Turbo-Bar Insertion Turbine Models TMP-600/60S • TMP-700 • TMP-910/960 Description EMCO EMCO gal/min EMCO 112.4 EMCO EMCO EMCO 112.4 gal/min EMCO EMCO Turbo-Bar insertion flow meters have three main components: the retractor, the rotor, and the electronics. The retractor positions the rotor within the pipe and houses a pickup assembly, which detects the rotation of the turbine rotor. The electronics converts the rotational frequency, which is proportional to the velocity of the fluid, to industry standard electrical output signals. Most Turbo-Bar flow meters can be installed on an isolation valve, which permits installation and removal without process shutdown. Integral pressure and/or temperature measurement may be combined with the Turbo-Bar and flow processor to provide mass or energy flow measurement from a single pipe tap. TMP-600/60S Features • Fluid types: liquid, gas, or steam • Pipe sizes: 3 to 80” • Rugged construction • Interchangeable rotors for a wide variety of applications • Process pressure up to 5000 psig (345 barg) • Process temperatures up to 750°F • Industry standard frequency and/or 4 to 20 mA output signals TMP-700 TMP-910/960 • Optional integral pressure and/or temperature measurement • Negligible head loss • EZ-Logic™ menu-driven user interface (microprocessor-based) • Linearization with EZ-Logic for enhanced accuracy at low velocities •Local programming via EZ-Logic keypad or magnet wand through explosion-proof enclosure Application Guide Temperature Range Maximum Pressure1 Line Sizes2 Model Liquid Gas Steam Hot Tap °F psi Seal Type inches 600 yes yes no yes -40 to 400 125 Viton® 3 to 20 60S no no yes yes -65 to 400 125 E/P3 3 to 20 700 yes yes yes no5 -200 to 600 20004Swagelok® 3 to 80 910 yes yes yes yes -200 to 400 flange rating Teflon® 3 to 80 960 yes yes yes yes -200 to 750 flange rating Grafoil® 3 to 80 Note: 1 Maximum pressure at maximum temperature with appropriate connection. 2 In some cases, especially in large pipe sizes, a one or two foot stem extension may be required (See dimensional outlines). 3 Ethylene-Propylene elastomer. 4 Rating listed is for NPT connection. For flange connections, use ANSI flange rating. 5 The TMP-700 is a fixed insertion meter; it cannot be removed or installed under pressure. Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only. In the interests of development and improvement of the product, we reserve the right to change the specification. 82 TI-8-603-US 8.13 Turbo-Bar Insertion Turbine Models TMP-600/60S • TMP-700 • TMP-910/960 Operating Specifications Measurable Velocity Limits See Rotor Selection Guide, p. 4, for linear and measurable ranges of available rotors. Continuous operation above the maximum velocity will shorten the life of the rotor and is not recommended. Process Viscosity Maximum 5 centipoise Ambient Temperature Limit EZ-Logic Electronics • 32 to 140°F All Other Electronics • –20 to 140°F Ambient Humidity Limit 0 to 100% relative humidity non-condensing Power Requirements EZ-Logic Electronics • 18 to 40 VDC (with totalizer on), 24 VDC nominal • 12 to 40 VDC (with totalizer off), 24 VDC nominal Output Signals EZ-Logic Electronics (LOC-TOT Option) Analog 4 to 20 mA, 2-wire system, digitally adjusted span Frequency 3-wire system, 1 to 10,000 Hz square wave, 50% duty cycle. • Low Level: 0 to 1 volts • High Level: power supply voltage-load Pulse 3-wire system. Output can be scaled so that 1 pulse indicates a specific quantity of fluid passing through the pipe. Display 2-line by 8-character LCD digital display alternately show flow rate and totalized flow in user-selectable engineering units. Performance Specifications Accuracy (Linear Ranges) L1, G1–G5 Rotors ±1.0% of reading G6 Rotor±3.0% of reading Repeatability (Linear Range) ±0.25% of reading Rotor Velocity Calibration Each rotor is factory calibrated in either water or air. Calibration is traceable to NIST. Accuracy of the Calibration Standard (Linear Range) Water±0.25% of reading Air±0.8% of reading Physical Specifications Materials Rotor Blades: 17–4 PH, ten blade, precision machined Housing: 316 stainless steel Pivots: tungsten carbide Rotor Bearing Type Liquid: CSJ stellite jewel Gas or Steam: DEV tungsten carbide Wetted Parts 316L stainless steel stem and housing (bronze and carbon steel housing TMP-600/60S) External PartsAluminum, 316 stainless steel, carbon steel (bronze and carbon steel on TMP-600/60S, TMP- 910/960) Electrical Connection Junction box with terminal block for external wiring. 0.75” female NPT connection for conduit. Electrical Enclosure 383 aluminum. Approved for NEMA 4X for watertight and dust tight requirements Sensor Electromagnetic pick–up, 10 mVp–p minimum, 330 Ω nominal resistance. Retractor Type TMP-600/60s Screw thread, rising stem TMP-700Not retractable TMP-910/960 Acme thread, non-rising stem Extended Length Stem (Optional) Use of the two foot extension is limited Longer stems are available for large pipe sizes or when the mounting dimensions exceed to gas applications only. the insertion capability. Extended stems are not available for the TMP-600/60S. Process Connection TMP-600/60S2” NPT TMP-7002” NPT 2” 150#, 300#, 600# or 900# ANSI raised face flange TMP-910/960 2” 150#, 300#, 600# or 900# ANSI raised face flange Spirax Sarco Inc. • 2150 Miller Drive • Longmont, CO 80501 • Telephone: (303) 682-7060 • Fax: (303) 682-7069 TI-8-603-US 8.13 83 Turbo-Bar Insertion Turbine Models TMP-600/60S • TMP-700 • TMP-910/960 Isolation Valve (TMP-600/60S only) 2” full-port bronze gate valve, 125 psig (8.62 barg) maximum. For TMP-910/960, see Accessories. Includes the RTD option with an additional 4 to 20 mA output, scaled to the desired temperature range. A temperature transmitter is not available with 110/220 VAC power and is not CE approved. Pressure Tap and Bleed Valve Standard 1/4” NPT pipe nipple with 1/4” stainless steel bleed valve. Provides connections for mounting optional pressure transmitter (Model PT). Remote Mount Electronics (RMT Option) 30 ft signal cable and U-bolts are provided with remote mount electronics. Cable must be run in conduit (conduit not supplied). Conduit connection is 3/4” NPT. Model PT Pressure Transmitter (Optional) A pressure transmitter can be mounted using the 1/4” NPT connection on the bleed valve supplied with the meter, eliminating the need for a separate pressure tap. A 4 to 20 mA output, scaled to the desired pressure range, is provided. All pressure transmitters include a siphon tube, bleed valve, plug, nipple, and tee. A pressure transmitter is not available with 110/220 VAC power. See the PT TIS for complete details. Note: Remote mount electronics are only available with EZ-Logic electronics (LOC-TOT Option). Temperature Sensor (RTD Option) A 1000 Ω, platinum RTD can be mounted inside the stem of the flowmeter probe, eliminating the need for a separate temperature tap. FM Approval (FM Option) Certified by FM for Class I, Division 2, Groups A, B, C and D; Classes II, III, Division 2, Groups F and G NEMA 4X locations. Note: FM not available when used with 4 to 20 mA temperature transmitter, a pressure transmitter 0 to 1000 psig, or special scaled pressure transmitter. Temperature Transmitter (TXX Option) Accessories Gate Valve (Model 2GV) - (for Use with TMP-910/960 Only) Installation with a 2” double flanged, raised-face, full port gate valve enables the flow sensor to be inserted and removed from the pipe under full flow conditions. Both the valve and pipe tap must have a minimum 2” internal diameter clearance. Flow Processor (Model FP-93) A microprocessor-based flow processor may be used to significantly increase the accuracy and functionality of any flow metering application. See the FP-93 TIS for complete details. Straight Run Piping Requirements One 90° elbow before the meter Two 90° elbows before the meter Two 90° elbows out of plane before the meter Reduction before the meter Regulator or valve partially closed before the meter UpstreamDownstream 10 D 5D 15 D 5D 30 D 5D 10 D 5D 30 D 5D D is equal to the internal diameter of the pipe. If there is not sufficient straight run of pipe, a flow rectifier may be used to reduce the above diameter measurements. Consult your local representative or the factory for your specific application. Other Installation Considerations Tap Size 2.0” minimum diameter. Mounting Position Turbo-Bar probes may be installed in vertical, horizontal, or angled pipe sections. The meter is attached perpendicular to the axis of the pipe and should not be mounted “upside-down” (with its top section hanging below the pipe mount). For liquid service, the fluid must completely fill the pipe. Site Selection The flow measurement location should be selected to minimize turbulence and swirl. The extent of these flow disturbances depends upon the piping configuration. Valves, elbows, pumps, and other piping components may add disturbances to the flow. Hot Tap Comapatibility The TMP-600/60S is hot tap compatible, which means that the sensor can be installed and removed under full flow conditions. The TMP-910/960 is hot tap compatible when installed with a 2” double flanged, full port ball or gate valve that adheres to the dimensions shown on page 5. TI-8-603-US Spirax Sarco Inc. • 2150 Miller Drive • Longmont, CO 80501 • Telephone: (303) 682-7060 • Fax: (303) 682-7069 84 05.12 Turbo-Bar Insertion Turbine Models TMP-600/60S • TMP-700 • TMP-910/960 Rotor Selection Guide G6 (1" rotor) Liquid Minimum and Maximum Velocity Rates G1 through G5, L1 (1.5" rotor) RotorFlow All Units Sizes 3 to 5” 6” 8+” V V V V V V V L1 ft/sec 30 1.4 0.5 1.5 0.6 1.6 0.7 max lin min lin min lin min Selection of the turbine rotor model depends upon the fluid type and operating velocity range of the fluid. • For all liquids, the model L1 rotor, with a maximum velocity of 30 ft/sec, must be used. • For gases and steam, six different rotors are available with maximum velocities ranging from 55 to 175 ft/sec. See Table for maximum velocity limits (V ) for all rotors. max. The turbine rotor typically will respond linearly over the velocity range from V to V – within ±1.0% (3.0% for G6 rotor). This is defined as the “linear” range of the rotor. The minimum “measurable” velocity (V ) can be considered the application minimum. Velocities from V to V are measurable and repeatable, but less accurate. lin max Note: Rotors have moving parts that require periodic maintenance. min min lin When determining the fluid velocity limits for a given rotor, the following equations can be used to compute fluid velocity. Note: All values in the above table are approximate and depend on the density of the fluid. Accuracy in both the linear and nonlinear ranges may be improved by using the advanced curve fitting techniques present in the FP-93 flow processors or the EZ-Logic electronics. Consult your local representative if your application falls outside the above limits. Average Fluid Velocities Fluid Liquid 0.4085 Gas 3.056 Q D2 Steam 0.051 M p D2 D = pipe inside diameter in gal/min Q = gas actual volumetric flow ft2/min 2 . lin min ρ N/A = density of fluid [lb/ft3] = not applicable ft/sec Q = liquid volumetric flow 1 1 2 Where: V = average fluid velocity V = maximum velocity of fluid [ft/sec] V = minimum velocity of fluid at which rotor response is linear [ft/sec] V = minimum measurable velocity of fluid [ft/sec] max Q D2 M = mass flow rate lb/h ρ = fluid density lb/ft3 Note: Measurable flow rates for your specific application are available using EMCOSIZE (downloadable at spiraxsarco.com/us/ resources). TI-8-603-US 05.12 Spirax Sarco Inc. • 2150 Miller Drive • Longmont, CO 80501 • Telephone: (303) 682-7060 • Fax: (303) 682-7069 85 Turbo-Bar Insertion Turbine Models TMP-600/60S • TMP-700 • TMP-910/960 Dimensions and Weights Dimensions are in inches TMP-600/60S * Add 12” for each additional foot of retractor length. Dimensions Model ConnectionC inches 600/60S 2” NPT 4.5 min 18 max 700 2” NPT 3 min 11.25 max 2” 150# 3 min 12.75 max 2” 300# 3 min 12.5 max 2” 600# 3 min 12.25 max 2” 900# 3 min 12 max TMP-910/960 TMP-700 * Add 12” for each additional foot of retractor length. Weight Dimensions Model ConnectionWeight Model Stem Length lb 600/60S 2” NPT 28 max 910/960 Standard 7001 2” NPT 9 2” 150# 12 2” 300# 14 2” 600# 16 2” 900# 20 910/9602 2” 150# 30 2” 300# 35 2” 600# 40 2” 900# 47 1 2 B A inchesinches 1.5 min 30 20 max Add 2.5lb for each additional foot of retractor length. Add 5 lb for each additional foot of retractor length. Gate Valve X Y Z Type inchesinchesinches 150# 7 3.515.325 300# 8.5 3.7516.325 600# 11.5 3.7517.875 Type 2" 150# 2" 300# 2" 600# Weight lb 46 58 84 TI-8-603-US Spirax Sarco Inc. • 2150 Miller Drive • Longmont, CO 80501 • Telephone: (303) 682-7060 • Fax: (303) 682-7069 86 05.12 Turbo-Bar Insertion Turbine Models TMP-600/60S • TMP-700 • TMP-910/960 Integral Electronics Pipe Mount Remote Electronics Remote Electronics Configuration Pipe Mount Wiring Diagrams EZ-Logic Electronics: Analog Output Scalable 4 to 20 mA output, 2-wire principle. Load resistor may be installed on supply or return line. V = 18 to 40 VDC. See graph below for permissible R values. s load EZ-Logic Electronics: Pulse Output 3 wire system. Output can be scaled so that 1 pulse indicates a specific quantity of fluid passing through the pipe. Vs = 18 to 40 VDC. TI-8-603-US 05.12 Spirax Sarco Inc. • 2150 Miller Drive • Longmont, CO 80501 • Telephone: (303) 682-7060 • Fax: (303) 682-7069 87 Turbo-Bar Insertion Turbine Models TMP-600/60S • TMP-700 • TMP-910/960 Pressure and Temperature Transmitter Wiring Remove the field wiring condulet cap to access the field wiring terminal block for power and signal wiring. Flow, pressure, and temperature output wiring connects to the terminal block. Refer to the previous section on 24 VDC power and signal wiring for Note: Maximum voltage with optional pressure transmitter is 30 VDC and 110/220 VAC power supply is not available with pressure and/or temperature transmitters. appropriate load resistance and power supply values. Pressure and temperature transmitters are scaled to the appropriate ranges at the factory. Wiring with Analog Output where: V R R R s p T F = 18 to 30 VDC = Pressure measuring resistance = Temperature measuring resistance = Flow rate measuring resistance Remote Mount Wiring Diagram (Only Available with EZ-Logic Electronics) Output wiring from remote electronics is identical to output wiring from integral electronics. Wiring from the remote electronics condulet to the electrical junction box must be performed in the field. Connect the remote cable to the terminal block in the junction box as shown. If nonconductive conduit is used, attach a ground strap from the ground screw on the remote electronics condulet. If the remote cable is cut to a shorter length, insulate shield with tape at electrical junction box. Note: If remote mounting is required with a pressure and/or temperature transmitter, two power supplies are required for operation: one for the remote flow transmitter and one for the pressure and/or temperature transmitter. Spirax Sarco Inc. • 2150 Miller Drive • Longmont, CO 80501 • Telephone: (303) 682-7060 • Fax: (303) 682-7069 88 TI-8-603-US 05.12 Turbo-Bar Insertion Turbine Models TMP-600/60S • TMP-700 • TMP-910/960 Category Suffix Codes Model TMP-600 Liquid or gas service, 400°F9 TMP-60S Steam service, 400°F9 Liquid, gas, or steam service, 600°F TMP-700 Liquid, gas, or steam service, 400°F TMP-910 TMP-960 Liquid, gas, or steam service, 750°F 7 Connection 2”, male NPT (model 700) 2NPT 2”, 150# flange (model 700, 910, 960) 2F150 2”, 300# flange (model 700, 910, 960) 2F300 2”, 600# flange (model 700, 910, 960) 2F600 2”, 900# flange (model 700, 910, 960) 2F900 3”, 150# flange (model 910, 960 extended stem)83F150 8 3”, 300# flange (model 910, 960 extended stem) 3F300 Rotor Liquid, 30 ft/sec maximum (9 m/sec) (40° pitch) L1 Gas or steam, 55 ft/sec maximum (40° pitch) G1 Gas or steam, 70 ft/sec maximum (30° pitch) G2 Gas or steam, 85 ft/sec maximum (20° pitch) G3 Gas or steam, 115 ft/sec maximum (15° pitch) G4 Gas or steam, 145 ft/sec maximum (10° pitch) G5 Gas or steam, 175 ft/sec maximum (5° pitch)1 G6 Electronics EZ-Logic with local rate and total3LOC-TOT Remote, only available with LOC-TOT option4RMT FM Approval5FM Pressure Transmitter No pressure transmitter XX PT for pressure range 0 to 50 psig (0 to 3.44 barg) 50 0 to 100 psig (0 to 6.89 barg) (models 600/60S, 700, 910/960) 100 0 to 150 psig (0 to 10.34 barg) (models 600/60S, 700, 910/960) 150 0 to 200 psig (0 to 13.79 barg) (models 600/60S, 700, 910/960) 200 0 to 250 psig (0 to 17.24 barg) (models 700, 910/960) 250 0 to 500 psig (0 to 34.47 barg) (models 700, 910/960) 500 0 to 1000 psig (0 to 68.95 barg) (models 700, 910/960) 1000 Special scaling requests6 PXX Temperature Sensor or Transmitter No temperature transmitter XXX RTD only RTD Temperature sensor with preamplifier scaled from 32 to 68°F2T09 0 to 250°F2T10 –40 to 150°F2T11 212 to 400°F2T12 212 to 800°F (models 700, 960)2T13 –17.7 to 121.1°C2T20 –40 to 65°C2T21 100 to 204°C2T22 100 to 260°C (models 700, 910/960)2T23 Special scaling requests 6, 2TXX Extended Stem None (standard length) XX 1’ extension (not available for models 600/60S) E1 2’ extension (gas/steam applications only) E2 (not available for models 600/60S) Pick-up Coil Wires TMP-700 Only: Teflon®, - 200 to 400°F T TMP-700 Only: Fiberglass, 150 to 600°F 7F TMP-700- 3F300- G3-LOC-TOT- 200- T12- E1- T 1 2 3 4 5 The G6 is the only available 1” shrouded rotor. Not available for use with bidirectional meters. Not available with European CE Mark. Unidirectional only. Unit has 4 to 20 mA and frequency output. Remote mount electronics are required for high process temperatures. The standard remote mount option comes with 30 feet (9.1 meters) of cable. Certified by FM for Class I, Div. 2, Groups A, B, C, & D; Class II,III, Div. 2, Groups F & G; NEMA 4X. FM approval with only LOC-TOT and RMT electronics options. If FM is required, use RTD option only for temperature selection. 0 to 1000 psia and special 6 7. 8 9 sealing pressure transmitter not available with FM. Special transmitter scaling is available. Please note scaling range below model code with ordering. If no special scaling is indicated, transmitter will be scaled per model code. Not available with FM approval. A 3” flange and 3” hole tap size are recommended for extended stems. For models 600 and 60s, the gate valve and thread-o-let must be ordered separately. See price list for details. Spirax Sarco Inc. • 2150 Miller Drive • Longmont, CO 80501 • Telephone: (303) 682-7060 • Fax: (303) 682-7069 Please specify the following information with your order: • Fluid type or composition • Maximum, minimum, & normal operating flow rate • Maximum, minimum, & normal operating temperatures • Maximum, minimum, & normal operating pressures • Specific weight & viscosity at normal operating conditions TI-8-603-US © Spirax Sarco, Inc. 2012 This example represents a liquid, gas, or steam Turbo-Bar TMP-700 at 600ºF, 3” 300# flange connection, 85 ft/sec gas or steam rotor, EZ-Logic electronics, 0 to 200 psig pressure transmitter, 212 to 400ºF temperature sensor, 1’ extended stem, and Teflon® coil wires. 05.12 89
© Copyright 2024