HOW TO PREVENT ELECTRICAL FIRES

HOW TO PREVENT ELECTRICAL FIRES
Electrical fires pose significant dangers for home ownership or property management. An electrical fire can cause the
loss of someone’s entire home, but there are several steps that will go a long way in preventing this type of fire.
The easiest step in avoiding an electrical fire is to avoid overloading a home’s electrical circuits. Electrical circuits are
connected to the service panel that distributes electricity throughout the home. The service panel contains circuit
breakers or fuses, in conjunction with cables that supply the house with power. It is preferable to have breakers instead
of fuses.
DEFINITIONS TO KNOW
•Ampere (amp): a unit of electrical current strength
•Voltage: a unit of electrical pressure
•Watts: units of power which measure the rate a device is using electrical energy
60 Amp Service Panel
100 Amp Service Panel
The Canadian Electrical Code allows for 60 amp
service in a single family dwelling where the floor
area (excluding the basement) is less than 861
square feet (80 m2). Larger homes require 100
amp service, although it is not mandatory they be
upgraded to this new standard.
Generally speaking, a 100 amp service panel is
adequate for most homes. If the service is original
to a home constructed in the 1950’s and 1960’s, an
upgrade may be required.
Older homes built in the 1950’s and 1960’s that are
1200 square feet or less, may still be equipped with
60 amp service that may be deemed acceptable
with an electrical inspection. For example, if the
home has a gas stove and dryer to offset the amount
of electricity, the situation might be acceptable.
Some older homes have been upgraded to the 100
amp service where only a new service panel was
installed, leaving the original ungrounded wiring
in place. The upgraded electrical panel should
have an electrical permit attached to the service
panel with the date the upgrade was completed
and inspected. If no permit exists on the upgraded
service panel, an inspection is required.
Insuranceisevolving.com
Modern Service Panel
with Breakers
Older Service Panel
with Fuses
HISTORY OF WIRING
If any of the following circumstances exist, a certified electrician should inspect the electrical system.
Ungrounded twin conductor cable (NMD-1)
• New method of wiring introduced
• Contained two conductors in one jacket
• No ground protection
• Supports a limited amount of outlets and switches
• Insulation deteriorates
Grounded twin conductor cable (NMD-3 or NMD-6)
• Homes now wired for 3 prong outlets
• Conductor supports temperature rates of 60° C to 75° C
• Works well for most circuits
• Not to be used in recessed lighting applications
• 1970 to 1980 installation of recessed lighting became
popular
• Due to higher heat that recessed lighting conducts, this
type of conductor overheats, resulting in fire
• Electrical code now requires conductors that support
temperatures of 90° C for the application of recessed
lighting
Aluminum wiring
• Due to escalating costs of copper, aluminum wiring was
introduced
• Prior to 1977 the outer covering of the cable is identified
with the word ALUMINUM or an abbreviation, ALUM, or AL
• After 1977 the outer covering of the cable may be
ALUMINUM, ACM, ALUM, ACM, or ALACM
• Receptacle and light switch device with a rating of 20 amp
or less must contain the word CO/ALR
• Receptacle greater than 20 amp device must contain the
word AL-CU or CU-AL
• Wire connector for combinations of either an aluminum
conductor(s), a copper conductor(s), or both, must
contain the word AL-CU or CU-AL
1984 TO
PRESENT
1950 1962
TO 1950
Knob and Tube
• Two separate conductors held in place by ceramic knobs
• Conductors run separately and only come together at the
switch, outlet, receptacle, fixture, or junction box etc.
• Conductor consists of one wire that is black (hot wire) and
one wire is white (neutral wire)
• No ground protection
• Supports 2 prong outlet
• Supports limited amount of outlets for the demands of
today
• Insulation deteriorates due to overloading circuits and
overheating conductors (wires)
• 3 prong outlets may be installed giving the impression
that there is ground protection
• Not suited for kitchens, bathrooms, laundry rooms, or
outdoor installations
1962 - 1984
AREAS OF CONCERN
1965 - LATE 1970’S
HISTORY OF WIRING TYPES
Modern cable (NMD-7 & NMD-90)
• Modern house wire
• Approved for recessed lighting
• Conductor supports temperature rates of 90° C
Insuranceisevolving.com
• Original aluminum rated outlet connections come loose
over time, potentially becoming a fire hazard
• Original aluminum rated outlets replaced with nonaluminum rated outlets
• Replacement wall switches and receptacles must be
approved for use with aluminum wiring and the device
must bear the marking “CO/ALR”
NOTE: Due to the specialized knowledge and techniques
required when dealing with aluminum wiring, it is
recommended that it be installed only by qualified
electricians
WARNING SIGNS FOR ELECTRICAL HAZARDS
If any of the following circumstances exist, a certified electrician should inspect the electrical system.
Dimming Lights
Lights that chronically flicker and dim can be a sign of loose connections or a
heavily loaded circuit.
Tripping circuit breakers
Repeated tripping could indicate overloaded circuits, a short circuit, or other
problems.
Reliance of extension cords
Extension cords aren’t a permanent fix to the problem of too few outlets.
Extension cords may not be able to handle the load placed on them, and can
become a fire or shock hazard if damaged.
Burning smell
Smoke or a smell of burning metal or plastic may be caused by a bulb of the
wrong size or wattage being used, or a sign of burned or overheated wiring.
Hot Receptacles
Receptacles, switch plates, cords, and plugs should never be hot to the
touch or discoloured from heat. This could mean a loose connection or other
problem.
Loose plugs
Plugs should fit snugly in outlets. Loose connections can be a shock hazard
and can generate heat.
Overloaded outlets Heavily used outlets can create a fire hazard if they generate too much heat.
Insuranceisevolving.com