ACG CERTIFIED COMMISSIONING AUTHORITY EXAMINATION APPENDIX For Use with Exam Questions 85 – 100 only Table of Contents Design Sequence Of Operation Figure 1 -- BAS Approved Submittal Drawing Figure 2 -- Design Airflow Drawing ACG CERTIFIED COMMISSIONING AUTHORITY EXAMINATION DESIGN SEQUENCE OF OPERATION FOR TYPICAL DUAL DUCT AIR HANDLING UNIT System Description The unit is designed as a heating-cooling, dual duct, variable volume air handling system. The unit consists of a single supply fan, with coils located in a blow thru configuration. Each unit is provided with a minimum amount of pretreated outside air. These systems shall supply air to dual duct air terminal mixing boxes. The unit shall function as a complete system and shall normally operate 24 hrs/day (the unit does not require occupied-unoccupied operation). In addition to the normal operating mode, the unit shall be provided with an emergency smoke control operating mode. In building areas requiring smoke compartmentalization, each AHU has been zoned to serve one smoke compartment (in some locations, the AHU will serve two smoke compartments). The AHU shall be enabled thru the building automation system (BAS). Interlocking Recirc pump shall be interlocked with supply fan. Outside Air Control Outside air shall be measured and controlled using a pressure-independent single duct, air terminal unit. Flow shall be constant volume (FA). Refer to air terminal unit schedule. The air terminal unit shall close off outside air flow when the AHU is not operating. Fan Control Each unit shall be furnished with a variable frequency drive (VFD). Fan shall start with VFD at low speed. The BAS shall monitor the hot deck static pressure (HDP) and the cold deck static pressure (CDP). A static pressure controller and its duct mounted static pressure sensors shall modulate the supply fan VFD to maintain the static pressure setpoint (FA) from the static pressure sensor requiring the most air volume. Static pressure setpoint shall be reset based on demand. Unless otherwise shown, static pressure sensors PE-5 and PE-2 shall be located 2/3 down the most hydraulically remote duct. One sensor shall be in the hot deck and one sensor shall be in the cold deck duct. Upon failure of the static pressure signal, the fan speed shall be controlled to maintain the lower limit static pressure setpoint. Test and balance shall give to the BAS contractor setpoints for the required hot deck (HDSP) and cold deck (CDSP) static pressures. Temperature Control The hot deck temperature shall be sensed by an averaging sensor, TE-5. Cold deck temperature shall be sensed by averaging sensors, TE-3 and TE-4. After proof of fan status, the temperature loops shall be enabled. The ACG CERTIFIED COMMISSIONING AUTHORITY EXAMINATION BAS shall modulate the hot deck control valve to maintain hot deck discharge air setpoint of 95 deg F (FA). The BAS shall reset the hot deck setpoint (HDSP) based upon outside air temperature. See following schedule. Outside Air Temperature Hot Deck Supply Temperature Setpoint 30 Deg F 70 Deg F 95 Deg F 80 Deg F The BAS shall modulate the chilled water control valve to maintain air setpoint, TE-3, of 52 Deg F (FA). The BAS shall modulate the hot water reheat control valve (N.C.) to maintain air setpoint, TE-4, of 54 Deg F. Recirculation pump shall run continuously. The BAS shall have the capability to reset the cold deck setpoint (CDSP). Reset shall be based upon the return air temperature (TE-2) and return air humidity (HE-1) or owner specified reset based upon the cooling requirements of the air terminals. Dehumidification Control Relative humidity in the return air duct shall be monitored by the BAS. Provide return air humidity sensor to act as a high limit override. If return air relative humidity exceeds 60%, reset cold deck discharge air temperature downward to maintain 60% RH. Provide a low limit cold deck discharge air temperature of 50 Deg F. Safeties The BAS shall monitor the discharge static pressure sensor. Upon a high static condition above setpoint (CDSP), the VFD control signal shall be overridden to limit discharge static pressure. Alarms An alarm shall be generated at the BAS workstation if any of the following incidents take place during normal operating mode. 1. 2. 3. 4. Discharge air temperature falls below 45 Deg F or above 65 Deg F for more than 5 minutes when the AHU is operating. The filter differential pressure switch exceeds 1.5” WG for 10 minutes The VFD Hand-Off-Auto switch is not in Auto Supply fan commanded value does not match status proof condition Smoke Mode For AHUs serving compartmentalized areas of the building, refer to Drawing MB6.002. For AHUs listed below, duct mounted smoke detectors shall automatically stop the supply fan on detecting the presence of smoke. AHU-AC-3-04 AHU-AC-3-05 AHU-AC-3-06 AHU-AC-3-07 AHU-AC-1-01 AHU-AC-P1-01 AHU-AC-P1-02 AHU-AC-P1-03 Figure 1 BAS Approved Submittal Drawing
© Copyright 2024