18-BC85D1-2 - Scott Brothers Heating & Air

18-BC85D1-2
Installer’s Guide
Heat Pumps
4TWB3018–060
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with
the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the
purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
Note: The manufacturer recommends installing only approved matched indoor and outdoor systems. All of the manufacture’s split
systems are AHRI rated only with TXV/EEV indoor systems. Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency, optimum performance and the best overall system reliability.
Table of Contents
Section 1. Safety...................................................................................... 2
Section 2. Unit Location Considerations.............................................. 3
Section 3. Unit Preparation..................................................................... 5
Section 4. Setting the Unit...................................................................... 5
Section 5. Refrigerant Line Considerations.......................................... 6
Section 6. Refrigerant Line Routing...................................................... 7
Section 7. Refrigerant Line Brazing....................................................... 8
Section 8. Refrigerant Line Leak Check.............................................. 10
Section 9. Evacuation............................................................................ 11
Section 10. Service Valves.................................................................... 11
Section 11. Electrical - Low Voltage..................................................... 13
Section 12. Electrical - High Voltage.................................................... 16
Section 13. Start Up............................................................................... 17
Section 14. System Charge Adjustment.............................................. 18
Section 15. Checkout Procedures and Troubleshooting.................... 23
Section 1. Safety
▲! WARNING
This information is intended for use by individuals
possessing adequate backgrounds of electrical and
mechanical experience. Any attempt to repair a central
air conditioning product may result in personal injury
and/or property damage. The manufacture or seller
cannot be responsible for the interpretation of this
information, nor can it assume any liability in connection with its use.
▲! WARNING
These units use R-410A refrigerant which operates
at 50 to 70% higher pressures than R-22. Use only
R-410A approved service equipment. Refrigerant
cylinders are painted a “Rose” color to indicate the
type of refrigerant and may contain a “dip” tube to
allow for charging of liquid refrigerant into the system. All R-410A systems use a POE oil that readily
absorbs moisture from the atmosphere. To limit this
“hygroscopic” action, the system should remain sealed
whenever possible. If a system has been open to the
atmosphere for more than 4 hours, the compressor oil
must be replaced. Never break a vacuum with air and
always change the driers when opening the system
for component replacement. For specific handling
concerns with R-410A and POE oil reference Retrofit
Bulletins SS-APG006-EN and APP-APG011-EN or
APPAPG012-EN.
▲! WARNING
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and troubleshooting of this product, it may be necessary to work
with live electrical components. Failure to follow all
electrical safety precautions when exposed to live
electrical components could result in death or serious
injury.
▲! CAUTION
If using existing refrigerant lines make certain that all
joints are brazed, not soldered.
! CAUTION
▲
Scroll compressor dome temperatures may be hot. Do
not touch the top of compressor; it may cause minor to
severe burning.
▲! WARNING
UNIT CONTAINS R-410A REFRIGERANT!
R-410A operating pressures exceed the limit of R-22.
Proper service equipment is required. Failure to use
proper service tools may result in equipment damage
or personal injury.
SERVICE
USE ONLY R-410A REFRIGERANT AND APPROVED POE COMPRESSOR OIL.
▲! WARNING
Extreme caution should be exercised when opening
the Liquid Line Service Valve. Turn counterclockwise
until the valve stem just touches the rolled edge. No
torque is required. Failure to follow this warning will
result in abrupt release of system charge and may
result in personal injury and /or property damage.
218-BC85D1-2
Section 2. Unit Location Considerations
2.1 Unit Dimensions and Weight
Table 2.1
Unit Dimensions and Weight
Models
H x D x W (in)
Weight* (lb)
4TWB3018D
29 x 30 x 33
160
4TWB3024D
29 x 30 x 33
160
4TWB3030C
33 x 30 x 33
193
4TWB3036C
33 x 34 x 37
198
4TWB3042B
33 x 34 x 37
219
4TWB3048B
37 x 34 x 37
234
4TWB3060B
41 x 34 x 37
248
W
H
* Weight values are estimated.
When mounting the outdoor unit on a roof, be
sure the roof will support the unit’s weight.
D
Properly selected isolation is recommended to
alleviate sound or vibration transmission to the
building structure.
2.2 Refrigerant Piping Limits
1. The maximum length of refrigerant lines
from outdoor to indoor unit should NOT
exceed sixty (60) feet.
2. The maximum vertical change should not
exceed sixty (60) feet.
3. Service valve connection diameters are
shown in Table 5.1.
Note: For line lengths greater than sixty (60)
feet, Refer to Refrigerant Piping Application
Guide, SS-APG006-EN or Refrigerant Piping
Software Program, 32-3312-03 (or latest revision).
Standard
Line Set
60’ Max
Line Length
60’
Max
Vertical
Change
60’
Max
Vertical
Change
18-BC85D1-2
3
2.3 Suggested Locations for Best Reliability
Ensure the top discharge area is unrestricted for
at least five (5) feet above the unit.
Avoid Install
Near Bedrooms
Three (3) feet clearance must be provided in
front of the control box (access panels) and any
other side requiring service.
It is not recommended to install in a location
where noise may distract the building occupants. Some examples of these types of locations are sleeping quarters and by windows of
a living area. Please discuss location with the
building owner prior to installation.
Min 5’ Unrestricted
Min. 12” to
Shrubbery
Min 3’
Unrestricted
Access Panel
Avoid locations such as near windows where
condensation and freezing defrost vapor can
annoy a customer.
Position the outdoor unit a minimum of 12” from
any wall or surrounding shrubbery to ensure
adequate airflow.
Outdoor unit location must be far enough away
from any structure to prevent excess roof runoff
water or icicles from falling directly on the unit.
Min. 12” to
Shrubbery
Min. 12”
to Wall
2.4 Cold Climate Considerations
NOTE: It is recommended that these precautions be taken for units being installed in areas
where snow accumulation and prolonged below
freezing temperatures occur.
• Units should be elevated 3-12 inches above
the pad or roof­top, depending on local
weather. This additional height will allow
drainage of snow and ice melted during
defrost cycle prior to its refreezing. Ensure
that drain holes in unit base pan are not
­obstructed preventing draining of defrost
water.
• If possible, avoid locations that are likely to
accumulate snow drifts. If not possible, a
snow drift barrier should be installed around
the unit to prevent a build-up of snow on the
sides of the unit.
Min. 12”
Snow
Barrier
Snow Legs
3-12” Elevation
Pad
418-BC85D1-2
2.5 Coastal Considerations
If installed within one mile of salt water, including seacoasts and inland waterways, models without factory supplied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at installation time.
Section 3. Unit Preparation
3.1 Prepare The Unit For Installation
STEP 1 - Check for damage and report promptly to the carrier any damage found to the unit.
STEP 2 - To remove the unit from the pallet,
remove tabs by cutting with a sharp tool.
Section 4. Setting the Unit
4.1 Pad Installation
When installing the unit on a support pad, such
as a concrete slab, consider the following:
• The pad should be at least 1” larger than the
unit on all sides.
• The pad must be separate from any structure.
• The pad must be level.
• The pad should be high enough above grade
to allow for drainage.
• The pad location must comply with National,
State, and Local codes.
18-BC85D1-2
5
Section 5. Refrigerant Line Considerations
5.1 Refrigerant Line and Service Valve Connection Sizes
Table 5.1
Line Sizes
Service Valve Connection Sizes
Model
Vapor
Line
Liquid
Line
Vapor Line
Connection
Liquid Line
Connection
4TWB3018D
5/8
3/8
5/8
3/8
4TWB3024D
5/8
3/8
5/8
3/8
4TWB3030C
3/4
3/8
3/4
3/8
4TWB3036C
3/4
3/8
3/4
3/8
4TWB3042B
3/4
3/8
3/4
3/8
4TWB3048B
7/8
3/8
7/8
3/8
4TWB3060B
7/8
3/8
7/8
3/8
5.2 Factory Charge
Outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit,
fifteen (15) feet of tested connecting line, and the smallest indoor evaporative coil match. If connecting line
length exceeds fifteen (15) feet and/or a larger indoor evaporative coil is installed, then final refrigerant
charge adjustment is necessary.
5.3 Required Refrigerant Line Length
Determine required line length and lift. You will
need this later in STEP 2 of Section 14.
Total Line Length = __________ Ft.
Line Length
Total Vertical Change (lift) = __________ Ft.
5.4 Refrigerant Line Insulation
Important: The Vapor Line must always be
insulated. DO NOT allow the Liquid Line and
Vapor Line to come in direct (metal to metal)
contact.
Liquid Line
Vapor Line
Insulation
618-BC85D1-2
5.5 Reuse Existing Refrigerant Lines
▲! CAUTION
If using existing refrigerant lines make certain that
all joints are brazed, not soldered.
For retrofit applications, where the existing
indoor evaporator coil and/or refrigerant lines
will be used, the following precautions should
be taken:
• Ensure that the indoor evaporator coil and
refrigerant lines are the correct size.
• Ensure that the refrigerant lines are free of
leaks, acid, and oil.
Important: For more information see publication numbers SS-APG006-EN.
Section 6. Refrigerant Line Routing
6.1 Precautions
Important: Take precautions to prevent noise
within the building structure due to vibration
transmission from the refrigerant lines.
Comply with National, State, and Local Codes when
isolating line sets from joists, rafters, walls, or other
structural elements.
For Example:
• When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type
hangers.
• Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
• Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
• Isolate the lines from all ductwork.
•Minimize the number of 90º turns.
8 Feet Maximum
Joist/Rafter
Isolator
Side View
8 Feet Maximum
Line Set
Secure Vapor line from joists using isolators every 8 ft. Secure
Liquid Line directly to Vapor line using tape, wire, or other appropriate method every 8 ft.
Isolation From Joist/Rafter
18-BC85D1-2
7
8 Feet Maximum
Wall
Isolator
8 Feet Maximum
Side View
Line Set
Secure Vapor Line using isolators every 8 ft. Secure Liquid Line
directly to Vapor Line using tape, wire, or other appropriate
method every 8 ft.
Isolation In Wall Spaces
Wall
Sealant
Ductwork
Insulation
Vapor Line
Isolator
Line Set
Isolation Through Wall
DO NOT hang line sets from ductwork
Section 7. Refrigerant Line Brazing
7.1 Braze The Refrigerant Lines
STEP 1 - Remove caps or plugs. Use a deburing tool to debur the pipe ends. Clean both
internal and external surfaces of the tubing
using an emery cloth.
818-BC85D1-2
STEP 2 - Remove the pressure tap cap and
valve cores from both service valves.
STEP 3 - Purge the refrigerant lines and indoor
coil with dry nitrogen.
STEP 4 - Wrap a wet rag around the valve
body to avoid heat damage and continue the
dry nitrogen purge.
Braze the refrigerant lines to the service
valves.
Continue the dry nitrogen purge. Do not remove the wet rag until all brazing is completed.
Important: Remove the wet rag before stopping
the dry nitrogen purge.
NOTE: Precautions should be taken to avoid
heat damage to basepan during brazing. It is
recommended to keep the flame directly off of
the basepan.
18-BC85D1-2
9
STEP 5 - Replace the pressure tap valve cores
after the service valves have cooled.
Section 8. Refrigerant Line Leak Check
8.1 Check For Leaks
STEP 1 - Pressurize the refrigerant lines and
evaporator coil to 150 PSIG using dry nitrogen.
150 PSIG
STEP 2 - Check for leaks by using a soapy solution or bubbles at each brazed location.
Remove nitrogren pressure and repair any leaks
before continuing.
1018-BC85D1-2
Section 9. Evacuation
9.1 Evacuate the Refrigerant Lines and Indoor Coil
Important: Do not open the service valves until
the refrigerant lines and indoor coil leak check
and evacuation are complete.
0350
Microns
STEP 1 - Evacuate until the micron gauge reads
no higher than 350 microns, then close off the
valve to the vacuum pump.
ON
OFF
STEP 2 - Observe the micron gauge. Evacuation
is complete if the micron gauge does not rise
above 500 microns in one (1) minute.
1 MIN.
Once evacuation is complete blank off the
vacuum pump and micron gauge, and close the
valves on the manifold gauge set.
Section 10. Service Valves
10.1 Open the Gas Service Valve
Important: Leak check and evacuation must be
completed before opening the service valves.
CAP
NOTE: Do not vent refrigerant gases into the
atmosphere.
VALVE STEM
STEP 1 - Remove valve stem cap.
STEP 2 - Using an adjustable wrench, turn valve
stem 1/4 turn counterclockwise to the fully open
position.
STEP 3 - Replace the valve stem cap to prevent
leaks. Tighten finger tight plus an additional 1/6
turn.
1/4 TURN ONLY
COUNTERCLOCKWISE
FOR FULL OPEN
POSITION
UNIT SIDE
OF VALVE
PRESSURE TAP PORT
GAS LINE CONNECTION
18-BC85D1-2
11
10.1 Open the Liquid Service Valve
▲! WARNING
Extreme caution should be exercised when
opening the Liquid Line Service Valve. Turn
counterclockwise until the valve stem just
touches the rolled edge. No torque is required.
Failure to follow this warning will result in abrupt
release of system charge and may result in
personal injury and /or property damage.
Cap
Unit Side
of Service
Valve
3/16” Hex Wrench
Rolled Edge to
Captivate Stem
Important: Leak check and evacuation must be
completed before opening the service valves.
Hex Headed
Valve System
STEP 1 - Remove service valve cap.
STEP 2 - Fully insert 3/16” hex wrench into the
stem and back out counterclockwise until valve
stem just touches the rolled edge (approximately
five (5) turns.)
Service Port
STEP 3 - Replace the valve cap to prevent leaks.
Tighten finger tight plus an additional 1/6 turn.
Section 11. Electrical - Low Voltage
11.1 Low Voltage Maximum Wire Length
Table 11.1 defines the maximum total length of
low voltage wiring from the outdoor unit, to the
indoor unit, and to the thermostat.
Table 11.1
24 VOLTS
WIRE SIZE
MAX. WIRE LENGTH
18 AWG
150 Ft.
16 AWG
225 Ft.
14 AWG
300 Ft.
1218-BC85D1-2
11.2 Low Voltage Hook-up Diagrams
Communicating Indoor Unit
with 24 V Control Hook-up
Diagram
Heat Pump
Neatly bundle all low voltage
wires as shown.
Comm. Variable Speed
Furnace or Air Handler
R
BK
D
Y1
Y2
G
W1
W2
W3
B
O
Comfort Control
R
Y1
Red
Yellow
G
W1
X2
Green
White
B
O
Blue
Orange
Orange
Red
Red
Black
Yellow
(X2)
Yellow
Blue
Black
Blue
Orange
Notes:
1. See User Interface 24
V Mode setup menu
for control mode and
cooling CFM options.
2. W3 terminal may not
be present on unit.
3. (Air Handlers only) If
electric heat does not
have 3rd contactor (CH), connect
a jumper wire from
W3 to W2. If electric
heat does not have
2nd contactor (BH),
connect a jumper wire
from W2 to W1.
4. W1 - X2 is a field
installed jumper.
Variable Speed Furnace
Hook-up Diagram
Heat Pump
Neatly bundle all low voltage
wires as shown.
Variable Speed
Furnace
Comfort Control
R
Y1
Red
Yellow
G
W1
X2
B
O
Green
White
Blue
Orange
R
YLO
Y
BK
G
W1
W2
B
O
Orange
Red
Red
Yellow
18-BC85D1-2
Black
(X2)
Yellow
Blue
Black
Blue
Notes:
1. Comfort control must
be dual fuel capable
or use accessory
TAYPLUS103A.
2. Ylo and BK may not be
present on unit.
3. W1 - X2 is a field
installed jumper.
Orange
13
TAM7 Air Handler
Hook-up Diagram
Heat Pump
Neatly bundle all low voltage
wires as shown.
Black
Air Handler
(X2)
Comfort Control
Blue
W1 - White
Yellow
Red
O - Orange
R - Red
B - Blue
Y1 - Yellow
Control Board
OUTDOOR
DH/BK
on
Must configure to
“OFF” for HP Units.
HP
1
1
R4
1 2 3 4 5
Field wiring
} Capacity (Tons)
AC (System)
2 (Stages)
2 (Compressor)
S1
1
INDOOR
R NET 1
R6
R1
on
R NET 2
CFM/Ton
Cool Off Delay
U1
C22
D9
C10
L1
C19
Torque
R14
C21
C15
C18
C12
R13
R22
1 2 3 4 5
Must configure to “OFF” for
single-stage compressors.
}
White
Green
Yellow
Orange
Red
Blue
Orange
}
X2
W
G
Y1
O
R
B
W3
W2
W1
G
YI (In)
O
R
B
YO (Out)
CFM
S2
+12V
TAM4 Air Handler
Hook-up Diagram
W2 Pink
W3 Brown
W1 White *
Yello
w
Orange
Purple YO
YI
Bl
ue
n
Gree
d
Re
Heat Pump
Yellow
Comfort Control
Black
Air Handler
(X2)
Orange
White
Green
Yellow
Orange
Red
Blue
W
G
Y
O
R
B
Field wiring
Y - Yellow
Blue
Red
O - Orange
B - Blue
R - Red
W1 - White
•• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat
•• YI and YO connections must be made as shown for proper operation, freeze protection, and internally mounted condensate
overflow circuits to work properly
•• Internally mounted condensate switch is optional and must be ordered separately
•• If a 3rd party condensate overflow switch is installed, it should be wired between Y of the thermostat and YI of the EEV control.
•• Some models have a terminal strip. Refer to air handler Installer’s Guide.
1418-BC85D1-2
GAM5 Air Handler
Hook-up Diagram
Heat Pump
W2 Pink
W3 Brown
W1 White
e
d
Re
Yellow
Blu
Green
Air Handler
Comfort Control
White
Green
Yellow
Orange
Red
Blue
W
G
Y
O
R
B
Black
(X2)
Orange
White
Green
Yellow
Orange
Red
Blue
Yellow
Red
Blue
R - Red
B - Blue
Y - Yellow
•• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat
•• Some models have a terminal strip. Refer to air handler Installer’s Guide.
Field wiring
GAM2 Air Handler
Hook-up Diagram
Heat Pump
W2 Pink
W3 Brown
W1 White
Green
Red
Blue
Air Handler
Comfort Control
White
Green
Yellow
Orange
Red
Blue
W
G
Y
O
R
B
Field wiring
Black
(X2)
Orange
White
Green
Yellow
Orange
Red
Blue
Yellow
Red
Blue
R - Red
B - Blue
Y - Yellow
•• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat
18-BC85D1-2
15
GAF2 Air Handler
Hook-up Diagram
Heat Pump
W1 White
Green
Red
Blue
Air Handler
Comfort Control
White
Green
Yellow
Orange
Red
Blue
W
G
Y
O
R
B
Black
(X2)
Yellow
Orange
White
Green
Yellow
Orange
Red
Blue
Red
Blue
R - Red
B - Blue
Y - Yellow
Field wiring
GAF2-36M Air Handler
Hook-up Diagram
White
n
Yello
w
Orange
Purple YO
YI
Bl
ue
Gree
d
Re
Heat Pump
Air Handler
Yellow
Black
(X2)
Comfort Control
Orange
White
Green
Yellow
Orange
Red
Blue
W
G
Y
O
R
B
Field wiring
Blue
Red
•• YI and YO connections must be made as shown
•• Internally mounted condensate switch is optional and must be ordered separately
•• If a 3rd party condensate overflow switch is installed, it should be wired between Y of the thermostat and YI of the EEV control.
1618-BC85D1-2
11.3 Defrost Control
Defrost controls have a selectable termination temperature. As shipped, defrost will terminate at 47°F. For a
higher termination temperature, cut Jumper J2 to achieve 70°F when at or below 30°F ambient. See Service
Facts shipped in the outdoor unit for more information.
Pin Identification (See Illustration at right)
1. TEST_COMMON (Shorting any of the other pins to this pin causes the function of the other pin to be
executed. Leaving this pin open results in the normal mode of operation.)
2. TST = Test (Shorting TEST_COMMON to this pin speeds up all defrost board timings.)
3. FRC_DFT = Forced Defrost (Short TEST_COMMON to this pin for two (2) seconds to initiate a forced
defrost. Remove the short after defrost initiates.)
Defrost Control Checkout
Normal operation requires:
• LED on board flashing 1 time/second.
• 24V AC between R & B.
• 24V AC between Y & B with unit operating.
• Defrost initiation when FRC_DFT pin is shorted to TEST_COMMON pin.
If a defrost control problem is suspected, refer to the service information in control box.
Defrost Termination Temperatures
As
Shipped
All
Termination
Temperature
>22°F
47°F
Defrost Board
Detail
J1
J2
J3
JUMPER 2
10°F–22°F
ODT + 25°F
6°F–10°F
35°F
>30°F
47°F
6°F–30°F
70°F
< 6°F
12 min. or 35°F
every 3 hrs.
18-BC85D1-2
FRC_DFT
TEST PINS
TST
TEST_COMMON
Cut
Jumper 2
Outdoor
Temperature
U1
17
Section 12. Electrical - High Voltage
12.1 High Voltage Power Supply
▲! WARNING
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and
troubleshooting of this product, it may be necessary to work with live electrical components.
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
The high voltage power supply must agree with
the equipment nameplate.
Power wiring must comply with national, state,
and local codes.
Follow instructions on unit wiring diagram located
on the inside of the control box cover and in the
Service Facts document included with the unit.
12.2 High Voltage Disconnect Switch
Install a separate disconnect switch at the
outdoor unit.
For high voltage connections, flexible electrical conduit is recommended whenever vibration transmission may create a noise problem
within the structure.
12.3 High Voltage Ground
Ground the outdoor unit per national, state, and
local code requirements.
1818-BC85D1-2
Section 13. Start Up
13.1 System Start Up
STEP 1 - Ensure Sections 7 through 12 have
been completed.
STEP 2 - Set System Thermostat to OFF.
OFF
DONE
CANCEL
STEP 3 - Turn on disconnect(s) to apply power
to the indoor and outdoor units.
ON
OFF
STEP 4 - Wait one (1) hour before starting the
unit if compressor crankcase heater accessory is used and the Outdoor Ambient is below
70ºF.
60 MIN.
STEP 5 - Set system thermostat to ON.
ON
DONE
18-BC85D1-2
CANCEL
19
Section 14. System Charge Adjustment
14.1 Temperature Measurements
STEP 1 - Check the outdoor temperatures.
Subcooling (in cooling mode) is the only recommended method of charging above 55º F ambient outdoor temperature. See Section 14.2.
120º F
See Section 14.2 for
Outdoor
Temperatures
Above 55º F
55º F
Outdoor Temp 1
For outdoor temperatures below 55º F, see Section 14.3.
Note: It is important to return in the spring or
summer to accurately charge the system in the
cooling mode when outdoor ambient temperature is above 55º F.
See Section 14.3 for
Outdoor
Temperatures
Below 55º F
55º F
Outdoor Temp 2
For best results the indoor temperature should
be kept between 70º F to 80º F.
80º F
70º F
Indoor Temp
14.2 Subcooling Charging in Cooling (Above 55º F Outdoor Temp.)
STEP 1 - Use the refrigerant line total length
and lift measurements from Section 5.3.
Total Line Length = __________ Ft.
Vertical Change (Lift) = __________ Ft.
LIFT
2018-BC85D1-2
STEP 2 - Determine the final subcooling value using total Line Length and Lift measured in STEP 1 and the charts below.
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
REFRIGERANT LINE LIFT (FEET)
2 Ton Heat Pump
REFRIGERANT LINE LIFT (FEET)
1 1/2 Ton Heat Pump
60
Add 3°
50
Add 2°
Add 1° of Subcooling
40
30
25
20
Use Design Subcool Value
15
10
0
10
20
25
30
40
60
TOTAL REFRIGERANT LINE LENGTH (FEET)
Add 4°
60
Add 2°
50
Add 1° of Subcooling
40
30
25
20
15
Use Design Subcool Value
10
0
10
20
25
30
40
60
TOTAL REFRIGERANT LINE LENGTH (FEET)
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
REFRIGERANT LINE LIFT (FEET)
3 Ton Heat Pump
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
REFRIGERANT LINE LIFT (FEET)
2 1/2 Ton Heat Pump
60
Add 4°
50
Add 3°
Add 2° of Subcooling
40
Add 1° of Subcooling
30
25
20
Use Design Subcool Value
15
10
0
10
20
25
30
40
60
TOTAL REFRIGERANT LINE LENGTH (FEET)
Add 5°
60
Add 4°
50
Add 3° of Subcooling
40
30
Add 2°
Add 1° of Subcooling
25
20
15
Use Design Subcool Value
10
0
10
20
25
30
40
60
TOTAL REFRIGERANT LINE LENGTH (FEET)
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
REFRIGERANT LINE LIFT (FEET)
4 Ton Heat Pump
REFRIGERANT LINE LIFT (FEET)
3 1/2 Ton Heat Pump
Add 6°
60
Add 5°
50
Add 3° of Subcooling
40
Add 2° of Subcooling
30
25
Add 1° of Subcooling
20
15
Use Design Subcool Value
10
0
10
20
25
30
40
60
TOTAL REFRIGERANT LINE LENGTH (FEET)
60
Add 6°
50
Add 4° of Subcooling
40
Add 3° of Subcooling
30
25
20
15
10
0
Add 2° of Subcooling
Add 1° of Subcooling
Use Design Subcool Value
10
20
25
30
40
60
TOTAL REFRIGERANT LINE LENGTH (FEET)
5 Ton Heat Pump
REFRIGERANT LINE LIFT (FEET)
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
Design Subcooling Value = __________º F
(from nameplate or Service Facts)
Add 6°
50
40
Add 5° of Subcooling
30
Add 4° of Subcooling
Subcooling Correction = __________º F
25
20
Add 2° of Subcooling
15
10
0
Design
Add 3° of Subcooling
Add 1° of Subcooling
Final Subcooling Value = __________º F
10
20
25
30
40
60
TOTAL REFRIGERANT LINE LENGTH (FEET)
STEP 3 - Stabilize the system by operating for a
minimum of 20 minutes.
At startup, or whenever charge is removed or
added, the system must be operated for a minimum of 20 minutes to stabilize before accurate
measurements can be made.
18-BC85D1-2
20 MIN.
21
STEP 4 - Measure the liquid line temperature
and pressure at the outdoor unit’s service valve.
Measured Liquid Line Temp = __________ º F
Liquid Gage Pressure = __________ PSI
Final Subcooling Value = __________ º F
STEP 5 - Use the final subcooling value, refrigerant temperature and pressure from STEP 4, to
determine the proper liquid gage pressure using
Table 14.2.
Example: Assume a 12º F Final Subcooling
value and liquid temp of 90º F.
1. Locate 12º F Final Subcooling in Table 14.2.
2. Locate the Liquid Temperarature (90º F) in
the left column.
3. The Liquid Gage Pressure should be approximately 327 PSIG. (This is the shown as
the intersection of the Final Subcooling column
and the Liquid Temperature row.
107 °F
Table 14.2
R-410A REFRIGERANT CHARGING CHART
FINAL SUBCOOLING (°F)
LIQUID
8
9
10 11 12 13 14
TEMP
(°F)
LIQUID GAGE PRESSURE (PSI)
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
179
195
211
229
247
267
287
309
331
355
381
407
435
464
495
182
198
215
232
251
271
291
313
336
360
386
413
441
470
501
185
201
218
236
255
275
296
318
341
365
391
418
446
476
507
188
204
222
240
259
279
300
322
346
370
396
424
452
482
514
191
208
225
243
263
283
304
327
351
376
402
429
458
488
520
195
211
229
247
267
287
309
331
355
381
407
435
464
495
527
198
215
232
251
271
291
313
336
360
386
413
441
470
501
533
From Dwg. D154557P01 Rev. 3
2218-BC85D1-2
STEP 6 - Adjust refrigerant level to attain
proper gage pressure.
Add refrigerant if the Liquid Gage Pressure
is lower than the chart value.
1. Connect gages to refrigerant bottle
and unit as illustrated.
2. Purge all hoses.
3. Open bottle.
4. Stop adding refrigerant when liquid
line temperature and Liquid Gage
Pressure matches the charging chart
Final Subcooling value.
Recover refrigerant if the Liquid Gage Pressure is higher than the chart value.
STEP 7 - Stabilize the system.
1. Wait 20 minutes for the system condition to stabilize between adjustments.
20 MIN.
Note: When the Liquid Line Temperature and
Gage Pressure approximately match the chart,
the system is properly charged.
2. Remove gages.
3. Replace service port caps to prevent
leaks. Tighten finger tight plus an additional 1/6 turn.
STEP 8 - Verify typical performance.
(Example only - see Service Facts)
PRESSURE TABLES FOR 4TWB30**
*AM4A0****** Air Handler
Heating
Cooling
Outdoor Size & AH
OD **
AH******
18
A18S11
24
A24S21
30
A30S21
36
A36S31
42 3
B42S31
Outdoor Size & AH
48
C48S41
60
C60S51
515
485
455
425
395
370
335
320
300
280
260
225
540
510
480
450
420
390
365
345
320
300
280
260
48
C48S41
60
C60S51
155
148
140
134
151
144
137
131
148
141
134
127
146
139
132
125
143
136
129
123
141
134
127
121
154
146
137
130
150
142
134
126
146
138
131
123
144
136
128
121
141
133
126
118
138
131
123
116
OD **
AH******
Discharge Pressure (PSIG)
490
460
435
405
375
350
325
305
285
265
245
225
515
485
455
425
395
370 4
335
320
300
280
260
225
Outdoor Size & AH
OD **
AH******
Outdoor
Temp.
Indoor Wet
Bulb
(Degree F)
(Degree F)
110
100
90 1
80
70
60
18
A18S11
24
A24S21
30
A30S21
71
67
63
59
71
67
63
59
71
67 2
63
59
71
67
63
59
71
67
63
59
71
67
63
59
36
A36S31
42 3
B42S31
55
45
35
25
153
146
139
132
148
141
134
128
144
137
131
124
141
134
128
122
138
131
125
119
135
128
122
116
154
147
139
133
150
143
136
129
147
139 4
133
127
144
137
131
124
141
134
128
122
139
132
125
119
15
5
-5
30
A30S21
36
A36S31
42
B42S31
48
C48S41
60
C60S51
445
405
365
420
385
345
395
360
325
380
345
305
365
325
285
345
305
270
325
285
255
315
275
235
445
405
365
415
380
345
395
355
320
380
340
305
355
320
285
335
300
265
320
280
245
305
265
230
48
C48S41
60
C60S51
142
120
98
83
68
55
44
35
134
114
94
81
66
53
42
33
Discharge Pressure (PSIG)
80
70
60
80
70
60
80
70
60
80
70
60
80
70
60
80
70
60
80
70
60
80
70
60
65
Suction Pressure (PSIG)
154
146
138
131
149
141
134
127
145
137
130
123
141
134
127
120
138
131
124
117
135
128
121
114
24
A24S21
Indoor
Entering
(Deg.F)
Outdoor Temperature (Degree F)
510
480
450
425
390
365
340
315
290
275
255
235
480
440
400
455
415
375
430
390
350
415
370
335
390
350
310
370
330
290
350
310
270
335
290
255
485
445
405
460
420
380
435
390
355
420
375
335
390
350
310
370
330
290
350
310
270
335
290
255
435
395
355
410
370
335
390
350
315
375
335
295
355
315
280
335
295
265
320
275
245
300
265
225
Outdoor Size & AH
OD **
AH******
18
A18S11
24
A24S21
30
A30S21
36
A36S31
42
B42S31
Suction Pressure (PSIG)
Outdoor Temperature
(Degree F)
Outdoor Temperature (Degree F)
Refer to System Pressure Tables in the Service
Facts to verify typical performance.
115
110
105
100
95
90 1
85
80
75
70
65
60
18
A18S11
65
55
45
35
25
15
5
-5
142
120
100
83
69
56
44
35
150
127
105
89
74
60
49
40
138
116
96
82
67
53
42
32
OUTDOOR TEMPERATURE (Degree F)
COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, DISCHARGE AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); LOCATE MODEL OUTDOOR (3); FIND INTERSECTION BETWEEN 1, 2, & 3 . (4) FIND TARGET PRESSURE.
EXAMPLE:
(1) OUTDOOR TEMP. 90 F.
(2) INDOOR WET BULB 67 F.
(3) OD 4TWB3042
(4) DISCHARGE PRESSURE IS 370 PSIG DISCHARGE PRESSURE
(5) SUCTION PRESSURE IS 139 PSIG SUCTION PRESSURE
ACTUAL:
SHOULD BE +/­ 10 PSIG OF CHART
SHOULD BE +/­ 3 PSIG OF CHART
INTERCONNECTING LINES
GAS ­ 3/4" O.D.
LIQUID ­ 3/8" O.D.
18-BC85D1-2
23
STEP 9 - Record System Information for reference.
Record system pressures and temperatures
after charging is complete.
Outdoor model number = _________________
Measured Suction Line Temp = __________ º F
Measured Outdoor Ambient = __________ º F
Liquid Gage Pressure = __________ PSIG
Measured Indoor Ambient = __________ º F
Suction Gage Pressure = __________ PSIG
Measured Liquid Line Temp = __________ º F
14.3 Subcooling Charging Below 55º F Outdoor Temp. (In Heating Only)
The Subcooling Charging method in cooling is
not recommended below 55º F outdoor temperature.
The only recommended method of charging at
outdoor temperatures below 55º F is weighing
in the charge in heating mode.
Table 14.3
STEP 1 - Determine additional charge.
From the nameplate label (shown in Section
12.1), record namplate charge below.
Note: The nameplate charge value represents
the amount of refrigerant shipped in the outdoor
unit and is compatible with 15 feet of AHRI rated
refrigerant lines and the smallest AHRI rated
coil.
Using Table 14.3, find the charge associated
with the additional length of tubing above 15 ft.
and record it below.
TUBING INFORMATION
LINE TYPE
REFRIGERANT TO ADD AT
SPECIFIED ADDITIONAL
LENGTH
Suction
Line
Liquid
Line
20 ft
30 ft
40 ft
1.5 – 2 Ton
5/8"
3/8"
3 oz
8 oz
14 oz 20 oz 25 oz
2.5 – 3.5 Ton
3/4"
3/8"
3 oz
9 oz
15 oz 21 oz 27 oz
4 – 5 Ton
7/8"
3/8"
3 oz
9 oz
16 oz 22 oz 28 oz
Tonnage
50 ft
60 ft
Namplate charge = ____________ Oz.
Charge adder = ______________ Oz.
(from Table 14.2)
2418-BC85D1-2
STEP 2 - Stabilize the system by operating for a
minimum of 20 minutes.
At startup, or whenever charge is removed or
added, the system must be operated for a minimum of 20 minutes to stabilize before accurate
measurements can be made.
20 MIN.
STEP 3 - Check the liquid line temperature and
liquid gage pressure to obtain a minimum of 10º
subcooling in heating mode.
Measured Liquid Line Temp = __________ º F
Liquid Gage Pressure = __________ PSIG
STEP 4 - Add charge if a minimum of 10º subcooling is not obtained with the namplate charge
plus additional charge previously added.
STEP 5 - Return to site for adjustment.
Important: Return in the spring or summer to
accurately charge the system in the cooling
mode with outdoor ambient above 55º F.
18-BC85D1-2
25
Section 15. Checkout Procedures and Troubleshooting
15.1 Operational And Checkout Procedures
Final phases of this installation are the unit Operational and Checkout Procedures. To obtain proper performance, all units
must be operated and charge adjustments made.
Important: Perform a final unit inspection to be sure that factory tubing has not shifted during shipment. Adjust tubing if necessary so tubes do not rub against each other when the unit runs. Also be sure that wiring connections are tight and properly
secured.
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list:
1. Leak check refrigerant lines. ......................................... [ ]
2. Properly insulate suction lines and fittings..................... [ ]
3. Properly secure and isolate all refrigerant lines............. [ ]
4. Seal passages through masonry.
If mortar is used, prevent mortar from coming
into direct contact with copper tubing............................ [ ]
5. Verify that all electrical connections are tight................. [ ]
6. Observe outdoor fan during on cycle for clearance
and smooth operation.................................................... [ ]
7. Be sure that indoor coil drain line drains freely. Pour water
into drain pan................................................................. [ ]
8. Be sure that supply registers and return grilles are .open
and unobstructed........................................................... [ ]
9. Be sure that a return air filter is installed....................... [ ]
10. Be sure that the correct airflow setting is used.
(Indoor blower motor).................................................... [ ]
11. Operate complete system in each mode to
ensure safe operation.................................................... [ ]
2618-BC85D1-2
15.2 Troubleshooting
.
DEF
OL
NTR DEF.
CO
Y
ST RELA ING
RO
K
T
D E F F RO S
LEA E
DE VALVE ECTIV
CK
DEF NG
CHE COIL LEAKI
S
SOV SOV CTION
T R I OW
RES AIRFL
IR.
EAT
.C
I.D.
R E F R E S. U P E R H N
S
PE
KO
TUC ION
V S CULAT
/EE
W
R
TXV RECI IRFLO
R
. A LES
D
.
. AI
B
O.D RES. O ENSA D
ND
L OA
NCO AP.
NO E EV ARGE
H
IV
ESS
ERC GE
EXC EF. OV CHAR .
R
P
R
NDE T COM
.U
REF FICIEN SSOR
E
F
INE OMPR USE
F
C
CK
IL
AG E
STU VOLT R CO
CTO STAT
L OW
O
NTA
CO HERM ER
M
T
OR
NSF ING
TRA WIR
OL
GE
TS
NTR
LTA NTAC
O
V
CO
CO LAY
E
LOW TOR
C
TR
NTA
TAR TOR
S
CO
AC I
CAP ITOR
C
RT
STA CAPA IOL
RUN SSOR G
RE IRIN
MP
CO AGE W PLY
OLT
SUP E
H V ER
H I G P OW K M O D
C
CHE
TO
AT
*
WH
SYSTEM FAULTS
REFRIGERANT CIRCUIT
Head Pressure Too High
Head Pressure Too Low
Suction Pressure Too High
Suction Pressure Too Low
Liquid Refrig. Floodback (TXV/EEV)
Liquid Refrig. Floodback
(Cap. Tube)
I.D. Coil Frosting
Compressor Runs
Inadequate or No Cooling/Htg
ELECTRICAL
Compressor & O.D. Fan
Won’t Start
Compressor Will Not Start
But O.D. Fan Runs
O.D. Fan Won’t Start
Compressor Hums But Won’t Start
Compressor Cycles on IOL
I.D. Blower Won’t Start
P
P
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
S
S
S
S
P
P
S
S
P
S
P
P
P
S
S
P
P
P
P
S
S
S
S
S
S
S
S
P
S
S
S
S
S
S
P
P
S
S
S
S
P
P
P
P
P
P
S
S
S
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
S
S
S
S
S
S
P
P
P
P
P
P
P
P
S
S
S
S
S
S
S
S
S
S
S
S
P
P
S
S
P
P
S
S
P
P
S
S
P
P
S
S
S
S
S
S
P
P
P
S
S
P
S
S
P
P
S
S
P
S
S
S
S
S
S
S
S
P
P
P
P
S
S
S
S
S
S
S
S
P
P
P
P
S
S
P
P
S
S
P
P
S
S
S
S
S
S
S
S
S
DEFROST
Unit Won’t Initiate Defrost
Defrost Terminates on Time
Unit Icing Up
C - Cooling
H - Heating
C
H
C
H
C
H
P - Primary Causes
P
P
P
S - Secondary Causes
18-BC85D1-2
P
P
P
*
S
S
S
P
P
- 3 Phase Only
27
The manufacturer has a policy of continuous product and product data improvement
and it reserves the right to change design and specifications without notice.
Representative-only illustrations included in this document.
© 2013 Trane
04/13
2818-BC85D1-2