CAPTIVATION 0-10V Relay Load Controller Simplifies adding lighting controls to existing projects

CAPTIVATION 0-10V Relay Load Controller
Simplifies adding lighting controls to existing projects
The Philips Captivation family of products helps
alleviate the often complex and cost-prohibitive
hurdle of adding lighting controls to a facility.
Captivation controllers can be used as stand
alone circuit controllers with off-the-shelf
switches, or networked with Philips Dynalite
products into an area, building or campus-wide
lighting system. The Captivation 0-V Relay Load
Controller is rated for incandescent, magnetic
low-voltage, electronic low-voltage, magnetic
fluorescent driver and general purpose switching,
including plug loads.
210.1 mm (8.27 in)
200.2 mm (7.88 in)
17 mm
(.66 in)
70.9 mm
(2.79 in)
191.7 mm (7.5 in)
69 mm
(2.7 in)
104.8 mm (4 in)
• Flexible control — Allows 16 A switching
and/or 0-10V (ANSI C82.11) dimming control
of any 120V and 277V lighting circuit.
48.2 mm
(1.9 in)
94 mm (3.7 in)
• Control to the user — Utilizes user
selectable standard dimming curves and
custom user curves for maximum dimming
operation across loads.
• Convenient mounting — Mounts on to any
contractor supplied deep back box.
• Naturally ventilated — Integral ventilation
means that no forced cooling is required,
thereby reducing maintenance.
• 100% compliance — Accommodates ‘freeair’ or piped low voltage control wiring to
meet with US and Canadian national code
requirements.
• Three dry-contact inputs — Software
configurable, allowing third-party devices
to operate the Captivation controller in
standalone mode, or to allow bridging of
devices onto a DyNet network.
• UL924 — Programmable UL924 rated input
on each device for emergency use.
• Motion sensor input — Included power
supply allows for direct connection of a +24
VDC motion sensor or Dynalite sensor.
• User control selection — Via DyNet or
DMX512.
For detailed product information, please
refer to the product information pages at
www.philips.com/lightingcontrolsna.
Electrical Diagram
Specifications
Due to continuous improvements and innovations, specifications may change without notice.
Details
Input Voltage
120 VAC and 277 VAC (+10% / -15%), 50 / 60 Hz,
Dedicated Single Phase branch device. Max 20 A
Power Supply Output
Supply:
120 – 277 VAC
600W 50/60Hz
Single Phase
LINE IN (Black)
NEUTRAL (WHITE)
EARTH (GREEN)
LOAD OUTPUT (RED)
60 mA @ 24 VDC for external device power
80 mA @ 24VDC for devices on the DyNet bus
8.27” x 4.0” x 2.7” (210.1 mm x 104.8 mm x 70.9 mm)
Construction
16 gauge galvanized steel
Operating Conditions
Temperature: 32 to 122° F (0 to 50° C) ambient
Humdity: 10 to 95% non-condensing
(indoor application only)
Storage & Transport
Temperature: -13 to 140° F (-25 to 60° C) ambient
Humidity: 10 to 90% non-condensing
Standard Product - 0-10 +
Relay 1 Circuit
0-20 + Relay 1 Circuit
(meeting City of Chicago Plenum
requirements)
Options &
Ordering
Additional spare box
mounting ring (1 included with
FCC Part 15A, UL916, cUL916, CSA 22.2 No 205, California
Title 24 Section 119, 2008 as part of a Dynalite system,
RoHS Compliant, ANSI C82.11 Dimming Compliant, Air
sealed model available to meet City of Chicago Plenum
requirements.
DC-DRD-I-1C-101 (Philips 12NC - 913701254501)
DC-RING-001 (Philips 12NC - 913701254902)
each controller)
Additional spare low
voltage wire protection
grommet (1 included with each
DC-GROMMET-001 (Philips 12NC - 913701254802)
controller)
Captivation Handheld
DMX Addressing Unit
+24VDC (60mA)
GND
Motion
µP
SHLD
MOTION
GND
+24VDC
SW1
CONTACT
INPUTS
SW2
2 X RJ24
SW off
GND
GND
Wiring Diagram
Load Wiring
Black - 120V/277V Line Input
Red - Load Output to Fixtures
White - Neutral
Green - Ground
J13:
* TE = Trailing Edge
(Reverse Phase)
Dimming
* LE = Leading Edge
(Forward Phase)
Dimming
+
-
+24V
24V+ (60mA)
MOTION
GND
Default jumper states shown
DMX default address = 1
J13 Only applicable to DC-DPD
J9 Only applicable to DC-DRD
+24V
+24V
DyNet DATADMXDyNet DATA+
DMX+
DyNet GND
DMX GND
GND
SHLD
SHLD
24V+
SW1
SW2
SW off
DYNET/DMX DYNET/DMX
IN or OUT
IN or OUT
GND
Captivation QG.4 7/16/2014
Load Compatibility
Load Type
DC-DRD-I-1S-101 (Philips 12NC - 913701252801
UL924
TRIGGER
DYNET/DMX IN or OUT
Dimensions (H x W x D)
GND
J17
CAT5/CAT6 with RJ45 terminations or 18-22 AWG twisted
pair RS485 compatible cabling to press release terminals
TRIG
DMX TERM
ON OFF
Data Wiring
TRIG
DD+
J18
Flying leads Line, Load, Neutral and Ground
+24VDC
DMX GND(ISO)
ON OFF
Power Wiring
+24VDC
GND
DIM
J13 TYPE
Linear (fluorescent)
Modified Linear (LED)
Off
+24VDC
SHLD
LE
TE
FWD
REV
PHSE PHSE
Operational Control
Curves
Compliance
DyNet
RS485
External device 24 VDC power to standalone sensors (60
mA max)
3 dry contact inputs (SW1, SW2, SWOFF)
Motion input - active high +24 VDC from sensor (wet
contact)
UL924 triggers DyNet panic preset 65,534
0 - 10 V dimming terminals routable as Class 1 or Class 2
Configuration
DMX TERM
SHLD
Service button
Test button
Factory set button
Configuration and monitoring via Philips Dynalite
EnvisionManager software. Programming via Philips Dynalite
EnvisionProject software.
On
SHLD
0 - 10 V dimming control capable of sourcing or sinking 40
mA. Can be wired as Class 1 or Class 2 circuit.
DMX512 input connection
DyNet connection
Certification
GND
0-10V
Control
Low Voltage Connections
DMX GND (ISO)
Off
GND
UL924 TRIGGER
User Controls
On
DD+
MOTION
Dimming Control
+24VDC
Rated for incandescent (tungsten & halogen), magnetic lowvoltage, electronic low-voltage, magnetic fluorescent driver
and general purpose switching (incuding plug loads)
CONTACT INPUTS
Output Load Control
Physical
- 0 – 10V Control (Grey)
+24VDC
Relay contact rated at 16 A @ 120 V & 10 A @ 277 V
Control
+ 0 – 10V Control (Purple)
0-10V
J9
Electrical
Specification
DYNET/DMX IN or OUT
Item
@ 120 V 50/60 Hz
@ 277 V 50/60 Hz
Resistive Load
16A
10 A
Tungsten Lamp
16A
10 A
Magnetic Driver
16A
10 A
Electronic Driver
16A
10 A
Magnetic Halogen
16A
10 A
Electronic Halogen
16A
10 A
Horsepower
1HP
2 HP
DL-CP-ZIPPY-NA
Philips Lighting North America
200 Franklin Square Dr
Somerset, NJ, United States
Philips Lighting Canada
281 Hillmount Road
Markham, Ontario L6C 2S3
Tel: 1-800-526-2731
Canada
Specifications subject to change without notice. © WMGD Pty Ltd Trading as Dynalite.
Unit 6, 691 Gardeners Road Mascot 2020 Australia. ABN 33 097 246 921. All rights
reserved. Dynalite, DyNet and associated logos are the registered trademarks of
WMGD Pty Ltd. Not to be reproduced without permission.
Email: [email protected]
Web: www.philips.com/lightingcontrolsna
CAPTIVATION 0-10V Nov-14