ZIEHL-ABEGG Sverige

15.
15.2.1-GB
Sensors
Differential pressure sensor for gaseous media
Type:
DSG...
Equipment / Functions
Sensor with a membrane system suitable for measuring differential or
negative pressure of non-aggressive gas. The differential pressure to be
measured takes effect on a silicone membrane, changes in position of
which are compensated by a measuring spring, dependent on the
degree of travel. Changes in position of the membrane are detected by
a differential transformer and converted into an output signal of 0-10 V
by an electronics unit in SMD technology.
The differential pressure sensor supplies an output signal (0-10 V) when
the pressure at the “+” connection exceeds the pressure at the „-”
connection.
Examples of applications in conjunction with controllers for fans:
• Pressure control for central extraction systems and variable air
volume systems (VVS)
• Air volume control together with centrifugal fans (by means of a
measuring device in the inlet duct)
DSG
DSG…A
Versions / Technical data
•
•
•
•
Type
Article-No.
Measuring range [Pa]
Overload protection (static pressure)
DSG50
00155595
0 - 50
500 Pa (max. 0.2 bar)
DSG200
00150229
0 - 200
0.2 bar (max. 0.2 bar)
DSG200*
00155589
0 - 200
0.2 bar (max. 0.2 bar)
DSG500
00150230
0 - 500
0.2 bar (max. 0.2 bar)
DSG1000
00150231
0 - 1000
0.2 bar (max. 0.2 bar)
DSG2000
00150684
0 - 2000
0.2 bar (max. 0.2 bar)
DSG4000
00150685
0 - 4000
0.2 bar (max. 0.2 bar)
DSG6000
00150694
0 - 6000
0.2 bar (max. 0.2 bar)
Design with integrated digital display (LCD, 3-digit (mbar / Pa)), height of numerals 9 mm) available on request
DSG50A*
384001
0 - 50
500 Pa (max. 0.2 bar)
DSG1000A*
384005
0 - 1000
0.2 bar (max. 0.2 bar)
DSG4000A*
384038
0 - 4000
0.2 bar (max. 0.2 bar)
• Interference emission EN 50081-1
Voltage supply 15 V ... 30 V = / 24∼ ±15 %
• Interference immunity EN 50082-2
Current consumption approx. 12 mA
• Fault limits
Output voltage 0-10 V, Imax = 2 mA
Use position: vertical, deviation of measuring value on
Zero point deviation
±0.75 %
Total of linearity and hysteresis
90° turning 25 Pa: DSG50 ... DSG200
40 Pa: DSG500 ... DSG6000
for measuring range 50 Pa (DSG50): ±1.0 %
Lead length approx. 0.5 m
for measuring range 200Pa (DSG200): ±0.5 %
Connection sockets ("+, -") ∅ 5 mm
Temperature drift zero point:
±0.3 %/10 K
Housing protection IP65
Temperature drift measurement range: ±0.2 %/10 K
Permissible ambient temperature -10…+50 °C
•
•
•
•
*inclusive test certificate
Dimension sheet [mm]
Ziehl-Abegg AG
Heinz-Ziehl-Straße
D-74653 Künzelsau
TIL99_48 1225
Connection diagram
Tel.: +49 (0) 7940 16-0
Fax: +49 (0) 7940 16-504
[email protected]
http://www.ziehl-abegg.de