How to Convert and Optimize Primary/Secondary Pumping Systems

How to Convert and Optimize
Primary/Secondary Pumping Systems
to Variable Flow Primary Systems
Presented By: Hemant Mehta, P.E.
History of Variable Primary Flow Projects
•
•
•
•
•
•
•
•
•
•
•
King Saud University - Riyadh (1977)
Louisville Medical Center (1984)
Yale University(1988)
Harvard University (1990)
MIT(1993)
Amgen (2001)
New York-Presbyterian Hospital (2002)
Pennsylvania State Capitol Complex (2005)
Duke University (2006)
NYU Medical Center (2007)
Memorial Sloan-Kettering Cancer Center (2007)
Oldest variable flow primary system
King Saud University – Riyadh (1977)
•
•
•
•
•
60,000 ton capacity with 30,000 tons for first phase
Six 5,000 ton Carrier DA chillers
Seven 10,000 GPM 240 TDH constant speed pumps
Major Problem: Too much head on chilled water pumps
Lesson Learned: Be realistic in predicting growth
Louisville Medical Center (1984)
• Existing system (1984)
– Primary/Secondary/Tertiary with 13,000 ton capacity
• Current System (2007)
– 120 feet TDH constant speed primary pumps with
building booster pumps – 30,000 ton capacity
– Changed the heads on some of the evaporator shells
to change number of passes
– Primary pumps are turned OFF during winter, Early
Spring and Late Fall. Building booster pumps are
operated to maintain flow.
Louisville Medical Center CW Sump
Yale University (1988)
• Existing system (1988)
– Primary/Secondary/Tertiary with 10,500 ton capacity
• Current System (2007)
– 180 feet TDH VFD / Steam Turbine driven variable
flow primary pumps – 25,000 ton capacity
– Changed the heads on some of the evaporator shells
to change number of passes
Amgen (2001)
• Creation of a computerized hydraulic model of the existing
chilled water plant and distribution system
• Identification of bottlenecks in system flow
• Evaluation of existing capacity for present and future loads
• Two plants interconnected: Single plant operation for most
of the year, second plant used for peaking
• Annual Energy Cost Savings: $500,000
Additional Variable Primary
Flow Projects
•
•
•
•
•
•
•
Harvard University (1990)
MIT(1993)
New York-Presbyterian Hospital (2002)
Pennsylvania State Capitol Complex (2005)
Duke University (2006)
NYU Medical Center (2007)
Memorial Sloan-Kettering Cancer Center (2007)
Duke University Background
• CCWP-1 plant was built four years ago
• CCWP-2 design was 90% complete
(Primary/Secondary pumping)
• We were retained by Duke to peer review the
design
• Peer review was time sensitive
• Plant design for CCWP-2 was modified to
Variable Primary pumping based on our
recommendations
Duke CCWP-1 Before
Duke CCWP-1 After
• Dark blue pipe replaces old primary pumps
Duke Levine Science Research
Center CHW System
Duke CIEMAS Building CHW System
90% closed
Triple duty valves
50% closed
Duke CIEMAS Building AHU-9
Balancing valve
50% closed
NYU Medical Center (2007)
• Plant survey and hydraulic model indicated unnecessary pumps
• 1,300 horsepower of pumps are being removed, including 11
pumps in two brand new chiller plants
• $300,000 implementation cost
• $460,000 annual energy savings
NYU Medical Center (2007)
• Plant survey and hydraulic model indicated unnecessary pumps
• 1,300 horsepower of pumps are being removed, including 11
pumps in two brand new chiller plants
• $300,000 implementation cost
• $460,000 annual energy savings
3 Pumps Removed
8 Pumps Removed
7 Pumps Removed
3 Pumps Removed
Memorial Sloan-Kettering - Before
Memorial Sloan-Kettering - After
Bypass or
removal of
pumps
Bypass
or
removal
of pump
Bypass or
removal of
pumps
Pump Cemetery
To date we have removed several hundred large
pumps from our clients’ chilled water systems
Good Engineers Always Ask
“Why?”
• Why does the industry keep installing
Primary/Secondary systems?
• Why don’t we get the desired system ΔT?
• Why does the industry allow mixing of
supply and return water?
Good Engineers Always Ask
“Why?”
• Why does the industry keep installing
Primary/Secondary systems?
• Why don’t we get the desired system ΔT?
• Why does the industry allow mixing of
supply and return water?
Answer: To keep consultants like us busy!
Why change?
Reasons to Change
• Chiller manufacturing industry supports
the concepts of Variable Primary Flow
• Evaporator flow can vary over a large
range
• Less space is required for fewer pumps
• Lower first cost and operating costs
Change is Starting Around the World
• Most of the large district cooling plants in Dubai currently use
Primary/Secondary pumping
• By educating the client we were able to convince them that
this is not necessary
• We are now currently designing three 40,000 ton chiller plants
in Abu Dhabi using Variable Primary Flow as part of a $6.9
billion development project
Design Guidelines of A Primary
Variable Flow System
• Main Equipment
– Minimize amount of installed equipment
– Estimate maximum chiller capacity required
with full build-out of your campus
– Use 350 SF/Ton as a guideline for most
building types
• Multiple Plants/ Virtual Central System
– Review your existing system and decide your
needs for ultimate build-out
Design Guidelines of A Primary
Variable Flow System
• Chillers
– Renegotiate with manufacturer to provide
maximum capacity based on the chiller
selection.
– Keep flow velocity around 6.5 ft/sec at peak
• Chilled Water Pumps
– Variable Frequency Drive
– Review feasibility of oversizing pumps in lieu
of providing a standby pump
Design Guidelines of A Primary
Variable Flow System
• Condenser Water Pumps
– Variable Speed Condenser Water Pumps?
• Cooling Towers
– Design for at least 2°F higher wet bulb temperature
than normal design wet bulb
– Specify full flow coverage at 50% of peak flow
• Pressurization Tank
– City water pressure may be adequate
– Tank May not be required for large system
• Air Separators
– Not required
Design Guidelines of A Primary
Variable Flow System
• Controls
– Flow control valves on CHWR and CWR lines to each chiller
– Chilled water differential pressure bypass valve at the plant
– Differential pressure sensors at the hydraulically most remote
buildings
– Flow meters on CHWR and CWR lines to each chiller
– Outside air weather station
• Temperature and humidity sensors for cooling tower controls
• Learn the behavior of your system
• Remember
– You can not manage what you do not measure
Design Guidelines of A Primary
Variable Flow System
• Chilled water flow controls and site
differential pressure
– Master Control
• CHWP VFD is controlled to maintain required
differential pressure at remote buildings
– Sub Master Control
• Provide to maintain individual chiller minimum flow
Variable Volume Primary System Flow Diagram
Variable Volume Primary System Flow Diagram
Chillers
Variable Volume Primary System Flow Diagram
CHW
Pumps
Variable Volume Primary System Flow Diagram
DP
Bypass
Variable Volume Primary System Flow Diagram
Condensers
Variable Volume Primary System Flow Diagram
Control
Valves
Variable Volume Primary System Flow Diagram
CW
Pumps
Variable Volume Primary System Flow Diagram
Cooling
Towers
Summary
• There are many chilled water plants with significant
opportunities for improvement
• WM Group has a proven record of providing smart solutions
that work
• We will be happy to review your plant logs with no obligation
Louisville Medical Center Chilled Water Operating Data
Production
50
Cost
0.200
1985: $ 0.171/ton-hr
45
C H W Pro d u ctio n
(m illio n to n -h o u rs)
35
0.150
30
2002: $0.096/ton-hr
25
0.125
20
0.100
15
10
0.075
5
0
0.050
1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002
Year
C o st
($/to n -h o u r)
0.175
40
Thank You
Hemant Mehta, P.E.
President
(646) 827-6400
[email protected]