STATIONARY BATTERIES
LOW MAINTANCE
OGi/OGiCa TYPE
Technical Information
MAIN APPLICATIONS







Power and Heating plants
Distribution energy companies
Telecommunication operators
Railway
Industrial Companies
UPS
Start power generators
BATTERY DESIGN
Type of Cell
Led technology
Positive and
negative electrode
Separation
Electrolyte
Container
Plugs
Connectors
vented, low maintenance cells with liquid electrolyte
low antimony or lead-calcium
pasted
Micro porous separator with low resistance
sulphuric acid with density 1,24 ± 0,01kg/l possible 1,27kg/l
high impact, transparent SAN (Styrol-Acryl-Nitril)
ceramic funnel plugs according DIN 40 740
(on request catalytic recombination plugs)
screw, rigid or flexible, insulated (on request welded)
EXPLOATATION DATAS
Project design life
Water – refilling - interval
Operational temperature
Floating voltage
Rectifier
Cycle work
Installation
Standards
OGi 20 years, OGiCa 20+ years

OGi in 3÷5 years (standard plugs)

OGiCa 5 years (standard plugs)

unrequire (catalytic plugs)
recommended 10°C - 30°C
2,23V/cell +/- 1%, between 10°C - 30°C
recommended IGBT transistor, permissible thyristor technology
900.1000 cycle (acc. IEC 869-1)
vertical






ISO 9001
IEC 896-1
DIN 40737-3
EN 60896
VDE 0510/2
EN 50272-2
ELCON SOLUTIONS OY
Pyhän Katariinan tie 308
FI-20760 Piispanristi
FINLAND
+358 2 512 3100
ELCON POWER SOLUTIONS
VALUE ADDED CLEAN POWER
WWW.ELCON.FI
PAGE 1 / 2
© ELCON GROUP
MAINTENANCE
Every quarter and half year
Once per year
Storage



check battery voltage
check temperature in battery room
check voltage and density of every battery (and level of charge if necessary)


capacity test and battery resistance acc PN – 76/E83005
record measured parameters in “ Battery exploitation book “



at 20°C - 3 months without recharge
at 30°C - 2 months without recharge
at 40°C - 1 month without recharge
TYPES, CAPACITIES, DIMENSION, WEIGHT
*) Nominal capacity Cn according to DIN 40739 and DIN 40734
**) Guarantee capacity C10 at 10h discharge in temp. 20°C to voltage 1,80 V/cell at density 1,24 kg/l
Notice: Due to permanent technology development, guaranteed data can be subject to alteration.
Please contact manufacturer or authorize distributor.
ELCON SOLUTIONS OY
Pyhän Katariinan tie 308
FI-20760 Piispanristi
FINLAND
+358 2 512 3100
ELCON POWER SOLUTIONS
VALUE ADDED CLEAN POWER
WWW.ELCON.FI
PAGE 2 / 2
© ELCON GROUP