KCD2-SCD-Ex1.HC SMART Current Driver Connection Assembly

SMART Current Driver
KCD2-SCD-Ex1.HC
Assembly
Features
•
•
•
•
•
•
•
•
1-channel isolated barrier
24 V DC supply (Power Rail)
Current output up to 625 Ω load
HART I/P and valve positioner
Lead breakage monitoring
Suitable for long field cables (> 1000 m)
Terminal blocks with test sockets
Up to SIL2 acc. to IEC 61508
Front view
Removable terminals
blue
1
3
LED green:
Power supply
2
4
KCD2-SCDEx1.HC
Function
PWR
S1
This isolated barrier is used for intrinsic safety applications.
It repeats the input signal from a control system to drive HART
I/P converters, valve actuators, and displays located in a
hazardous area.
S2
S3
S4
I
Switch 1 ... 4
II
5 6
7 8
9 10
Bi-directional communication is supported for HART devices.
Place for labeling
An open field circuit presents a high impedance to the control
side to allow alarm conditions to be monitored by control
systems.
Removable terminals
green
Test sockets for the connection of HART communicators are
integrated into the terminals of the device.
2
236982_eng.xml
Connection
KCD2-SCD-Ex1.HC
Release date 2012-07-31 16:00
I
56+
HART
P
HART
Date of issue 2015-02-16
1+
mA
2-
9+
10-
Zone 0, 1, 2
Div. 1, 2
24 V DC
Power Rail
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
USA: +1 330 486 0002
Germany: +49 621 776 2222
www.pepperl-fuchs.com
[email protected]
[email protected]
Singapore: +65 6779 9091
[email protected]
24 V DC
Zone 2
Div. 2
1
Technical data
KCD2-SCD-Ex1.HC
General specifications
Signal type
Analog output
Supply
Connection
Rated voltage
Ripple
Rated current
Power loss
Power Rail or terminals 9+, 10Un
19 ... 30 V DC
In
≤ 35 mA
Power consumption
≤ 10 %
≤ 600 mW
≤ 700 mW
Input
Connection
terminals 5-, 6+
Input signal
4 ... 20 mA , limited to approx. 27 mA
Input voltage
depending on switch configuration
open loop voltage of the control system < 19 V
open loop voltage of the control system < 26 V
Voltage drop
depending on switch configuration
open loop voltage of the control system < 19 V: approx. 5 V at 20 mA
open loop voltage of the control system < 26 V: approx. 12 V at 20 mA
Input resistance
> 100 kΩ, with field wiring open
Output
Connection
terminals 1+, 2-
Current
4 ... 20 mA
Load
0 ... 625 Ω
Voltage
≥ 12.5 V at 20 mA
Ripple
20 mV rms
Transfer characteristics
Deviation
at 20 °C (68 °F), 0/4 ... 20 mA
≤ ± 0.1 % incl. non-linearity and hysteresis
Influence of ambient temperature
Frequency range
< 2 µA/K (0 ... 60 °C (32 ... 140 °F)); < 4 µA/K (-20 ... 0 °C (-4 ... 32 °F))
field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 1 mApp signal 0 ... 3 kHz (-3 dB)
Rise time
10 to 90 % ≤ 100 ms
Electrical isolation
Input/Output
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply
functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Output/power supply
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC
EN 61326-1:2006
Conformity
Electromagnetic compatibility
NE 21:2006
Degree of protection
IEC 60529:2001
Ambient conditions
Ambient temperature
-20 ... 60 °C (-4 ... 140 °F)
Release date 2012-07-31 16:00
Date of issue 2015-02-16
236982_eng.xml
Mechanical specifications
Degree of protection
IP20
Mass
approx. 100 g
Dimensions
12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 in) , housing type A2
Mounting
on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection
with Ex-areas
EC-Type Examination Certificate
CESI 11 ATEX 094 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection
¬ II (1)G [Ex ia Ga] IIC , ¬ II (1) D [Ex ia Da] IIIC , ¬ I (M1) [Ex ia Ma] I
Output
Ex ia IIC, Ex iaD
Supply
Maximum safe voltage
Equipment
Voltage
Current
Power
Um
Uo
Io
Po
250 V AC (Attention! Um is no rated voltage.)
terminals 1+, 220 V
100 mA
500 mW
Permissible connection values [EEx ia]
Statement of conformity
Group, category, type of protection,
temperature class
PF 11 CERT 1968X , observe statement of conformity
¬ II 3G Ex nA IIC T4 Gc
Directive conformity
Directive 94/9/EC
EN 60079-0 , EN 60079-11 , EN 60079-15 , EN 60079-26 , EN 61241-11 , EN 50303:2000
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
USA: +1 330 486 0002
Germany: +49 621 776 2222
www.pepperl-fuchs.com
[email protected]
[email protected]
Singapore: +65 6779 9091
[email protected]
2
Technical data
KCD2-SCD-Ex1.HC
International approvals
IECEx approval
Approved for
IECEx CES 12.0004
[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
General information
EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
Conformity and instructions have to be observed where applicable. For information see www.pepperlfuchs.com.
Release date 2012-07-31 16:00
Date of issue 2015-02-16
236982_eng.xml
Supplementary information
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
USA: +1 330 486 0002
Germany: +49 621 776 2222
www.pepperl-fuchs.com
[email protected]
[email protected]
Singapore: +65 6779 9091
[email protected]
3
Technical data
KCD2-SCD-Ex1.HC
Configuration
Switch position
Function
1
3
2
4
S1
S2
S3
S4
Open loop voltage of the control system
< 19 V
I
I
II
II
Open loop voltage of the control system
< 26 V
II
I
II
II
Factory settings: open loop voltage of the control system < 19 V
PWR
S1
S1
S2
S2
S3
S4
I
II
S3
S4
5 6
7 8
9 10
I
II
Accessories
Power feed module KFD2-EB2
The power feed module is used to supply the devices with 24 V DC via the Power Rail. The fuse-protected power feed module
can supply up to 150 individual devices depending on the power consumption of the devices. Collective error messages received
from the Power Rail activate a galvanically-isolated mechanical contact.
Power Rail UPR-03
The Power Rail UPR-03 is a complete unit consisting of the electrical insert and an aluminium profile rail 35 mm x 15 mm. To
make electrical contact, the devices are simply engaged.
Profile Rail K-DUCT with Power Rail
The profile rail K-DUCT is an aluminum profile rail with Power Rail insert and two integral cable ducts for system and field cables.
Due to this assembly no additional cable guides are necessary.
Release date 2012-07-31 16:00
Date of issue 2015-02-16
236982_eng.xml
Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".