Data sheet LI 9TU High-efficiency air-to-water heat pump Max. flow temperature: 60 °C Casing colour: White (similar to RAL 9003) Brown-red design screen (RAL 3011) Heat pump for heating purposes for indoor installation with integrated WPM Econ5Plus control. Sound-optimised through the use of slow-running EC 3D radial fan, an encapsulated compressor housing and a free-swinging compressor baseplate for solid-borne sound insulation. High coefficients of performance (COP) through high-performance evaporator, electronic expansion valve and compliance with the requirements of EN 14511 for larger volume flows on the heat consumption side. High operational safety through sensor monitoring of the refrigeration circuit for energy-efficient defrosting; integrated thermal energy metering (display of the thermal energy volume for heating and domestic hot water preparation on the WPM EconPlus heat pump manager). The integrated air circuit with 90° air deflection enables installation in a corner without air ducts or wall installation with air ducts on the air outlet side. Variable installation thanks to air intake from the rear, flexible air outlet to the right, left or top, and the option of making the hydraulic connections from right to left. The control panel is integrated into a brown-red design screen and can also be used as wired remote control using the wall mounting set (special accessories MS PGD). Universal design for low temperature heating systems with flexible expansion options for: - Room temperature control via Smart RTC (special accessory) - Bivalent or bivalent-renewable operating mode - Distribution systems with unmixed and mixed heating circuits - Use of load-variable tariffs (SG Ready) At an external temperature of -10 °C, the maximum flow temperature that can be achieved is 56 °C. Integrated flow and return sensors; external sensor (standard NTC-2) included in the scope of supply. Dirt trap and flow rate switch built in. Technical data Dimplex High-efficiency air-to-water heat pump (Low temperature) Order reference LI 9TU Heat pump code Casing colour Max. flow temperature Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation) Heat output A-7/W35 / COP A-7/W35* Heat output A2/W35 / COP A2/W35* Heat output A7/W35 / COP A7/W35* Heat output A10/W35 / COP A10/W35* Nominal power consumption according to EN 14511 at A2/W35 Nominal power consumption according to EN 14511 at A7/W35 Sound power level device Sound pressure level in 1 m (indoors) Refrigerant / Amount of refrigerant Max. heating water flow rate / Pressure drop Heat source flow (min.) Dimensions (W x H x D)** Weight Rated voltage Starting current with soft starter Fuse protection*** Type of defrosting Connection heating Seal of approval EHPA (valid until) 1009 White (similar to RAL 9003) 60 °C -20 to 35 °C 5,40 kW / 3,00 6,80 kW / 3,90 8,50 kW / 4,70 8,90 kW / 5,00 1,7 kW 1,8 kW 49 dB (A) 42 dB (A) R410A / 3,7 kg 1,5 m³/h / 19300 Pa 3700 m³/h 960 x 1560 x 780 mm 256 kg 3/N/PE ~400 V, 50 Hz 16 A C 10 A Reverse circulation 1 ¼ inch Yes / 12.12.2017 *Heat output and COP according to EN 14511 **Please note that additional space is required for pipe connections, operation and maintenance. ***Die Absicherung ist als allpolige Trennvorrichtung auszuführen (gemeinsame Abschaltung aller Phasen)! Glen Dimplex Deutschland GmbH Dimplex Division Am Goldenen Feld 18 95326 Kulmbach Page 1/6 Subject to change and errors! E-mail: [email protected] Internet: www.dimplex.de Internet: 09.03.2015 Phone: +49 (0)9221 709-201 Fax: +49 (0)9221 709-339 System accessories LI 9TU Description Article Sample number item LI 9TU SYL 250 KOMP 32 SMF 32 364060 352260 362060 362140 1 LUS 9A-2 LKB 600A LKB 800A VSLK 600 VSLK 800 ARLK 600 ARLK 800 DMK 600-1 DMK 800-1 LUH 600 RSG 600 RSG 800 370120 366150 366170 367680 367700 370270 370290 356120 356140 358620 340230 340250 SAS 110 PSW 100 PSW 200 PSW 500 DDV 25 UPH 60-25 VTB 25 VTB 32 WWM 25 MMH 25 MMB 25 340330 351090 339830 339210 358390 367870 339870 367770 346600 348640 348880 1 UPE 70-25 362790 1 UPE 80-25 362810 VSE 32-50 VSE 32-100 VSE 32-150 VSE 32-200 VSE 32-300 HDLR 450 HCT 300 362520 362530 362540 362550 362560 337450 351210 SRX 080EM SRX 120EM SRX 140EM SRX 180EM SRX 140M 367500 367510 367520 367530 359100 WWSP 332 FLH 60 FLHU 70 FLH 90 FLH 25M SVK 852 WWSP 442 346610 338060 338070 366130 349430 326660 372840 WWSP 442E 353370 Order ref. Item Price Heat pumps High-efficiency air-to-water heat pump Elasticated sound insulation underlay strips DN 32 double-sphere rubber expansion joint DN 32 dirt trap Heat source accessories Air duct hose kit for LI 9/12TU and LI 15TE outlet 90° air duct bend* 90° air duct bend* Connection kit Connection kit Connection frame set air duct Connection frame set air duct Sealing collar 600 Sealing collar 800 Deflector hood Rain guard for LI Rain guard for LI(H) 1 1 1 1 Hydraulic accessories Heating water hose connection set Free-standing buffer tank 100 l* Free-standing buffer tank 200 l* Universal buffer tank (500 l)* Dual differential pressureless manifold Electronically controlled circulating pump with coupling relay Manifold bar Manifold bar (3-fold) for modules DN 25 and DN 32 Domestic hot water module/unmixed heating circuit module Mixed heating circuit module with temperature sensor Mixer module for bivalent systems Electronically regulated wet running pump (0-10 V) with coupling relay Electronically regulated wet running pump (0-10 V) with coupling relay Ready-for-use DN 32 stainless steel Wellflex pipe Ready-for-use DN 32 stainless steel Wellflex pipe Ready-for-use DN 32 stainless steel Wellflex pipe Ready-for-use DN 32 stainless steel Wellflex pipe Ready-for-use DN 32 stainless steel Wellflex pipe Immersion heater pipe assembly* 3 kW pipe heater 1 1 1 Heating accessories Fan convector heating with EC fan Fan convector heating with EC fan Fan convector heating/cooling with EC fan Fan convector heating with EC fan Fan convectors heating 1400 W DHW preparation accessories Domestic hot water cylinder (300l) with temperature sensor Flange heater for domestic hot water Flange heater for domestic hot water Flange heater for domestic hot water FLH 25M flange heater Safety valve combination Domestic hot water cylinder (400 l) with temperature sensor* Design domestic hot water cylinder with sheet metal coverings and temperature sensor* 400l solar cylinder for heat pump* Hydro Tower without regulation* Combination tank heating and domestic hot water preparation* PWS 650 combination tank* Glen Dimplex Deutschland GmbH Dimplex Division Am Goldenen Feld 18 95326 Kulmbach WWSP 432 SOL HWK 332 PWS 332 PWS 650 Page 2/6 Subject to change and errors! E-mail: [email protected] Internet: www.dimplex.de 1 1 361080 362360 348620 367660 Internet: 09.03.2015 Phone: +49 (0)9221 709-201 Fax: +49 (0)9221 709-339 System accessories LI 9TU Description Order ref. Combo tank for heating and domestic hot water preparation with central flow* Pump unit DN 25 for direct connection of the domestic hot water cylinder Electronically controlled circulating pump with coupling relay Fresh water station FWS 27 FWS WT fresh water station Article Sample number item PWD 750 349100 WPG 25 356030 1 UPH 60-25 FWS 27 FWS WT 367870 367310 368100 1 NWPM EWPM LWPM 410 AP PGD FG 3115 NTC-10M KRRV 003 356960 356970 339410 356570 336620 363600 322070 Item Price Control accessories Extension for an Ethernet network connection Extension for a KNX/EIB bus connection Extension for a Modbus connection Remote control for WPM 2006/2007/EconPlus/R* Outside temperature sensor with casing Temperature sensor NTC-10 with metal sleeve Thermostat for heating and domestic hot water * Other specific accessories available / required Notes: Heat output according to EN 14511 at A2/W35 (A2 = air intake temp. +2 °C, W35 = heating water outlet temp. +35 ℃). Important information: The combination of the components and the quantities indicated represent a non-binding sample system, which needs to be tested and individually adapted as required. Pump dimensioning must be reviewed according to the pressure loss of the system and the minimum heating water flow rate of the heat pump. Glen Dimplex Deutschland GmbH Dimplex Division Am Goldenen Feld 18 95326 Kulmbach Page 3/6 Subject to change and errors! E-mail: [email protected] Internet: www.dimplex.de Internet: 09.03.2015 Phone: +49 (0)9221 709-201 Fax: +49 (0)9221 709-339 Air-to-water heat pump, Integration Diagram, Heat pump and immersion heater Note: The given hydraulic integration schematic is a schematic representation of the key components and serves as an aid for planning your customized system. The current status is available at all times under www.dimplex.de/nc/en/professional/onli ne-planner/hydraulic-integrations.html. It does not contain all the required safety devices, the components needed to maintain constant pressure, or any other additional valves which may be required for maintenance and service work as stipulated by EN 12828. The heat pump manager settings and any external regulation system which may be connected must be adapted to the present integration diagram. Software updates may be required! Glen Dimplex Deutschland GmbH Dimplex Division Am Goldenen Feld 18 95326 Kulmbach Page 4/6 Subject to change and errors! E-mail: [email protected] Internet: www.dimplex.de Internet: 09.03.2015 Integration Diagram: 10231024 Phone: +49 (0)9221 709-201 Fax: +49 (0)9221 709-339 Air-to-water heat pump, Integration Diagram, Heat pump and immersion heater System description: Presettings: • Air-to-water heat pumps with defrosting by reverse circulation extract the energy required for defrosting from the heating system. In the case of air-to-water heat pumps, a buffer tank connected in series, into which the immersion heater is screwed, must be installed in the flow in mono energy systems to ensure defrosting. A dirt trap with a mesh size of between 0.6mm and 0.8mm is to be installed in order to protect the plate heat exchanger from larger dirt deposits. Clean the filter sieve of the dirt trap one day after start-up. These intervals can be extended as soon as no more impurities are detected. When the level of impurities is significantly high (e.g. due to corrosion found in the building), it is recommended that a sludge trap be installed in order to minimise the need for regular cleaning. A permanent corrosion process, caused by the entry of oxygen into the system, is characteristic of heating systems featuring open diffusion. This is best alleviated using an electrophysical anti-corrosion system. Condensate which forms during defrosting must be drained off without risk of frost. Acoustic emissions must be taken into account, and a free air circuit provided for, when the installation location is being selected. Heat pumps without weather-proof protective covers in particular need to be installed outdoors in such a manner that the air outlet is not positioned against the main wind direction. • A buffer tank connected in series is recommended for heat pump heating systems, to ensure the minimum heat pump runtime of 6 minutes for all operating statuses. Pre-configuration Setting Operating mode Mono energy Heating circuit 1 Yes Heating circuit 2 No DHW preparation Yes DHW preparation request by Domestic hot water preparation flange heater Swimming pool water preparation Sensor Yes No • The heat pump supplies a large part of the required heat output. An electric heating element (immersion heater) supplements the heat pump on days when the external temperature lies below the bivalence point. In mono energy systems, the contactor for the immersion heater (E10.1) must be set according to the output. It is controlled (230 V AC) by the heat pump manager via terminals X1/N and J13/NO4. • The heat exchanger in the hot water cylinder must transfer the maximum heat output at the maximum heat source temperature. In systems with high hot water consumption (multiple dwellings, industrial applications) the cylinder must be set to the maximum peak demand while taking the shut-off times into account. The maximum heat output and the maximum heating water flow must be adhered to! • The contactor for the flange heater (E9) in the hot water cylinder should be dimensioned according to the output and must be supplied by the customer. It is controlled (230 V AC) by the heat pump manager via terminals X1/N and J16/NO10. The maximum heat output of the heat pump and the water flow are to be observed. • The dual differential pressureless manifold ensures that the required minimum water flow rate is maintained, independent of both the number of open heating circuits and of how the system is used. Hydraulic isolation is carried out using two connections between flow and return; each connection is fitted with a check valve. The characteristic curve of the pump in the consumer circuit must be set in such a way that a maximum spread of 10 Kelvin is not exceeded, in order to prevent unnecessary surging of the heat pump. Electronically regulated pumps must be operated at a constant pressure. Glen Dimplex Deutschland GmbH Dimplex Division Am Goldenen Feld 18 95326 Kulmbach Page 5/6 Subject to change and errors! E-mail: [email protected] Internet: www.dimplex.de Internet: 09.03.2015 Integration Diagram: 10231024 Phone: +49 (0)9221 709-201 Fax: +49 (0)9221 709-339 Air-to-water heat pump, Integration Diagram, Heat pump and immersion heater Legend: 1. 1.1 1.2 1.3 1.4 1.5 1.6 1.7 2. 3. 3.1 4. 5. 6. 7. 8. 9. 10. 13. 15. 16. 17. Heat Pump Air-to-water heat pump Brine-to-water heat pump Water-to-water heat pump Reversible air-to-water heat pump Reversible brine-to-water heat pump Reversible water-to-water heat pump Air-to-water heat pump split design Heat pump manager Parallel buffer tank Buffer tank Hot water cylinder Swimming pool heat exchanger Passive cooling station with cooling controller N6 Heating and silent or dynamic cooling Fan convector with 4-wire connection Cooling circuit only Heating circuit only Heat source Hydraulic tower Scalding protection Hydro tower HWK 332 Domestic hot water distribution system: DDV 25 DDV 32 EB KPV KPV 25 MMB 25 MMH 25 VTB 25 WWM 25 Dual differential pressureless manifold (up to 2.0 m³/h)* Dual differential pressureless manifold (up to 2.5 m³/h)* Extension module for compact manifold (up to 2.0 m³/h)* Compact manifold with overflow valve (up to 1.3 m³/h)* In combination with EB KPV (up to 2.0 m³/h)* Mixer module, bivalent (up to 2.0 m³/h)* Mixer module for heating circuit Manifold bar (up to 2.5 m³/h)* Hot water module / unmixed heating circuit (up to 2.5 m³/h)* * Recommended max. heating waterflow Solarthermics: SST 25 SOLPU 1 SOLCU 1 T1 T2 T3 Solar station for hot water Solar station Solar controller Temperature sensor (collector sensor) Temperature sensor (cylinder 1) Temperature sensor (cylinder 2 /optional display function) Glen Dimplex Deutschland GmbH Dimplex Division Am Goldenen Feld 18 95326 Kulmbach B3 B4 B7 E9 E10 E10.1 E10.2 E10.3 E10.5 F7 F10 K20 K21 M11 M12 M13 M14 M15 M16 M17 M18 M19 M20 M21 M22 M25 N1 N2 N3 N12 N17.1 N17.2 N17.3 N17.4 R1 R2 R3 R4 R5 R9 R11 R13 SMF TC Y5 Y6 Y7 Y8 Y12 Y13 Page 6/6 Subject to change and errors! E-mail: [email protected] Internet: www.dimplex.de Hot water thermostat Swimming pool thermostat Thermostat primary circuit Flange heater, hot water 2nd heat generator (HG2) Immersion heater Oil/gas boiler Solid fuel boiler Solar energy system Safety temperature monitor Flow rate switch Contactor for 2nd heat generator Contactor for immersion heater hot water Primary pump for heating operation Primary pump for cooling operation Heat circulating pump for main circuit Heat circulating pump for heating circuit 1 Heat circulating pump for heating circuit 2 Auxiliary circulating pump Cooling circulating pump Hot water circulating pump Swimming pool water circulating pump Heat circulating pump heating /cooling circuit 3 still Mixer Mixer heating/cooling circuit 2 Circulating pump for heating and domestic hot water preparation Heating controller Cooling controller for reversible heat pumps Room climate control stations Solar controller Cooling module general Cooling module active Cooling module passive Solar module WPM Econ SOL External wall sensor Return flow sensor Hot water sensor Return flow sensor for cooling water Temperature sensor for heating circuit 2 Flow sensor (antifreeze) Flow sensor for cooling water Sensor for heating circuit 3 / bivalent-renewable Dirt trap Room temperature controller Three-way distribution valve Two-way valve Three-way mixing valve Three-way valve (closing time max. 10 sec.) External 4-way reversing valve Three-way reversing valve Internet: 09.03.2015 Integration Diagram: 10231024 Phone: +49 (0)9221 709-201 Fax: +49 (0)9221 709-339
© Copyright 2024