 – 130.0 V TUV2 0.05 – 100.00 TUV2 0.00 – 300.00 s TUV2R UV3 TUV3 VBLK UV1-k UV1-α UV1-C UV2-k UV2-α UV2-C ZPS1 0.0 – 300.0 s 5.0 – 130.0 V 0.00 – 300.00 s 5.0 – 20.0 V 0.00 – 300.00 0.00 – 5.00 0.000 – 5.000 0.00 – 300.00 0.00 – 5.00 0.000 – 5.000 1.0 – 160.0 V TZPS1 0.05 – 100.00 TZPS1 0.00 – 300.00 s TZPS1R ZPS2 0.0 – 300.0 s 1.0 – 160.0 V TZPS2 0.05 – 100.00 TZPS2 0.00 – 300.00 s TZPS2R ZPS1-k ZPS1-α ZPS1-C ZPS2-k ZPS2-α ZPS2-C NPS1 0.0 – 300.0 s 0.00 – 300.00 0.00 – 5.00 0.000 – 5.000 0.00 – 300.00 0.00 – 5.00 0.000 – 5.000 1.0 – 160.0 V TNPS1 0.05 – 100.00 TNPS1 0.00 – 300.00 s TNPS1R 0.0 – 300.0 s ZPS NPS 177 Contents Curve setting. (if OV1EN = C) Configurable IDMT Curve setting. (if OV2EN = C) UV1 Threshold UV1 Time multiplier (if UV1EN = IDMT) UV1 Definite time (if UV1EN = DT) UV1 Definite time reset UV2 Threshold UV2 Time multiplier (if UV2EN = IDMT) UV2 Definite time (if UV2EN = DT) UV2 Definite time reset UV3 Threshold UV3 Definite time UV Blocking Configurable IDMT Curve setting. (if UV1EN = C) Configurable IDMT Curve setting. (if UV2EN = C) ZPS1 Threshold ZPS1 Time multiplier (if ZPS1EN = IDMT) ZPS1 Definite time (if ZPS1EN = DT) ZPS1 Definite time reset ZPS2 Threshold ZPS2 Time multiplier (if ZPS2EN = IDMT) ZPS2 Definite time (if ZPS2EN = DT) ZPS2 Definite time reset Configurable IDMT Curve setting. (if ZPS1EN = C) Configurable IDMT Curve setting. (if ZPS2EN = C) NPS1 Threshold NPS1 Time multiplier (if NPS1EN = IDMT) NPS1 Definite time (if NPS1EN = DT) NPS1 Definite time reset Default 1.00 0.000 1.00 1.00 0.000 60.0 V 10.00 0.10 s 0.0 s 60.0 V 10.00 0.10 s 0.0 s 20.0 V 0.10 s 10.0 V 1.00 1.00 0.000 1.00 1.00 0.000 20.0 V 10.00 0.00 s 0.0 s 40.0 V 10.00 0.00 s 0.0 s 1.00 1.00 0.000 1.00 1.00 0.000 20.0 V 10.00 0.00 s 0.0 s 6 F 2 T 0 1 7 6 Menu Name NPS NPS2 Range 1.0 – 160.0 V TNPS2 0.05 – 100.00 TNPS2 0.00 – 300.00 s TNPS2R NPS1-k NPS1-α NPS1-C NPS2-k NPS2-α NPS2-C 0.0 – 300.0 s 0.00 – 300.00 0.00 – 5.00 0.000 – 5.000 0.00 – 300.00 0.00 – 5.00 0.000 – 5.000 45.00 – 55.00 Hz 54.00 – 66.00 Hz 0.00 – 100.00 s 45.00 – 55.00 Hz 54.00 – 66.00 Hz 0.00 – 100.00 s 0.1 – 9.9 Hz/s 45.00 – 55.00 Hz 54.00 – 66.00 Hz 0.00 – 100.00 s 45.00 – 55.00 Hz 54.00 – 66.00 Hz 0.00 – 100.00 s 0.1 – 9.9 Hz/s 45.00 – 55.00 Hz 54.00 – 66.00 Hz 0.00 – 100.00 s 45.00 – 55.00 Hz 54.00 – 66.00 Hz 0.00 – 100.00 s 0.1 – 9.9 Hz/s 45.00 – 55.00 Hz 54.00 – 66.00 Hz 0.00 – 100.00 s 45.00 – 55.00 Hz 54.00 – 66.00 Hz 0.00 – 100.00 s 0.1 – 9.9 Hz/s 40 – 100 V Off / On Off / On Off / On F11 TF11 Protection F12 TF12 DF1 F21 TF21 F22 TF22 DF2 FRQ F31 TF31 F32 TF32 DF3 F41 TF41 F42 TF42 DF4 FVBLK Test A.M.F. UVTEST IECTST 178 Contents NPS2 Threshold NPS2 Time multiplier (if NPS2EN = IDMT) NPS2 Definite time (if NPS2EN = DT) NPS2 Definite time reset Configurable IDMT Curve setting. (if NPS1EN = C) Configurable IDMT Curve setting. (if NPS2EN = C) Over frequency stage 1 threshold OF1 time delay Under frequency stage1 Threshold UF1 time delay DFRQ stage1 Over frequency stage 2 Threshold OF2 time delay Under frequency stage2 Threshold UF2 time delay DFRQ stage2 Over frequency stage 3 Threshold OF3 time delay Under frequency stage3 Threshold UF3 time delay DFRQ stage3 Over frequency stage 4 Threshold OF3 time delay Under frequency stage4 Threshold UF4 time delay DFRQ stage4 Under voltage block Automatic monitoring Under voltage test IEC103 test mode Default 40.0 V 10.00 0.00 s 0.0 s 1.00 1.00 0.000 1.00 1.00 0.000 51.00 Hz 61.00 Hz 1.00 s 49.00 Hz 59.00 Hz 1.00 s 0.5 Hz/s 51.00 Hz 61.00 Hz 1.00 s 49.00 Hz 59.00 Hz 1.00 s 0.5 Hz/s 51.00 Hz 61.00 Hz 1.00 s 49.00 Hz 59.00 Hz 1.00 s 0.5 Hz/s 51.00 Hz 61.00 Hz 1.00 s 49.00 Hz 59.00 Hz 1.00 s 0.5 Hz/s 40 V Off Off Off 6 F 2 T 0 1 7 6 Appendix H Commissioning Test Sheet (sample) 1. Relay identification 2. Preliminary check 3. Hardware check 3.1 User interface check 3.2 Binary input/binary output circuit check 3.3 AC input circuit check 4. Function test 4.1 Overvoltage and undervoltage elements test 4.2 Negative sequence overvoltage elements test 5. Protection scheme test 6. Metering and recording check 179 6 F 2 T 0 1 7 6 1. Relay identification Type Serial number Model System frequency Station Date Circuit Engineer Protection scheme Witness Active settings group number 2. Preliminary check Ratings Power supply Wiring Calendar and clock 3. Hardware check 3.1 User interface check 3.2 Binary input/binary output circuit check Binary input circuit Binary output circuit 3.3 AC input circuit check 180 6 F 2 T 0 1 7 6 4. Function test 4.1 Overvoltage and undervoltage elements test (1) Operating value test Element Voltage setting Measured voltage OV1 OV2 OV3 UV1 UV2 UV3 ZPS1 ZPS2 (2) Operating time test (IDMT) Element Multiplier setting Changed voltage OV1 × Voltage setting × Voltage setting × Voltage setting OV2 × Voltage setting × Voltage setting × Voltage setting UV1 × Voltage setting × Voltage setting × Voltage setting UV2 × Voltage setting × Voltage setting × Voltage setting ZPS1 × Voltage setting × Voltage setting × Voltage setting ZPS2 × Voltage setting × Voltage setting × Voltage setting 181 Measured time 6 F 2 T 0 1 7 6 4.2 Negative overvoltage elements test (1) Operating value test Element Voltage setting Measured voltage NPS1 NPS2 (2) Operating time test (IDMT) Element Multiplier setting Changed voltage NPS1 × Voltage setting × Voltage setting × Voltage setting NPS2 × Voltage setting × Voltage setting Measured time × Voltage setting 4.3 Frequency elements test Element Frequency setting FRQ1 FRQ2 FRQ3 FRQ4 5. Protection scheme test 6. Metering and recording check 7. Conjunctive test Scheme Results On load check Tripping circuit 182 Measured frequency 6 F 2 T 0 1 7 6 Appendix I Return Repair Form 183 6 F 2 T 0 1 7 6 RETURN / REPAIR FORM Please complete this form and return it to TOSHIBA CORPORATION together with the GRE130 to be repaired. TOSHIBA CORPORATION Fuchu Operations – Industrial and Power Systems & Services 1, Toshiba-cho, Fuchu-shi, Tokyo, Japan For: Power Systems Protection & Control Department Quality Assurance Section Type: GRE130 (Example: Type: Model: GRE130 Model: 411A ) Product No.: Serial No.: Date: 1. Reason for returning the relay mal-function does not operate increased error investigation required others 2. Fault records, event records or disturbance records stored in the relay and relay settings are very helpful information to investigate the incident. Please provide relevant information regarding the incident on USB stick or CD rom, or fill in the attached fault record sheet and relay setting sheet. 184 6 F 2 T 0 1 7 6 Fault Record Date/Month/Year / : Time / : . (Example: 04/ Jul./ 2012 15:09:58.442) Faulty phase: Prefault values Van: Vbn: Vcn: Vab: Vbc: Vca : Vph: V0: V1: V2: f: V V V V V V V V V V Hz Fault values Van: Vbn: Vcn: Vab: Vbc: Vca : Vph: V0: V1: V2: f: V V V V V V V V V V Hz 185 / 6 F 2 T 0 1 7 6 3. What was the message on the LCD display at the time of the incident? 4. Describe the details of the incident: 5. Date incident occurred Day/Month/Year: / / / (Example: 10/Dec/2012) 6. Give any comments about the GRE130, including any relevant documents: 186 6 F 2 T 0 1 7 6 Customer Name: Company Name: Address: Telephone No.: Facsimile No.: Signature: 187 6 F 2 T 0 1 7 6 Appendix J Technical Data 188 6 F 2 T 0 1 7 6 TECHNICAL DATA Ratings AC voltage Vn: Frequency: Power supply: 63.5V / 110V 50/60Hz 110-250Vdc or 100-220Vac (Operative range: 88–300Vdc / 88–264Vac) 48-110Vdc (Operative range: 38.4 – 132Vdc) Superimposed AC ripple on DC supply: Power supply interruption: Binary input circuit DC voltage: 24-48Vdc (Operative range: 19.2 – 60.0Vdc) maximum 12% maximum 50ms at 110V For alarm indication 110-250Vdc (Operative range: 88 - 300Vdc) 48-110Vdc (Operative range: 38.4 - 132Vdc) 24-48Vdc (Operative range: 19.2 – 60.0Vdc) For trip circuit supervision Operative range: ≥38.4V (for 110Vdc rating) ≥88V (for 220/250Vdc rating) ≥19.2V (for 48Vdc rating) ≥9.6V (for 24Vdc rating) Overload Ratings AC voltage inputs: 2 times rated voltage continuous Burden AC phase voltage inputs: Power supply: ≤ 0.1 VA (at rated voltage) ≤ 10W (quiescent), Binary input circuit: ≤ 0.5W per input at 220Vdc ≤ 15W (maximum) Overvoltage Protection (59) 1st, 2nd, 3rd Overvoltage thresholds: Delay type: IDMTL Time Multiplier Setting TMS: DTL delay: DO/PU ratio Reset Delay: OFF, 10.0 – 200.0V in 0.1V steps DTL, IDMTL 0.05 - 100.00 in 0.01 steps Inst, 0.01 - 300.00s in 0.01s steps 10 - 98% in 1% steps Instantaneous, 0.1 – 300.0s in 0.1s steps Undervoltage Protection (27) 1st, 2nd, 3rd Undervoltage thresholds: Delay type: IDMTL Time Multiplier Setting TMS: DTL delay: Reset Delay: OFF, 5.0 – 130.0V in 0.1V steps DTL, IDMTL 0.05 - 100.00 in 0.01 steps Inst, 0.01 - 300.00s in 0.01s steps Instantaneous, 0.1 – 300.0s in 0.1s steps Zero Sequence Overvoltage (ZPS) Protection (59N) st nd 1 , 2 ZPS Overvoltage thresholds: st Delay type (1 threshold only): IDMTL Time Multiplier Setting TMS: DTL delay: Reset Delay (1st threshold only): OFF, 1.0 – 130.0V in 0.1V steps DTL, IDMTL 0.05 - 100.00 in 0.01 steps Inst, 0.01 - 300.00s in 0.01s steps Instantaneous, 0.1 – 300.0s in 0.1s steps 189 6 F 2 T 0 1 7 6 Negative Phase Sequence Overvoltage (NPS) Protection (47) 1st, 2nd NPS Overvoltage thresholds: Delay type (1st threshold only): IDMTL Time Multiplier Setting TMS: DTL delay: st Reset Delay (1 threshold only): OFF, 1.0 – 130.0V in 0.1V steps DTL, IDMTL 0.05 - 100.00 in 0.01 steps Inst, 0.01 - 300.00s in 0.01s steps Instantaneous, 0.1 – 300.0s in 0.1s steps Frequency Protection (81U/O) 1st – 4th Under frequency 45.00 – 50.00 Hz in 0.01Hz steps (rated frequency: 50Hz) 54.00 – 60.00 Hz in 0.01Hz steps (rated frequency: 60Hz) 1st – 4th Under frequency 50.00 – 55.00 Hz in 0.01Hz steps (rated frequency: 50Hz) 60.00 – 66.00 Hz in 0.01Hz steps (rated frequency: 60Hz) +0.1 to +9.9Hz/s in 0.1Hz/s steps −0.1 to −9.9Hz/s in 0.1Hz/s steps 0.00 – 100.00 s in 0.01 s steps Frequency rate-of-change st Timer for stage 1 Frequency UV Block th 4 40 – 100V in 1V steps Accuracy IDMTL Overvoltage Pick-up: 100% of setting ± 5% All Other Overvoltage Pick-ups: 100% of setting ± 5% approx, 95% (settable for phase overvoltage) Overvoltage PU/DO ratio: IDMTL Undervoltage Pick-up: All Other Undervoltage Pick-ups: Undervoltage PU/DO ratio: Over Frequency Pick-ups: Under Frequency Pick-ups: Frequency rate-of-change Pick-ups: Inverse Operate Time: 95% of setting ± 5% 100% of setting ± 5% approx, 105% 100% of setting ± 0.05Hz (setting: ≥ rated frequency - 5.00Hz) 100% of setting ± 0.05Hz (setting: ≤ rated frequency + 5.00Hz) 100% of setting ± 0.07Hz/s (setting: ≤ 5.00Hz/s) IEC60255-127, ±5% or 100ms (OV; 1.2 ≤ G/Gs ≤ GD/Gs , UV; 0 ≤ G/Gs ≤ 1) OV Definite Operate Time; ≤DTL + 45ms (DT, input: ≥ 200% of setting) UV Definite Operate Time; ≤DTL + 45ms (DT, input: ≤ 80% of setting) ZPS Definite Operate Time; ≤DTL + 45ms (DT, input: ≥ 200% of setting) NPS Definite Operate Time; ≤DTL + 50ms (DT, input: ≥ 200% of setting) Under/Over Frequency Operate Time DTL + 80-200ms (rated frequency: 50Hz) GD = 300V DTL + 70-170ms (rated frequency: 60Hz) Frequency rate-of-change Operate Time 190-300ms (rated frequency: 50Hz, input: ≥ 200% of setting) 160-250ms (rated frequency: 60Hz, input: ≥ 200% of setting) Time delays includes operating time of trip contacts Front Communication port - local PC (USB2.0) Connector type: Cable length: USB-Type B 5m (max.) Rear Communication port - remote PC (RS485) Connection: Cable type: Cable length: Multidrop (max. 32 relays) Twisted pair 1200m (max.) 190 6 F 2 T 0 1 7 6 Connector: Isolation: Transmission rate: Screw terminals 1kVac for 1 min. 19.2 kbps Rear Communication port (Ethernet) 100BASE-TX RJ-45 connector 100BASE-FX SC connector Binary Inputs Operating voltage For signal detection Typical 154Vdc (min. 110Vdc) for 220Vdc rating Typical 77Vdc (min. 70Vdc) for 110Vdc rating Typical 33.6Vdc (min. 24Vdc) for 48Vdc rating Typical 16.8Vdc(min. 12Vdc) for 24Vdc rating For trip circuit supervision ≥88V for 220/250Vdc rating ≥38.4Vdc for 110Vdc rating ≥19.2V for 48Vdc rating ≥9.6V for 24Vdc rating Binary Outputs Number Ratings 4 or 8 (excluding Relay Fail contact) Make and carry: 5A continuously model 410 and 411; BO#1 and #2 model 412: BO#1,#2,#5 and #6 other BOs Durability: Make and carry: 5A continuously Contact : 0.4A 250Vdc, 8A 380Vac, 3040VA, 150W Make and carry: 30A, 250Vdc for 0.5s (L/R=40ms) Break: 0.1A, 250Vdc (L/R=40ms) Make and carry: 4A continuously Contact: 0.2A 110Vdc, 8A 250Vac, 2000VA, 240W Loaded contact: ≥1,000 operations Unloaded contact: ≥10,000 operations Pickup time: Less than 15ms Reset time: Less than 10ms Mechanical design Weight 1.5kg for model 410A and 411A Width 1.8kg for model 412A 149mm for model 410A and 411A Height 223mm for model 412A 177mm Depth 168mm Case color Installation Munsell No. 10YR8/0.5 Flush mounting with attachment kits 191 6 F 2 T 0 1 7 6 ENVIRONMENTAL PERFORMANCE Test Standards Details Atmospheric Environment Temperature IEC 60068-2-1/2 IEC 60068-2-30 Operating range: -20°C to +60°C. Humidity IEC 60068-2-78 Enclosure Protection IEC 60529 56 days at 40°C and 93% relative humidity. IP52 (front), IP20 (rear), IP40 (top) Storage / Transit: -25°C to +70°C. Mechanical Environment Vibration IEC 60255-21-1 Shock and Bump IEC 60255-21-2 Response - Class 1 Endurance - Class 1 Shock Response Class 1 Shock Withstand Class 1 Bump Class 1 Seismic IEC 60255-21-3 Class 1 Dielectric Withstand IEC 60255-5 IEEE C37.90.0 2kVrms for 1 minute between all terminals and earth. 2kVrms for 1 minute between independent circuits. 1kVrms for 1 minute across normally open contacts. High Voltage Impulse IEC 60255-5 Three positive and three negative impulses of 5kV(peak) for CT, Power Supply Unit (PSU), BI and BO circuits; between terminals and earth, and between independent circuits 3kV (peak) for RS485 circuit; between terminals and earth 3kV (peak) for BO circuit; across normally open contacts Electrical Environment 1.2/50µs, 0.5J between all terminals and between all terminals and earth. Electromagnetic Environment High Frequency Disturbance / Damped Oscillatory Wave IEC 60255-22-1 Class 3, IEC 61000-4-12 IEEE C37.90.1 IEC 60255-22-2 Class 3, IEC 61000-4-2 1MHz 2.5kV to 3kV (peak) applied to all ports in common mode. 1MHz 1.0kV applied to all ports in differential mode. Radiated RF Electromagnetic Disturbance IEC 60255-22-3 Class 3, IEC 61000-4-3 Field strength 10V/m for frequency sweeps of 80MHz to 1GHz and 1.7GHz to 2.2GHz. Additional spot tests at 80, 160, 450, 900 and 1890MHz. Fast Transient Disturbance IEC 60255-22-4 Class A, IEC 61000-4-4, IEEE C37.90.1 4kV, 2.5kHz, 5/50ns applied to all inputs. Surge Immunity IEC 60255-22-5, IEC 61000-4-5 1.2/50µs surge in common/differential modes: HV, PSU and I/O ports: 2kV/1kV (peak) RS485 port: 1kV (peak) Conducted RF Electromagnetic Disturbance IEC 60255-22-6 Class 3, IEC 61000-4-6 10Vrms applied over frequency range 150kHz to 100MHz. Additional spot tests at 27 and 68MHz. Power Frequency Disturbance IEC 60255-22-7 Class A, IEC 61000-4-16 300V 50Hz for 10s applied to ports in common mode. 150V 50Hz for 10s applied to ports in differential mode. Not applicable to AC inputs. Electrostatic Discharge 6kV contact discharge, 8kV air discharge. 192 6 F 2 T 0 1 7 6 Test Conducted and Radiated Emissions Standards IEC 60255-25, EN 55022 Class A, IEC 61000-6-4 Details Conducted emissions: 0.15 to 0.50MHz: <79dB (peak) or <66dB (mean) 0.50 to 30MHz: <73dB (peak) or <60dB (mean) Radiated emissions (at 10m): 30 to 230MHz: <40dB 230 to 1000MHz: <47dB European Commission Directives 89/336/EEC 73/23/EEC Compliance with the European Commission Electromagnetic Compatibility Directive is demonstrated according to generic EMC standards EN 61000-6-2 and EN 61000-6-4. Compliance with the European Commission Low Voltage Directive is demonstrated according to product safety standard EN 60255-27. 193 6 F 2 T 0 1 7 6 Appendix K Symbols Used in Scheme Logic 194 6 F 2 T 0 1 7 6 The symbols used in the scheme logic and their respective meanings are as follows: Signal names Marked with : Measuring element output signal Marked with : Binary signal input from or output to external equipment Marked with [ ] Marked with " " Unmarked : Scheme switch : Scheme switch position : Internal scheme logic signal AND gates A B A 1 B C 1 1 Other cases Output 1 0 & Output & Output A 1 B C 1 0 Other cases Output 1 0 & Output A 1 B C 0 0 Other cases Output 1 0 ≥1 Output A 0 B C 0 0 Other cases Output 0 1 ≥1 Output A 0 B C 0 1 Other cases Output 0 1 ≥1 Output A 0 B C 1 1 Other cases Output 0 1 C A B C A B C OR gates A B C A B C A B C 195 6 F 2 T 0 1 7 6 Signal inversion A 1 A 0 1 Output Output 1 0 Timer t Delayed pick-up timer with fixed setting 0 XXX: Set time XXX 0 Delayed drop-off timer with fixed setting t XXX: Set time XXX t Delayed pick-up timer with variable setting 0 XXX - YYY: Setting range XXX - YYY 0 Delayed drop-off timer with variable setting t XXX - YYY: Setting range XXX - YYY One-shot timer A A Output Output XXX - YYY XXX - YYY: Setting range Flip-flop S 0 1 0 1 S F/F Output R R 0 0 1 1 Output No change 1 0 0 Scheme switch A Output ON + Output ON 196 A Switch 1 ON Other cases Switch ON OFF Output 1 0 Output 1 0 6 F 2 T 0 1 7 6 Appendix L Modbus: Interoperability 197 6 F 2 T 0 1 7 6 Modbus: Interoperability 1. Physical and Data Link Layer - RS485(EIA/TIA-485) 2-wire interface - RTU mode only - Coding System: 8–bit binary (1 start bit, 8 data bits, 1 parity bit, 1 stop bit) Even parity - Address setting range: 1-247 - Baud rate setting range: 9600 or 19200 2. Application Layer (1) Modbus response format FC Description Supplementary explanation 01 02 03 04 05 06 07 08 16 17 43 Returns remote control enable flag Returns BIs or LED lamp status, etc. Returns value of analog inputs Remote command and Time synchronization Need to specify record number Returns relay and CB status Current time setting, etc. Returns device ID Returns device information Read Coils Read Discrete Inputs Read Holding Registers Read Input Register Write Single Coil Write Single Register Read Exception status Diagnostic Write Multiple Registers Report Slave ID Read device Identification (SC:14) For FC=01, 02, 03, 04, 05, 06 and 16, the response format is the same as described in "MODBUS Application Protocol Specification V1.1b". For other FCs, the response format is as following: 07 Read Exception status Response Data Output Data (1byte) bit Description 0 IN SERVICE (LED) 1 TRIP (LED) 2 ALARM (LED) 3 RELAY FAIL (LED) 4 CB CLOSED (LED) 5 CB OPEN (LED) 6 Relay fail output (BO) 7 <Reserved> 08 Diagnostic Response Data 198 6 F 2 T 0 1 7 6 SC 00 01 02 03- Response Data Field Echo Request Data (2Bytes) <not supported> Diagnostic Register Contents (2Bytes) bit0 IN SERVICE (LED) bit1 TRIP (LED) bit2 ALARM (LED) bit3 RELAY FAIL (LED) bit4 <Reserved> bit5 <Reserved> bit6 <Reserved> bit7 <Reserved> bit8 3-phase current balance alarm bit9 CB contact status alarm bit10 CB operation number alarm bit11 <Reserved> bit12 V0 error alarm bit13 V2 error alarm bit14 <Reserved> bit15 <Reserved> <not supported> 17 Report Slave ID Response Data Byte Count (1byte) Slave ID (17bytes) GRE130-411A-10-10 Run Indicator Status (1byte) Return Diagnostic Register 18bytes Relay type and model ID ASCII 0x00=out of service, 0xFF=in service 43 Read Device Identification (SC:14) Response Data Param OID 01 00 TOSHIBA 01 GRE130-411 02 A 02 03 <Non> 04 GRE130 05 411A-10-10 06 Overvoltage Relay 07<Reserved> 03 80 <SPACE> 81 GS1EM1-03-A 04 Description Return Query Data Basic device identification Vendor Name Product Code Major Minor Revision Regular device identification Vendor URL Product Name Model Name User Application Name Reserved Extended device identification Software version One specific identification object <not supported> 199 6 F 2 T 0 1 7 6 (2) Modbus address map group Modbus data model Address(ID) Coils 0x0200 (Read/Write) 0x0400 Discrete Input (Read Only) 0x1000 0x1016 0x1040 0x1080 0x1201 Input Registers 0x2000 (Read Only) 0x2800 Holding Registers 0x3000 (Read/Write) 0x3200 Number Data specification 1 Remote control (enable flag) Remote control (command, interlock), Time 4 synchronization, Clear command 6 BI 5 Relay fail output, BO 14 LED(Relay status, R/L, CB on/off status) 16 Virtual LED - Signal list (see Appendix A for detail) Analog data (Van, Vbn, Vcn, Vab, Vbc, Vca, V0 etc., not 40 converted to engineering units) 2-word long Analog data (Van, Vbn, Vcn, Vab, Vbc, Vca, V0 etc., 40 converted to engineering units) 2-word long Fault record (No., Time, Phase, Type), max. 4 records, 29 write protected Event record (No., Time, ID, Status), 10 out of max. 200 72 records, write protected 4 Current time data (IEC format) 30 Counter data (number of trips etc), 2-word long 2 Password for remote control - Setting value (see Appendix H for detail), Read Only Undefined after this address 0x3800 0x3810 0x3E82 0x4000 0x8000 Discrete Input Coils Input Registers Holding Registers Single bit Single bit 16-bit word 16-bit word (3)Modbus address map Address Description Read-Only Read-Write Read-Only Read-Write Supplementary explanation Coils 0200 0400 0401 0402 0403 Remote control (R/W) Remote control enable flag Remote control command Remote interlock command Remote reset command Time synchronization command Write (control) is enable only 0x0200=1 (on/off) Write (control) is enable only 0x0200=1 (on/off) Write (control) is enable only 0x0200=1 (on) Call time synchronization task (on) 200 6 F 2 T 0 1 7 6 Address Description Discrete Input BI status (R) 1000 BI1 1001 BI2 1002 BI3 1003 BI4 1004 BI5 1005 BI6 BO status (R) 1016 Relay fail output 1017 BO1 1018 BO2 1019 BO3 101A BO4 101B BO5 101C BO6 101D BO7 101E BO8 LED lamp status (R) 1040 IN SERVICE 1041 TRIP 1042 ALARM 1043 RELAY FAIL 1044 CB CLOSED 1045 CB OPEN 1046 LOCAL 1047 REMOTE 1048 LED1 1049 LED2 104A LED3 104B LED4 104C LED5 104D LED6 Virtual LED status (R) 1080 IND1 BIT1 1081 IND1 BIT2 1082 IND1 BIT3 1083 IND1 BIT4 1084 IND1 BIT5 1085 IND1 BIT6 1086 IND1 BIT7 1087 IND1 BIT8 1088 IND2 BIT1 1089 IND2 BIT2 Supplementary explanation Only for GRE130-411A Only for GRE130-411A Only for GRE130-411A Only for GRE130-411A Only for GRE130-412A Only for GRE130-412A Only for GRE130-412A Only for GRE130-412A 201 6 F 2 T 0 1 7 6 Address 108A 108B 108C 108D 108E 108F Description IND2 BIT3 IND2 BIT4 IND2 BIT5 IND2 BIT6 IND2 BIT7 IND2 BIT8 Supplementary explanation Address Description Supplementary explanation 1201 1202 … Signal list (R) Signal No.1 Signal No.2 Signal No.n See Appendix A See Appendix A Address for signal No.n = 0x1200 + n. See Appendix A Address Description Supplementary explanation Input Registers Analog data (R) 2000 Van / Vab / Vph (H) 2001 Van / Vab / Vph (L) 2002 Van / Vab (H) 2003 Van / Vab (L) 2004 Vbn / Vbc (H) 2005 Vbn / Vbc (L) 2006 Vbn / Vbc (H) 2007 Vbn / Vbc (L) 2008 Vcn / Vca (H) 2009 Vcn / Vca (L) 200A Vcn / Vca (H) 200B Vcn / Vca (L) 200C V0 (H) 200D V0 (L) 200E V0 (H) 200F V0 (L) 2010 V2 (H) 2011 V2 (L) 2012 V2 (H) 2013 V2 (L) 2014 V1 (H) 2015 V1 (L) 2016 V1 (H) 2017 V1 (L) 2018 <Reserved> 2019 <Reserved> 201A <Reserved> 201B <Reserved> Followings are NOT converted to engineering units. Primary: value×0.125×PVT_RATIO/1000(kV) Secondary: Value×0.125(V) Phase angle: value×0.01 (deg) Primary: value×0.125×PVT_RATIO/1000(kV) Secondary: Value×0.125(V) Phase angle: value×0.01 (deg) Primary: value×0.125×PVT_RATIO/1000(kV) Secondary: Value×0.125(V) Phase angle: value×0.01 (deg) Primary: value×0.125×PVT_RATIO/1000(kV) Secondary: Value×0.125(V) Phase angle: value×0.01 (deg) Primary: value×0.125×PVT_RATIO/1000(kV) Secondary: Value×0.125(V) Phase angle: value×0.01 (deg) Primary: value×0.125×PVT_RATIO/1000(kV) Secondary: Value×0.125(V) Phase angle: value×0.01 (deg) 202 6 F 2 T 0 1 7 6 Address Description 201C 201D 201E 201F 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029 202A 202B 202C 202D 202E 202F 2030 2031 2032 2033 2034 2035 2036 2037 <Reserved> <Reserved> <Reserved> <Reserved> <Reserved> <Reserved> <Reserved> <Reserved> <Reserved> <Reserved> f (H) f (L) fmax (H) fmax (L) fmin (H) fmin (L) df / dt (H) df / dt (L) df / dtx (H) df / dtx (L) df / dtn (H) df / dtn (L) <Reserved> <Reserved> <Reserved> <Reserved> <Reserved> <Reserved> Address Description Supplementary explanation Analog data (R) The following are converted to engineering units. (the same as the displayed value) 2800 2801 2802 2803 2804 2805 2806 2807 2808 2809 280A 280B 280C Supplementary explanation f × 0.01 (Hz) f × 0.01 (Hz) f × 0.01 (Hz) f × 0.01 (Hz) f × 0.01 (Hz) f × 0.01 (Hz) Van (H) Van (L) Van (H) Van (L) Vbn (H) Vbn (L) Vbn (H) Vbn (L) Vcn (H) Vcn (L) Vcn (H) Vcn (L) Vab (H) 203 6 F 2 T 0 1 7 6 Address Description 280D 280E 280F 2810 2811 2812 2813 2814 2815 2816 2817 2818 2819 281A 281B 281C 281D 281E 281F 2820 2821 2822 2823 2824 2825 2826 2827 2828 2829 282A 282B 282C 282D 282E 282F 2830 2831 2832 2833 2834 2835 2836 2837 Vab (L) Vab (H) Vab (L) Vbc (H) Vbc (L) Vbc (H) Vbc (L) Vca (H) Vca (L) Vca (H) Vca (L) Vph (H) Vph (L) V0 (H) V0 (L) V0 (H) V0 (L) V1 (H) V1 (L) V1 (H) V1 (L) V2 (H) V2 (L) V2 (H) V2 (L) f (H) f (L) fmax (H) fmax (L) fmin (H) fmin (L) df / dt (H) df / dt (L) df / dtx (H) df / dtx (L) df / dtn (H) df / dtn (L) <Reserved> <Reserved> <Reserved> <Reserved> <Reserved> <Reserved> Supplementary explanation 204 6 F 2 T 0 1 7 6 Address Description Holding Registers Fault record (R) 3000 records count 3001 No.1 3002 3003 3004 3005 3006 3007 milliseconds hours/minutes months/days year Fault phase Trip mode 3008 No.2 3009 300A 300B 300C 300D 300E milliseconds hours/minutes months/days year Fault phase Trip mode 300F No.3 3010 3011 3012 3013 3014 3015 milliseconds hours/minutes months/days year Fault phase Trip mode 3016 No.4 3017 3018 3019 301A 301B 301C milliseconds hours/minutes months/days year Fault phase Trip mode Supplementary explanation Number of record saved (max. 4) Indication of record #1. If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) Indication of record #2. If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) Indication of record #3. If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) Indication of record #4. If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) 205 6 F 2 T 0 1 7 6 Address Description Supplementary explanation 3200 3201 3202 3203 3204 3205 3206 3207 3208 Event record (R) records count set No. (R/W) No. X milliseconds hours/minutes months/days year Event ID Action 3209 No.X+1 320A 320B 320C 320D 320E 320F milliseconds hours/minutes months/days year Event ID Action 3210 No.X+2 3211 3212 3213 3214 3215 3216 milliseconds hours/minutes months/days year Event ID Action 3217 No.X+3 3218 3219 321A 321B 321C 321D milliseconds hours/minutes months/days year Event ID Action 321E No.X+4 321F 3220 3221 3222 3223 3224 milliseconds hours/minutes months/days year Event ID Action 10 records are obtained at a time. Number of records saved (max. 200) Requesting first record number (If 1, returns the latest 10 records) Returns "Set No.". If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) See Appendix B 1:on 、2:off、 Returns "Set No.+1". If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) See Appendix B 1:on 、2:off Returns "Set No.+2". If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) See Appendix B 1:on 、2:off Returns "Set No.+3". If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) See Appendix B 1:on 、2:off Returns "Set No.+4". If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) See Appendix B 1:on 、2:off 206 6 F 2 T 0 1 7 6 Address Description 3225 No.X+5 3226 3227 3228 3229 322A 322B milliseconds hours/minutes months/days year Event ID Action 322C No.X+6 322D 322E 322F 3230 3231 3232 milliseconds hours/minutes months/days year Event ID Action 3233 No.X+7 3234 3235 3236 3237 3238 3239 milliseconds hours/minutes months/days year Event ID Action 323A No.X+8 323B 323C 323D 323E 323F 3240 milliseconds hours/minutes months/days year Event ID Action 3241 No.X+9 3242 3243 3244 3245 3246 3247 milliseconds hours/minutes months/days year Event ID Action Supplementary explanation Returns "Set No.+5". If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) See Appendix B 1:on 、2:off Returns "Set No.+6". If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) See Appendix B 1:on 、2:off Returns "Set No.+7". If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) See Appendix B 1:on 、2:off Returns "Set No.+8". If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) See Appendix B 1:on 、2:off Returns "Set No.+9". If no data, all of the following data is set to 0. 0-59999 (millisecond) 0-23(h)、0-59(m) 1-12(m)、1-31(d) 0-99(y) See Appendix B 1:on 、2:off 207 6 F 2 T 0 1 7 6 Address 3800 3801 3802 3803 3810 3811 3812 3813 3814 3815 3816 3817 3E82 3E83 4000 7FFF Description Supplementary explanation Current time in IEC60870-5-4 format Current time data (R/W) milliseconds 0-59999 (millisecond) hours/minutes 0-23(h)、0-59(m) months/days 1-12(m)、1-31(d) year 0-99(y) Counters (R/W) Trips Phase-A (H) Can be set to an initial value. Trips Phase-A (L) Trips Phase-B (H) Can be set to an initial value. Trips Phase-B (L) Trips Phase-C (H) Can be set to an initial value. Trips Phase-C (L) Trips any phase (H) Can be set to an initial value. Trips any phase (L) Password Control (H) Password for remote control (in ASCII code) Control (L) Setting values See the next table for setting values. <Reserved> 208 6 F 2 T 0 1 7 6 (4) Modbus address for setting values Setting Group (Menu) Event Record Disturbance Record Address Name Contents 6034 BI1 comm. BI 1 command trigger setting 6035 6036 6037 BI2 comm. BI3 comm. BI4 comm. BI 2 command trigger setting BI 3 command trigger setting BI 4 command trigger setting 6038 6039 603C BI5 comm. BI6 comm. Time1 BI 5 command trigger setting BI 6 command trigger setting Disturbance record period before fault 6000 6001 6002 6003 Time2 OV UV ZPS 6004 6005 6006 6007 6008 6009 600A NPS Trip BI OV UV ZPS NPS NPS element for disturbance Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger 603D 600B 600C 600D 600E 600F 6010 FRQ SIG1 SIG2 SIG3 SIG4 SIG5 SIG6 Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger 6011 6012 SIG7 SIG8 Disturbance trigger Disturbance trigger 6013 6014 SIG9 SIG10 Disturbance trigger Disturbance trigger 6015 6016 SIG11 SIG12 Disturbance trigger Disturbance trigger 6017 6018 6019 601A 601B 601C 601D 601E 601F 6020 6021 6022 SIG13 SIG14 SIG15 SIG16 SIG17 SIG18 SIG19 SIG20 SIG21 SIG22 SIG23 SIG24 Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance record period after fault OC element for disturbance EF element for disturbance SEF element for disturbance 209 6 F 2 T 0 1 7 6 Setting Group (Menu) Disturbance Record Counter Status Binary Input Address Name Contents 6023 SIG25 Disturbance trigger 6024 6025 6026 6027 6028 SIG26 SIG27 SIG28 SIG29 SIG30 Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger Disturbance trigger 6029 602A 602B 602C 602D 6030 6400 6401 6402 640A 6C00 SIG31 SIG32 TCSPEN CBSMEN TCAEN TCALM Display Time sync. GMT GMTm BITHR1 6C01 6C02 6C03 BITHR2 BI1 BI1 BI1PUD BI1DOD BI threshold for BI3-6 Binary Input 1 Pick-up delay Binary Input 1 Drop-off delay 6C04 6C05 BI1 BI1 BI1SNS BI1SGS Binary Input 1 Sense Binary Input 1 Settings Group Select 6C06 6C07 6C08 6C09 6C0A 6C0B BI1 BI1 BI1 BI1 BI1 BI1 OV1BLK OV2BLK OV3BLK UV1BLK UV2BLK UV3BLK OV1 Block OV2 Block OV3 Block UV1 Block UV2 Block UV3 Block 6C0C 6C0D BI1 BI1 ZP1BLK ZP2BLK ZPS1 Block ZPS2 Block 6C0E 6C0F 6C10 6C11 6C12 6C13 6C14 6C15 6C16 6C17 6C18 6C19 6C1A 6C1B BI1 BI1 BI1 BI1 BI1 BI1 BI1 BI1 BI1 BI1 BI1 BI1 BI1 BI1 NP1BLK NP2BLK TCFALM CBOPN CBCLS EXT3PH EXTAPH EXTBPH EXTCPH RMTRST SYNCLK STORCD Alarm1 Alarm2 NPS1 Block NPS2 Block Trip Circuit Fail Alarm Circuit Breaker Open Circuit Breaker Close External Trip - 3 phase External Trip - A phase External Trip - B phase External Trip - C phase Remote Reset Synchronize clock Store Disturbance Record Alarm screen 1. Alarm screen 2. Disturbance trigger Disturbance trigger Trip Circuit Supervision Enable Circuit Breaker State Monitoring Alarm Enable Trip Count Alarm Enable Trip Count Alarm Threshold setting Metering Time synchronization method Time zone (Hours) Time zone (minutes) BI threshold for BI1 & BI2 210 6 F 2 T 0 1 7 6 Setting Group (Menu) Binary Input Address Name Contents 6C1C BI1 Alarm3 6C1D 6C1E 6C1F 6C20 6C21 BI1 BI1 BI1 BI1 BI1 Alarm4 RMTOPN RMTCLS CNTLCK FRQ1BLK Alarm screen 4. Remote CB Open Control Remote CB Close Control Interlock Input FRQ1 Block 6C22 6C23 6C24 6C25 6C26 6C27 6C28 6C29 6C2A 6C2B 6C2C 6C2D 6C2E 6C2F BI1 BI1 BI1 BI2 BI2 BI2 BI2 BI2 BI2 BI2 BI2 BI2 BI2 BI2 FRQ2BLK FRQ3BLK FRQ4BLK BI2PUD BI2DOD BI2SNS BI2SGS OV1BLK OV2BLK OV3BLK UV1BLK UV2BLK UV3BLK ZP1BLK FRQ2 Block FRQ3 Block FRQ4 Block Binary Input 2 Pick-up delay Binary Input 2 Drop-off delay Binary Input 2 Sense Binary Input 2 Settings Group Select OV1 Block OV2 Block OV3 Block UV1 Block UV2 Block UV3 Block ZPS1 Block 6C30 6C31 BI2 BI2 ZP2BLK NP1BLK ZPS2 Block NPS1 Block 6C32 6C33 6C34 6C35 6C36 6C37 BI2 BI2 BI2 BI2 BI2 BI2 NP2BLK TCFALM CBOPN CBCLS EXT3PH EXTAPH NPS2 Block Trip Circuit Fail Alarm Circuit Breaker Open Circuit Breaker Close External Trip - 3 phase External Trip - A phase 6C38 6C39 BI2 BI2 EXTBPH EXTCPH External Trip - B phase External Trip - C phase 6C3A 6C3B 6C3C 6C3D 6C3E 6C3F 6C40 6C41 6C42 6C43 6C44 6C45 6C46 6C47 BI2 BI2 BI2 BI2 BI2 BI2 BI2 BI2 BI2 BI2 BI2 BI2 BI2 BI2 RMTRST SYNCLK STORCD Alarm1 Alarm2 Alarm3 Alarm4 RMTOPN RMTCLS CNTLCK FRQ1BLK FRQ2BLK FRQ3BLK FRQ4BLK Remote Reset Synchronize clock Store Disturbance Record Alarm screen 1. Alarm screen 2. Alarm screen 3. Alarm screen 4. Remote CB Open Control Remote CB Close Control Interlock Input FRQ1 Block FRQ2 Block FRQ3 Block FRQ4 Block 211 Alarm screen 3. 6 F 2 T 0 1 7 6 Setting Group (Menu) Binary Input Address Name Contents 6C48 BI3 BI3PUD Binary Input 3 Pick-up delay 6C49 6C4A 6C4B 6C4C 6C4D BI3 BI3 BI3 BI3 BI3 BI3DOD BI3SNS BI3SGS OV1BLK OV2BLK Binary Input 3 Drop-off delay Binary Input 3 Sense Binary Input 3 Settings Group Select OV1 Block OV2 Block 6C4E 6C4F 6C50 6C51 6C52 6C53 6C54 6C55 6C56 6C57 6C58 6C59 6C5A 6C5B BI3 BI3 BI3 BI3 BI3 BI3 BI3 BI3 BI3 BI3 BI3 BI3 BI3 BI3 OV3BLK UV1BLK UV2BLK UV3BLK ZP1BLK ZP2BLK NP1BLK NP2BLK TCFALM CBOPN CBCLS EXT3PH EXTAPH EXTBPH OV3 Block UV1 Block UV2 Block UV3 Block ZPS1 Block ZPS2 Block NPS1 Block NPS2 Block Trip Circuit Fail Alarm Circuit Breaker Open Circuit Breaker Close External Trip - 3 phase External Trip - A phase External Trip - B phase 6C5C 6C5D BI3 BI3 EXTCPH RMTRST External Trip - C phase Remote Reset 6C5E 6C5F 6C60 BI3 BI3 BI3 SYNCLK STORCD Alarm1 Synchronize clock Store Disturbance Record Alarm screen 1. 6C61 6C62 6C63 BI3 BI3 BI3 Alarm2 Alarm3 Alarm4 6C64 6C65 BI3 BI3 RMTOPN RMTCLS Remote CB Open Control Remote CB Close Control 6C66 6C67 6C68 6C69 6C6A 6C6B 6C6C 6C6D 6C6E 6C6F 6C70 6C71 6C72 6C73 BI3 BI3 BI3 BI3 BI3 BI4 BI4 BI4 BI4 BI4 BI4 BI4 BI4 BI4 CNTLCK FRQ1BLK FRQ2BLK FRQ3BLK FRQ4BLK BI4PUD BI4DOD BI4SNS BI4SGS OV1BLK OV2BLK OV3BLK UV1BLK UV2BLK Interlock Input FRQ1 Block FRQ2 Block FRQ3 Block FRQ4 Block Binary Input 4 Pick-up delay Binary Input 4 Drop-off delay Binary Input 4 Sense Binary Input 4 Settings Group Select OV1 Block OV2 Block OV3 Block UV1 Block UV2 Block 212 Alarm screen 2. Alarm screen 3. Alarm screen 4. 6 F 2 T 0 1 7 6 Setting Group (Menu) Binary Input Address Name Contents 6C74 BI4 UV3BLK UV3 Block 6C75 6C76 6C77 6C78 6C79 BI4 BI4 BI4 BI4 BI4 ZP1BLK ZP2BLK NP1BLK NP2BLK TCFALM ZPS1 Block ZPS2 Block NPS1 Block NPS2 Block Trip Circuit Fail Alarm 6C7A 6C7B 6C7C 6C7D 6C7E 6C7F 6C80 6C81 6C82 6C83 6C84 6C85 6C86 6C87 BI4 BI4 BI4 BI4 BI4 BI4 BI4 BI4 BI4 BI4 BI4 BI4 BI4 BI4 CBOPN CBCLS EXT3PH EXTAPH EXTBPH EXTCPH RMTRST SYNCLK STORCD Alarm1 Alarm2 Alarm3 Alarm4 RMTOPN Circuit Breaker Open Circuit Breaker Close External Trip - 3 phase External Trip - A phase External Trip - B phase External Trip - C phase Remote Reset Synchronize clock Store Disturbance Record Alarm screen 1. Alarm screen 2. Alarm screen 3. Alarm screen 4. Remote CB Open Control 6C88 6C89 BI4 BI4 RMTCLS CNTLCK Remote CB Close Control Interlock Input 6C8A 6C8B 6C8C 6C8D 6C8E 6C8F BI4 BI4 BI4 BI4 BI5 BI5 FRQ1BLK FRQ2BLK FRQ3BLK FRQ4BLK BI5PUD BI5DOD FRQ1 Block FRQ2 Block FRQ3 Block FRQ4 Block Binary Input 5 Pick-up delay Binary Input 5 Drop-off delay 6C90 6C91 BI5 BI5 BI5SNS BI5SGS 6C92 6C93 6C94 6C95 6C96 6C97 6C98 6C99 6C9A 6C9B 6C9C 6C9D 6C9E 6C9F BI5 BI5 BI5 BI5 BI5 BI5 BI5 BI5 BI5 BI5 BI5 BI5 BI5 BI5 OV1BLK OV2BLK OV3BLK UV1BLK UV2BLK UV3BLK ZP1BLK ZP2BLK NP1BLK NP2BLK TCFALM CBOPN CBCLS EXT3PH 213 Binary Input 5 Sense Binary Input 5 Settings Group Select OV1 Block OV2 Block OV3 Block UV1 Block UV2 Block UV3 Block ZPS1 Block ZPS2 Block NPS1 Block NPS2 Block Trip Circuit Fail Alarm Circuit Breaker Open Circuit Breaker Close External Trip - 3 phase 6 F 2 T 0 1 7 6 Setting Group (Menu) Binary Input Address Name Contents 6CA0 BI5 EXTAPH External Trip - A phase 6CA1 6CA2 6CA3 6CA4 6CA5 BI5 BI5 BI5 BI5 BI5 EXTBPH EXTCPH RMTRST SYNCLK STORCD External Trip - B phase External Trip - C phase Remote Reset Synchronize clock Store Disturbance Record 6CA6 6CA7 6CA8 6CA9 6CAA 6CAB 6CAC 6CAD 6CAE 6CAF 6CB0 6CB1 6CB2 6CB3 BI5 BI5 BI5 BI5 BI5 BI5 BI5 BI5 BI5 BI5 BI5 BI6 BI6 BI6 Alarm1 Alarm2 Alarm3 Alarm4 RMTOPN RMTCLS CNTLCK FRQ1BLK FRQ2BLK FRQ3BLK FRQ4BLK BI6PUD BI6DOD BI6SNS Alarm screen 1. Alarm screen 2. Alarm screen 3. Alarm screen 4. Remote CB Open Control Remote CB Close Control Interlock Input FRQ1 Block FRQ2 Block FRQ3 Block FRQ4 Block Binary Input 6 Pick-up delay Binary Input 6 Drop-off delay Binary Input 6 Sense 6CB4 6CB5 BI6 BI6 BI6SGS OV1BLK Binary Input 6 Settings Group Select OV1 Block 6CB6 6CB7 6CB8 6CB9 6CBA 6CBB BI6 BI6 BI6 BI6 BI6 BI6 OV2BLK OV3BLK UV1BLK UV2BLK UV3BLK ZP1BLK OV2 Block OV3 Block UV1 Block UV2 Block UV3 Block ZPS1 Block 6CBC 6CBD BI6 BI6 ZP2BLK NP1BLK ZPS2 Block NPS1 Block 6CBE 6CBF 6CC0 6CC1 6CC2 6CC3 6CC4 6CC5 6CC6 6CC7 6CC8 6CC9 6CCA 6CCB BI6 BI6 BI6 BI6 BI6 BI6 BI6 BI6 BI6 BI6 BI6 BI6 BI6 BI6 NP2BLK TCFALM CBOPN CBCLS EXT3PH EXTAPH EXTBPH EXTCPH RMTRST SYNCLK STORCD Alarm1 Alarm2 Alarm3 NPS2 Block Trip Circuit Fail Alarm Circuit Breaker Open Circuit Breaker Close External Trip - 3 phase External Trip - A phase External Trip - B phase External Trip - C phase Remote Reset Synchronize clock Store Disturbance Record Alarm screen 1. Alarm screen 2. Alarm screen 3. 214 6 F 2 T 0 1 7 6 Setting Group (Menu) Binary Input Binary Output Address Name Contents 6CCC BI6 Alarm4 6CCD 6CCE 6CCF 6CD0 6CD1 BI6 BI6 BI6 BI6 BI6 RMTOPN RMTCLS CNTLCK FRQ1BLK FRQ2BLK Remote CB Open Control Remote CB Close Control Interlock Input FRQ1 Block FRQ2 Block 6CD2 6CD3 7428 7429 7400 7401 7402 7403 7450 742A 742B 7404 7405 7406 BI6 BI6 BO1 BO1 BO1 BO1 BO1 BO1 BO1 BO2 BO2 BO2 BO2 BO2 FRQ3BLK FRQ4BLK Logic Reset In #1 In #2 In #3 In #4 TBO Logic Reset In #1 In #2 In #3 FRQ3 Block FRQ4 Block Logic Gate Type Reset operation Functions Functions Functions Functions Delay/Pulse Width Logic Gate Type Reset operation Functions Functions Functions 7407 7451 BO2 BO2 In #4 TBO Functions Delay/Pulse Width 742C 742D 7408 7409 740A 740B BO3 BO3 BO3 BO3 BO3 BO3 Logic Reset In #1 In #2 In #3 In #4 Logic Gate Type Reset operation Functions Functions Functions Functions 7452 742E BO3 BO4 TBO Logic Delay/Pulse Width Logic Gate Type 742F 740C 740D 740E 740F 7453 7430 7431 7410 7411 7412 7413 7454 7432 BO4 BO4 BO4 BO4 BO4 BO4 BO5 BO5 BO5 BO5 BO5 BO5 BO5 BO6 Reset In #1 In #2 In #3 In #4 TBO Logic Reset In #1 In #2 In #3 In #4 TBO Logic Reset operation Functions Functions Functions Functions Delay/Pulse Width Logic Gate Type Reset operation Functions Functions Functions Functions Delay/Pulse Width Logic Gate Type 215 Alarm screen 4. 6 F 2 T 0 1 7 6 Setting Group (Menu) Binary Output Configurable LED Address Name Contents 7433 BO6 Reset Reset operation 7414 7415 7416 7417 7455 BO6 BO6 BO6 BO6 BO6 In #1 In #2 In #3 In #4 TBO Functions Functions Functions Functions Delay/Pulse Width 7434 7435 7418 7419 741A 741B 7456 7436 7437 741C 741D 741E 741F 7457 BO7 BO7 BO7 BO7 BO7 BO7 BO7 BO8 BO8 BO8 BO8 BO8 BO8 BO8 Logic Reset In #1 In #2 In #3 In #4 TBO Logic Reset In #1 In #2 In #3 In #4 TBO Logic Gate Type Reset operation Functions Functions Functions Functions Delay/Pulse Width Logic Gate Type Reset operation Functions Functions Functions Functions Delay/Pulse Width 7020 7021 LED1 LED1 Logic Reset LED1 Logic Gate Type LED1 Reset operation 7022 7023 7024 7025 7026 7027 LED2 LED2 LED3 LED3 LED4 LED4 Logic Reset Logic Reset Logic Reset LED2 Logic Gate Type LED2 Reset operation LED3 Logic Gate Type LED3 Reset operation LED4 Logic Gate Type LED4 Reset operation 7028 7029 LED5 LED5 Logic Reset LED5 Logic Gate Type LED5 Reset operation 702A 702B 7000 7001 7002 7003 7004 7005 7006 7007 7008 7009 700A 700B LED6 LED7 LED1 LED1 LED1 LED1 LED2 LED2 LED2 LED2 LED3 LED3 LED3 LED3 Logic Reset In #1 In #2 In #3 In #4 In #1 In #2 In #3 In #4 In #1 In #2 In #3 In #4 LED6 Logic Gate Type LED6 Reset operation LED Functions LED Functions LED Functions LED Functions LED Functions LED Functions LED Functions LED Functions LED Functions LED Functions LED Functions LED Functions 216 6 F 2 T 0 1 7 6 Setting Group (Menu) Configurable LED Configurable LED Active group/ Common Address Name Contents 700C LED4 In #1 LED Functions 700D 700E 700F 7010 7011 LED4 LED4 LED4 LED5 LED5 In #2 In #3 In #4 In #1 In #2 LED Functions LED Functions LED Functions LED Functions LED Functions 7012 7013 7014 7015 7016 7017 7060 7061 7062 7063 7064 7065 7066 7050 LED5 LED5 LED6 LED6 LED6 LED6 LED1 LED2 LED3 LED4 LED5 LED6 CB CLOSED IND1 Reset In #3 In #4 In #1 In #2 In #3 In #4 Color Color Color Color Color Color Color LED Functions LED Functions LED Functions LED Functions LED Functions LED Functions LED Color LED Color LED Color LED Color LED Color LED Color LED Color IND1 Reset operation 7051 7030 IND2 Reset IND1 BIT1 IND1 Reset operation Virtual LED 7031 7032 7033 7034 7035 7036 IND1 IND1 IND1 IND1 IND1 IND1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Virtual LED Virtual LED Virtual LED Virtual LED Virtual LED Virtual LED 7037 7038 IND1 IND2 BIT8 BIT1 Virtual LED Virtual LED 7039 703A 703B 703C 703D 703E 703F 6800 IND2 IND2 IND2 IND2 IND2 IND2 IND2 Active gp. BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 BIT8 Virtual LED Virtual LED Virtual LED Virtual LED Virtual LED Virtual LED Virtual LED Active setting group 6803 6804 6805 6806 6807 AOLED Control Interlock Control Kind Frequency ALARM LED light control for alarm output Control enable Interlock enable Control Hierarchy (if Control = Enable) Frequency 217 6 F 2 T 0 1 7 6 Setting Group (Menu) Protection Address Name Contents Gr.1 Gr.2 4C00 4C01 4017 4000 4001 5C00 5C01 5017 5000 5001 PVT RVT SVCNT OV OV OV1EN OV2EN VT ratio Residual VT ratio AC input imbalance OV1 Enable OV2 Enable 4002 4003 4004 4005 4006 4007 4008 4009 400A 400B 400C 400D 400E 400F 5002 5003 5004 5005 5006 5007 5008 5009 500A 500B 500C 500D 500E 500F OV UV UV UV UV ZPS ZPS NPS NPS FRQ1 FRQ1 FRQ1 FRQ2 FRQ2 OV3EN UV1EN UV2EN UV3EN VBLK ZPS1EN ZPS2EN NPS1EN NPS2EN FT1 DFT1 Logic1 FT2 DFT2 OV3 Enable UV1 Enable UV2 Enable UV3 Enable UVBLOCK Enable ZPS1 Enable ZPS2 Enable NPS1 Enable NPS2 Enable FRQ1 Enable / Type DFRQ1 Enable / Type FRQ1 Logic FRQ2 Enable / Type DFRQ2 Enable / Type 4010 4011 4012 4013 4014 4015 5010 5011 5012 5013 5014 5015 FRQ2 FRQ3 FRQ3 FRQ3 FRQ4 FRQ4 Logic2 FT3 DFT3 Logic3 FT4 DFT4 FRQ2 Logic FRQ3 Enable / Type DFRQ3 Enable / Type FRQ3 Logic FRQ4 Enable / Type DFRQ4 Enable / Type 4016 4800 4803 4400 5016 5800 5803 5400 FRQ4 OV OV OV Logic4 OV1 TOV1 TOV1 FRQ4 Logic OV1 Threshold setting OV1 Time multiplier setting OV1 Definite time setting 4804 4805 4801 4816 4401 4817 4806 4802 4402 4807 4818 4819 481A 481B 5804 5805 5801 5816 5401 5817 5806 5802 5402 5807 5818 5819 581A 581B OV OV OV OV OV OV OV OV OV OV OV OV OV OV TOV1R OV1DPR OV2 TOV2 TOV2 TOV2R OV2DPR OV3 TOV3 OV3DPR OV1-k OV1-α OV1-C OV2-k 218 OV1 Definite time reset delay OV1 DO/PU ratio OV2 Threshold setting OV2 Time multiplier setting OV2 Definite time setting OV2 Definite time reset delay OV2 DO/PU ratio OV3 Threshold setting OV3 Definite time setting OV3 DO/PU ratio Configurable IDMT Curve setting of OV1 Configurable IDMT Curve setting of OV1 Configurable IDMT Curve setting of OV1 Configurable IDMT Curve setting of OV2 6 F 2 T 0 1 7 6 Setting Group (Menu) Protection Address Name Contents Gr.1 Gr.2 481C 481D 4808 480B 581C 581D 5808 580B OV OV UV UV OV2-α OV2-C UV1 TUV1 Configurable IDMT Curve setting of OV2 Configurable IDMT Curve setting of OV2 UV1 Threshold setting UV1 Time multiplier setting 4403 480C 4809 481E 4404 481F 480A 5403 580C 5809 581E 5404 581F 580A UV UV UV UV UV UV UV TUV1 TUV1R UV2 TUV2 TUV2 TUV2R UV3 UV1 Definite time setting UV1 Definite time reset delay UV2 Threshold setting UV2 Time multiplier setting UV2 Definite time setting UV2 Definite time reset delay UV2 Threshold setting 4405 480D 4820 4821 4822 4823 4824 5405 580D 5820 5821 5822 5823 5824 UV UV UV UV UV UV UV TUV3 VBLK UV1-k UV1-α UV1-C UV2-k UV2-α UV3 Definite time setting UV Block Threshold setting Configurable IDMT Curve setting of UV1 Configurable IDMT Curve setting of UV1 Configurable IDMT Curve setting of UV1 Configurable IDMT Curve setting of UV2 Configurable IDMT Curve setting of UV2 4825 480E 5825 580E UV ZPS UV2-C ZPS1 Configurable IDMT Curve setting of UV2 ZPS1 Threshold setting 4810 4406 4811 480F 4826 5810 5406 5811 580F 5826 ZPS ZPS ZPS ZPS ZPS TZPS1 TZPS1 TZPS1R ZPS2 TZPS2 ZPS1 Time multiplier setting ZPS1 Definite time setting ZPS1 Definite time reset delay ZPS2 Threshold setting ZPS2 Time multiplier setting 4407 4827 5407 5827 ZPS ZPS TZPS2 TZPS2R ZPS2 Definite time setting ZPS2 Definite time reset delay 4828 4829 5828 5829 ZPS ZPS ZPS 1-k ZPS 1-α Configurable IDMT Curve setting of ZPS1 Configurable IDMT Curve setting of ZPS1 482A 482B 482C 482D 582A 582B 582C 582D ZPS ZPS ZPS ZPS ZPS 1-C ZPS 2-k ZPS 2-α ZPS 2-C Configurable IDMT Curve setting of ZPS1 Configurable IDMT Curve setting of ZPS2 Configurable IDMT Curve setting of ZPS2 Configurable IDMT Curve setting of ZPS2 4812 4814 4408 4815 4813 482E 4409 482F 4830 4831 5812 5814 5408 5815 5813 582E 5409 582F 5830 5831 NPS NPS NPS NPS NPS NPS NPS NPS NPS NPS NPS1 TNPS1 TNPS1 TNPS1R NPS2 TNPS2 TNPS2 TNPS2R NPS 1-k NPS 1-α NPS1 Threshold setting NPS1 Time multiplier setting NPS1 Definite time setting NPS1 Definite time reset delay NPS2 Threshold setting NPS2 Time multiplier setting NPS2 Definite time setting NPS2 Definite time reset delay Configurable IDMT Curve setting of NPS1 Configurable IDMT Curve setting of NPS1 219 6 F 2 T 0 1 7 6 Setting Group (Menu) Protection Address Name Contents Gr.1 Gr.2 4832 4833 4834 4835 5832 5833 5834 5835 NPS NPS NPS NPS NPS 1-C NPS 2-k NPS 2-α NPS 2-C 4836 440A 4837 440B 4838 4839 440C 5836 540A 5837 540B 5838 5839 540C FRQ FRQ FRQ FRQ FRQ FRQ FRQ F11 TF11 F12 TF12 DF1 F21 TF21 F11 Threshold setting F11 Time delay setting F12 Threshold setting F12 Time delay setting DFRQ1 Threshold setting F21 Threshold setting F21 Time delay setting 483A 440D 483B 483C 440E 483D 440F 583A 540D 583B 583C 540E 583D 540F FRQ FRQ FRQ FRQ FRQ FRQ FRQ F22 TF22 DF2 F31 TF31 F32 TF32 F22 Threshold setting F22 Time delay setting DFRQ2 Threshold setting F31 Threshold setting F31 Time delay setting F32 Threshold setting F32 Time delay setting 483E 483F 583E 583F FRQ FRQ DF3 F41 DFRQ3 Threshold setting F41 Threshold setting 4410 4840 4411 4841 4842 5410 5840 5411 5841 5842 FRQ FRQ FRQ FRQ FRQ TF41 F42 TF42 DF4 FVBLK Configurable IDMT Curve setting of NPS1 Configurable IDMT Curve setting of NPS2 Configurable IDMT Curve setting of NPS2 Configurable IDMT Curve setting of NPS2 F41 Time delay setting F42 Threshold setting F42 Time delay setting DFRQ4 Threshold setting FRQ Block threshold setting 3. CB remote control To control the CB at remote site with the Modbus communication, do the following. ・Operation item - Remote control (CB on / off) - Change of interlock position - LED reset ・Operating procedure To control the CB at remote site with Modbus communication is require the following three steps. - Pass word authentication - Enable flag setting for remote control - Remote control CAUTION To control the CB at remote site, set the control hierarchy setting of relay to “Remote”. 220 6 F 2 T 0 1 7 6 A. Pass word authentication To authenticate the password, enter the password for control function to the address of “3E82” . The password is the same as that of control function. The password retention is 1 minute. If no password is set, please enter “0000” as password. The sending messages transmitted with ASCII code. Ex. “0000” -> “303030303” Message example (Relay address:01, Password:0000, need CRC frame) to relay 01103E8200020430303030 from relay 01103E820002 B. Enable flag setting for remote control To enable the remote control, turn on the address of “0200 : Remote control enable flag”. When the operation completed or time-out occurs, the flag is reset. Flag state can be checked in the command of “FC=01 Read Coils”. Message example to relay 02050200FF00 from relay 02050200FF00 C. Remote control To control the CB at remote site, turn on or off the address of “0400: Remote control command”, ”0401: Remote interlock command” or “0402: Remote reset command”. The “On” operation command is “FF00”. The “Off” operation command is “0000”. The operation reply is checked by the “BO” or “LED” signals according to the relay settings. Message example (Relay address:01、CB on, need CRC frame) to relay 01050400FF00 from relay 01050400FF00 Message example (Relay address:01、CB off, need CRC frame) to relay 010504000000 from relay 010504000000 221 6 F 2 T 0 1 7 6 Appendix M IEC60870-5-103: Interoperability 222 6 F 2 T 0 1 7 6 IEC60870-5-103: Interoperability 1. Physical Layer 1.1 Electrical interface: EIA RS-485 Number of devices, 32 for one protection equipment 1.2 Transmission speed User setting: 9600 or 19200 bit/s 2. Application Layer COMMON ADDRESS of ASDU (Application Service Data Unit) One COMMON ADDRESS OF ASDU (identical with station address) 3. IEC60870-5-103 Interface 3.1 Spontaneous events The events created by the relay will be sent using the Function type (FUN) / Information numbers (INF) to the IEC60870-5-103 master station. 8 wide-use events are provided. 3.2 General interrogation The GI request can be used to read the status of the relay, the Function types and Information numbers that will be returned during the GI cycle are shown in the table below. 3.3 Cyclic measurements The relay will produce measured values using Type ID=3 and 9 on a cyclical basis, this can be read from the relay using a Class 2 poll. The rate at which the relay produces new measured values is 2 seconds. It should be noted that the measurands transmitted by the relay are sent as a proportion of either 1.2 or 2.4 times the rated value of the analog value. Either 1.2 or 2.4 can be selected by the “IECNFV” and “IECNFf” settings. 3.4 Commands A list of the supported commands is contained in the table below. The relay will respond to other commands with an ASDU 1, with a cause of transmission (COT) of negative acknowledgement of a command. 3.5 Test mode In test mode, both spontaneous messages and polled measured values, intended for processing in the control system, are designated by means of the CAUSE OF TRANSMISSION ‘test mode’. This means that CAUSE OF TRANSMISSION = 7 ‘test mode’ is used for messages normally transmitted with COT=1 (spontaneous) or COT=2 (cyclic). For details, refer to the standard IEC60870-5-103. 3.6 Blocking of monitor direction If the blocking of the monitor direction is activated in the protection equipment, all indications and measurands are no longer transmitted. For details, refer to the standard IEC60870-5-103. 223 6 F 2 T 0 1 7 6 4. List of Information List of Information INF Description Contents GI Typ e ID COT FUN Standard Information numbers in monitor direction System Function 0 End of General Interrogation Transmission completion of GI items. -- 8 10 255 0 Time Synchronization Time Synchronization ACK. -- 6 8 255 2 Reset FCB Reset FCB(toggle bit) ACK -- 5 3 215 3 Reset CU Reset CU ACK -- 5 4 215 4 Start/Restart Relay start/restart -- 5 5 215 5 Power On Relay power on. Not supported Status Indications 16 Auto-recloser active 17 Teleprotection active 18 Protection active 19 LED reset If it is possible to use auto-recloser, this item is set active, if impossible, inactive. If protection using telecommunication is available, this item is set to active. If not, set to inactive. If the protection is available, this item is set to active. If not, set to inactive. Reset of latched LEDs Block the 103 transmission from a relay to control system. IECBLK: "Blocked" setting. Transmission of testmode situation froma relay to control system. IECTST: "ON" setting. When a setting change has done at the local, the event is sent to control system. Not supported Not supported GI 1 1, 7, 9, 12, 20 215 -- 1 7, 11, 12, 20 215 GI 1 9, 11 215 GI 1 9 215. 20 Monitor direction blocked 21 Test mode 22 Local parameter Setting 23 Characteristic1 Setting group 1 active GI 1 24 Characteristic2 Setting group 2 active GI 1 25 Characteristic3 Setting group 3 active Not supported 26 Characteristic4 Setting group 4 active Not supported 27 Auxiliary input1 User specified signal 1 (Signal specified by IECB1: ON) (*1) GI 1 1, 7, 9 215 28 Auxiliary input2 User specified signal 2 (Signal specified by IECB2: ON) (*1) GI 1 1, 7, 9 215 29 Auxiliary input3 User specified signal 3 (Signal specified by IECB3: ON) (*1) GI 1 1, 7, 9 215 30 Auxiliary input4 User specified signal 4 (Signal specified by IECB4: ON) (*1) GI 1 1, 7, 9 215 Not supported 7, 9, 11, 12, 20 7, 9, 11, 12, 20 215 215 Supervision Indications 32 Measurand supervision I Zero sequence current supervision 33 Measurand supervision V Zero sequence voltage supervision GI 1 Not supported 1, 7, 9 215 35 Phase sequence supervision Negative sequence voltage supevision GI 1 1, 7, 9 215 36 Trip circuit supervision Output circuit supervision GI 1 7, 9 215 37 I>>backup operation 38 VT fuse failure VT failure 39 Teleprotection disturbed CF(Communication system Fail) supervision 46 Group warning Only alarming GI 1 1, 7, 9 215 47 Group alarm Trip blocking and alarming GI 1 1, 7, 9 215 Not supported Not supported Not supported Earth Fault Indications 48 Earth Fault L1 A phase earth fault (*2) Not supported 49 Earth Fault L2 B phase earth fault (*2) Not supported 50 Earth Fault L3 C phase earth fault (*2) Not supported 51 Earth Fault Fwd Earth fault forward (*2) Not supported 52 Earth Fault Rev Earth fault reverse (*2) Not supported 224 6 F 2 T 0 1 7 6 INF Description Contents GI Typ e ID COT FUN Fault Indications 64 Start/pick-up L1 A phase, A-B phase or C-A phase element pick-up GI 2 1, 7, 9 215 65 Start/pick-up L2 B phase, A-B phase or B-C phase element pick-up GI 2 1, 7, 9 215 66 Start/pick-up L3 C phase, B-C phase or C-A phase element pick-up GI 2 1, 7, 9 215 67 Start/pick-up N Earth fault element pick-up GI 2 1, 7, 9 215 68 General trip BO status specified by IECGT: ON (*1) -- 2 1, 7 215 69 Trip L1 BO status specified by IECAT: ON (*1) -- 2 1, 7 215 70 Trip L2 BO status specified by IECBT: ON (*1) -- 2 1, 7 215 71 Trip L3 BO status specified by IECCT: ON (*1) -- 2 1, 7 215 72 Trip I>>(back-up) Back up trip Not supported 73 Fault location X In ohms Fault location (prim. [ohm] / second. [ohm] / km selectable by IECFL) Not supported 74 Fault forward/line Forward fault Not supported 75 Fault reverse/Busbar Reverse fault Not supported 76 Teleprotection Signal transmitted Carrier signal sending Not supported 77 Teleprotection Signal received Carrier signal receiving Not supported 78 Zone1 Zone 1 trip Not supported 79 Zone2 Zone 2 trip Not supported 80 Zone3 Zone 3 trip Not supported 81 Zone4 Zone 4 trip Not supported 82 Zone5 Zone 5 trip Not supported 83 Zone6 Zone 6 trip 84 General Start/Pick-up Any elements pick-up 85 Breaker Failure CBF trip or CBF retrip 86 Trip measuring system L1 Not supported 87 Trip measuring system L2 Not supported 88 Trip measuring system L3 Not supported 89 Trip measuring system E 90 Trip I> Inverse time OC trip (OC1 trip) Not supported 91 Trip I>> Definite time OC trip (OR logic of OC1 to OC3 trip) Not supported 92 Trip IN> Inverse time earth fault OC trip (OR logic of EF1 and SEF1 trip) Not supported 93 Trip IN>> Definite time earth fault OC trip (OR logic of EF1 to EF3 and SEF1 to SEF3 trip) Not supported CB close command output Not supported Not supported GI 2 1, 7, 9 Not supported Not supported Autoreclose indications 128 CB 'ON' by Autoreclose 129 CB 'ON' by long-time Autoreclose 130 Autoreclose Blocked Not supported Autoreclose block Not supported Note (*1): Not available if the setting is "0". (∗2): Not available when neither the EF nor SEF element is used. 225 215 6 F 2 T 0 1 7 6 INF Description Contents IECI1 User specified 1 Signal specified by IECE1: ON (*1) IECI2 User specified 2 Signal specified by IECE2: ON (*1) IECI3 User specified 3 Signal specified by IECE3: ON (*1) IECI4 User specified 4 Signal specified by IECE4: ON (*1) IECI5 User specified 5 Signal specified by IECE5: ON (*1) IECI6 User specified 6 Signal specified by IECE6: ON (*1) IECI7 User specified 7 Signal specified by IECE7: ON (*1) IECI8 User specified 8 Signal specified by IECE8: ON (*1) GI IECG1 (yes/no) IECG2 (yes/no) IECG3 (yes/no) IECG4 (yes/no) IECG5 (yes/no) IECG6 (yes/no) IECG7 (yes/no) IECG8 (yes/no) Typ e ID COT FUN 2 1, 7 215 2 1, 7 215 2 1, 7 215 2 1, 7 215 2 1, 7 215 2 1, 7 215 2 1, 7 215 2 1, 7 215 Measurands(*3) 144 Measurand I <meaurand I> 145 Measurand I,V Vb measurand <meaurand I> -- Not supported 3.2 2, 7 146 Measurand I,V,P,Q Vb measurand <meaurand I> -- 3.3 2, 7 215 147 Measurand IN,VEN Ve measurand <meaurand I> -- 3.4 2, 7 215 148 Measurand IL1,2,3, VL1,2,3, P,Q,f Va, Vb, Vc measurand <meaurand II> -- 3 2, 7 215 215 Generic Function 240 Read Headings Not supported 241 Read attributes of all entries of a group Not supported 243 Read directory of entry Not supported 244 Real attribute of entry Not supported 245 End of GGI Not supported 249 Write entry with confirm Not supported 250 Write entry with execute Not supported 251 Write entry aborted Not supported Note (∗3): depends upon the relay model as follows: Model Model 410 Model Model 410 Type ID=3.1 (INF=144) IL2 0 Type ID=9 (INF=148) IL1 0 Type ID=3.2 Type ID=3.3 Type ID=3.4 (INF=145) (INF=146) (INF=147) IL2 VL1-VL2 IL2 VL1-VL2 3-phase P 3-phase Q IN 0 Vab 0 Vab 0 0 0 IL2 0 IL3 0 VL1 Va VL2 Vb Above values are normalized by IECNF∗. 226 VL3 Vc 3-phase P 3-phase Q 0 0 VEN Ve f f 6 F 2 T 0 1 7 6 INF Description Contents COM Typ e ID -- 7 9 215 -- 6 8 215 COT FUN Selection of standard information numbers in control direction System functions Initiation of general 0 interrogation 0 Time synchronization General commands 16 Auto-recloser on/off 17 Teleprotection on/off Not supported 18 Protection on/off (*4) 19 LED reset 23 Not supported ON/OFF 20 20 215 Reset indication of latched LEDs. ON 20 20 215 Activate characteristic 1 Setting Group 1 ON 20 20 215 24 Activate characteristic 2 Setting Group 2 ON 20 20 215 25 Activate characteristic 3 Setting Group 3 Not supported 26 Activate characteristic 4 Setting Group 4 Not supported Generic functions Read headings of all defined 240 groups Read values or attributes of all 241 entries of one group 243 244 245 Not supported Not supported Read directory of a single entry Not supported Read values or attributes of a single entry General Interrogation of generic data Not supported Not supported 248 Write entry Not supported 249 Write entry with confirmation Not supported 250 Write entry with execution Not supported 251 Write entry abort Not supported Note (∗4): When the relay is receiving the "Protection off" command, the " IN SERVICE LED" is off. Description Contents GRE130 supported Comment Basic application functions Test mode Yes Blocking of monitor direction Yes Disturbance data No Generic services No Private data No Miscellaneous Max. MVAL = rated value times Measurand Current L1 Ia No Current L2 Ib No Current L3 Ic No Voltage L1-E Va 1,2 or 2,4 IECNFV setting Voltage L2-E Vb 1,2 or 2,4 IECNFV setting IECNFV setting Voltage L3-E Vc 1,2 or 2,4 Active power P P No Reactive power Q Q No Frequency f f 1,2 or 2,4 IECNFf setting Voltage L1 - L2 Vab 1,2 or 2,4 IECNFV setting 227 6 F 2 T 0 1 7 6 [Legend] GI: General Interrogation Type ID: Type Identification (refer to IEC60870-5-103 section 7.2.1) 1 : time-tagged message 2 : time-tagged message with relative time 3 : measurands I 4 : time-tagged measurands with relative time 5 : identification 6 : time synchronization 8 : general interrogation termination 9 : measurands II 10: generic data 11: generic identification 20: general command 23: list of recorded disturbances 26: ready for transmission for disturbance data 27: ready for transmission of a channel 28: ready for transmission of tags 29: transmission of tags 30: transmission of disturbance values 31: end of transmission COT: Cause of Transmission (refer to IEC60870-5-103 section 7.2.3) 1: spontaneous 2: cyclic 3: reset frame count bit (FCB) 4: reset communication unit (CU) 5: start / restart 6: power on 7: test mode 8: time synchronization 9: general interrogation 10: termination of general interrogation 11: local operation 12: remote operation 20: positive acknowledgement of command 21: negative acknowledgement of command 31: transmission of disturbance data 40: positive acknowledgement of generic write command 41: negative acknowledgement of generic write command 42: valid data response to generic read command 43: invalid data response to generic read command 44: generic write confirmation 228 6 F 2 T 0 1 7 6 Appendix P IEC61850: Interoperability 229 6 F 2 T 0 1 7 6 1. IEC61850 Documentation IEC61850 Model Implementation Conformance Statement (MICS) for GRE130 The GRE130 relay supports IEC 61850 logical nodes and common data classes as indicated in the following tables. Logical nodes in IEC 61850-7-4 Logical Nodes GRE130 L: System Logical Nodes LPHD Yes Common Logical Node Yes LLN0 Yes P: Logical Nodes for Protection functions PDIF --PDIR --PDIS --PDOP --PDUP --PFRC Yes PHAR --PHIZ --PIOC --PMRI --PMSS --POPE --PPAM --PSCH --PSDE --PTEF --PTOC --PTOF Yes PTOV Yes PTRC Yes PTTR --PTUC --PTUV Yes PUPF --PTUF Yes PVOC --PVPH --PZSU --R: Logical Nodes for protection related functions RDRE --RADR --RBDR --RDRS --RBRF --RDIR --RFLO --RPSB --RREC --RSYN --C: Logical Nodes for Control 230 6 F 2 T 0 1 7 6 Logical Nodes GRE130 CALH --CCGR --CILO Yes CPOW --CSWI Yes G: Logical Nodes for Generic references GAPC --GGIO Yes GGIO (for GOOSE) Yes GSAL --I: Logical Nodes for Interfacing and archiving IARC --IHMI --ITCI --ITMI --A: Logical Nodes for Automatic control ANCR --ARCO --ATCC --AVCO --M: Logical Nodes for Metering and measurement MDIF --MHAI --MHAN --MMTR --MMXN --MMXU Yes MSQI Yes MSTA --S: Logical Nodes for Sensors and monitoring SARC --SIMG --SIML --SPDC --X: Logical Nodes for Switchgear XCBR Yes XSWI --T: Logical Nodes for Instrument transformers TCTR --TVTR --Y: Logical Nodes for Power transformers YEFN --YLTC --YPSH --YPTR --Z: Logical Nodes for Further power system equipment ZAXN --ZBAT --ZCAB --ZCAP --ZCON --- 231 6 F 2 T 0 1 7 6 Logical Nodes ZGEN ZGIL ZLIN ZMOT ZREA ZRRC ZSAR ZTCF ZTCR GRE130 ------------------- Common data classes in IEC61850-7-3 Common data classes Status information SPS DPS INS ACT ACD SEC BCR Measured information MV CMV SAV WYE DEL SEQ HMV HWYE HDEL Controllable status information SPC DPC INC BSC ISC Controllable analogue information APC Status settings SPG ING Analogue settings ASG CURVE Description information DPL LPL CSD 232 GRE130 Yes --Yes Yes Yes ----Yes Yes --Yes Yes Yes ------Yes Yes Yes --------Yes Yes --Yes Yes --- 6 F 2 T 0 1 7 6 LPHD class Attribute Name LNName Data PhyName PhyHealth OutOv Proxy InOv NumPwrUp WrmStr WacTrg PwrUp PwrDn PwrSupAlm RsStat Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) M/O GRE130 DPL INS SPS SPS SPS INS INS INS SPS SPS SPS SPC M M O M O O O O O O O O Physical device name plate Physical device health Output communications buffer overflow Indicates if this LN is a proxy Input communications buffer overflow Number of Power ups Number of Warm Starts Number of watchdog device resets detected Power Up detected Power Down detected External power supply alarm Reset device statistics T Common Logical Node class Attribute Name Attr. Type Explanation T LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2) Data Mandatory Logical Node Information (Shall be inherited by ALL LN but LPHD) Mod Beh Health NamPlt INC INS INS LPL Mode Behaviour Health Name plate Optional Logical Node Information Loc SPS Local operation EEHealth INS External equipment health EEName DPL External equipment name plate OpCntRs INC Operation counter resetable OpCnt INS Operation counter OpTmh INS Operation time Data Sets (see IEC 61850-7-2) Inherited and pecialized from Logical Node class (see IEC 61850-7-2) Control Blocks (see IEC 61850-7-2) Inherited and pecialized from Logical Node class (see IEC 61850-7-2) Services (see IEC 61850-7-2) Inherited and pecialized from Logical Node class (see IEC 61850-7-2) LLNO class Attribute Name LNName Data Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) Common Logical Node Information Loc OpTmh SPS INS LN shall inherit all Mandatory Data from Common Logical Node Class Local operation for complete logical device Operation time Diag LEDRs SPC SPC Run Diagnostics LED reset Controls T 233 Y Y N Y N N N N N N N N M/O GRE130 M M M M Y Y Y Y O O O O O O N N N N N N M/O GRE130 M Y O O Y N O O Y Y 6 F 2 T 0 1 7 6 PFRC class Attribute Name LNName Data Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) Common Logical Node Information M/O GRE130 M Y O N M M O Y Y Y OpCntRs INC LN shall inherit all Mandatory Data from Common Logical Node Class Resetable operation counter Str Op BlkV ACD ACT SPS Start Operate Blocked because of voltage StrVal BlkVal OpDlTmms RsDlTmms ASG ASG ING ING Start Value df/dt Voltage Block Value Operate Delay Time Reset Delay Time O O O O Y Y N N Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) M/O GRE130 M Y O N M M O Y Y Y Status Information Settings PTOF class Attribute Name LNName Data T Common Logical Node Information OpCntRs INC LN shall inherit all Mandatory Data from Common Logical Node Class Resetable operation counter Str Op BlkV ACD ACT SPS Start Operate Blocked because of voltage StrVal BlkVal OpDITmms RsDITmms ASG ASG ING ING Start Value (frequency) Voltage Block Value Operate Delay Time Reset Delay Time O O O O Y Y Y N Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) M/O GRE130 M Y O N M O O Y Y N O O O O O O O N Y N N N Y N Status Information Settings PTOV class Attribute Name LNName Data T Common Logical Node Information OpCntRs INC LN shall inherit all Mandatory Data from Common Logical Node Class Resetable operation counter Str Op TmVSt ACD ACT CSD Start Operate Active curve characteristic TmVCrv StrVal TmMult MinOpTmms MaxOpTmms OpDlTmms RsDlTmms CURVE ASG ASG ING ING ING ING Operating Curve Type Start Value Time Dial Multiplier Minimum Operate Time Maximum Operate Time Operate Delay Time Reset Delay Time Status Information Settings 234 T 6 F 2 T 0 1 7 6 PTRC class Attribute Name LNName Data Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) M/O GRE130 LN shall inherit all Mandatory Data from Common Logical Node Class Resetable operation counter M Y O N C C Y N O N Common Logical Node Information OpCntRs INC Tr Op ACT ACT Str ACD Trip Operate (combination of subscribed Op from functions) Sum of all starts of all connected Logical Nodes TrMod TrPlsTmms ING ING Trip Mode Trip Pulse Time O O N N Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) M/O GRE130 M Y O N M M O Y Y N Status Information Settings protection Condition C: At least one of the two status information (Tr, Op) shall be used. PTUV class Attribute Name LNName Data Common Logical Node Information OpCntRs INC LN shall inherit all Mandatory Data from Common Logical Node Class Resetable operation counter Str Op TmVSt ACD ACT CSD Start Operate Active curve characteristic TmVCrv StrVal TmMult MinOpTmms MaxOpTmms OpDlTmms RsDlTmms CURVE ASG ASG ING ING ING ING Operating Curve Type Start Value Time Dial Multiplier Minimum Operate Time Maximum Operate Time Operate Delay Time Reset Delay Time O O O O O O O N Y N N N Y N Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) M/O GRE130 M Y O N M M O Y Y Y O O O O Y Y Y N Status Information Settings PTUF class Attribute Name LNName Data T Common Logical Node Information OpCntRs INC LN shall inherit all Mandatory Data from Common Logical Node Class Resetable operation counter Str Op BlkV ACD ACT SPS Start Operate Blocked because of voltage StrVal BlkVal OpDlTmms RsDlTmms ASG ASG ING ING Start Value (frequency) Voltage Block Value Operate Delay Time Reset Delay Time Status Information Settings 235 T 6 F 2 T 0 1 7 6 CILO class Attribute Name LNName Data Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) M/O GRE130 LN shall inherit all Mandatory Data from Common Logical Node Class M Y Enable Open Enable Close M M Y Y M/O GRE130 M Y O O N N M O O O O O Y N N N N N M/O GRE130 M Y O O O O N N N N Common Logical Node Information Status Information EnaOpn EnaCls SPS SPS CSWI class Attribute Name LNName Data Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) Common Logical Node Information Loc OpCntRs SPS INC LN shall inherit all Mandatory Data from Common Logical Node Class Local operation Resetable operation counter Pos PosA PosB PosC OpOpn OpCls DPC DPC DPC DPC ACT ACT Switch, general Switch L1 Switch L2 Switch L3 Operation “Open Switch” Operation “Close Switch” GGIO class Attribute Name LNName Data Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) Controls Common Logical Node Information T T EEHealth EEName Loc OpCntRs INS DPL SPS INC LN shall inherit all Mandatory Data from Common Logical Node Class External equipment health (external sensor) External equipment name plate Local operation Resetable operation counter AnIn MV Analogue input O N SPCSO DPCSO ISCSO SPC DPC INC Single point controllable status output Double point controllable status output Integer status controllable status output O O O N N N IntIn Alm Ind01 Ind02 Ind03 Ind04 Ind05 Ind06 Ind07 Ind08 Ind09 Ind10 ::: INS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS Integer status input General single alarm General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) O O O O O O O O O O O O N N Y Y Y Y Y Y Y Y Y Y Ind32 SPS General indication (binary input) O Y Measured values Controls Status Information 236 6 F 2 T 0 1 7 6 GGIO (for GOOSE) class Attribute Name Attr. Type Explanation T LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2) Data Common Logical Node Information M/O GRE130 M Y O O O O N N N N EEHealth EEName Loc OpCntRs INS DPL SPS INC LN shall inherit all Mandatory Data from Common Logical Node Class External equipment health (external sensor) External equipment name plate Local operation Resetable operation counter AnIn MV Analogue input O N SPCSO DPCSO ISCSO SPC DPC INC Single point controllable status output Double point controllable status output Integer status controllable status output O O O N N N IntIn Alm Ind01 Ind02 Ind03 Ind04 Ind05 Ind06 Ind07 Ind08 Ind09 Ind10 Ind11 Ind12 Ind13 Ind14 Ind15 Ind16 INS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS Integer status input General single alarm General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) O O O O O O O O O O O O O O O O O O N N Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y MMXU class Attribute Name LNName Data Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) M/O GRE130 M Y O N O O O O O O O O O O O O O N N N N Y Y Y N N N N N N Measured values Controls Status Information Common Logical Node Information EEHealth INS LN shall inherit all Mandatory Data from Common Logical Node Class External equipment health (external sensor) TotW TotVAr TotVA TotPF Hz PPV PhV A W VAr VA PF Z MV MV MV MV MV DEL WYE WYE WYE WYE WYE WYE WYE Total Active Power (Total P) Total Reactive Power (Total Q) Total Apparent Power (Total S) Average Power factor (Total PF) Frequency Phase to phase voltages (VL1VL2, …) Phase to ground voltages (VL1ER, …) Phase currents (IL1, IL2, IL3) Phase active power (P) Phase reactive power (Q) Phase apparent power (S) Phase power factor Phase Impedance Measured values 237 6 F 2 T 0 1 7 6 MSQI class Attribute Name LNName Data Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) Common Logical Node Information M/O GRE130 M Y O O N N EEHealth EEName INS DPL LN shall inherit all Mandatory Data from Common Logical Node Class External equipment health (external sensor) External equipment name plate SeqA SeqV DQ0Seq ImbA ImbNgA ImbNgV ImbPPV ImbV ImbZroA ImbZroV MaxImbA MaxImbPPV MaxImbV SEQ SEQ SEQ WYE MV MV DEL WYE MV MV MV MV MV Positive, Negative and Zero Sequence Current Positive, Negative and Zero Sequence Voltage DQ0 Sequence Imbalance current Imbalance negative sequence current Imbalance negative sequence voltage Imbalance phase-phase voltage Imbalance voltage Imbalance zero sequence current Imbalance zero sequence voltage Maximum imbalance current Maximum imbalance phase-phase voltage Maximum imbalance voltage C C O O O O O O O O O O O N Y N N N N N N N N N N N Attr. Type Explanation T Shall be inherited from Logical-Node Class (see IEC 61850-7-2) M/O GRE130 M Y O O M N N Y Measured values Condition C: At least one of either data shall be used. XCBR class Attribute Name LNName Data Common Logical Node Information EEHealth EEName OpCnt INS DPL INS LN shall inherit all Mandatory Data from Common Logical Node Class External equipment health (external sensor) External equipment name plate Operation counter Pos BlkOpn BlkCls ChaMotEna DPC SPC SPC SPC Switch position Block opening Block closing Charger motor enabled M M M O Y Y Y N SumSwARs BCR Sum of Switched Amperes, resetable O N CBOpCap POWCap MaxOpCap INS INS INS Circuit breaker operating capability Point On Wave switching capability Circuit breaker operating capability when fully charged M O O Y N N Controls Metered Values Status Information 238 6 F 2 T 0 1 7 6 SPS class Attribute Name DataName DataAttribute status Attribute Type FC Value/Value Range BOOLEAN Quality TimeStamp ST ST ST subEna subVal subQ subID BOOLEAN BOOLEAN Quality VISIBLE STRING64 SV SV SV SV configuration, description and extension dchg qchg TRUE | FALSE TRUE | FALSE d VISIBLE STRING255 DC dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 13 (see IEC 61850-7-3) Text INS class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute status stVal q t INT32 Quality TimeStamp ST ST ST subEna subVal subQ subID BOOLEAN INT32 Quality VISIBLE STRING64 SV SV SV SV Substitution M/O/C GRE130 M M M Y Y Y PICS_SUBST PICS_SUBST PICS_SUBST PICS_SUBST N N N N O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M N N N N N Inherited from Data Class (see IEC 61850-7-2) stVal q t substitution TrgOp configuration, description and extension d VISIBLE STRING255 DC dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 13 (see IEC 61850-7-3) dchg qchg Text 239 M/O/C GRE130 M M M Y Y Y PICS_SUBST PICS_SUBST PICS_SUBST PICS_SUBST N N N N O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M N N N N N 6 F 2 T 0 1 7 6 ACT class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute status general phsA phsB phsC neut q t BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN Quality TimeStamp configuration, description and extension ST ST ST ST ST ST ST dchg dchg dchg dchg dchg qchg operTm TimeStamp CF d VISIBLE STRING255 DC dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 13 (see IEC 61850-7-3) Text ACD class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute status general dirGeneral BOOLEAN ENUMERATED ST ST dchg dchg phsA dirPhsA BOOLEAN ENUMERATED ST ST dchg dchg phsB dirPhsB BOOLEAN ENUMERATED ST ST dchg dchg phsC dirPhsC BOOLEAN ENUMERATED ST ST dchg dchg neut dirNeut BOOLEAN ENUMERATED ST ST dchg dchg q t Quality TimeStamp ST ST qchg configuration, description and extension d VISIBLE STRING255 DC dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 13 (see IEC 61850-7-3) unknown | forward backward | both M/O/C GRE130 M O O O O M M Y Y Y Y Y Y Y O O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M N N N N N N M/O/C GRE130 M |M Y Y unknown backward | forward GC_2 (1) |GC_2 (1) Y Y unknown backward | forward GC_2 (2) |GC_2 (2) Y Y unknown backward | forward GC_2 (3) |GC_2 (3) Y Y unknown backward | forward GC_2 (4) |GC_2 (4) Y Y Text 240 M M Y Y O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M N N N N N 6 F 2 T 0 1 7 6 MV class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute measured values instMag mag range AnalogueValue AnalogueValue ENUMERATED MX MX MX q t Quality TimeStamp MX MX subEna subVal subQ subID BOOLEAN AnalogueValue Quality VISIBLE STRING64 SV SV SV SV substitution configuration, description and extension units Unit CF db INT32U CF zeroDb INT32U CF sVC ScaledValueConfig CF rangeC RangeConfig CF smpRate INT32U CF d VISIBLE STRING255 DC dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 21 (see IEC 61850-7-3) dchg dchg qchg M/O/C O M normal | high | low | high-high |O low-low |… M M see Annex A 0 … 100 000 0 … 100 000 Text 241 GRE130 N Y N Y Y PICS_SUBST PICS_SUBST PICS_SUBST PICS_SUBST N N N N O O O AC_SCAV GC_CON O O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M Y N N Y N N N N N N N 6 F 2 T 0 1 7 6 CMV class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute measured values instCVal cVal range Vector Vector ENUMERATED MX MX MX q t Quality TimeStamp MX MX subEna subVal subQ subID BOOLEAN Vector Quality VISIBLE STRING64 SV SV SV SV substitution configuration, description and extension O M normal | high | low | high-high |O low-low |… M M dchg dchg qchg units Unit CF db INT32U CF zeroDb INT32U CF rangeC RangeConfig CF magSVC ScaledValueConfig CF angSVC ScaledValueConfig CF angRef ENUMERATED CF smpRate INT32U CF d VISIBLE STRING255 DC dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 21 (see IEC 61850-7-3) WYE class Attribute Name DataName Data phsA phsB phsC neut net res DataAttribute Attribute Type see Annex A 0 … 100 000 0 … 100 000 V | A | other … Text TrgOp Value/Value Range GRE130 N Y N Y Y PICS_SUBST PICS_SUBST PICS_SUBST PICS_SUBST N N N N O O O GC_CON AC_SCAV AC_SCAV O O O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M Y N N N Y N N N N N N N N M/O/C GRE130 GC_1 GC_1 GC_1 GC_1 GC_1 GC_1 Y Y Y Y N N Inherited from Data Class (see IEC 61850-7-2) CMV CMV CMV CMV CMV CMV configuration, description and extension angRef FC M/O/C ENUMERATED CF d VISIBLE STRING255 DC dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 21 (see IEC 61850-7-3) Va | Vb | Vc | Aa | Ab | Ac | VabO | Vbc | Vca | Vother | Aother Text O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M 242 N N N N N N 6 F 2 T 0 1 7 6 DEL class Attribute Name DataName Data phsAB phsBC phsCA DataAttribute Attribute Type TrgOp CMV CMV CMV ENUMERATED CF d VISIBLE STRING255 DC dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 21 (see IEC 61850-7-3) SEQ class Attribute Name DataName Data c1 c2 c3 DataAttribute Attribute Type M/O/C GRE130 GC_1 GC_1 GC_1 Y Y Y FC TrgOp Va | Vb | Vc | Aa | Ab | Ac | VabO | Vbc | Vca | Vother | Aother Text O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M N Value/Value Range M/O/C GRE130 M M M Y Y Y pos-neg-zero | dir-quad-zero M Y A|B|C|… Text O O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M N N N N N N N N N N N Inherited from Data Class (see IEC 61850-7-2) CMV CMV CMV measured attributes seqT Value/Value Range Inherited from Data Class (see IEC 61850-7-2) configuration, description and extension angRef FC ENUMERATED configuration, description and extension MX phsRef ENUMERATED CF d VISIBLE STRING255 DC dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 21 (see IEC 61850-7-3) 243 6 F 2 T 0 1 7 6 SPC class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute control and status ctlVal operTm origin ctlNum SBO BOOLEAN TimeStamp Originator_RO INT8U_RO VISIBLE STRING65 CO CO CO, ST CO, ST CO SBOw SBOW CO Oper Cancel Oper Cancel CO CO stVal q t stSeld BOOLEAN Quality TimeStamp BOOLEAN ST ST ST ST subEna subVal subQ subID BOOLEAN BOOLEAN Quality VISIBLE STRING64 SV SV SV SV Substitution configuration, description and extension off (FALSE) | on (TRUE) 0..255 dchg qchg FALSE | TRUE dchg FALSE | TRUE pulseConfig PulseConfig CF CtlModel CtlModels CF sboTimeout INT32U CF sboClass SboClasses CF d VISIBLE STRING255 DC Text dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 31 (see IEC 61850-7-3) and Table E.2 (see IEC 61850-8-1) 244 M/O/C GRE130 AC_CO_M N AC_CO_O N AC_CO_O N AC_CO_O N AC_CO_SBO_N_ N M AC_CO_SBOW_E N _M AC_CO _M Y AC_CO_SBO_N_ N M and AC_CO_SBOW_E _M and AC_CO_TA_E_M AC_ST Y AC_ST Y AC_ST Y AC_CO_O N PICS_SUBST PICS_SUBST PICS_SUBST PICS_SUBST N N N N AC_CO_O M AC_CO_O AC_CO_O O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M N Y N N N N N N N 6 F 2 T 0 1 7 6 DPC class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute control and status ctlVal operTm origin ctlNum SBO BOOLEAN TimeStamp Originator INT8U VISIBLE STRING65 CO CO CO, ST CO, ST CO SBOw SBOW CO Oper Cancel Oper Cancel CO CO stVal CODED ENUM ST dchg q t stSeld Quality TimeStamp BOOLEAN ST ST ST qchg subEna subVal BOOLEAN CODED ENUM SV SV subQ subID Quality VISIBLE STRING64 SV SV substitution configuration, description and extension M/O/C GRE130 off (FALSE) | on (TRUE) dchg AC_CO_M N AC_CO_O N AC_CO_O N 0..255 AC_CO_O N AC_CO_SBO_N_ Y M AC_CO_SBOW_E N _M AC_CO _M Y AC_CO_SBO_N_ Y M and AC_CO_SBOW_E _M and AC_CO_TA_E_M intermediate-state | off | on |M Y bad-state M Y M Y AC_CO_O N PICS_SUBST intermediate-state | off | on |PICS_SUBST bad-state PICS_SUBST PICS_SUBST pulseConfig PulseConfig CF ctlModel CtlModels CF sboTimeout INT32U CF sboClass SboClasses CF d VISIBLE STRING255 DC Text dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 31 (see IEC 61850-7-3) and Table E.3 (see IEC 61850-8-1) 245 AC_CO_O M AC_CO_O AC_CO_O O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M N N N N N Y Y N N N N N N 6 F 2 T 0 1 7 6 INC class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute control and status ctlVal operTm origin ctlNum SBO INT32 TimeStamp Originator INT8U VISIBLE STRING65 CO CO CO, ST CO, ST CO SBOw SBOW CO Oper Cancel Oper Cancel CO CO stVal Q t stSeld INT32 Quality TimeStamp BOOLEAN ST ST ST ST subEna subVal subQ subID BOOLEAN INT32 Quality VISIBLE STRING64 SV SV SV SV substitution configuration, description and extension 0..255 dchg qchg dchg FALSE | TRUE CtlModel CtlModels CF sboTimeout INT32U CF sboClass SboClasses CF minVal INT32 CF maxVal INT32 CF stepSize INT32U CF 1 … (maxVal – minVal) D VISIBLE STRING255 DC Text dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 31 (see IEC 61850-7-3) and Table E.4 (see IEC 61850-8-1) 246 M/O/C GRE130 AC_CO_M N AC_CO_O N AC_CO_O N AC_CO_O N AC_CO_SBO_N_ N M AC_CO_SBOW_E N _M AC_CO _M N AC_CO_SBO_N_ N M and AC_CO_SBOW_E _M and AC_CO_TA_E_M M Y M Y M Y AC_CO_O N PICS_SUBST PICS_SUBST PICS_SUBST PICS_SUBST N N N N M AC_CO_O AC_CO_O O O O O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M Y N N N N N N N N N N 6 F 2 T 0 1 7 6 ING class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute setting setVal setVal INT32 INT32 configuration, description and extension SP SG, SE minVal INT32 CF maxVal INT32 CF stepSize INT32U CF d VISIBLE STRING255 DC dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 39 (see IEC 61850-7-3) 1 … (maxVal – minVal) Text ASG class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute setting setMag setMag AnalogueValue AnalogueValue configuration, description and extension SP SG, SE units Unit CF sVC ScaledValueConfig CF minVal AnalogueValue CF maxVal AnalogueValue CF stepSize AnalogueValue CF d VISIBLE STRING255 DC dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 42 (see IEC 61850-7-3) see Annex A 1 … (maxVal – minVal) Text DPL class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute configuration, description and extension vendor VISIBLE STRING255 DC hwRev VISIBLE STRING255 DC swRev VISIBLE STRING255 DC serNum VISIBLE STRING255 DC model VISIBLE STRING255 DC location VISIBLE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 45 (see IEC 61850-7-3) 247 M/O/C GRE130 AC_NSG_M AC_SG_M Y N O O O O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M N N N N N N N N M/O/C GRE130 AC_NSG_M AC_SG_M Y N O AC_SCAV O O O O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M Y Y N N N N N N N N M/O/C GRE130 M O O O O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M Y N N N N N N N N 6 F 2 T 0 1 7 6 LPL class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute configuration, description and extension vendor swRev d dU configRev ldNs VISIBLE STRING255 VISIBLE STRING255 VISIBLE STRING255 UNICODE STRING255 VISIBLE STRING255 VISIBLE STRING255 DC DC DC DC DC EX lnNs VISIBLE STRING255 EX cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 45 (see IEC 61850-7-3) Logical nodes for GRE130 Logical Nodes PFRC PFRC1 PFRC2 PFRC3 PFRC4 PTOF PTOF1 PTOF2 PTOF3 PTOF4 PTOV PTOV11 PTOV12 PTOV13 PTOV21 PTOV22 PTOV31 PTOV32 PTRC PTRC1 PTUV PTUV11 PTUV12 PTUV13 PTUF PTUF1 PTUF2 PTUF3 PTUF4 M/O/C M M M O AC_LN0_M shall be included in LLN0 AC_LN0_EX only; for example "IEC 61850-7-4:2003" AC_DLD_M AC_DLNDA_M AC_DLNDA_M AC_DLN_M Relay Element FRQ (Setting) FRQ (Setting) FRQ (Setting) FRQ (Setting) FRQ (Setting) FRQ (Setting) FRQ (Setting) FRQ (Setting) OV1 OV2 OV3 ZPS1 ZPS2 NPS1 NPS2 General Trip UV1 UV2 UV3 FRQ (Setting) FRQ (Setting) FRQ (Setting) FRQ (Setting) 248 GRE130 Y Y Y N Y Y N N N N 6 F 2 T 0 1 7 6 IEC61850 ACSI Conformance Statement for GRE series IED ・NTRODUCTION This document specifies the Protocol Implementation Conformance Statement (PICS) of the IEC 61850 interface in GRE series IED with communication firmware MVM850-01 series. Together with the MICS, the PICS forms the basis for a conformance test according to IEC 61850-10. ・CONTENTS OF THIS DOCUMENT Each tables of this document is specified in IEC 61850-7-2 Annex A.3 “ACSI models conformance statement”. 249 6 F 2 T 0 1 7 6 Client-server roles B11 Server side (of TWO-PARTYAPPLICATION-ASSOCIATION) B12 Client side of (TWO-PARTYAPPLICATION-ASSOCIATION) SCSMs supported B21 SCSM: IEC61850-8-1 used B22 SCSM: IEC61850-9-1 used B23 SCSM: IEC61850-9-2 used B24 SCSM: other Generic substation event model (GSE) B31 Publisher side B32 Subscriber side Transmission of sampled value model (SVC) B41 Publisher side B42 Subscriber side If Server side (B11) supported M1 Logical device M2 Logical node M3 Data M4 Data set M5 Substitution M6 Setting group control Reporting M7 Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 GI M8 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion M8-4 data-set-name M8-5 data-reference M8-6 BufTm M8-7 IntgPd M8-8 GI Logging M9 Log control M9-1 IntgPd M10 Log M11 Control If GSE (B31/B32) is supported GOOSE M12-1 entryID M12-2 DataRefInc M13 GSSE If SVC (B41/B42) is supported M14 Multicast SVC M15 Unicast SVC M16 Time M17 File Transfer Server S1 GetServerDirectory Client/ subscriber Server/ publisher IED - c1 Y c1 - - Y N N O O - Y Y O O - N N c2 c3 c4 c5 O O c2 c3 c4 c5 O O Y Y Y Y N Y O O O O O O O O O M O M Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y N N N N Y O O Y O O N O O M O O O M O N N Y N M Y 250 Remarks 6 F 2 T 0 1 7 6 Application association S2 Associate S3 Abort S4 Release Logical device S5 GetLogicalDeviceDirectory Logical node S6 GetLogicalNodeDirectory S7 GetAllDataValues Data S8 GetDataValues S9 SetDataValues S10 GetDataDirectory S11 GetDataDefinition Data set S12 GetDataSetValues S13 SetDataSetValues S14 CreateDataSet S15 DeleteDataSet S16 GetDataSetDirectory Substitution S17 SetDataValues Setting group control S18 SelectActiveSG S19 SelectEditSG S20 SetSGValues S21 ConfirmEditSGValues S22 GetSGValues S23 GetSGCBValues Reporting Buffered report control block (BRCB) S24 Report S24-1 data-change (dchg) S24-2 quality-change (qchg) S24-3 data-update (dupd) S25 GetBRCBValues S26 SetBRCBValues Unbuffered report control block (URCB) S27 Report S27-1 data-change (dchg) S27-2 quality-change (qchg) S27-3 data-update (dupd) S28 GetURCBValues S29 SetURCBValues Logging Log control block S30 GetLCBValues S31 SetLCBValues Log S32 QueryLogByTime S33 QueryLogAfter S34 GetLogStatusValues Generic substation event model (GSE) GOOSE-CONTROL-BLOCK S35 SendGOOSEMessage S36 GetGoReference S37 GetGOOSEElementNumber S38 GetGoCBValues S39 SetGoCBValues GSSE-CONTROL-BLOCK S40 SendGSSEMessage S41 GetGsReference S42 GetGSSEDataOffset S43 GetGsCBValues S44 SetGsCBValues M M M M M M Y Y Y M M Y M O M M Y Y M O O O M O M M Y N Y Y O O O O O M O O O O Y N N N Y M M N O O O O O O O O O O O O Y N N N N Y c6 c6 c6 c6 c6 c6 Y Y Y N Y Y c6 c6 c6 c6 c6 c6 Y Y Y N Y Y M O M M N N c7 c7 M M M M N N N c8 O O O O c8 c9 c9 O O Y N N Y Y c8 O O O O c8 c9 c9 O O N N N N N 251 6 F 2 T 0 1 7 6 Transmission of sampled value model (SVC) Multicast SVC S45 SendMSVMessage S46 GetMSVCBValues S47 SetMSVCBValues Unicast SVC S48 SendUSVMessage S49 GetUSVCBValues S50 SetUSVCBValues Control S51 Select S52 SelectWithValue S53 Cancel S54 Operate S55 CommandTermination S56 TimeActivatedOperate File Transfer S57 GetFile S58 SetFile S59 DeleteFile S60 GetFileAttributeValues Time T1 Time resolution of internal clock T2 Time accuracy of internal clock T3 Supported TimeStamp resolution c10 O O c10 O O N N N c10 O O c10 O O N N N M M O M M O O O O M O O Y Y Y Y N N O O O O M O O O N N N N 100ms 100ms 100ms M – Mandatory O – Optional c1 – shall be ‘M’ if support for LOGICAL-DEVICE model has been declared. c2 – shall be ‘M’ if support for LOGICAL-NODE model has been declared. c3 – shall be ‘M’ if support for DATA model has been declared. c4 – shall be ‘M’ if support for DATA-SET, Substitution, Report, Log Control, or Time model has been declared. c5 – shall be ‘M’ if support for Report, GSE, or SV models has been declared. c6 – shall declare support for at least one (BRCB or URCB) c7 – shall declare support for at least one (QueryLogByTime or QueryLogAfter). c8 – shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage) c9 – shall declare support if TWO-PARTY association is available. c10 – shall declare support for at least one (SendMSVMessage or SendUSVMessage). 252 6 F 2 T 0 1 7 6 PICS for A-Profile support A-Profile shortcut A1 A2 Profile Description Client F/S c1 c2 Server F/S c1 c2 IED Remarks Client/server A-Profile Y GOOSE/GSE Y management A-Profile A3 GSSE A-Profile c3 c3 N A4 TimeSync A-Profile c4 c4 Y c1 Shall be ‘m’ if support for any service specified in Table 2 are declared within the ACSI basic conformance statement. c2 Shall be ‘m’ if support for any service specified in Table 6 are declared within the ACSI basic conformance statement. c3 Shall be ‘m’ if support for any service specified in Table 9 are declared within the ACSI basic conformance statement. c4 Support for at least one other A-Profile shall be declared (e.g. in A1-A3) in order to claim conformance to IEC 61850-8-1. PICS for T-Profile support A-Profile Profile Description Client shortcut F/S T1 TCP/IP T-Profile c1 T2 OSI T-Profile c2 T3 GOOSE/GSE T-Profile c3 T4 GSSE T-Profile c4 T5 TimeSync T-Profile o c1 Shall be ‘m’ if support for A1 is declared. Otherwise, shall be 'i'. c2 Shall be ‘o’ if support for A1 is declared. Otherwise, shall be 'i'. c3 Shall be ‘m’ if support for A2 is declared. Otherwise, shall be 'i'. c4 Shall be ‘m’ if support for A3 is declared. Otherwise, shall be 'i'. Server F/S c1 c2 c3 c4 o 253 IED Y N Y N Y Remarks 6 F 2 T 0 1 7 6 Protcol Implementation eXtra Information for Testing (PIXIT) for IEC61850 interface in GRE series IED ・Introduction This document specifies the protocol implementation extra information for testing (PIXIT) of the IEC 61850 interface in GRE series IED with communication firmware MVM850-01 series version upper than A (MVM850-01-A). Together with the PICS and the MICS the PIXIT forms the basis for a conformance test according to IEC 61850-10. ・Contents of this document Each chapter specifies the PIXIT for each applicable ACSI service model as structured in IEC 61850-10. PIXIT for Association model ID As1 As2 Description Maximum number of clients that can set-up an association simultaneously TCP_KEEPALIVE value As3 Lost connection detection time As4 As5 Is authentication supported What association parameters are necessary for successful association As6 If association parameters are necessary for association, describe the correct values e.g. What is the maximum and minimum MMS PDU size As7 As8 What is the maximum startup time after a power supply interrupt Value / Clarification 6 7200 seconds at the default setting. Setting range is from 1s to 43200s. After the KEEPALIVE is no response, retrying 9 times every “X” seconds until declaring that the association has been lost. “X” is one tenth of TCP_KEEPALIVE value. Ex. The lost connection detection time is 18s (9 times x 2 s), when TCP_KEEPALIVE value is 20 s. N Transport selector N Session selector N Presentation selector N AP Title N AE Qualifier N N.A. Max MMS PDU size 8172 Min MMS PDU size Not limited. It depends on a request. 180 seconds Check the start-up signal (No.227) 254 6 F 2 T 0 1 7 6 PIXIT for Server model ID Sr1 Description Which analogue value (MX) quality bits are supported (can be set by server) Sr2 Which status value (ST) quality bits are supported (can be set by server) Sr3 What is the maximum number of data values in one GetDataValues request What is the maximum number of data values in one SetDataValues request Which Mode / Behavior values are supported Sr4 Sr5 Value / Clarification Validity: Y Good, Y Invalid, N Reserved, Y Questionable N Overflow Y OutofRange N BadReference N Oscillatory Y Failure N OldData N Inconsistent N Inaccurate (Only Hz) Source: N Process N Substituted Y Test N OperatorBlocked Validity: Y Good, Y Invalid, N Reserved, Y Questionable N BadReference N Oscillatory Y Failure N OldData N Inconsistent N Inaccurate Source: N Process N Substituted Y Test N OperatorBlocked Not restricted; depend on the max. MAX PDU size given in previous page. N.A. 255 On Blocked Test Test/Blocked Off Y N Y N N 6 F 2 T 0 1 7 6 PIXIT for Data set model ID Ds1 Ds2 Ds3 Description Value / Clarification What is the maximum number of data Not limited by an internal configuration elements in one data set (compare ICD parameter. setting) This IED does not have CreateDataSet service. But any DataSet can be defined by using engineering tool. The maximum number depends on the memory size of IED. How many persistent data sets can be Not limited by an internal configuration created by one or more clients parameter. (this number includes predefined datasets) The maximum number depends on the memory size of IED. How many non-persistent data sets N.A. can be created by one or more clients PIXIT for Substitution model ID Sb1 Description Are substituted volatile memory? values stored in Value / Clarification N.A. PIXIT for Setting group control model ID Sg1 Sg2 Sg3 Sg4 Sg5 Description Value / Clarification What is the number of supported 2 setting groups for each logical device (compare NumSG in the SGCB) What is the effect of when and how the Just SelectActiveSG service will be non-volatile storage is updated supported according to PICS. (compare IEC 61850-8-1 $16.2.4) After changing setting group number with LCD panel, you can see new setting group with GetSGCBValue service. Can multiple clients edit the same N.A. setting group What happens if the association is lost N.A. while editing a setting group Is EditSG value 0 allowed? N.A. 256 6 F 2 T 0 1 7 6 PIXIT for Reporting model ID Rp1 Description The supported trigger conditions are (compare PICS) Rp2 The supported optional fields are Rp3 Rp4 Rp5 Rp6 Rp7 Rp8 Rp9 Rp10 Rp11 Can the server send segmented reports Mechanism on second internal data change notification of the same analogue data value within buffer period (Compare IEC 61850-7-2 $14.2.2.9) Multi client URCB approach (compare IEC 61850-7-2 $14.2.1) What is the format of EntryID What is the buffer size for each BRCB or how many reports can be buffered Pre-configured RCB attributes that cannot be changed online when RptEna = FALSE (see also the ICD report settings) May the reported data set contain: - structured data objects? - data attributes? What is the scan cycle for binary events? Is this fixed, configurable Does the device support to pre-assign a RCB to a specific client in the SCL Value / Clarification integrity data change quality change data update general interrogation sequence-number report-time-stamp reason-for-inclusion data-set-name data-reference buffer-overflow entryID conf-rev segmentation Y Y Y Y N Y Y Y Y Y Y Y Y Y Y Send report immediately Each URCB is visible to all clients It is made up of the circular buffer counter at the time the event was entered. For example, LLN0$ST$Health can be stored 40 events. N.A. 257 Y Y GRE110: More than 1500 milliseconds Fixed N 6 F 2 T 0 1 7 6 PIXIT for Logging model ID Description Lg1 What is the default value of LogEna (Compare IEC 61850-8-1 $17.3.3.2.1, the default value should be FALSE) Lg2 What is the format of EntryID (Compare IEC 61850-8-1 $17.3.3.3.1) Lg3 If there are multiple Log Control Blocks that specify the Journaling of the same MMS NamedVariable and TrgOps and the Event Condition (Compare IEC 61850-8-1 $17.3.3.3.2) Lg4 Pre-configured LCB attributes that cannot be changed online PIXIT for Generic substation events model ID Description Go1 What elements of a subscribed GOOSE header are checked to decide the message is valid and the allData values are accepted? If yes, describe the conditions. Note: the VLAN tag may be removed by a ethernet switch and should not be checked Go2 Go3 Go4 Go5 Go6 Value / Clarification N.A. N.A. N.A. N.A. Value / Clarification N source MAC address Y destination MAC address = as configured Y Ethertype = 0x88B8 Y APPID = as configured and 0 Y gocbRef = as configured N timeAllowedtoLive N datSet Y goID = as configured N t N stNum Y sqNum Y test N confRev Y ndsCom N numDatSetEntries N Can the test flag in the published GOOSE be turned on / off What is the behavior when the If the configuration is incorrect, the GOOSE GOOSE publish configuration is isn’t published. incorrect When is a subscribed GOOSE Message does not arrive prior to TAL. marked as lost? (TAL = time allowed to live value from the last received GOOSE message) What is the behavior when one or [stNum is out-of-order, or missed] more subscribed GOOSE messages No fail will be detected. isn’t received or syntactically incorrect (missing GOOSE) [sqNum is out-of-order, or missed] GOOSE subscribe quality information will become QUESTIONABLE | INCONSISTENT (=1100 0000 1000 0). After receiving message with correct sqNum order, the quality information is set to GOOD (=0000 0000 0000 0). What is the behavior when a Refer to Go5. subscribed GOOSE message is 258 6 F 2 T 0 1 7 6 ID Go7 Go8 Go9 Go10 Go11 Go12 Go13 Go14 Go15 Go16 Description out-of-order What is the behavior when a subscribed GOOSE message is duplicated Does the device subscribe to GOOSE messages with/without the VLAN tag? May the GOOSE data set contain: - structured data objects (FCD)? - timestamp data attributes? Note: data attributes (FCDA) is mandatory Published FCD supported common data classes / data types are Subscribed FCD supported common data classes / data types are What is the slow retransmission time? Is it fixed or configurable? What is the minimum supported retransmission time? What is the maximum supported retransmission time? Is it fixed or configurable? Can the Goose publish be turned on / off by using SetGoCBValues(GoEna) What is the fast retransmission scheme? Is it fixed or configurable? What is the behavior when one subscribed GOOSE message exceeds the previous time Allowed to Live (TAL) Value / Clarification GOOSE subscribe quality information will become QUESTIONABLE | INCONSISTENT (=1100 0000 1000 0). Y, with the VLAN tag Y, without the VLAN tag Subscribed Y N Published N N 60 seconds with TAL = 120 seconds Fixed. <minTime> 300 milliseconds <maxTime> Fixed Y 300 milliseconds with TAL = 600 milliseconds Fixed. When expected time (TAL) spends without GOOSE message, GOOSE subscribe quality information will become QUESTIONABLE (=1100 0000 0000 0). After that, when IED receive time exceeded GOOSE with SqNum=0, GOOSE subscribe quality information will become GOOD (=0000 0000 0000 0). When IED receive time exceeded GOOSE with SqNum!=0, GOOSE subscribe quality information will become QUESTIONABLE | INCONSISTENT (=1100 0000 1000 0) When GOOSE with TAL=0 is received, GOOSE subscribe quality information will become QUESTIONABLE | INCONSISTENT (=1100 0000 1000 0) Go17 What is the behavior when a subscribed GOOSE message is “test” Payload data consistency is not used to determine if TAL is exceeded. GOOSE subscribe quality information will become QUESTIONABLE | TEST (=1100 0000 259 6 F 2 T 0 1 7 6 ID Go18 Go19 Description What is the behavior when a subscribed GOOSE message is “ndsCom” Acceptable data type Value / Clarification 0001 0). Payload data is not received. GOOSE subscribe quality information will become QUESTIONABLE | INACCURATE (=1100 0000 0100 0). Payload data is not received. Boolean BitSring Integer Unsigned Integer But each data size shall be less than 32 bits. Go20 Other types (TimeStamp, OctetString, etc) will be ignored by IED. When GOOSE subscribe quality information is GOOD, the IED receives the payload data. Dataset structure of a subscribed This is not checked. Two GOOSEs, which have GOOSE same header (e.g.GoID) and different dataset structure, are treated as the same GOOSEs. And if received GOOSEs have same header, the fixed position of the GOOSE dataset is read. E.g. the 1st element of the dataset is set to read, it keeps reading the 1st element even if the dataset structure is different. Go21 Go22 Note: Subscribed payload data structure is checked to determine if IED accepts/discards the data; however the TAL timeout is reset even when such data is discarded. What is the behavior when the The device starts sending GOOSE from device starts up? stNum=1 and sqNum=1. Is it supported to set the “ndsCom” N as TRUE? TAL = Time Allowed to Live 260 6 F 2 T 0 1 7 6 PIXIT for Control model ID Description Ct1 What control models are supported (compare PICS) Ct2 Ct3 Ct4 Ct5 Ct6 Ct7 Ct8 Ct9 Ct10 Is the control model fixed, configurable and/or online changeable? Is Time activated operate supported Is “operate-many” supported Will the DUT activate the control output when the test attribute is set in the SelectWithValue and/or Operate request (when N test procedure Ctl2 is applicable) Value / Clarification Y status-only Y direct-with-normal-security Y sbo-with-normal-security N direct-with-enhanced-security N sbo-with-enhanced-security Configurable (need to restart after configuration) N N N FALSE TRUE Test flag IED Mode Normal Accepted Rejected Test Rejected Accepted Accepted: The control request is accepted by IED. Rejected: The control request is rejected by IED with AddCause “Blocked-by-Mode”. What are the conditions for the time N.A. (T) attribute in the SelectWithValue and/or Operate request? Is pulse configuration supported N What is the behavior of the DUT when Only interlock bit is checked. the check conditions are set? This behavior is fixed. Is this behavior fixed, configurable, online changeable? Note: When interlock is an enable, the control request is rejected by IED with AddCause “Blocked-by-Interlocking”. What additional cause diagnosis are Y Not-supported supported? N Blocked-by-switching-hierarchy Y Select-failed N Invalid-position N Position-reached N Parameter-change-in-execution N Step-limit Y Blocked-by-Mode N Blocked-by-process Y Blocked-by-interlocking N Blocked-by-synchrocheck N Command-already-in-execution N Blocked-by-health N 1-of-n-control N Abortion-by-cancel N Time-limit-over N Abortion-by-trip (only for BCPU) Y Object-non-selected How to force a “test-not-ok” respond with SelectWithValue request? 261 Set orCat with unsupported value. 6 F 2 T 0 1 7 6 ID Ct11 Ct12 Ct13 Ct14 Description How to force a “test-not-ok” respond with Select request? How to force a “test-not-ok” respond with Operate request? Which origin categories are supported? What happens if the orCat is not supported? Ct15 Does the IED accept a SelectWithValue/Operate with the same ctlVal as the current status value? Ct16 Does the IED accept a select/operate on the same control object from 2 different clients at the same time? Does the IED accept a Select/SelectWithValue from the same client when the control object is already selected (tissue 334) Is for SBOes the internal validation performed during the SelectWithValue and/or Operate step? Can a control operation be blocked by Mod=Off or Blocked Does the IED support local / remote operation? Does the IED send an InformationReport with LastApplError as part of the Operate response- for control with normal security? Ct17 Ct18 Ct19 Ct20 Ct21 Value / Clarification N.A. DOns, SBOns: Set orCat with unsupported value. DOes, SBOes: N.A. N DOns, SBOns: “test-not-ok” IED respond DOes, SBOes: N.A. DOns, SBOns: N The control request is rejected by IED with AddCause “Blocked-by-Interlocking”. DOes, SBOes: N.A. DOns,: Y SBOns: N DOes, SBOes: N.A. SBOns: N SBOes: N.A. 262 N.A. Y Y DOns: N SBOns: Y 6 F 2 T 0 1 7 6 PIXIT for TIME AND TIME SYNCHONISATION model ID Description Value / Clarification Tm1 What quality bits are supported N LeapSecondsKnown (may be set by the IED) N ClockFailure Y ClockNotSynchronized Tm2 Describe the behavior when the time The quality attribute “ClockNotSynchronized” synchronization signal/messages are will be set to TRUE. lost Tm3 When is the time quality bit "Clock N.A. failure" set? Tm4 When is the time quality bit "Clock It depends on the condition of not synchronised” set? synchronization. Typically 120 seconds Tm5 Is the timestamp of a binary event N adjusted to the configured scan cycle? Tm6 Does the device support time zone Y and daylight saving? Support time zone only. Tm7 Which attibutes of the SNTP Y Leap indicator not equal to 3? response packet are validated? N Mode is equal to SERVER N OriginateTimestamp is equal to value sent by the SNTP client as Transmit Timestamp Y RX/TX timestamp fields are checked for reasonableness Y SNTP version 3 and/or 4 N other (describe) PIXIT for FILE TRANSFER model ID Description Ft1 What is structure of directories? files and Value / Clarification N.A. Where are the COMTRADE files stored? Ft2 Ft3 Ft4 Ft5 Ft6 Ft7 Ft8 Are comtrade files zipped and what files are included in each zip file? Directory names are separated from the file name by The maximum file name size including path (recommended 64 chars) Are directory/file name case sensitive? Maximum file size Is the requested file path included in the file name of the MMS fileDirectory respond? Is the wild char supported MMS fileDirectory request? Is it allowed that 2 client get a file at the same time? 263 N.A. N.A. N.A. N.A. N.A. N.A. N.A. 6 F 2 T 0 1 7 6 IEC61850 Tissues conformance statement (TICS) of the IEC61850 communication interface GRE series IED ・Introduction According to the UCA IUG QAP the tissue conformance statement is required to perform a conformance test and is referenced on the certificate. This document is applicable for GRE series IED with communication firmware MVM850-01 series version upper than A (MVM850-01-A). ・Mandatory Intop Tissues During the October 2006 meeting IEC TC57 working group 10 decided that: • green Tissues with the category “IntOp” are mandatory for IEC 61850 edition 1 • Tissues with the category “Ed.2” Tissues should not be implemented. Below table gives an overview of the implemented IntOp Tissues. 264 6 F 2 T 0 1 7 6 Part 8-1 7-4 7-3 7-2 Part 6 NOTE: Tissue Nr Description Implemented Y/n.a. 116 165 183 None 28 54 55 60 63 65 219 270 30 31 32 35 36 37 39 40 41 42 43 44 45 46 47 49 50 51 52 53 151 166 185 189 190 191 234 275 278 1 5 8 10 17 169 GetNameList with empty response? Improper Error Response for GetDataSetValues GetNameList error handling Y Y Y Definition of APC Point def xVal, not cVal Ineut = Ires ? Services missing in tables mag in CDC CMV Deadband calculation of a Vector and trigger option operTm in ACT WYE and DEL rms values control parameter T Typo Typo in syntax Typo Syntax Control time Syntax parameter DSet-Ref missing Syntax GOOSE "T" type Add DstAddr to GoCB GOOSE Message “AppID” to “GoID” GsCB “AppID” to “GsID” SV timestamp: “EntryTime” to “TimeStamp" Control "T" semantic AddCause - Object not sel Missing AddCauses (neg range) Synchro check cancel "." in LD Name? BRCB TimeOfEntry (part of #453) LNName start with number? ARRAY [0..num] missing Ambiguity GOOSE SqNum Add DstAddr to GsCB, SV Name constraint for control blocks etc. DataRef attribute in Log Logging - Integrity periode SV Format BRCB: EntryId and TimeOfEntry (part of #453) BRCB: Integrity and buffering reports (part of #453) New type CtxInt (Enums are mapped to 8 bit integer) Confusing statement on GI usage (part of #453) EntryId not valid for a server (part of #453) Syntax tExtensionAttributeNameEnum is restricted SIUnit enumeration for W Base type for bitstring usage DAI/SDI elements syntax Ordering of enum differs from 7-3 n.a. n.a. n.a. Y Y Y n.a. Y n.a n.a. n.a. n.a. n.a. n.a. Y Y n.a. n.a. n.a. n.a. Y n.a. Y Y Y n.a. Y n.a. Y n.a. n.a. n.a. Y Y n.a. Y Y Y Y n.a. Y Y Y Tissue 49, 190, 191, 275 and 278 are part of the optional tissue #453, all other technical tissues in the table are mandatory if applicable. Optional IntOp Tissues 265 6 F 2 T 0 1 7 6 After the approval of the server conformance test procedures version 2.2 the following IntOp tissues were added or changed. It is optional to implement these tissues. Part Tissue Nr Description 8-1 8-1 7-2 7-2 6 6 246 545 333 453 245 529 Control negative response (SBOns) with LastApplError Skip file directories with no files Enabling of an incomplete GoCB Combination of all reporting and logging tissues Attribute RptId in SCL Replace sev - Unknown by unknown Implemented Y/N/n.a. Y n.a n.a. N N n.a. Other Implemented Tissues Part Tissue Nr 8-1 109 118 121 344 76 38 3 6 7 11 15 7-4 7-2 6 Description GOOSE, GSE, SV Addresses File directory GOOSE subscriber behavior TimeOfEntry misspelled CBOpCap and SwOpCap Syntax "AppID" or "GoID" Missing ENUMs ReportControl/OptFields Duplication of attributes Schema for IP Addr? bufOvfl in Schema? 266 Implemented Y/N/n.a. Y n.a. Y Y N Y Y N N N Y 6 F 2 T 0 1 7 6 2. CB remote control To control the CB at remote site with the IEC 61850 communication, do the following. ・Operation item - Remote control by the Select Before Operate or Direct Operate (CB Open / CB Close) - Change of interlock position (BlkOpn or BlkCls) - Trip LED reset ・Operating procedure To control the CB at remote site with ICE 61850 communication is require the following three steps. - get Logical nodes by using IEC 61850 data setting tools (such as TAMARACK tool). - change the control logical node (XCBR, CILO or CSWI). When CB is remote controlled from PC, showing below the control reaction depending on the CB Status. CB Status Response BI-a (CB_OPC_BI) BI-b (CB_CLC_BI) CB LED lighting 0 0 CLOSE 1 0 CLOSE 1 1 CLOSE 0 1 OPEN CB Open Operation ・Unlock: operate ・Lock※: not operate ・Unlock: operate ・Lock: not operate ・Unlock: not operate ・Lock: not operate ・Unlock: not operate ・Lock: not operate CB Close Operation ・Unlock: not operate ・Lock: not operate ・Unlock: not operate ・Lock: not operate ・Unlock: not operate ・Lock: not operate ・Unlock: operate ・Lock: not operate ※Lock condition is as follows. • Setting the Inter lock in the Control screen of front panel LCD (see chapter 4.2.6.11) and remote setting the CB open lock and CB close lock from PC. • Occurring Relay Trip. • When Local/Remote status is “Local” (see chapter 4.2.7.1). • When Control status is “Disable” (see chapter 4.2.6.11). 267 6 F 2 T 0 1 7 6 Appendix O Ordering 268 6 F 2 T 0 1 7 6 Ordering Under/Overvoltage Relay GRE130 Type: Voltage Relay Model: - Model 410: Four pole GRE130 2 x BIs, 4 x Bos, 1 x Relay fail 6 x BIs, 4 x BOs, 1 x Relay fail 6 x BIs, 8 x BOs, 1 x Relay fail Rating: VT: 110V, f: 50/60Hz, 110-250Vdc or 100-220Vac VT: 110V, f: 50/60Hz, 48-110Vdc VT: 110V, f: 50/60Hz, 24-48Vdc Standard and language: IEC (English) ANSI (English) Chinese Communication: RS485 1port (Modbus/IEC60870-5-103) RS485 1port (Modbus/DNP3.0) Following options can be equipped with Model 402 and 422 only RS485 2ports (Modbus/IEC60870-5-103) RS485 2ports (Modbus/DNP3.0) 100BASE-TX 1port (Modbus/IEC61850) +RS485 1port (Modbus/IEC60870-5-103) 100BASE-TX 1port (Modbus/ DNP3.0) +RS485 1port (Modbus/DNP3.0) 100BASE-TX 2ports (Modbus/IEC61850) +RS485 1port (Modbus/IEC60870-5-103) 100BASE-TX 2ports (Modbus/ DNP3.0) +RS485 1port (Modbus/DNP3.0) 100BASE-FX 1port (Modbus/IEC61850) +RS485 1port (Modbus/IEC60870-5-103) 100BASE-FX 1port (Modbus/ DNP3.0) +RS485 1port (Modbus/DNP3.0) 100BASE-FX 2ports (Modbus/ IEC61850) +RS485 1port (Modbus/IEC60870-5-103) 100BASE-FX 2ports (Modbus/ DNP3.0) +RS485 1port (Modbus/DNP3.0) 269 410 411 412 1 2 A 0 1 2 10 11 20 21 A0 A1 B0 B1 C0 C1 D0 D1 A 0 6 F 2 T 0 1 7 6 Version-up Records Version No. Date 0.0 1.0 Nov. 24, 2010 Apr. 19, 2012 1.1 Jan. 28, 2013 1.2 2.0 Feb. 26, 2013 May.29, 2014 Revised Section -4.2.6 Appendix G Appendix J Appendix L Appendix F Appendix J Appendix M Appendix J 1 3.2.2 3.2.4 3.3.3 4.1 4.2 4.5 4.6 5 Appendix A Appendix B Appendix C Appendix E Appendix F Appendix G Appendix J Appendix L Appendix M Appendix N Appendix O Contents First issue Modified the description. Modified the description. Modified the description. Modified the description. Modified the diagrams. Modified the description. Modified the Ordering Cords. Modified the description. Add model 412A and IEC60850-5-103 and IEC61850 communication Add the 412A model and communication. Modified the description. Add the description. Modified the description Add the description of GRE130-412A. Add the communication settings. Add the IEC60870-5-103. Add the IEC61850 Add the GRE130-412A descriptions. Modified the Signal List Modified the description Add the GRE130-412A. Add the GRE130-412A Add the GRE130-412A Modified the description Modified the description Modified the description Add the description. Add the description Modified the section No. 270
© Copyright 2024