Mount Instr. - Delray Lighting

CYLINDRO III
Mounting Instructions
WARNING: disconnect main power at the source prior to installation! Only qualified electricians should install Delray Lighting products.
Standard Surface Mount Canopy
Mount cable gripper with
#8 screw, or mount directly
to 1/4 20 stud.
Secure lamp cord in
canopy with strain relief
10”
dia.
Use cable tie to
join cord to cable
NOTE: use 1/4 – 20 toggle
bolt and fender washer
(or equivalent) to cover
the hole.
2.5”
Mount Driver Canopy to J-Box
3 Mounting Points:
6803 – on 31.625” diameter, 27.39” centers
6804 – on 43.625” diameter, 37.8” centers
6805 – on 55.375” diameter, 48” centers
*Max. Wiring Distance (at full load)
Wire Size (AWG)
Distance (ft.)
18
16
14
12
10
18
29
46
71
120
NOTE: multiple drivers
must be mounted no less
than 4 inches apart
side-by-side, and 1 inch
apart end-to-end, to avoid
overheating.
SLRD Option Remote Driver
Remote driver housing must
remain accessible. Use bar
hangers to mount in ceiling.
Bottom
base
threaded
for 1/4 -20.
Mud ring or
octagonal box,
by others.
See
Chart*
0000000000000
00
000000000000000
MAR 2015
Flexible conduit and wire,
by others
w w w. del r a yl i ghti ng. c o m