fdoot241-a3, fdoot241-a4, fdoot241

FDOOT241-A3, FDOOT241-A4,
FDOOT241-A9, FDOOT241-8
Sinteso™
S-LINE
Multi-sensor fire detectors
for step-wise modernization
ASAtechnologyTM
For the modernization from AnalogPLUS, SIGMALOOP, collective or MS8 to
Sinteso FDnet
Signal processing with ASAtechnology (Advanced Signal Analysis)
Event-controlled detection behavior
Early and reliable detection of emerging fires
High immunity to deceptive phenomena
Highest system availability thanks to redundant sensory analysis
Suitable for air speeds of 1… 20 m/s
Ecological material concept
Building Technologies
CPS Fire Safety
Characteristics
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Environmental benefits
ecologically processing
recyclable materials
electronic und synthetic material simple separable
ecologically beneficial detector testing without gas
Characteristics
resistant to environment and interference factors such as dust, fibers, insects, humidity, extreme temperatures, electro-magnetic interference, corrosive vapors, vibration,
synthetic aerosols and atypical fire phenomena
insensitive to impact, tamper protection
signal processing with ASAtechnology ('Advanced Signal Analysis')
time- and process-dependent detection behavior
proven and tested immunity to power electronics disturbances
protected electronics, high-quality components
sophisticated sensor and electronics surveillance
redundant, high-quality sensor system
built-in alarm indicator (AI), visible at 360°
integrated short-circuit isolator
the same detector base type can be used for all detector types
Multi-sensor fire detectors FDOOT241-A3, FDOOT241-A4, FDOOT241-A9, FDOOT241-8, neural ASA
Function
– works according to the scattered light principle with two sensors, optical forward and
backward scattering
– opto-electronic sampling chamber holds off disturbing extraneous light but optimally
detects both dark and light smoke particles
– two additional heat sensors increase the fire detector’s immunity to deceptive phenomena
– software can be set to multi-sensor smoke detector, smoke detector or heat detector
– selectable detection behavior thanks to application-specific ASA parameter sets
– Multi-protocol:
– FDOOT241-A3 (AnalogPLUS, FDnet)
– FDOOT241-A4 (SIGMALOOP, FDnet)
– FDOOT241-A9: collective/GMT (Cerberus, Siemens) / SynoLINE300, FDnet
– FDOOT241-8 (MS8/PMT, FDnet)
Application
– for the early detection of flaming fires caused by the combustion of liquid and solid
matters, as well as smoldering fires
– for the early and reliable fire detection in environments with deceptive phenomena
– addressable application possible, for the step-by-step modernization from:
– FDOOT241-A3 from AnalogPLUS to Sinteso FDnet ( ) 1
– FDOOT241-A4 from SIGMALOOP to Sinteso FDnet ( )
– FDOOT241-A9 from SynoLINE300 to Sinteso FDnet ( )
– FDOOT241-8 from MS8 to Sinteso FDnet
1
( ) Compatibility with FS20 on FDnet protocol only available if enabled in your country-specific FS20 software
2
Building Technologies
CPS Fire Safety
Installation
Easy, time-saving mounting
– no wiring required, base adapter FDB281/FDB241/FDB299 already pre-wired
– remove detector AnalogPLUS, SIGMALOOP, collective or MS8
– FDB241
base adapter for AnalogPLUS (DB1131A)
base adapter for SIGMALOOP (SPF3600)
base adapter for Interaktiv (DB1151A)
– turn detectors FDOOT241-A3 or FDOOT241-A4 in the base adapter FDB241 and
simply turn into both units into the AnalogPLUS base or SIGMALOOP base, by hand
or with the detector exchanger (and tester)
FDB241
Base adapter
AnalogPLUS (DB1131A) or
SIGMALOOP (SPF3600) detector base
FDOOT241-A3 / FDOOT241-A4
Multi-sensor smoke detector
Alarm indicator
FDUD291 detector exchanger or
FDUD292 detector exchanger and
tester
– FDB299
base adapter for AlgoRex collective (DB1101A)
base adapter for SIGMACON (SPF600)
– turn detector FDOOT241-A9 in the base adapter FDB299 and simply turn into both
units into the collective detector base DB1101A or SPF600, by hand or with the detector exchanger (and tester).
FDB299
Base adapter
AlgoRex-collective (DB1101A) or
SIGMACON (SPF600) detector base
FDOOT241-A9
Multi-sensor smoke detector
Alarm indicator
FDUD291 detector exchanger or
FDUD292 detector exchanger and
tester
3
Building Technologies
CPS Fire Safety
– FDB281 base adapter for MS8
– turn detector FDOOT241-8 in the base adapter FDB281 and simply turn into both
units into the MS8 detector base, by hand or with the detector exchanger (and tester).
FDB281
Base adapter
Detector base MS8
FDOOT241-8
Multi-sensor smoke detector
Alarm indicator
FDUD291 Detector exchanger or
FDUD292 Detector exchanger and
tester
Efficiency on site
– no wiring, only detector exchange
– detector exchange without ladder up to 8 m height with detector exchanger
FDUD291 or detector exchanger and tester and telescope rod or extension rod
4
Building Technologies
CPS Fire Safety
Dimensions
Ø100
45.6
49.5
with base FDB222 for gap free ceiling mounting,
only for recess cable entry
54.5
45.6
with base FDB2x1, FDB2x1-AA for surface cable to Ø6 mm
possible
Ø100
Detector bases AnalogPLUS (DB1131)- or
SIGMALOOP (SPF3600)- or
Collective (DB1101A)
Base adapter FDB241 or FDB299
Multi-Sensor fire detector FDOOT241-A3,
FDOOT241-A4, FDOOT241-A9
Detector base MS8
Base adapter FDB281
Multi-Sensor smoke detector FDOOT241-8
5
Building Technologies
CPS Fire Safety
Technical data
FDOOT241-A3
FDOOT241-A4
FDOOT241-8
FDOOT241-A9
FDOOT241-8,
FDOOT241-A3,
FDOOT241-A4
FDOOT241-A9
Operating voltage
In detector system
In detector system
In detector system
In detector system
AnalogPLUS
SIGMALOOP
MS8
collective
DC 16... 28 V
DC 14... 28 V
DC 14... 28 V
DC 14... 28 V
DC 12... 33 V
200 A
200 A
200 A
200 A
200... 280 A
2
2
not supported
(1 internal + 1 exter-
(1 internal + 1 exter-
nal connectable)
nal connectable)
in FDnet
(modulated)
Operating current
(quiescent)
Alarm indicator
(AI)
2
2
(1 internal + 1 exter-
(1 internal + 1 exter-
nal connectable)
nal connectable)
AnalogPLUS
SIGMALOOP
MS8/PMT
collective
FDnet
AlgoRex
SIGMASYS
SIGMASYS, BMS,
AlgoRex
FS20 ( )
SM80/88/D100, SRS
SIGMASYS,
Communication
protocol
System compatibility
2
CZ10
Operating tem-
-25... +70 °C
-25... +70 °C
-25... +70 °C
-35... +70°C
-30... +75 °C
-30... +75 °C
-30... +75 °C
-35... +75°C
perature
Storage temperature
Humidity
95 % rel.
Color
white, ~RAL 9010
Protection cat.
EN60529/IEC529
– base FDB221,
FDB222
IP43
– base attach-
IP44
ment FDB291
– base adapter
IP44
FDB281
– base adapter
IP44
FDB241 and
base DB1131A
or SPF3600
– base adapter
IP44
FDB299 and
collective detector base
DB1101A
Standards
CEA4021, EN54-5, EN54-7, EN54-17
Approvals
– VdS
G211125
– LPCB
126ah/04
Permissible air
G212007
G204133
G212036
126ah/05
1… 20 m/s
speed
QS standards
2
Siemens Standard SN 36350
( ) Compatibility with FS20 on FDnet protocol only available if enabled in your country-specific FS20 software
6
Building Technologies
CPS Fire Safety
FDOOT241-A3
FDOOT241-A4
FDOOT241-A9
FDOOT241-8
Details for ordering
Type
FDOOT241-A3
FDOOT241-A4
FDOOT241-A9
FDOOT241-8
FDOOT241-8M
Part no
S54310-F10-A1
S54310-F9-A1
S54310-F11-A1
A5Q00004663
A5Q00016038
FDOOT241-8B
A5Q00015956
FDUD290
FDB241
FDB299
FDB281
S54370-S13-A1
S54319-F13-A1
S54319-F14-A1
A5Q00004929
Designation
Fire detector Sinteso(A+)
Fire detec. Sinteso(SIGMA)
Neural fire detector, ASA
Multi-sensor smoke detector
Migration kit
(FDOOT241-8 + FDB281)
Migration kit
(FDOOT241-8 + FDB221)
Removing tool for adaptor
Adapter base Sinteso (SIGMA/A+)
Adapter base Sinteso (AlgoRex-coll)
Adapter base MS8/P2
Weight
0.106 kg
0.106 kg
0.106 kg
0.106 kg
0.235 kg
0.162 kg
0.098 kg
0.086 kg
0.086 kg
0.125 kg
Detector and detector base accessories see data sheet 007775
Technical details see document A6V10323158
Details see equipment overview 008164
Details about system compatibility see List of compatibility 008331
7
Building Technologies
CPS Fire Safety
Siemens Switzerland Ltd
Infrastructure & Cities sector
Building Technologies Division
International Headquarters
CPS Fire Safety
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 724 24 24
www.siemens.com/buildingtechnologies
Document no.
008141_t_en_--
Edition
02.2013
© 2013 Copyright by
Siemens Switzerland Ltd
Data and design subject to change without notice.
Supply subject to availability.
Manual FD20
Section 2