Document 253067

B
A
CL
ERECTION BOLT
6 1/4"
E
ANDREWS
ARCHITECTS
10'-0"
6 1/4"
S101
AS REQ'D
2'-0" MIN.
EL. 792'-8 1/2"
(E)W16X31
1'-0"
(E)W27X114
10'-0"
MC6X12
MC6X12
(E)W21X50
EL. 792'-8 1/2"
TYP.
CL OF ARM
3/16
3/16
3/16
3/16
TYP.
L3X3X3/16
ADJACENT TO CLIP
PL'S @ EA. W16
2
1'-8"
L3X3X3/16 HANGER TYP.
TYP.
F
3/16
3/16
(E)W27X114
10'-0"
L3X3X3/16
L3X3X3/16
W6 (SEE PLAN)
W6X9
W6X16
W6X9
W6X16
S101
(E)W21X50
6631 Commerce Parkway, Studio B
Dublin, Ohio 43017
L3X3X3/16 HANGER TYP.
3/16
3/16
(E)W16X31
1'-8"
2'-10"
L3 1/2X3 1/2X3/16
CONT. @ EA. W6
L3X3X3/16
HANGER TYP.
CL
2'-10"
(E) W16
(E) W16
(SEE PLAN)
L3X3X3/16
@ EA. W16
Architecture
Planning
Interior Design
ERECT. BOLT TYP.
SHIM AS REQ'D
Tel: 614 . 766 . 1117
Fax: 614 . 766 . 2023
www.AndrewsArchitects.com
Seal:
P1001 (SEE PLAN)
CEILING
2'-10"
1'-8"
1'-8"
P1001 (SEE PLAN)
2'-10"
CEILING
W6 (SEE PLAN)
SHIM AS REQ'D
(E)W16X31
F
UNISTRUT
P1001 TYP.
B
S101
6"
SECTION
C
3/4" = 1'-0"
SECTION
3/4" = 1'-0"
Key Plan:
(E)W27X114
D
10'-0"
W6X9
W6X16
W6X16
(E)W21X50
W6X9
S101
10'-0" (MAX.)
10'-0" (MAX.)
1'-0 19/32"
2'-0"
(MIN.)
3"
ERECTION
BOLT
T.O.STL.
B
(E)W16X31
S101
W6X15
L3X3X3/16
HANGER TYP.
C
S101
1/4X6X12 PL THUS:
3/16
3/16
1/4" = 1'-0"
1 1/2
1 1/2
5"
6 1/4"
3/16
3" 3"
5/16"
EQUIPMENT SUPPORT PLAN
A
(E) CONCRETE ON MTL.
DECK SLAB
MC6X12
(2 THUS)
EL. 792'-8 1/2"
7"
L3X3X5/16
(ON ALL 4 SIDES)
W6X15
3/16
3/16
L3 1/2X3 1/2X5/16X1' 4"
OhioHealth
TYP.
6.03"
W/ 4" EMBED (TYP. OF 4)
BOLT PER PHILIPS
DRAWINGS
1.
2.
3.
3/16
3/16
MATERIALS:
a. STRUCTURAL STEEL WIDE FLANGE: ASTM 992; STRUCTURAL STEEL CHANNEL,
ANGLES, PLATES, ETC.: ASTM A36, FY = 36 KSI; HIGH STRENGTH BOLTS: ASTM
A325 OR A490; ANCHOR BOLTS: ASTM A307 OR A36; ELECTRODES: SERIES E70;
EXPANSION BOLTS: HILTI "KWIK-BOLT TZ," SIMPSON STRONG-TIE "STRONG-BOLT"
OR APPROVED EQUAL. ADHESIVE ANCHORS: HILTI "HIT-ICE/HIT HY 150,"
SIMPSON STRONG-TIE "ACRYLIC-TIE," ITW RED-HEAD "A7 ACRYLIC."
SPECIFICATION: WELDING PERSONNEL AND PROCEDURES ARE TO BE QUALIFIED
PER AWS D1.1. UNLESS SPECIFICALLY SHOWN OTHERWISE, DESIGN, FABRICATION
AND ERECTION TO BE GOVERNED BY:
a. AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
(MARCH 9, 2005).
b. AISC CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES
(MARCH 18, 2005).
c. STRUCTURAL WELDING CODE, AWS D1.1/D1.1 M: 2012 OF THE AMERICAN
WELDING SOCIETY.
d. SPECIFICATIONS FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS
(JUNE 30, 2004).
EP POWER BOOM
CEILING PL BY PHILIPS
2'-0"
CEILING
TYP.
1'-0"
GENERAL NOTES:
STRUCTURAL STEEL:
L3X3X3/16
(ON ALL 4 SIDES)
L3X3X1/4
HANGER
(4 THUS)
1/2X4 PLATE
(4 THUS)
AS REQ'D
2'-0" MIN.
5/8" THICK PLATE
D
SECTION
3/4" = 1'-0"
E
SECTION
PROVIDE OPENING &
BOLT HOLES IN PLATE
AS REQUIRED BY
EQUIPMENT SUPPLIER
PROVIDE OPENING &
BOLT HOLES IN PLATE
AS REQUIRED BY
EQUIPMENT SUPPLIER
3/4" = 1'-0"
3/8" THICK PLATE
AS REQ'D
COORD. EL.
W/EQUIP. SUPPLIER
F
EP Lab #1
Renovation
Riverside Methodist Hospital
3535 Olentangy River Road
Columbus, Ohio 43214
Project Number:
Original Issue Date:
Revised Date:
SCHEMATIC DESIGN
DESIGN DEVELOPMENT
ZONING SUBMISSION
CONSTRUCTION DOCUMENTS
RECORD/ AS-BUILT'S
SECTION
SURGICAL LIGHT SUPPORT
3/4" = 1'-0"
PAINT:
a. PROVIDE ONE SHOP COAT TO ALL STEEL.
BC
REVISION HISTORY
NO. DATE
DESCRIPTION
A
-
-
B
-
-
1
-
-
2
-
-
3
-
-
4
-
-
5
-
-
6
-
-
CATH LAB
EQUIPMENT
SUPPORT PLAN
AND DETAILS
PBK
BC
S-101
The work contained within these instruments of service is the property of Andrews Architects, Inc. and is protected by U.S. Copyright Law. These drawings may not be modified, duplicated, sold or otherwise distributed except that these drawings may be used solely by the owner or contractors of the indicated project for the purpose of constructing the indicated project. No party may create derivative work based on information provided within these drawings in whole or in part. Any reproductions or modifications without the express written consent of Andrews Architects, Inc. is strictly prohibited.
GENERAL NOTES:
1.
FIELD VEIFY EXACT SIZE AND LOCATION OF EXISTING
DUCTWORK, PIPING AND EQUIPMENT PRIOR TO STARTING
WORK.
2.
COORDINATE ALL UTILITY SHUTDOWNS WITH THE OWNER
TWO WEEKS IN ADVANCE OF SHUTDOWN.
ANDREWS
ARCHITECTS
3.
EXISTING FIRE PROTECTION SYSTEM TO REMAIN IN PLACE.
ADJUST LOCATION OF SPRINKLER HEADS AS NECESSARY
TO ACCOMMODATE NEW BOOMS AND CEILING MOUNTED
EQUIPMENT.
Architecture
Planning
Interior Design
4.
EXISTING CEILING IS TO BE REMOVED AND REINSTALLED.
REMOVE, PROTECT, AND REINSTALL ALL CEILING AIR
DEVICES AND SPRINKLER HEAD ESCUTCHEONS.
2
2
STORZ
AV RACK
MB
MA
MP
MG
3
3
6631 Commerce Parkway, Studio B
Dublin, Ohio 43017
3 4"
Tel: 614 . 766 . 1117
Fax: 614 . 766 . 2023
CODED NOTES:
(R) 3/4" VAC
1.
EXISTING MEDICAL GAS ZONE VALVE BOX TO REMAIN.
2.
EXISTING WAGD, VAC, O2, AND MA INLETS/OUTLETS TO
REMAIN.
3.
EXISTING VAC, O2, AND MA INLETS/OUTLETS TO REMAIN.
4.
BOOM CONTAINS (1) MA, (2) O2, (2) VAC, AND (1) WAGD
INLETS/OUTLETS. PROVIDE 1/2" MA, 1/2" O2, 3/4" VAC, AND
3/4" WAGD PIPING TO BOOM. CONTRACTOR TO MAKE FINAL
PIPING CONNECTIONS TO BOOM. COORDINATE WITH BOOM
MANUFACTURER.
5.
BOOM CONTAINS (2) VAC, (1) 02, AND (1) MA
INLETS/OUTLETS. CONTRACTOR TO MAKE FINAL PIPING
CONNECTIONS TO BOOM. COORDINATE WITH BOOM
MANUFACTURER.
(R) 1/2" O2
Head
End
(E)MA
(E)O2
12"
(E)WAGD
(E)VAC
(E)O2
(E)MA
(E)VAC
EP LAB #1
Seal:
Key Plan:
12"
3 4"
(E)O2
(E)WAGD
(E)MA
(E)VAC
(E)O2
(E)WAGD
(E)MA
(E)WAGD
(E)VAC
3 4"
1
12"
4
(R) 1/2" MA
www.AndrewsArchitects.com
EP LAB #1
5
1/2"
1/2"
3/4"
3/4"
OhioHealth
A
SECOND FLOOR
1/4 = 1' 0"
DEMOLITION PLAN
0'
1'
2'
4'
B
SECOND FLOOR
EP Lab #1
Renovation
1/4 = 1' 0"
NEW WORK PLAN
0'
1'
2'
4'
Riverside Methodist Hospital
3535 Olentangy River Road
Columbus, Ohio 43214
Project Number:
Original Issue Date:
Revised Date:
SCHEMATIC DESIGN
DESIGN DEVELOPMENT
ZONING SUBMISSION
CONSTRUCTION DOCUMENTS
RECORD/ AS-BUILT'S
REVISION HISTORY
NO. DATE
DESCRIPTION
A
-
-
B
-
-
1
-
-
2
-
-
3
-
-
4
-
-
5
-
-
6
-
-
FLOOR PLAN
PLUMBING WORK
Ed Keener
Jesse Whitehead
P-101
The work contained within these instruments of service is the property of Andrews Architects, Inc. and is protected by U.S. Copyright Law. These drawings may not be modified, duplicated, sold or otherwise distributed except that these drawings may be used solely by the owner or contractors of the indicated project for the purpose of constructing the indicated project. No party may create derivative work based on information provided within these drawings in whole or in part. Any reproductions or modifications without the express written consent of Andrews Architects, Inc. is strictly prohibited.
(E)26/14
(E)26/14
GENERAL NOTES:
(E)26/12
(E)26/12
TB2
R1-24/10
940
2
7
2.
COORDINATE ALL UTILITY SHUTDOWNS WITH THE OWNER
TWO WEEKS IN ADVANCE OF SHUTDOWN.
ANDREWS
ARCHITECTS
3.
EXISTING CEILING IS TO BE REMOVED AND REINSTALLED.
REMOVE, PROTECT, AND REINSTALL ALL CEILING AIR
DEVICES. COORDINATE FINAL LOCATION OF CEILING AIR
DEVICES WITH ARCHITECTURAL REFLECTED CEILING PLAN.
Architecture
Planning
Interior Design
CODED NOTES:
6631 Commerce Parkway, Studio B
Dublin, Ohio 43017
10 TB1
(E)22/12
MB
MP
MA
MG
R2-24/10
940
4
T
FIELD VEIFY EXACT SIZE AND LOCATION OF EXISTING
DUCTWORK, PIPING AND EQUIPMENT PRIOR TO STARTING
WORK.
24/10
(1500) 8
2
STORZ
AV RACK
1
1.
9 (750)
T
5
(R)22/12
11
(E)14/10
(E)14/10
3
1.
EXISTING TERMINAL BOX TO REMAIN.
2.
REMOVE EXISTING TERMINAL BOX AND TURN OVER TO THE
OWNER.
3.
EXISTING TEMPERATURE SENSOR, HUMIDITY SENSOR, AND
MOTION SENSOR TO REMAIN.
www.AndrewsArchitects.com
4.
EXISTING TEMPERATURE SENSOR TO REMAIN.
Seal:
5.
EXISTING DUCT DROPS IN CHASE TO SERVE LOW RETURN
REGISTER.
6.
EXISTING AIR DEVICE TO BE REUSED.
7.
REMOVE EXISTING AIR DEVICES AND TURN OVER TO THE
OWNER.
8.
RE-BALANCE EXISTING AIR TERMINAL BOX FOR INDICATED
AIR FLOW.
9.
RE-BALANCE EXISTING AIR DEVICE FOR INDICATED AIR
FLOW.
14/10
3
T
T
H
22/12
H
S
S
6
6
9 (400)
Head
End
(400) 12
11 4 "
9 (400)
6
(E)30/12
(E)20/12
(E) HWS
(E) HWR
(E)14/10
(E)30/12
(E)20/12
(E) HWS
(E)14/10
(E) HWR
11 4 "
10. CONNECT EXISTING HEATING HOT WATER SUPPLY AND
RETURN PIPING AND CONTROLS TO NEW TERMINAL BOX.
REUSE EXISTING CONTROLS AND VALVES.
Tel: 614 . 766 . 1117
Fax: 614 . 766 . 2023
Key Plan:
11. EXISTING TEMPERATURE SENSOR IS TO CONTROL NEW
TERMINAL BOX.
6
12. RELOCATE AND RE-BALANCE EXISTING AIR DEVICE FOR
INDICATED AIR FLOW.
EP LAB #1
EP LAB #1
(400) 12
5
MECHANICAL EQUIPMENT :
9 (750)
1
TB1
(1600) 8
PROVIDE TITUS MODEL DESV TERMINAL BOX OR
INLET AND A 2-ROW HOT WATER HEATING COIL.
BALANCE FOR 940 CFM. HEATING COIL TO BE
BALANCED FOR 2.0 GPM AND HAVE A CAPACITY OF
30.5 MBH.
TB2
PROVIDE TITUS MODEL DESV TERMINAL BOX OR
OhioHealth
INLET. BALANCE FOR 940 CFM.
R1
PROVIDE TITUS MODEL 350RL REGISTER OR
LOUVER.
R2
A
SECOND FLOOR
1/4 = 1' 0"
DEMOLITION PLAN
0'
1'
2'
4'
B
PROVIDE TITUS MODEL 301RL REGISTER OR
LOUVER.
SECOND FLOOR
1/4 = 1' 0"
NEW WORK PLAN
0'
1'
2'
EP Lab #1
Renovation
Riverside Methodist Hospital
3535 Olentangy River Road
Columbus, Ohio 43214
4'
Project Number:
Original Issue Date:
Revised Date:
SCHEMATIC DESIGN
DESIGN DEVELOPMENT
ZONING SUBMISSION
CONSTRUCTION DOCUMENTS
RECORD/ AS-BUILT'S
REVISION HISTORY
NO. DATE
DESCRIPTION
A
-
-
B
-
-
1
-
-
2
-
-
3
-
-
4
-
-
5
-
-
6
-
-
FLOOR PLAN
HVAC WORK
Ed Keener
Jesse Whitehead
H-101
The work contained within these instruments of service is the property of Andrews Architects, Inc. and is protected by U.S. Copyright Law. These drawings may not be modified, duplicated, sold or otherwise distributed except that these drawings may be used solely by the owner or contractors of the indicated project for the purpose of constructing the indicated project. No party may create derivative work based on information provided within these drawings in whole or in part. Any reproductions or modifications without the express written consent of Andrews Architects, Inc. is strictly prohibited.
Final Site Preparation Support Document
www.healthcare.philips.com
B
12/11/2013
AL, A1, S2: Added Berchtold ceiling booms
HN
C
12/19/2013
A1/S1/S2/E1/E2: Revised room layout per updated CAD background.
CP
Section A - Equipment Plan
General Notes ----------------------------------------- AN
Equipment Legend ------------------------------------ AL
Equipment Plan ---------------------------------------- A1
Transport Details ------------------------------------ AD1
Equipment Details -------------------------- AD2 - AD6
Section S - Support Plan
Support Notes ------------------------------------------ SN
Support Legend ---------------------------------------- SL
Support Plan - Floor & Wall ------------------------- S1
Support Plan - Ceiling -------------------------------- S2
Support Details ------------------------------ SD1 - SD4
Drawn By: Christy Perez
HN
Email: [email protected]
Created final site preparation support document
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
10/09/2013
Allura FD10 Ceiling
A
Contact Number: (304) 625-1612
By
Date
Philips Contacts
Project Manager: Michael Whelchel
Revision Descriptions
Rev.
Project
Table of Contents
N-EAS131715 C
Revision History
Note for Architects and/or Contractors: If revisions are listed, these drawings must be thoroughly reviewed so that all changes can be incorporated into your project
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
The equipment components shown in this drawing package are based on the current proposed purchase and
are subject to change if modifications are made to the configuration.
Electrical Notes ---------------------------------------- EN
Electrical Legend -------------------------------------- EL
Electrical Plan ------------------------------------------- E1
Raceway & Conduit Information ------------- E2 - E3
Electrical Details ---------------------------- ED1 - ED3
Remote Service Network --------------------- N1 - N2
Check List -------------------------------------------- CHK
Project Details
Drawing Number
Section E - Electrical Plan
C1
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
Healthcare
HVAC Requirement for General Equipment Locations
Minimum Site Preparation Requirements
Equipment's designed airflow is from bottom to top and front to back. Please design the air
handling in the rack cabinet equipment area accordingly.
(12.0)
2. Doors and windows, especially radiation protection barriers, installed and finished with
locksets operational.
3. All electrical convenience, conduit, raceway, knockouts, cable openings, chase nipples, and
junction boxes installed and operational.
Supply Configuration:
3 phase, 3 wire power and ground, delta (preferred) or wye
3 phase, 4 wire power with neutral + ground, wye (without gssPDU)
All contractor supplied cables pulled and terminated.
Nominal Line Voltage:
480 VAC, 60 Hz
8.
A dust-free environment in and around the procedure room.
Branch Power Requirement:
Circuit Breaker:
225 KVA
3 pole, 125 Amps
9. All HVAC (heating, ventilating and air conditioning) installed and operational as per
specifications.
(12.0)
10. Architectural features such as computer floor, wood floor, casework, bulkheads, installed
and finished. When technical cabinets are installed in a closet with doors, it is suggested that
the customer install a temperature alarm in the event of an air conditional failure.
Remote Control of Room Lighting
The control of customer lighting must incorporate an electrical isolation system such as
demonstrated on Sheet ED2. Lighting scheme is the responsibility of the customer.
6. Schedule
The general contractor should provide Philips with a schedule of work to assist in the
coordination of delivery of Philips supplied products which are to be installed by the
contractor and delivery of the primary equipment.
13. Clear door openings for moving equipment into the building must be 42" (1067mm) W x 82"
(2083mm) H min. 48" (1219mm) W x 82" (2083mm) H rec., Or larger contingent on an 8'-0"
(2438mm) corridor width.
12. Philips does not install or connect developing tanks, automatic processors or associated
equipment, built in illuminators, cassette pass boxes, loading benches and cabinets, lead
protective screens, panels or lead glass window and frame. This is to be done by the
customer/contractor.
14. Countertop is 30" (765mm) for seated height and 36" (915mm) for standing height.
Note
Once Philips has moved equipment into the suite and started the installation, the contractor shall
schedule his work around the Philips installation team on site. It is suggested that a telephone
be provided in the room to receive telephone calls. This would alleviate facility staff from
answering calls for Philips personnel.
Remote Service Diagnostics
Medical imaging equipment to be installed by Philips Medical is equipped with a service
diagnostic feature which allows for remote and on site service diagnostics. To establish this
feature, a RJ45 type ethernet 10/100/1000 Mbit network connector must be installed as shown
on plan. Access to customer's network via their remote access server is needed for Remote
Service Network (RSN) connectivity. All cost with this feature are the responsibility of the
customer.
(12.0)
(12.0)
Project Details
Drawing Number
(12.0)
Drawn By: Christy Perez
7.
11. All plumbing installed and finished.
8. Infection Control and Interim Life Safety Measures
Compliance with all Infection Control and Interim Life Safety Measures shall be the sole
responsibility of the customer. The customer shall provide all means and methods
necessary for compliance with Infection Control (IC) and Interim Life Safety Measures
(ILSM) in connection with the construction and installation/operation of the products shown
herein and shall bear any expenses related to same.
100KW
6. All support structure correctly installed. All channels, pipes, beams and/or other supporting
devices should be level, parallel, and free of lateral or longitudinal movements.
5. Labor
In the event local labor conditions make it impossible or undesirable to use Philips' regular
employees for such installation and connection, such work shall be performed by laborers
supplied by the customer, or by an independent contractor chosen by the customer at the
customer's expense, and in such case, Philips agrees to furnish adequate engineering
supervision for proper completion of the installation.
7. Extended Installation or Turnkey Work by Philips
Any room preparation requirements for Philips equipment indicated on these drawings is
the responsibility of the customer. If an extended installation or turnkey contract exists
between Philips and the customer for room preparation work required by the equipment
represented on these drawings, some of the responsibilities of the customer as depicted
in these drawings may be assumed by Philips. In the event of a conflict between the work
described in the turnkey contract workscope and these drawings, the turnkey contract
workscope shall govern.
Power Output:
AN
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
120V convenience outlets operational.
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
5.
Email: [email protected]
Incoming mains power operational and connected to room x-ray breaker.
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
4.
Electrical Requirements
Velara with gssPDU
Allura FD10 Ceiling
4. Asbestos and Other Toxic Substances
Philips assumes no hazardous waste (i.e., PCB's in existing transformers) exists at the
site. If any hazardous material is found, it shall be the sole responsibility of the customer
to properly remove and dispose of this material at its expense. Any delays caused in the
project for this special handling shall result in Philips time period for completion being
extended by like period of time. Philips assumes that no asbestos material is involved in
this project in any ceilings, walls or floors. If any asbestos material is found anywhere on
the site, it shall be the customer's sole responsibility to properly remove and/or make safe
this condition, at the customer's sole expense.
1. Walls to be painted or covered, baseboards installed, floors to be tiled and/or covered,
ceiling shall have grid tiles and lighting fixtures installed and operational.
20% - 80% with 10% max. variation.
Contact Number: (304) 625-1612
3. Radiation Protection
The customer or his contractor, at his own expense, shall obtain the service of a licensed
radiation physicist to specify radiation protection. (X-Ray Tube output 150 KVp max.)
Heating, ventilation, air conditioning requirement for general equipment locations must maintain
N-EAS131715 C
2. Permits
Customer shall obtain all permits and licenses required by federal, state/provincial or local
authorities in connection with the construction, installation and operation of the products
and related rules, regulations, shall bear any expense in obtaining same or in complying
with any ordinances and statutes.
A smooth efficient installation is vital to Philips and their customers. Understanding what the
minimum site preparation requirements are will help achieve this goal. The following list clearly
defines the requirements which must be fulfilled before the installation can begin.
Project
1. Responsibility
The customer shall be solely responsible, at its expense for preparation of site, including
any required structural alterations. The site preparation shall be in accordance with plans
and specifications provided by Philips. Compliance with all safety electrical and building
codes relevant to the equipment and its installation is the sole responsibility of customer.
The customer shall advise Philips of conditions at or near the site which could adversely
affect the carrying out of the installation work and shall ensure that such conditions are
corrected and that the site is fully prepared and available to Philips before the installation
work is due to begin. The customer shall provide all necessary plumbing, carpentry work,
or conduit wiring required to attach and install products ready for use.
Philips Contacts
Project Manager: Michael Whelchel
General Specifications
Equipment Legend
Furnished and installed by Philips
Furnished by customer/contractor and installed by customer/contractor
Installed by customer/contractor
Furnished by Philips and installed by contractor
Existing
Future
Optional item furnished by Philips
A
MG
Velara Generator 40E Cabinet
510
2971 AD3
A
MP
Peripheral 40E Cabinet
510
2049 AD3
A
MA
Mains 40E Cabinet
826
5464 AD3
220
1250 AD3
D PDU gssPDU
A
MB
Image 40E Cabinet
826
5464 AD5
A
CY
Viewing/Control
126
567 AD3
A
DB
Documentation Box - Mounted on Wheels
(Final location to be coordinated with customer
and/or local Philips Service)
176
0 AD4
A
ATY Exam Room Auxiliary Box
7
1.7 AD4
603
1020 AD4
167
350 AD5
11
34 AD4
11
34 AD4
73
2424 AD5
1082
- AD6
A
TV
56" LCD Monitor Suspension with Exam Lamp
A MAV Mavig Ceiling Track w/ Radiation Shield
A
VB1 Video Connection Box
~
A
VB9 Video Connection Box
A EPN EP Navigator
A
EPB EP Power Boom (Including Accessories)
A
Berchtold Boom A
-
-
-
B
B
Berchtold Boom B
-
-
-
B
C
Berchtold Boom C
-
-
-
Project Details
Drawing Number
B
Drawn By: Christy Perez
205 AD2
AL
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
1693
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
1195 AD2
Email: [email protected]
A MSA Angio Diagnost 7 with Pivot
2387
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
Poly G Stand (Ceiling Version)
Allura FD10 Ceiling
SP
Contact Number: (304) 625-1612
A
Weight Heat Load
(lbs)
(btu/hr)
N-EAS131715 C
Description
Detail Sheet
Project
Equipment Designation
Philips Contacts
Project Manager: Michael Whelchel
A
B
C
D
E
F
G
1"
12'-24
4'-05
8"
STORZ
AV RACK
1'-6"
PDU
Equipment
closet doors to
be hung from
ceiling mounted
track, no floor
tracks allowed
A
3
!
3
!
C
VB6
VB7
VB8
VB9
Exact location to be coordinated by Customer
and local Philips service.
General Notes
1
!
* Counters and cabinetry shown to be supplied and installed by contractor.
EPB
* Local Philips Service to consult with customer for final placement of control desk
components.
11'-0"
2
!
Planning Issues and Considerations
1
!
Relocate endstops on the Monitor Suspension to avoid collision with the EP
Power Boom. [Maximum overhang = 5 7/8" (150mm)]
14'-3"
2
!
Patient loading may be difficult. Verify with customer requirement.
3
!
Third Party Items - It is the region's responsibility to interface and coordinate
customer's non-catalog item(s) with Philips' equipment. Verify feasibility and
ensure full functionality and movement of Poly G Stand and Monitor
Suspension.
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
Poly G / Table
3"
23'-416
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Drawn By: Christy Perez
VB5
Email: [email protected]
VB4
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
VB3
5'-6"
Allura FD10 Ceiling
DB
2'-0"
Recommended
Minimum
2'-8"
Contact Number: (304) 625-1612
2m
N-EAS131715 C
1m
Keyboard tray
supplied and
installed by
customer
Project
8'
Philips Contacts
Project Manager: Michael Whelchel
.5m
4'
Project Details
Drawing Number
0
2'
11"
31'-616
1'
AD7 Table Floor Plate
0
!
B
11"
31'-616
3
Required Ceiling Height: 9' - 6 16
", +38" / -0 (2900mm, +10mm / -0)
Ceiling Height measured from finished floor to bottom of Unistrut.
3
7'-6"
Equipment Layout
A1
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
2'-0" High
Wall
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
Pallet
Kick Wheels Wide
Kick Wheels Small
Height
57.09" (1450mm)
54.80" (1392mm)
49.25" (1251mm)
49.25" (1251mm)
Weight
2033 lbs (922 kg)
1911 lbs (867 kg)
1764 lbs (800 kg)
1764 lbs (800 kg)
[1100mm]
[1100mm]
[1653mm]
Transport Possibilities
Crate
Pallet
Klick Wheels
Height
77.95" (1980mm)
75.59" (1920mm)
70.08" (1780mm)
Weight
2028 lbs (920 kg)
1907 lbs (865 kg)
1764 lbs (800 kg)
(12.0)
Transport Possibilities
AD1
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
Drawn By: Christy Perez
Crate
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
[923mm]
Email: [email protected]
[1568mm]
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
[928mm]
Allura FD10 Ceiling
[1000mm]
Contact Number: (304) 625-1612
Detail - Poly Diagnost G (C-ARM) Transport Details
Project
5"
3'-016
[2918mm]
5'-13
4"
N-EAS131715 C
1"
5'-516
9'-67
8"
9"
3'-016
Philips Contacts
Project Manager: Michael Whelchel
5"
3'-716
[2918mm]
9'-67
8"
[2990mm]
9'-93
4"
[3000mm]
1"
9'-108
3'-33
8"
Project Details
Drawing Number
5"
3'-716
[2357mm]
7'-83
4"
[2500mm]
7"
8'-216
[2500mm]
7"
8'-216
Detail - Poly Diagnost G Ceiling (L-ARM) Transport Details
Side
SP
[19mm]
Min.
3"
4
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
Floor Plate
1"
8'-68
3"
1'-1116
[2594mm]
[588mm]
11"
5'-1016
[1795mm]
Weight
Heat Dissipation
2387 lbs
1195 btu/hr
Front
Poly G Stand (Ceiling Version)
MSA
[290mm]
Table Pivot is optional. This allows the table to rotate -90, +180 degrees
about center of table base.
(12.0)
Angio Diagnost 7
(12.0)
Weight
Heat Dissipation
1693 lbs
205 btu/hr
9"
12'-916
[990mm]
AD2
3.15.13
1"
1'-716
[484mm]
[484mm]
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Allura FD10 Ceiling
Indicates equipment movement
Drawn By: Christy Perez
Email: [email protected]
[290mm]
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
7"
1116
Contact Number: (304) 625-1612
7"
1116
Project
[1350mm]
N-EAS131715 C
[650mm]
Philips Contacts
Project Manager: Michael Whelchel
1"
4'-58
Project Details
Drawing Number
9"
2'-116
[117mm]
45
8"
Top
[2900mm, +10mm / -0]
Required ceiling height
[650mm]
3 ", +3/8" / -0
9'-616
[3900mm]
Maximum Travel
Max.
9"
2'-116
3'-3"
1"
1'-716
[1795mm]
[1072mm]
Hose Arm
and Outlet
on opposite
side
(Optional)
3"
3'-616
Parked position
limited 300mm
for shorter rooms
1'-0"
[2330mm]
[305mm]
[990mm]
1'-0"
7'-73
4"
[305mm]
[1900mm]
6'-213
16"
3'-3"
[792mm]
3"
2'-716
[1065mm]
3'-515
16"
Minimum clearance required for installation of
carriage into rails (either side)
Hose Outlet
Optional Table
Pivot
(-90, +180 degrees)
11"
5'-1016
[276mm]
[520mm]
1'-0"
[305mm]
[260mm]
103
4"
[273mm]
6"
Top
Front
11"
1'-716
[500mm]
Acoustic noise level:
without UPS: <= 45 dB(A) in any 1 meter (3.28') direction
with UPS: <= 52 dB(A) in any 1 meter (3.28') direction
220 lbs
1250 btu/hr
CRC Cover
Front
Side
Side
Top
Top
1'-95
8"
67
8"
1"
1'-82
1'-95
8"
67
8"
1"
1'-82
[550mm]
[175mm]
[520mm]
[550mm]
[175mm]
[520mm]
Keyboard / Mouse
LCD Monitor
Side
126 lbs
567 btu/hr
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
Side
The CRC Cover must be attached to the 40E rack only, not to the wall.
Acoustic noise level: <= 65 dB(A) @ 1 meter in front of the rack and
1 meter high (1 meter = 39.37")
Acoustic noise level: <= 55 dB(A) @ 1 meter in front of the rack and
1 meter high (1 meter = 39.37")
(12.0)
Heat Dissipation
Front
The CRC Cover must be attached to the 40E rack only, not to the wall.
(12.0)
View/Control (All Components)
Weight
[1955mm]
6'-415
16"
Front
Front
Side
Connection Box
(See SD3 for mounting options)
CRC Cover
[1955mm]
6'-415
16"
[548mm]
9"
1'-916
[800mm]
[143mm]
Top
1"
2'-72
55
8"
CRC Cover
(12.0)
Peripheral 40E Cabinet
MP
Weight
Heat Dissipation
510 lbs
2049 btu/hr
Velara Generator 40E Cabinet
MG
Email: [email protected]
[60mm]
[35mm]
5"
1'-716
13
8"
23
8"
Weight
Heat Dissipation
510 lbs
2971 btu/hr
Drawn By: Christy Perez
Heat Dissipation
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
5464 btu/hr
Weight
Contact Number: (304) 625-1612
826 lbs
PDU
N-EAS131715 C
Heat Dissipation
Project
[100mm]
Weight
Allura FD10 Ceiling
gssPDU
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
(13.0)
(12.0)
Mains 40E Cabinet
MA
[490mm]
CY
Side
Top
[425mm]
Front
Back
CRC Cover
[485mm]
1"
1'-78
1'-43
4"
[213mm]
83
8"
[189mm]
Top
2'-0"
[610mm]
Front
The CRC Cover must be attached to the 40E rack only, not to the wall.
Imaging Cardio T.S.O.
(Optional)
Review Module
2.50" dia.
knockout plug
(2x)
Side
Acoustic noise level: <= 55 dB(A) @ 1 meter in front of the rack and
1 meter high (1 meter = 39.37")
Side
1'-85
8"
[524mm]
.87" dia.
knockout plug
Philips Contacts
Project Manager: Michael Whelchel
Front
[153mm]
Project Details
Drawing Number
Side
315
16"
Front
6"
[153mm]
[690mm]
3"
2'-316
[547mm]
[260mm]
[302mm]
7"
716
7"
416
1"
104
9"
1'-916
CRC Cover
6'-415
16"
[178mm]
7"
Top
[98mm]
37
8"
Top
117
8"
Side
Geometry T.S.O.
(Optional)
[1955mm]
Front
[112mm]
Side
XPER Module
[250mm]
913
16"
Front
Service
Clearance
AD3
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
[160mm] 1'-81"
2
3'-0"
107
8"
Seismic fixation shall be fixed
maintaining functional isolation to
building steel. This can be verified
with a Megger or Ohm meter. The test
voltage shall not exceed 500V. The
minimum isolation impedance shall be
>5MOhm at 0Hz, >100kOhm at 60Hz
and >10kOhm at 1kHz.
[915mm]
[550mm]
5"
616
[524mm]
[126mm]
1"
104
1'-95
8"
Top
1'-85
8"
[178mm]
415
16"
7"
[125mm]
Top
[178mm]
[313mm]
[231mm]
1"
98
5"
1'-016
415
16"
7"
[231mm]
1"
98
Top
CRC Cover
CRC Extension
VB1
~
VB8
Weight
Heat Dissipation
176 lbs
0 btu/hr
7"
916
1"
92
[240mm]
[242mm]
Front
Side
Weight
Heat Dissipation
11 lbs
34 btu/hr
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
Top
5"
5'-016
Video Connection Box
TV
Front
(12.0)
[1531mm]
Side
(13.0)
56" LCD Monitor Suspension
(12.0)
Weight
Heat Dissipation
603 lbs
1020 btu/hr
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Allura FD10 Ceiling
Bearing Forces:
(Tension) Tmax = 661 lbs/support
(Shear) Vmax =
150 lbs/support
[335mm]
AD4
3.15.13
[1875mm]
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
Drawn By: Christy Perez
Email: [email protected]
Documentation Box
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
For swing labs, 2700mm long ceiling rails are delivered. Maximum longitudinal column travel = 2100mm.
Weight shown is total weight including monitors, suspension, cabling, and options.
Project
[2765mm]
Contact Number: (304) 625-1612
[3900mm]
N-EAS131715 C
[3510mm]
9'-07
8"
Philips Contacts
Project Manager: Michael Whelchel
9"
12'-916
Project Details
Drawing Number
3"
11'-616
[2014mm]
Side
Top
[1694mm]
3"
1'-116
11"
5'-616
[550mm]
[130mm]
1'-95
8"
6'-113
16"
1.7 btu/hr
1"
58
7 lbs
[250mm]
913
16"
Heat Dissipation
5"
6'-716
DB
Weight
Recommended viewing
height from floor.
[195mm]
[1588mm]
1"
5'-22
Front
[55mm]
Front
3"
216
Top
[335mm]
ATY
3"
1'-116
[285mm]
1"
114
[65mm]
9"
216
Top
[1120mm]
1"
3'-816
[1220mm]
4'-0"
11"
716
6'-43
4"
[1950mm]
Side
Auxiliary Box
(12.0)
Examination
Light
(Optional)
CRC Cover
Top
1'-95
8"
67
8"
1"
1'-82
[550mm]
[175mm]
[520mm]
7"
8'-216
Front
[2500mm]
Detail - Cross Support
(Not to scale)
1"
2'-72
[800mm]
Max.
Two,
1
2"
Side
The CRC Cover must be attached to the 40E rack only, not to the wall.
Acoustic noise level: <= 48 dB(A) @ 1 meter in front of the rack and
1 meter high (1 meter = 39.37")
(12mm) Dia. holes
826 lbs
5464 btu/hr
19" (480mm) Flat Panel Monitor
[66mm]
Side
[50mm]
25
8"
115
16"
1"
42
[170mm]
Top
[115mm]
CPU
Email: [email protected]
Side
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
Front
Front
Contact Number: (304) 625-1612
Side
11"
616
[83mm]
1"
34
Front
N-EAS131715 C
[336mm]
Philips Contacts
Project Manager: Michael Whelchel
1"
1'-14
[442mm]
1'-53
8"
[516mm]
[425mm]
Top
[750mm]
1"
1'-816
[510mm]
1'-43
4"
5"
1'-816
[336mm]
Top
1'-67
8"
77"
16
1"
1'-14
[402mm]
1'-313
16"
2'-1113
16"
[910mm]
[2190mm]
Maximum Travel
1"
2'-52
[189mm]
1"
7'-24
[479mm]
Top
Project
Bearing Forces:
(Tension) Tmax = 908 lbs/support
(Shear) Vmax =
38 lbs/support
1'-6"
[457mm]
Note: For Integris Systems, the post of the Rad Shield post needs to be mounted
on the head-end of the table in relation to the Monitor Suspension transverse carriage.
Front
Side
Keyboard / Mouse
Weight shown is for all components.
(12.0)
(12.0)
EP Navigator
Mavig Ceiling Track
MAV
C4
Weight
Heat Dissipation
167 lbs
350 btu/hr
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
EPN
Weight
Heat Dissipation
73 lbs
2424 btu/hr
Drawn By: Christy Perez
Heat Dissipation
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Weight
Allura FD10 Ceiling
MB
Project Details
Drawing Number
1"
716
[180mm]
Radiation Shield
[336mm]
Cross Support
1"
1'-14
(12.0)
Image 40E Cabinet
AD5
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
[1955mm]
6'-415
16"
CRC Cover
1"
2'-72
[800mm]
1'-615
16"
[481mm]
[261mm]
Email: [email protected]
MED-Gas
1. The EP Boom comes with option MED-Gas outlets for customer convenience. Connection and interfacing of the MED-Gas
to the EP Power Boom is the customer/contractor's responsibility.
2. Outlet types must be selected by Sales during quoting phase from one of the following: Chemetron, DISS, Ohmeda, Puritan
Bennett, No gas fitting.
3. All changes must be processed prior to start of system production.
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
Project
[718mm]
Contact Number: (304) 625-1612
Side
N-EAS131715 C
[540mm]
Philips Contacts
Project Manager: Michael Whelchel
Front
1"
2'-44
[361mm]
1"
1'-94
1"
1'-24
[600mm]
[40mm]
9"
116
1'-115
8"
1"
104
[800mm]
Project Details
Drawing Number
[2230mm]
7'-313
16"
1"
2'-72
Boom Brakes
Compressed Air / Nitrogen (minimum 72.5 PSI, maximum 116 PSI @ 2.6 CFM) is needed to activate the brakes for the EP Power
Boom. Connect to the 0.31" (8mm) copper inlet at EP Power Boom interface plate.
Delivery in Crate
110" (2800mm) L x 31.5" (800mm) W x 55" (1400mm) H - Weight = 68 lbs (30.8 kg).
Weight shown is for all components.
(12.0)
EP Power Boom
EPB
C5
Weight
Heat Dissipation
1082 lbs
- btu/hr
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
Drawn By: Christy Perez
[700mm]
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
9"
2'-316
Allura FD10 Ceiling
57"
8
[150mm]
[700mm]
[324mm]
1"
1'-118
9"
2'-316
1'-03
4"
MED-Gas (if ordered) - Oxygen, Vacuum,
Nitrous Oxide
Equipment Grounding (Qty 6)
Network Drops (Qty 2)
[588mm]
Top
AD6
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
R7'-93
4"
[R2382mm]
Shelf height variable at installation.
Weight 110 lbs (50 kg) per shelf.
110V Hospital Power Outlets (Qty 4*)
110V Emergency Power Outlets (Qty 4*)
3rd Party Equipment (powered by Hospital
Equipment Support Information
1. General
The customer shall be solely responsible, at its expense, for preparation of the site, including any required structural alterations. The site
preparation shall be in accordance with this plan and specifications, the architectural/construction drawings and in compliance with all safety
and building codes. The customer shall be solely responsible for obtaining all construction permits from jurisdictional authority.
2. Equipment Anchorage
Philips provides, with this plan and specifications, information relative to equipment size, weight, shape, anchoring hole locations and forces
which may be exerted on anchoring fasteners. The customer shall be solely responsible, through the engineer of record for the building, to
provide on the architectural/construction drawings, information regarding the approved method of equipment anchoring to floors, wall and/or
ceiling of the building. Any anchorage test required by local authority shall be the customer's responsibility. Stud type anchor bolts should
not be specified as they hinder equipment removal for service. Consult with Philips service prior to specifying anchor methods.
4. Ceiling Support Apparatus
a. Philips provides, with this plan and specifications, information relative to size, weight and shape of ceiling supported equipment. The
customer shall be solely responsible, through the engineer of record for the building, to provide on the architectural/construction drawings,
information regarding the approved method of structural support apparatus, fasteners and anchorage to which Philips will attach equipment.
Any anchorage and/or load test required by local authority shall be the customer's responsibility.
8. Floor Obstructions/ Floor Coverings
There shall be no obstructions on the floor (sliding door tracks, etc.) in front of the Philips technical cabinets. Floor must be clear to allow
cabinets to be pulled away from the wall for service.
Contractor to verify with Philips the preferred floor covering installation method.
9. Safety Factors
In a worst case situation the dynamic bolt force of a floor or ceiling must be multiplied by factor 4. (static bolt force of the ceiling must be
multiplied by factor 8). All safety factors are included in the bearing force values in sheet SD1.
Project Details
Drawing Number
10. Stiffness Requirements of Ceiling
Stiffness: 10,000,000 Newton/meter - 57.1 klb/in
Stiffness: 20,000,000 Newtonmeter/Rad - (177,014 klb in)/Rad
The maximum deflection on the Philips rails must not exceed 0.04" (1mm) caused by the static load (weight) of the ceiling stand
11. Vibration
The maximal allowed external frequency that will not destroy the image quality of our equipment is:
a.
b.
0 Hz till 20 Hz (frequency area of our equipment) - Displacement amplitude is smaller than 0.005mm
Greater than 20 Hz - Displacement amplitude is smaller than 0.01mm
(13.0)
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
Drawn By: Christy Perez
7. Seismic Anchorage (For Seismic Zones Only)
All seismic anchorage hardware, including brackets, backing plates, bolts, etc., shall be supplied and installed by the customer/contractor
unless otherwise specified within the support legend on this sheet. Installation of electronic cabinets to meet seismic anchorage
requirements must be accomplished using flush mounted expansion type anchor/bolt systems to facilitate the removal of a cabinet for
maintenance. Do not use threaded rod/adhesive anchor systems. Consult with Philips regarding any anchor system issues.
Email: [email protected]
6. Ceiling Obstructions
There shall be no obstructions that project below the finished ceiling in the area covered by ceiling suspended equipment travel.
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
5. Lighting
Lighting fixtures shall be placed in such a position that they are not obscured by equipment or its movement, nor shall they interfere with
Philips ceiling rails and equipment movement or otherwise adversely affect the equipment. Such lighting fixture locations shall be the sole
responsibility of the customer.
Project
Fasteners/anchors (i.e., bolts, spring nuts, lock and flat washers) and strip closures shall be provided by the customer.
Philips Contacts
Project Manager: Michael Whelchel
e.
Allura FD10 Ceiling
d. Any drilling and/or tapping of holes required to attach Philips equipment to the structural support apparatus shall be the responsibility of
the customer.
Contact Number: (304) 625-1612
c. The structural support apparatus surface to which Philips equipment is to be attached, shall have horizontal equipment attachment
1
surfaces parallel, square and level to within plus or minus 16
" (2mm) per entire span.
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Contractor to clearly mark Philips equipment longitudinal centerline on bottom of each structural support.
N-EAS131715 C
b.
SN
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
3. Floor Loading and Surface
Philips provides, with this plan and specifications, information relative to size, weight and shape of floor mounted equipment. The customer
shall be solely responsible, through the engineer of record for the building, to provide on the architectural/construction drawings confirmation
of the structural adequacy of the floor upon which the equipment will be placed. Any load test required by local authority, shall be the
customer's responsibility.
1
The floor surface upon which Philips equipment is to be placed/anchored shall be flat and level to within plus or minus 16
" (2mm) over a
length of 39" (1m).
Floor & Wall Support Legend
See S1 for Floor & Wall Support Layout
Furnished and installed/anchored by Philips (exceptions may exist, see Note 2)
Furnished and installed by customer/contractor and installed/anchored by customer/contractor
Installed/anchored by customer/contractor
Furnished by Philips and installed/anchored by contractor
Existing
Future
Optional
Item Number
Detail Sheet
Support in wall for Control Room Connection Box (CY)
SD3
A
F2
Anchors in wall for Control Room Connection Box (CY)
SD3
Ceiling Support Legend
Furnished and installed by Philips
Furnished by customer/contractor and installed by customer/contractor
Installed by customer/contractor
Furnished by Philips and installed by contractor
Existing
Future
Optional
Item Number
Detail Sheet
Description
C1
2 - Philips Poly G Rails
A
C2
2 - Philips Monitor Equipment Rails
SD1
SD2
SD2
B
C3
Unistrut (P1001 or equal) - Bottom of Unistrut 41" (6mm) Below Finished Ceiling
SD2
A
C4
Mavig Ceiling Track
AD5
D
C5
EP Power Boom Ceiling Plate
SD4
B
C6
Additional Opening on Finished Ceiling - Required for Installation of the Boom
(to be covered after EP Power Boom is installed)
SD4
Project Details
Drawing Number
A
Philips Contacts
Project Manager: Michael Whelchel
A
B
C
D
E
F
G
Project
See S2 for Ceiling Support Layout
Drawn By: Christy Perez
F2
SL
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
B
Email: [email protected]
SD1
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
AD7 Universal Floor Plate
Allura FD10 Ceiling
F1
Contact Number: (304) 625-1612
D
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Description
N-EAS131715 C
Notes:
1. Anchors for items that are installed/anchored by customer/contractor shall be
provided by customer/contractor.
2. Anchors for items that are installed/anchored by Philips shall be provided by
Philips. If customer's engineering documents specify anchors other than those
listed in this document, the anchors shall be provided by customer/contractor and
installed by Philips.
3. In all instances, the wall and/or floor support are the sole responsibility of the
customer/contractor. The customer's architect/engineer of record shall specify
wall and/or floor support sufficient for the bolt forces shown on the details.
A
B
C
D
E
F
G
Poly G / Table
Refer to Floor/Wall Support Legend Sheet SL
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
8'
2m
S1
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Allura FD10 Ceiling
3
Required Ceiling Height: 9' - 6 16
", +38" / -0 (2900mm, +10mm / -0)
Ceiling Height measured from finished floor to bottom of Unistrut.
Drawn By: Christy Perez
Email: [email protected]
14'-3"
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
1m
Contact Number: (304) 625-1612
.5m
4'
N-EAS131715 C
2'
Project
0
1'
Philips Contacts
Project Manager: Michael Whelchel
AD7 Table Floor Plate
0
Project Details
Drawing Number
11'-0"
Floor & Wall Support Layout
13'-1"
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
3'-5 9 "
16
C5
C6
1"
2'-84
5'-0"
14'-3"
Poly G / Table
Refer to Ceiling Support Legend Sheet SL
Email: [email protected]
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
S2
3.15.13
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Allura FD10 Ceiling
Project
2'-2"
2'-2"
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
Drawn By: Christy Perez
Contact Number: (304) 625-1612
5'-0"
N-EAS131715 C
Philips Contacts
Project Manager: Michael Whelchel
AD7 Table Floor Plate
2'-2"
6'-6"
1"
7'-102
2'-2"
2'-07"
8
2'-2"
57
8"
7'-6"
Project Details
Drawing Number
11'-0"
2m
2'-2"
1m
8'
7'-213
16"
1'-2"
11"
316
1'-65" 1'-65"
8
8
3'-2"
.5m
4'
57
8"
2'
215"
16
215
16"
0
1'
11"
516
5"
3'-716
0
1"
4'-102
3
Required Ceiling Height: 9' - 6 16
", +38" / -0 (2900mm, +10mm / -0)
Ceiling Height measured from finished floor to bottom of Unistrut.
7'-11"
Ceiling Support Layout
1"
14'-102
4'-6"
Detail - Structural Allura FD10 (Ceiling)
Detail - AD7 Table, Fixed/Pivot Base - Clearance Area
(Not Site Specific)
(Not to scale)
27
8"
[1497mm]
[73mm]
[595mm]
[1200mm]
[697mm]
7"
2'-316
AD7 Universal
Floor Plate
[150mm]
Max.
1'-13
4"
3"
1'-1116
[350mm]
[588mm]
2'-2"
9"
12'-916
Floor Plate
[660mm]
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Drawn By: Christy Perez
Stand
(Not to scale)
Email: [email protected]
[38mm]
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
[450mm]
11"
1'-816
[150mm]
1"
12
11"
1'-516
Detail - Cable Hose Outlet
57
8"
[170mm]
11"
616
[38mm]
[525mm]
11"
1'-516
[450mm]
1"
12
[525mm]
11"
1'-816
Contact Number: (304) 625-1612
1. 1.18" (30mm) thick floor plate, flush mounted with top of slab.
1
2. Level within 16
" (1.5mm) across surface of plate.
N-EAS131715 C
Project
(Not to scale)
(12.0)
Philips Contacts
Project Manager: Michael Whelchel
Detail - AD7 Universal Floor Plate - Notes for Installation
(Not to scale)
Philips Flush
Mounted Floor Plate
Allura FD10 Ceiling
[262mm]
(12.0)
Detail - Clip Rail Spacing
2'-113
8
[525mm]
5"
1016
Note: The bearing force shown for the Poly G is the maximum instantaneous equipment bearing load that can
result from abusive use of the system. This force can occur at two locations simultaneously
on the same Unistrut (or equal) rail. If seismic forces must be considered,
please refer to the seismic calculation sheets provided by Philips for the specific system components.
C1
11"
1'-816
AD7 Table
Floor Plate to Floor Bolt Forces:
(Tension)
Tmax = 1950 lbs/bolt
(Shear)
Vmax = 776 lbs/bolt
Project Details
Drawing Number
F1
1'-1015
16"
Poly G
Poly G Bearing Forces:
(Tension)
Tmax = 2639 lbs/support
(Shear)
Vmax = 561 lbs/support
[582mm]
[3900mm]
27" (685mm) maximum allowed distance between unistrut (seven unistrut required)
Floor plate supplied by Philips / installed by Customer. Counterbored holes are sized for 21" (12mm) anchors per Seismic requirements.
Six mounting holes, M6
1"
42
1"
42
[115mm]
[115mm]
Four holes, 0.74" (19mm) dia.
Counterbored 1.57" (40mm)
dia. x 0.83" (21mm) deep
57
8"
[248mm]
11"
616
[170mm]
Floor plate mounting to the building:
In case threaded rods are used and the nut protrudes above the floor plate surface, DO
NOT GRIND DOWN THE NUT, but follow the procedure stated below to ensure the nut is
flush with the floor plate surface.
[25mm]
[25mm]
1"
93
4"
1"
[138mm]
7"
516
[150mm]
Offset border of floor
covering (Vinyl) by 0.16"
(4mm) outwards. Follow
outline of raised portion of
floor plate.
F1
(12.0)
1.
2.
3.
4.
Use Jam nuts M16 (h=8.0mm) or (h=9.5mm)
Use only 1 washer.
Use loctite 243 instead of a lock washer.
Use fastening torque wrench between 40 and 50 Nm.
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
(12.0)
SD1
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
1'-2"
2'-2"
2'-2"
2'-2"
2'-2"
2'-2"
[355mm] [660mm] [660mm] [660mm] [660mm] [660mm]
57
8"
[10mm]
[93mm]
1"
3'-114
Floor Plate
(Scribe Mark)
3"
8
11"
316
7"
1'-1116
[1900mm]
4'-1015
16"
[945mm]
3"
3'-116
6'-213
16"
Hose Outlet
Detail - Clip Rail Cross-Section
Detail - Restricted Ceiling Area for Objects that Project Below Finished Ceiling
(Not to scale)
(Not site specific)
Table Floor Plate
13'-3"
[4039mm]
1"
64
Table
1"
6'-108
5'-27
8"
[2086mm]
[1597mm]
6'-3"
[1905mm]
Finished
Ceiling
Nothing shall be attached to the Unistrut with any fastener
that protrudes into the Unistrut which would interfere with
positioning of the fixing block.
Fixing Block
1"
14
515
16"
[32mm]
[151mm]
Fixing blocks for Philips ceiling rails (Clip rails) are designed
to be installed in P1001 Unistrut.
(12.0)
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
No objects that project more than 4.5" (115mm) below finished ceiling are allowed in
this area (lights, smoke detectors, sprinkler heads, soffit, etc).
[17mm]
5"
8
The inside of the Unistrut must be clear of obstructions
(including paint).
Unistrut elements must be rigid and comply with the ceiling
structure requirements. See SN sheet, line #4 "Ceiling
Support Apparatus".
Welding Unistrut may warp Unistrut and deteriorate the
structural integrity of the Unistrut. Consult the Structural
Engineer of Record prior to welding any Unistrut.
C1 C2 C3
(12.0)
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
Drawn By: Christy Perez
Finished ceiling must NOT be lower than the bottom of the
Unistrut in order to prevent damage to the finished ceiling
during the installation of clip rails. Finished ceiling height to
be mounted 41" (6mm) above bottom of Unistrut.
B
SD2
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
[6mm]
1
4"
P1001 (or equal) Unistrut
No objects that project below finished ceiling are allowed in this area (lights, smoke
detectors, sprinkler heads, etc).
Email: [email protected]
Philips does not specify the overhead equipment support
structure. Unistrut (or equal) may or may not be used. If
Unistrut are used, it is up to Unistrut and the structural
engineer for the project to determine which of it's products
are appropriate for each project.
A
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
(Not to scale)
Allura FD10 Ceiling
Detail - Fixing Block for Philips Ceiling Rails (Clip Rails)
Contact Number: (304) 625-1612
B
N-EAS131715 C
Clip Rail
A
Project
5'-0"
Cover
[1524mm]
315
16"
Self-locking
Bolt, M10x40
[100mm]
A
Clip
Philips Contacts
Project Manager: Michael Whelchel
Fixing Block
Project Details
Drawing Number
[72mm]
Stand/Table
See S2
Sheet
6'-3"
See S2
Sheet
[1905mm]
[101mm]
27
8"
5'-0"
[151mm]
4"
[1524mm]
[159mm]
515
16"
Detail - Wall Connection Box - Hole Pattern for Mounting
(Not to scale)
Pre-Evaluated and -Approved Anchor Reference List for Philips Installers
Anchors for items that are installed/anchored by customer/contractor shall be provided by customer/contractor. Anchors for items that are
installed/anchored by Philips shall be provided by Philips. If customer's engineering documents specify anchors other than those listed below, the
anchors shall be provided by customer/contractor and installed by Philips. In all instances, the wall and/or floor support are the sole responsibility of
the customer/contractor. The customer's architect/engineer of record shall specify wall and/or floor support sufficient for the bolt forces shown on the
details.
[120mm]
[53mm]
A
Bolts, flat washer, lock
washer, spring nuts
A
(provided & installed by
customer/contractor)
A307 Grade or ASME
Grade 5 Bolts: 38"
(10mm) x 2" (50mm) L
Spring Nuts: 38" (10mm)
8
Unistrut
Round Phillips Head
Self Drilling Screws
#10-16 x 1 21" (38mm) L
3
Drywall with minimum 20 gauge
Steel backing
B
SPAX Multipurpose flat
head screw
#10 x 1 21" (38mm) L
3
Drywall with minimum 20 gauge
Steel backing
C
Toggler Snaptoggle and
(round head screws)
#BA and (#10-24 x
2 21" (63.5mm) L)
87
8"
Minimum
3
5
8"
(16mm) Drywall
[226mm]
(13.0)
(12.0)
F2
(13.0)
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
[838mm]
[30mm]
Project
[550mm]
1'-95
8"
[590mm]
[630mm]
1"
1'-114
Email: [email protected]
[50mm]
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
[250mm]
Contact Number: (304) 625-1612
[760mm]
N-EAS131715 C
115
16"
Philips Contacts
Project Manager: Michael Whelchel
[548mm]
5"
1'-05
8"
[50mm]
Connection Box
wall mounted
under counter
(Preferred)
913
16"
[127mm]
[320mm]
3"
2'-116
[640mm]
[800mm]
2'-9"
115
16"
2'-515
16"
Min. gap between wall raceway
for Connection Box
(13.0)
Wall Raceway
6"
Wall Raceway
1"
2'-72
When the extruded plate
is removed, use caution
to protect cables against
sharp edges
9"
1'-916
1'-1113
16"
[605mm]
1"
2'-22
[673mm]
Closing Cover
(Only one closing cover included)
Cable Outlet
(Rear)
(6mm)
[50mm]
Front Cover
Connection
Box
[5mm]
2'-013
16"
1
4"
3
16"
Project Details
Drawing Number
To be made
locally
[15mm]
3"
116
[8mm]
(5mm)
Top
Connection Box
on table
(Optional)
Side
[700mm]
[5mm]
3
16"
1"
Front
Bolt Forces:
(Tension) Tmax = 14 lbs/bolt
(Shear) Vmax =
25 lbs/bolt
[3mm]
5
16"
9"
2'-316
[25mm]
115
16"
[190mm]
[36mm]
7"
116
[46mm]
113
16"
[30mm]
1
8"
[65mm]
9
16"
[350mm]
1
72"
3"
116
Bracket to be made locally.
3
16"
Front
Side
(13.0)
[152mm]
Cable Outlet
(Rear)
Cable Outlet (Bottom)
Notes:
Connection Box needs to be electrically
isolated from building steel.
Locate box within 6.5' (2m) of the review
module and monitors.
[380mm]
1'-13
4"
Cable Outlet (Top)
(Not to scale)
[700mm]
Connection Box
Detail - Connection Box - Bracket Mount Option
(Not to scale)
9"
2'-316
1'-215
16"
Detail - Connection Box
Support Frame Option
9"
216
(Not to scale)
[110mm]
Detail - Connection Box - Wall Mount Template
(Not to scale)
5"
416
Detail - Connection Box - Cable Outlets
Drawn By: Christy Perez
(provided by Philips)
Connection Box
(13.0)
SD3
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
(provided by Philips)
Qty.
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Anchor Size
Allura FD10 Ceiling
Control Room Connection
Box (IXR)
[53mm]
[181mm]
Mavig Ceiling Track
1"
216
Support Size & Material
Anchor Style
Option
43
4"
1"
78
Equipment
1"
216
Detail - Calculation of Bolt/Tube Length from Ceiling Frame Power Boom
Detail - Exploded Ceiling Frame Power Boom
(Not to scale)
(Not to scale)
Calculation of Threaded Bolt Length:
BL = H - 3.30" (84mm)
Structural Ceiling / Support
Calculation of Tube Length:
TL = H - 6.85" (174mm)
Re
fer
e
To structural ceiling (4X)
nc
eL
ine
Ceiling plate Power Boom
Note: Align ceiling plate power boom
properly to structural ceiling
Note: Cut threaded bolt and tube to
desired length and make sure the
distance between the interface plate
and the false ceiling is 5.25" (134mm)
due to ceiling cover.
To fixing disk (6X)
Lock washer (6X) apply loctite 243
& nut M16 (6X)
Bottom fixing disk (6X)
Threaded bolt M16 x 13" (330mm) (6X)
(12.0)
Spring washer (6X) & nut M16 (6X)
apply loctite 243
Detail - EP Power Boom Ceiling Plate
[640mm]
11"
1'-716
[70mm]
[500mm]
13"
16
23
4"
[20mm]
(Not to scale)
3"
2'-116
0.78" (20mm) thick ceiling plate, mounted to the
parent ceiling.
[540mm]
Two holes, 4.72"
(120mm) dia.
[500mm]
1"
1'-94
11"
1'-716
Four holes, 1.10"
(30mm) dia.
Re
Ceiling plate mounting to the building:
Use heavy load anchors (4X) (not supplied),
recommended:
1. HILTI HST M20 x 170
30
2. HSL M16
25 bolts (pull force 3800 lbs (1724 kg))
3. HSL-TZ M16
50
fer
e
nc
eL
ine
Pull force per bolt: 3215 lbs (1458 kg)
Bolts to be installed by customer/contractor.
C5
57
8"
57
8"
[150mm]
[150mm]
C5
(12.0)
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
(12.0)
Drawn By: Christy Perez
C5 C6
Email: [email protected]
Washer (6X) apply loctite 243,
spring washer (6X), & nut M16 (6X)
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
Finished Floor
Contact Number: (304) 625-1612
Interface Plate
N-EAS131715 C
Project
[660mm]
Power Boom Arm (To be
installed by Philips)
Philips Contacts
Project Manager: Michael Whelchel
2'-2"
Project Details
Drawing Number
** Additional opening on the false ceiling
must be covered/re-finished after the
boom is installed to leave a 26" (660mm)
square opening.
82.68" (2100mm)
Tube (6X)
Delivered length 31.5" (800mm)
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
* For installation, an additional 31"
(790mm) x 26" (660mm) opening is
required on the opposite side of the EPB
(See E1 Sheet) electrical box.
Allura FD10 Ceiling
[785mm]
Threaded bolt M16 (6X) apply
loctite 243
Delivered length 39.37" (1000mm)
[710mm]
2'-315
16"
False Ceiling **
2'-7"
SD4
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
1"
54
[134mm]
Recommended Ceiling Frame (to be
installed by customer/contractor per
engineer of record)
Reference Line
TL = Tube Length
BL = Threaded Bolt Length
NOTE:
H = Distance between ceiling plate
and lower edge of false ceiling,
Min. 11.81" (300mm)
Max. 39.36" (1000mm)
False Ceiling *
To be installed by customer/contractor per engineer of record.
Emergency Power
General Electrical Information
1. General
The customer shall be solely responsible, at its expense, for preparation of the site, including any required electrical alterations. The site preparation shall be in accordance
with this plan and specifications, the architectural/construction drawings and in compliance with all safety and electrical codes, the customer shall be solely responsible for
obtaining all electrical permits from jurisdictional authority.
Philips does not require equipment to be on emergency power. If the customer deems it necessary for the
equipment to be supplied with emergency power, the following specifications must be applied:
The gssPDU feeding an Allura Xper system will have an absolute peak surge current of <380A.
To reduce the emergency power generator load demand, Philips equipment can be put into a lower power mode
(5.5kVA fluoroscopy + 4kVA geometry) of operation by the connection of a potential free closure from the transfer
switch. This potential free, normally open contact, has to be rated for 24VDC/100mA. For Philips cardio/vascular
Allura equipment, the two wires from this contact have to be routed to the equipment area and connected to the
System Coordinator cabinet (MA).
(13.0)
Electrical Requirement Notes for Systems with PDU
2. Materials and Labor
The customer shall be solely responsible, at its expense, to provide and install all electrical ducts, boxes, conduit, cables, wires, fittings, bushing, etc., As separately specified
herein.
3. Electrical Ducts and Boxes
Electrical ducts and boxes shall be accessible and have removable covers. Floor ducts and boxes shall have watertight covers. Ducts shall be divided into as many as four
separate channels by metal dividers, separately specified herein, to separate wiring and/or cables into groups as follows: Group A: incoming power wiring with associated
protective earth wiring (PE). Group B: Output power wiring with associated protective earth wiring (PE). Group C: signal and/or data wiring and/or cables. Group D: X-Ray
high-voltage cables, the use of 90 deg. ells is not acceptable. On ceiling duct and wall duct use 45 deg. bends at all corners. All intersecting points in duct to have cross over
tunnels supplied and installed by contractor to maintain separation of cables.
4. Conduit
Conduit point - to - point runs shall be as direct as possible. Empty conduit runs used for cables may require pull boxes located along the run. Consult with Philips. A pull wire
or cord shall be installed in each conduit run. All conduits which enter duct prior to their termination point must maintain separation from other cables via use of dividers, cross
over tunnels, or conduit supplied and installed by contractor from entrance into duct to exit from duct. Do not use flex conduit unless approved by Philips Service.
5.
Conductors
Electrical power distribution at the facility shall comply with:
6. Disconnecting Means
A disconnecting means shall be provided as separately specified.
Power Quality Guidelines
3. All pre - terminated, cut to length cables, will be supplied and installed by Philips. All cables to the breakers, will be supplied and installed by the contractor, subject to
local arrangements.
1. Power supplied to medical imaging equipment must be separate from power feeds to air conditioning,
elevators, outdoor lighting, and other frequently switched or motorized loads. Such loads can cause waveform
distortion and voltage fluctuations that can hinder high quality imaging.
4.
2. Equipment that utilizes the facility power system to transmit control signals (especially clock systems) may
interfere with medical imaging equipment, thus requiring special filtering.
Provide and install 50mm diameter. Chase nipples between adjacent wall boxes.
3.
The following devices provide a high impedance, nonlinear voltage source, which may affect image quality:
5. Electrical raceway shall be installed with removable covers. The raceway should be accessible for the entire length. In case of non - accessible floors, walls and ceilings,
an adequate number of access hatches should be supplied to enable installation of cabling. Approved conduits may be substituted. All raceways will be designed in a
manner that will not allow cables to fall out of the raceway when the covers are removed. In most cases, this will require above - ceiling raceway to be installed with the covers
removable from the top. Raceway system as illustrated on this drawing are based upon length of furnished cables. Any changes in routing of raceway system could exceed
maximum allowable length of furnished cables. Conduit or raceway above - ceiling must be kept as near to finished ceiling as possible.
4.
Static UPS systems, Series filters, Power conditioners, and Voltage regulators.
6.
Conduit sizes shall be verified by the architect, electrical engineer or contractor, in accordance with local or National Electrical Codes, whichever govern.
7.
Convenience outlets are not illustrated. Their number and location are to be specified by the customer/architect.
5. Do not install such devices at the mains supply to medical imaging equipment without consulting Philips
installation or service personnel.
6. Line impedance is the combined resistance and inductance of the electrical system and includes the
impedance of the power source, the facility distribution system, and all phase conductors between the source and
the imaging equipment. Philips publishes recommended conductor sizes based on equipment power
requirements, acceptable voltage drops, and assumptions about the facility source impedance. The minimum
conductor size is based on the total line impedance and NEC requirements. Unless impedance calculations are
performed by an electrical engineer, the recommended values must be used.
(13.0)
8. Electrical contractor shall install ground bond wires at conduit openings within wall boxes as required by national and local electrical codes. Ground bond wires and lugs
shall be installed in such a way to prevent the inadvertent contact with the installed Philips equipment to maintain Philips isolated ground scheme and maintain patient safety.
Install an insulated stranded ground wire per feeder/conductor size from the Main Disconnect (CB) to the ERB and from the ERB to the PDU wall box (per NEC clause
250.146(D)).
9.
Philips equipment must be electrically isolated from conduits, raceways, ducts, etc.
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Drawn By: Christy Perez
2. The contractor shall supply & install all pull boxes, raceways, conduit runs, stainless steel covers, etc. Conduit/raceways must be free from burrs and sharp edges over its
entire length. A Greenlee pull string/measuring tape (part no. 435, or equivalent) shall be provided with conduit runs.
Philips Contacts
Project Manager: Michael Whelchel
1. The contractor will supply & install all breakers, shunt trip and incoming power to the breakers. The exact location of the breakers and shunt trips will be determined by
the architect or contractor.
Project Details
Drawing Number
Electrical Notes
ANSI / NFPA 70 - National Electrical Code
Article 250 - Grounding
Article 517 - Healthcare Facilities
ANSI / NFPA 99 - Healthcare Facilities
NEMA standard XR9 - Power Supply Guideline for X-ray Machines
Project
(12.0)
Email: [email protected]
The Philips system uses an isolated ground scheme supplying only the Allura system per clause 250.96B of the
NEC. The raceway from the X-ray breaker to the gssPDU shall be supplemented by an internal insulated
equipment grounding conductor installed in accordance with clause 250.146(D) of the NEC. All conduits that
attach to the gssPDU shall have insulated bushing at their connection to the gssPDU rear panel.
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
8. Dimmer Switches
X-ray room lights should be provided with dimmer switches.
Metal conduit shall not be used as the equipment ground conductor.
Allura FD10 Ceiling
Phase conductors to be size for instantaneous voltage drop per NEC 517 - 73 and Philips recommendations.
7. Warning Lights and Door Switches
"X-ray on" warning lights and x-ray termination door switches should be provided at all entrances to x-ray rooms as required by code.
Contact Number: (304) 625-1612
Voltage to be supplied is 3 phase, delta or wye.
N-EAS131715 C
Utilization voltages per ANSI C84.1 - 1982 range A.
(13.0)
EN
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
The transfer switch must be double actuator type with a minimum time delay of 400 milliseconds in both directions
(utility to emergency - emergency to utility). This time is required to allow filters to dissipate their stored energy
before a different mains voltage is applied. Russelectric type RMTD, Asco Series 7000 delayed transition transfer
switch or equivalent is recommended.
Electrical Legend
Furnished and installed by Philips
Furnished by customer/contractor and installed by customer/contractor
Installed by customer/contractor
Furnished by Philips and installed by contractor
Existing
Future
Optional
A
B
C
D
E
F
G
Item Number
Detail Sheet
Local building steel (i.e. I-beam, rebar, raceway steel). (Not shown on plan)
B
B
ERB
PBK
D MP
Equi-Potential Reference Bar mounted in a 12" (305mm) W x 12" (305mm) H x 4" (105mm) D pull box with hinged
cover, surface mounted to the bottom of "WR2" when possible.
ED2
18" (460mm) W x 18" (460mm) H x 8" (205mm) D flanged-edge terminal wall box with removable screw-type
cover plate, surface mounted 12" (305mm) above finished floor to bottom of box, provide (1) 1/2" (15mm) and (2)
2" (55mm) conduits through "PBK" cover plate to PDU cabinet (Conduits shall have insulated bushing where
connected to the gssPDU panel. The conduits themselves shall be bonded to the raceway and building steel).
ED1
MG 19 1" (490mm) W x 67" (1705mm) H x 4" (105mm) D flanged-edge terminal wall box, surface mounted 75"
4
MA (1905mm) A.F.F. to top of box. General contractor to cut top and/or bottom of box as required.
ED2
B
N1
B
N2
B
120V/20A dedicated duplex outlet EPN (EP Navigator).
B
120V/20A dedicated duplex outlet for each of the Video Connection Boxes. Verify electrical requirements for
customer provided equipment.
B
B
Grommet opening on "WR3". Approximate location shown is recommended and may be changed - verify
WM relocation with local Philips Service.
VB1
VB2
EPN
CY
MSA
B
10" (255mm) W x 10" (255mm) L x 6" (155mm) D floor box, flush mounted with underside of AD7 Universal Floor
Plate.
B
B
SP
18" (460mm) W x 18" (460mm) L x 6" (155mm) D ceiling box, flush mounted with removable screw-type cover
plate. Provide one 3" (80mm) diameter knockout.
B
TV
18" (460mm) W x 18" (460mm) L x 6" (155mm) D ceiling box, flush mounted with removable screw-type cover
plate. Provide a 2 21" (65mm) round cutout (Two 2 21" (65mm) round cutouts are required for systems with two
monitor carriages - verify with local Philips Service).
B
10" (255mm) W x 4" (105mm) D wall raceway, surface mounted with removable screw-type cover plate. "WR1" is
WR1
WR2 at finished floor. "WR2" is at 75" (1905mm) A.F.F. to bottom of raceway.
ED3
10" (255mm) W x 4" (105mm) D wall raceway, surface mounted with removable screw-type cover plate. "WR3" is
at finished floor. "WR3" may need to be cut at the location of the "CY" connection box.
ED3
ED3
B
WR3
B
R1
10" (255mm) W x 4" (105mm) D riser duct with removable screw-type cover plate, surface mounted from wall
raceway to wall box.
B
PHY
Stub up point for physiological monitoring cables. Run conduit to customer's physiological console location.
Contact manufacturer for power requirements, etc.
B
ATY
Auxiliary Box - 6" (155mm) W x 6" (155mm) H x 4" (105mm) D wall box, flush mounted 70" (1780mm) A.F.F. to
the bottom of the box with removable screw-type cover plate. Height and location shown are recommended and
may be changed - verify height and relocation with local Philips Service.
4" (105mm) W x 4" (105mm) H x 4" (105mm) D pull box with removable screw-type cover plate, flush mounted.
VB3
Exact height to be determined. Location shown is recommended and may be changed - verify relocation with
VB4
local Philips Service.
VB5
VB6
VB7
VB8
VB9
18" (460 mm) W x 18" (460 mm) L x 6" (150 mm) D ceiling box, flush mounted with removable screw-type cover
EPB
plate. Provide minimum 72.5 PSI to maximum 116 PST @ 2.6 CFM of compressed air for boom movement
AIR
control; connect to the 8mm inlet attached at the bottom of the EP Boom Interface Plate.
1
Provide (2) 120V/20A power supply for the EP Power Boom convenience and emergency outlets.
Customer/contractor to install power to the EP Boom.
See E1 - E3 sheets for conduit and raceway requirements.
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
N1
120V/20A dedicated duplex outlet for service in the equipment room. (Not shown on plan)
B
MB
B
S
ED2
Drawn By: Christy Perez
GE
DS
ED2
EL
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
B
B
Warning Light - Provide a surface or flush mounted light fixture above door to indicate when X-ray is on, if
required by local code or physicist of record. See Sheet "ED2" diagram for connection details. (Not shown on
plan)
Door Switch - 120V/5A switch limited to open when door is open. Mount in upper corner on strike side of main
entry door(s) (Cooper no. 1665 or equivalent), if required by local code or physicist of record. See Sheet "ED2"
diagram for connection details. (Not shown on plan)
RJ45 type Ethernet 10/100/1000 Mbit network connector with access to customer's network. Locate within 10'
(3050mm) of network card. Network fiber optic and Ethernet cabling, connectors, wall boxes, patch panels, etc.
are the responsibility of the purchaser. Philips assumes no responsibility for procurement, installation, or
maintenance of these components.
RJ45 type Ethernet 10/100/1000 Mbit network connector. Access to customer's network via their remote access
server is needed for Remote Service Network (RSN) connectivity.
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Shunt Trip (emergency off) - Large mushroom-head button on remote control station with contacts to operate
feature of "CB" (if required by local code or owner, and mandatory for VA and D.O.D installations). (Not shown on
plan)
WL
Email: [email protected]
ST
B
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
B
ED1
Allura FD10 Ceiling
480V, 3 phase 125 AMP circuit breaker with shunt trip. Run power from breaker to "PBK", leaving an 8'
(2440mm) tail at "PBK", and from "PBK" to "MG", leaving an 8' (2440mm) tail at each end. See Sheet "ED1" for
power quality requirements. Location per local code or owner requirements. (Not shown on plan)
Contact Number: (304) 625-1612
CB
N-EAS131715 C
B
Description
Project
Description
Detail Sheet
Philips Contacts
Project Manager: Michael Whelchel
Item Number
Furnished and installed by Philips
Furnished by customer/contractor and installed by customer/contractor
Installed by customer/contractor
Furnished by Philips and installed by contractor
Existing
Future
Optional
Project Details
Drawing Number
A
B
C
D
E
F
G
Electrical Legend
VB4
VB5
VB6
VB7
VB8
VB9
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
1
1'-115
8"
EPB
AIR
14'-3"
Poly G / Table
Refer to Electrical Legend - Sheet EL
and Raceway/Conduit - Sheet E2-E3
6'-3"
8'
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
WM
E1
3.15.13
6'-0"
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
Drawn By: Christy Perez
Electrical Layout
Allura FD10 Ceiling
Project
AD7 Table Floor Plate
6'-3"
Email: [email protected]
Exact location to be coordinated by Customer
and local Philips service.
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
WR3
Contact Number: (304) 625-1612
2m
N-EAS131715 C
1m
10'-1"
2'-0"
Philips Contacts
Project Manager: Michael Whelchel
.5m
4'
2'-0"
Project Details
Drawing Number
0
2'
2'-0"
11'-0"
VB3
1'
2'-0"
1"
1016
3'-0"
1'-5"
4'-11"
55"
16
0
3'-7 5 "
16
3
Required Ceiling Height: 9' - 6 16
", +38" / -0 (2900mm, +10mm / -0)
Ceiling Height measured from finished floor to bottom of Unistrut.
3'-0"
WR2
WR1
2'-7"
PBK
R1
Equipment Closet
(Site Specific)
10"
12'-0"
1'-5"
2'-0"
2'-0"
2'-0"
2'-0"
2'-7"
MA
MP
MG
10"
6'-3"
MB
9'-6"
ERB
10"
Finished Floor
EPN WM
CY
WR3
N1
5'-2"
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
N2
PHY
2'-2"
* Countertop Height Guide:
30" (765mm) for standard seated height.
36" (915mm) for standard standing height.
* Ensure that the wall junction boxes are mounted perpendicular to the
floor.
* Verify exact ceiling height of Equipment and Control Room Area.
* Local Philips Service to consult with customer for final placement of
control desk components.
Project Details
Drawing Number
2'-6"
N1
x2
WR3
Note: The use of 90 degree ells is not acceptable. Use 45
degree bends at all raceway corners. For conduit runs, use the
minimum bending radius specific to the conduit diameter. The
use of crossover tunnels at all applicable locations is required.
The above mentioned recommendations will help to ensure the
integrity of the cables and fiber optic runs.
Drawn By: Christy Perez
VB1
VB2
Email: [email protected]
3'-0"
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
3'-0"
8'-0"
10'-1"
Allura FD10 Ceiling
(Site Specific)
Philips Contacts
Project Manager: Michael Whelchel
Project
Control Room
Contact Number: (304) 625-1612
Finished Floor
R1
N-EAS131715 C
WR1
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
PBK
E2
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
WR2
Conduit Required
Conduit Required
General Notes
B
3
B
4
C
5
6
CB
CB
PBK
ST
ERB
GE
C
7
ERB
Room
Outlets
C
8
MA
WL
Per N.E.C. Per N.E.C.
1
P
1
2"
-
2
P
2"
-
1
P
2"
50'
P
3
4"
1
From
To
A
31
MA
WM
1
S
1"
82'
See sheet ED1 for functional insulation requirements.
C
32
TV
WR3
2
S
1 21"
-
See sheet ED1 for functional insulation requirements.
C
33
MSA
WR3
2
S
1 21"
-
C
34
MSA
PHY
1
S
2 21"
-
1
S
2"
33'
50'
G
35
Physio
PHY
Monitor
Third Third
Party Party
Third
Party ERB
P
3
4"
6'
1
P
3
4"
-
1
P
3
4"
55'
55'
A
39
VB2
MB
41'
A
40
VB3
MB
1
C
9
ATY
DS
1
S
3
4"
A
10
ATY
MA
1
S
2 21"
75'
41.5'
A
11
ATY
TV
1
S
3
4"
A
12
SP
MG
1
H
2 21"
See Sheet "ED2" for details.
H.T. Cables.
G
36
G
37
A
38
VB1
MB
-
-
-
-
-
G
-
-
1
S
1 21"
68'
1
S
1
1
2"
68'
1
S
1 21"
68'
1
2"
68'
A
41
VB4
MB
1
S
1
A
42
VB5
MB
1
S
1 21"
68'
1
2"
68'
A
13
SP
MG
1
P
1"
41.5'
A
43
VB6
MB
1
S
1
A
14
SP
MG
1
S
1 21"
41.5'
A
44
VB7
MB
1
S
1 21"
68'
1
2"
1
2"
68'
A
15
SP
MP
1
S
2
A
16
SP
MP
1
P
1"
33'
A
45
VB8
MB
1
S
1
33'
A
46
VB9
MB
1
S
1 21"
68'
68'
A
17
SP
MP
2
C
2"
33'
Cooling fluid hoses for tube.
A
47
VB3
CY
1
S
1
2"
A
18
SP
MP
2
C
2 21"
33'
Cooling fluid hoses for detector.
A
48
VB4
CY
1
S
1
2"
68'
1
2"
36'
A
49
VB5
CY
1
S
1
2"
68'
42'
A
50
VB6
CY
1
S
1
2"
68'
68'
A
19
SP
MA
1
S
2
A
20
MSA
MP
1
S
2 21"
A
21
MSA
MP
1
P
1"
42'
A
51
VB7
CY
1
S
1
2"
A
22
MSA
MA
1
S
2 21"
42'
A
52
VB8
CY
1
S
1
2"
68'
42'
A
53
VB9
CY
1
S
1
2"
68'
Special Requirements
For optional equipment (IE. Physio Monitor/ Slave
Monitor).
For future options (Patient Monitoring). Verify with local
Philips Service if med gas pedestal should be used.
For future options (Patient Monitoring). Verify with local
Philips Service if med gas pedestal should be used.
Optional for remote location.
For Injector, Medical Gas Pedestal, Patient Monitoring,
Video Networking, etc.
For Injector, Medical Gas Pedestal, Patient Monitoring,
Video Networking, etc.
A
23
MSA
MA
1
P
3
4"
A
24
TV
MB
1
P
2"
52'
G
54
EPB
WR3
1
S
2 21"
-
For 3rd party equipment.
A
25
TV
MB
1
S
2 21"
52'
G
55
EPB
WR3
1
P
2 21"
-
For 3rd party equipment.
A
26
TV
MP
1
S
2"
54'
G
56
WR1
WR3
1
P
2 21"
-
For 3rd party equipment to control room.
A
27
TV
CY
1
S
3
4"
65'
G
57
WR1
WR3
1
S
2 21"
-
For 3rd party equipment to control room.
A
28
CY
MP
1
S
2"
50'
A
29
CY
MA
1
P
2"
55'
A
58
EPN
MP
1
S
1 21"
55'
A
30
CY
MA
1
S
2 21"
55'
A
59
EPN
TV
1
S
1"
45'
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
For Intercom.
* Verify
with 3rd party vendor for conduit and power requirements of the components placed in the EP Power Boom (EPB).
57
Drawn By: Christy Perez
2
P
Run
No.
E3
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
B
1
Minimum Maximum
Conduit
Conduit
Length
Size
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
CB
PDU
PBK
Cabinet
PDU
PBK
Cabinet
Cable
Type
(*)
Email: [email protected]
Power
Panel
Conduit
Quantity
Power (AC)
Power (DC)
Ground
Signal
High Tension
Cooling Hose
Air Supply Hose
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
1
Conduit
Special Requirements
*
P
D
G
S
H
C
A
Allura FD10 Ceiling
To
Minimum Maximum
Conduit
Conduit
Length
Size
Conduit supplied/installed by contractor - Philips cables installed by Philips
Conduit supplied/installed by contractor - Philips cables installed by contractor
Conduits and cables supplied and installed by contractor
Conduit existing - cables supplied and installed by Philips
Conduit existing - cables supplied by Philips and installed by contractor
Conduit existing - cables supplied and installed by contractor
Optional equipment, verify with local Philips Service
Contact Number: (304) 625-1612
From
Cable
Type
(*)
A
B
C
D
E
F
G
Power (AC)
Power (DC)
Ground
Signal
High Tension
Cooling Hose
Air Supply Hose
N-EAS131715 C
Run
No.
Conduit
Quantity
*
P
D
G
S
H
C
A
All conduit runs must take most direct route point to point.
All conduit runs must have a pull string.
Project
Conduit supplied/installed by contractor - Philips cables installed by Philips
Conduit supplied/installed by contractor - Philips cables installed by contractor
Conduits and cables supplied and installed by contractor
Conduit existing - cables supplied and installed by Philips
Conduit existing - cables supplied by Philips and installed by contractor
Conduit existing - cables supplied and installed by contractor
Optional equipment, verify with local Philips Service
Conduit
C
1.
2.
Philips Contacts
Project Manager: Michael Whelchel
A
B
C
D
E
F
G
C
General Notes
All conduit runs must take most direct route point to point.
All conduit runs must have a pull string.
Project Details
Drawing Number
1.
2.
Detail - gssPDU Mounting
Power Quality Requirements
Velara 100KW with gssPDU
[500mm]
11"
1'-716
One 78" (25mm) and two 2 21" (65mm) knock outs.
Use one 21" (15mm) and two 2" (55mm)
nipples mounted through J-box "PBK" cover plate.
Conduit nipple connections shall have insulation
verified using a Megger measurement with test
voltage <=500V. In practice, the measurement
can be carried out with an Ohm meter as well
since the insulation is classified as functional
insulation, not as a means of protection. The
minimum insulation impedance shall be >5MOhm
at 0Hz, >100kOhm at 60Hz, and >10kOhm at
1kHz.
18" (460mm) x 18" (460mm) x 8" (200mm)
J-box "PBK"
100KW
3 phase, 3 wire power and Protective Earth (PE), delta (preferred) or wye
3 phase, 4 wire power w/ Neutral + ground, wye (without gssPDU)
Nominal Line Voltage:
Line Voltage Variation:
480 VAC, 60 Hz
RMS values with a measurement window of 1 week. At least 95% of all measured 10
Line Voltage Balance:
Frequency Variation:
2% maximum of nominal voltage between phases
Voltage Surges:
To 110% of steady-state voltage 100 msecs. Maximum duration, 6 per hour max.
Voltage Sags:
To 90% of steady-state voltage 100 msecs. Maximum duration, 6 per hour max.
Line Impulses:
1000 VPK above phase-neutral RMS absolute maximum. No more than 1 impulse
per hour to exceed 500 VPK.
Neutral-Ground Voltage:
Neutral-Ground Impulses:
2.0 volts maximum RMS value
No more than 1 per hour that exceeds 25 volts and 1 Mjoule
High Frequency Noise:
3.0 volts steady-state maximum. Over 3.0 volts permitted for 100 msec. maximum, 1
per hour max.
Grounded Conductor Impedance:
0.1 Ohms @ 60 hz. maximum
gssPDU with J-box "PBK" flush or surface mounted behind unit.
305 A
Max. Phase-phase
impedance @ CB Panel
<
Shunt
Trip
Max. Load Voltage
Drop @ CB Panel
18.2 V
Percent Regulation at
Maximum Load @ CB Panel
3.8%
Mains "MA"
Rack
X-ray Generator
#6 AWG
Output Voltage gssPDU:
Max Inst. Current @ PDU output:
Max Phase-Phase Impedance:
Max Load Voltage Drop:
Percent Regulation at Max. Load:
"MG"
Local Building Steel
305 Amps
<
24.4 V @ PDU output
6.4% @ PDU output
Emergency Power
Note: Conductors, destinations, and number of conduit runs from PDU to J-box "PBK"
and from J-box to equipment will vary from system to system. Consult individual site plans for detailed conduit schedules.
Diagram - gssPDU Electrical Interface
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
(13.0)
CB
(12.0)
Drawn By: Christy Perez
Inst. Current @ CB Panel
Email: [email protected]
Out (X-ray Generator)
Mains "MA" Rack
Allura FD10 Ceiling
Input
gssPDU
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
(Pass-through)
3 Phase & Ground
Contact Number: (304) 625-1612
Pull box for
Ground
Busbar
"ERB"
C.B.
480VAC
95 ft (29m)
120 ft (36.6m)
151 ft (46m)
193 ft (58.8m)
226 ft (68.9m)
271 ft (82.6m)
365 ft (111.3m)
N-EAS131715 C
18" (460mm) x 18" (460mm)
x 8" (200mm) J-box
"PBK"
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
250 KCM
300 KCM
400 KCM
Project
** Conductor Size Chart: Recommended conductor sizes for 1% impedance of supply conductors to circuit breaker (CB). Based on
Two 2" (55mm) chase nipples with fittings
(each input and output)
Provided by Customer / Electrical Contractor.
Refer to gssPDU mounting detail above
for functional insulation requirements.
Facility Source
(
If required by facility
or local code
225 KVA
8 Amps. @ 3 mA, 110 KVP continuous
3 pole, 125 amperes
201 KVA (1000 mA @ 100 KVP)
Philips Contacts
Project Manager: Michael Whelchel
Branch Power:
Max Stand by Current:
Circuit Breaker:
Maximum Instantaneous Power:
Wiring and circuit sizes from source
supply must meet Philips regulation
requirements and must be
determined by contractor to meet
building conditions and local codes.
3 Phase, + PE (Protective Earth).
**Size per conductor size chart
Size per equipment
power requirements
Velara 100KW with gssPDU
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Branch Circuit and Wire Gauge Requirements
(13.0)
Project Details
Drawing Number
PBK
ED1
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
For Seismic: Seismic fixation shall be fixed
maintaining galvanic insulation to building steel.
This can be verified with a Megger or Ohm meter.
The test voltage shall not exceed 500V.
The minimum insulation impedance shall be
>5MOhm at 0Hz, >100kOhm at 60Hz, and
>10kOhm at 1kHz.
J-box "PBK", nipples and
other mounting hardware must be
supplied by customer as required.
Power Output:
Supply Configuration:
Detail - Wall Box Mounting
Detail - Equi-Potential Reference Bar Application
1"
22
1"
22
[64mm]
[64mm]
(Not to scale)
(Not to scale)
Invasive Procedures
Size per
conductors
To gssPDU
[139mm]
43
4"
Wall Duct
1"
52
1'- 1
7
4"
9m
m]
[48
[120mm]
From
Circuit Breaker
To be installed in
12" (305mm) x 12"
(305mm) x 4"
(105mm) cut-out
box or equivalent.
Terminal Box
General contractor
to cut bottom of
box as required
73
4"
Full size grommeted
opening in
top/bottom of wall
duct, with grommet
material applied to
all edges for
protection of cables.
Test performed by GSSNA service require that
these specifications are met by the GSSNA
equipment. It is the facility's responsibility to
ensure that these specifications are met by the
wall outlet, facility structure, and other
equipment not installed by GSSNA.
Xray On Light
Only used if
customer chooses to
have the room lights
switched off when
X-ray is on
#10 Pan
Screw
Supplied by Contractor.
Contractor to locate relay
box in ceiling space away
from Philips equipment.
To room lights
circuit
n.c.
Only used if customer
chooses to have the
room lights switched on
and off with the system's
room light's foot switch.
n.c.
Com
Com
n.o.
n.o.
#6 AWG green
stranded wire
Pass Through
Lug
Supplied by Contractor.
To be located in ceiling
space away from
Philips equipment.
Raceway
N
N
Philips X105:2
"MA" Rack (NC)
110V Relay*
F24
X2:2
MA
Box
MB
Box
24V Relay
24V Relay
Philips ATY box
Supplied by Contractor.
To be located in ceiling
space away from Philips
equipment.
PBK
X106:2
(NC)
X106:1
(NO)
X105:3
(P)
1A
Door Switch
MP
Box
110V Relay*
X105:1
(NO)
X2:1
MG
Box
This allows for the use
of a three way switch
on the wall of the
exam room for
additional control of
lights.
X106:3
(P)
Philips
"MA" Rack
F25
20 A
Hospital
supplied
24 VAC
Philips "MA" Rack
* The 110V relay should have heavy-duty contacts to handle the room lights current.
All items shown (except Philips items) to be supplied by Customer / Contractor.
Raceway
(13.0)
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
WL
DS
Diagram - Typical Connection of
X-Ray On Light, Door Switch, & Room Lights
Drawn By: Christy Perez
*ERB - Busbar
Hospital supplied
110 VAC
N HOT
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
* ERB to be placed at a reachable height.
(Recommended location is above "PBK")
Use when customer wishes to
control some of the room lights
using the "X-ray On" signal.
Email: [email protected]
To room lights circuit
(13.0)
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
Detail - Grounding
(Not to scale / Not site specific)
To Philips' equipment
insulated from
accidental earthing
(i.e. Philips Hemo,
patient monitoring)
Allura FD10 Ceiling
ERB
To other
3rd party
equipment
and room
outlets
Contact Number: (304) 625-1612
(12.0)
#6 AWG to metallic
structure within
patient vicinity and
local building steel
Equi-Potential Reference Bar (ERB)
A) Equip-Potential Conductor Bar (ECB)
B) Protective Conductor Bar (PCB)
C) Philips Protective Conductor Bar (PPCB)
N-EAS131715 C
MB
Conductor sizes
#14 - #4 AWG
Project
3.
Furnished and installed by Customer / Contractor
Purchase from local Ferraz Shawmut distributor,
http://www.ferrazshawmutsales.com/index.htm
Catalog #69143.
62000 - 69000 Series Blocks
http://www.ferrazshawmutsales.com/pdfs/PDB-LARGE.pdf
Philips Contacts
Project Manager: Michael Whelchel
Finished Floor
The GSSNA specified "Equi-Potential
Reference Bar (ERB)" serves as a ground
reference for GSSNA equipment. It may also
serve as the "Reference Grounding Point" of
the room as defined in NFPA 99-3.3.140 for
non-Philips Healthcare equipment.
PPCB
Project Details
Drawing Number
1.
2.
PCB
[82mm]
6'-3"
[1905mm]
1"
34
ECB
(12.0)
ED2
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
[197mm]
Wall Duct
MG MP MA
This equipment may be used for invasive
procedures; therefore, the area to be installed
is classified as critical care area per NFPA-99
and NFPA-70 (NEC). These documents
specify maximum touch voltages and ground
impedance in these areas.
Detail - Cable Trough Divisions
(Not to scale)
Input Power
+PE
It is important that all cables are placed in the appropriate trough and
at not given point do any cables from one division cross cables from
another. Trough separation must be continuous from the beginning.
Trough or ducts: steel with steel dividers grounded to building ground.
Contractor to provide cable restraints in all troughs.
(12.0)
Contact Number: (304) 625-1612
Email: [email protected]
N-EAS131715 C
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
Drawn By: Christy Perez
Philips Contacts
Project Manager: Michael Whelchel
Project Details
Drawing Number
Project
WR1 WR2 WR3 R1
Signal, Data
and Video
(if not in conduit)
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
6.
7.
High-Voltage
Allura FD10 Ceiling
5.
Output
Power
+PE
ED3
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
Troughs or ducts must be separated by metal barriers into four sections:
1. Input Power wires and associated PE.
2. Output Power wires and associated PE.
3. High-Voltage wires to X-Ray stands.
4. Signal, data and video cables.
Philips Healthcare Remote Services Network (RSN)
Secure broadband connection required for Philips remote technical support, diagnostics, and applications assistance
Broadband Site-to-Site Connectivity (Preferred)
This connectivity method is designed for customers who prefer a connection from the RSN Data
Center to the Health Care Facility (HCF) utilizing their existing VPN equipment.
Connectivity Details:
- A Site-to-Site connection from the RSN data center's Cisco router will be established to the
HCF's VPN concentrator.
- The VPN Tunnel will be an IPSEC, 3DES encrypted Tunnel using IKE as standard, but
alternative standards are also available, such as AES, MD5, SHA, Security Association lifetime
and Encryption Mode.
- Every system that we will be servicing remotely will have a static NAT IP that we configure on
the RSN Data center side.
Healthcare Facility
HCF VPN
Concentrator
Philips
Router
General Network
Nuc Med
Overview
Philips
Philips
(Not site specific)
PACS
MR
Option 2: Back End Connected to the HCF Firewall Connectivity Method
This connectivity method is designed for customers who prefer a Philips RSN Router installed
on site by setting up an IP-Based policy allowing access thru existing HCF Firewall to Philips
equipment.
General Network
Overview
(Not site specific)
Philips
Router
Healthcare Facility
Philips
Nuc Med
Philips
PACS
Philips
MR
c
Philips
X-Ray
Hospital
Network
Internet
Philips VPN or
Site-to-Site VPN
Philips
CT
Patient Monitoring
Ultrasound
Philips Router
Healthcare Facility
Philips
Philips
Philips
PACS Nuc Med
MR
Firewalls
Hospital
Network
Internet
Philips VPN or
Site-to-Site VPN
Ultrasound
Patient
Monitoring
Philips
X-Ray
Philips
CT
Action Required by Hospital:
- Assign a fixed public IP Address from the ISP to be configured on the Philips router. This is
the DOTTED link on the picture connected to the firewall.
- Assign a Back end IP for the Philips router on the Hospital Network.
- Complete appropriate Site Checklist.
- Route traffic from within the hospital network with destination addresses 192.68.48.0/22 to
internal Philips router Ethernet interface. This is the DASHED line connected to the firewall.
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
Philips
MR
c
Hospital
Network
Internet
Philips VPN or
Site-to-Site VPN
Ultrasound
Patient
Monitoring
Philips
X-Ray
Philips
CT
Action Required by Hospital:
- Assign a fixed public IP Address from the ISP to be configured on the Philips router. This is the
DOTTED link on the picture connected to the firewall.
- Assign a Back end IP for the Philips router on the Hospital Network.
- Complete appropriate Site Checklist.
- Route traffic from within the hospital network with destination addresses 192.68.48.0/22 to
internal Philips router Ethernet interface. This is the DASHED line connected to the firewall.
- Configure and allow on the firewall on the DASHED line interface IPSec protocol
communication by opening protocol 500, 50, 51, 47 and port 23 + TACACS. Traffic should be
between external IP Address located on the Philips router and the RSN Data center IP address
192.68.48/24 and IP address AOSN TACAS.
- Configure and allow on the firewall on the DASHED line interface access between the IP
address allocated by the hospital to the Philips internal Ethernet router interface and the target
modality IP address.
(12.0)
Drawn By: Christy Perez
General Network
Overview
(Not site specific)
Philips
Nuc Med
Philips
PACS
N1
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
Option 1: Parallel to HCF Firewall Connectivity Method
This connectivity method is designed for customers who prefer a Philips RSN Router installed
on site utilizing all the security features provided and managed by Philips.
Healthcare Facility
Email: [email protected]
Connectivity Details:
- An RSN Cisco 1711 or 1712 router will be preconfigured and installed at the HCF by Philips
in conjunction with the HCF IT representative.
- The VPN Tunnel will be an IPSEC, 3DES encrypted Tunnel using IKE and will be established
from the RSN-DC and terminated at the RSN Router on-site.
- One to One NAT is used to limit access to Philips equipment only.
- Router Config and IP auditing is enabled for Customer IT to view via website 24/7.
- Dedicated DSL connections are also supported.
General Network
Overview
(Not site specific)
Philips
Router
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
Broadband Router Installed at Health Care Facility
This connectivity method is designed for customers who have a dedicated high speed
connection for Philips equipment.
Option 3: Router Installed Inside the HCF's DZM
This connectivity method is designed for customers who prefer the RSN Router installed inside
and existing, or new DMZ, allowing access to Philips equipment.
Allura FD10 Ceiling
Action Required by Hospital:
- Review and approve connection details.
- Complete appropriate Site Checklist.
- Configure and allow Site-to-Site access prior to setting up connectivity depending on the
access criteria that the HCF decides to implement (ex: Source IP filtering, destination IP
filtering, NAT assignment, etc.).
- Route traffic from within the hospital network with destination addresses 192.68.48.0/22 to
the designed IP provided by Philips.
Contact Number: (304) 625-1612
Philips
CT
N-EAS131715 C
Patient
Monitoring
Project
Ultrasound
Action Required by Hospital:
- Assign a fixed public IP Address from the ISP to be configured on the Philips router. This is
the DOTTED link on the picture connected to the firewall.
- Assign a Back end IP for the Philips router on the Hospital Network.
- Complete appropriate Site Checklist.
- Route traffic from within the hospital network with destination addresses 192.68.48.0/22 to
internal Philips router Ethernet interface. This is the DASHED line connected to the firewall.
- Configure and allow on the firewall on the DASHED line interface access between the IP
address allocated by the hospital to the Philips internal Ethernet router interface and the target
modality IP address.
Philips Contacts
Project Manager: Michael Whelchel
Shared VPN
Philips
X-Ray
Project Details
Drawing Number
Hospital
Network
Internet
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
c
NOTE: It is the customer's responsibility to coordinate with the local Philips Engineer to provide ALL required network information and install ALL required network cabling
System Network Information &IMPORTANT
drops according to Philips specifications PRIOR to the scheduled installation start date. Failure to do so may delay system installation and jeopardize the customer hand over date.
]yes [
Time Synchronization
]no
Location 1
Location 2
Location3
Physical Location:
Hostname:
Physical Location:
Server Name:
MAC Address:
Hostname:
RIS
IP Address
MAC Address:
Netmask:
IP Address
Hostname:
Gateway:
Netmask:
IP Address:
AE Title:
Gateway:
Port Number (5101):
AE Title:
AE Title:
Max PDU Size:
Port Number
(3010):
Physical Location:
Remote Software Installation (RPS)
Hostname:
Enable Distribution:
[
] yes [
] no
MAC Address:
Enable Installation:
[
] yes [
] no
IP Address
Dicom Printer
Location 1
Location 2
Location3
Location 4
Secure Node:
[ ] yes [ ] no
[ ] yes [ ] no
PPSM IHE
Compatible:
Hostname:
IP Address
AE Title:
IP for X-Ray Modality:
Allura Xper:
20/21(ftp), 80(http), 443(https), 5900(vnc),
9903(fsf.net)
Allura CV20:
20/21(ftp), 80(http), 4440(fsf)
XtraVision:
20/21(ftp), 80(http), 443(https), 5660(ist/ice),
5900(vnc), 9905(lots)
EP Navigator (R3):
20/21(ftp), 443(https), 5660(ist/ice), 9055(lots)
EP Cockpit (R1.2):
20/21(ftp), 80(http), 443(https), 5900(vnc),
9903(fsf.net)
Port Number :
IP Sec [
]yes [
]no
PACS
Physical Location:
Physical Location:
Store/
Import 1
Hostname:
MAC Address:
Hostname:
IP Address
IP Address
Netmask:
AE Title:
Gateway:
Port Number :
AE Title:
PACS
IP Sec [
]yes [
]no
Physical Location:
Hostname:
MAC Address:
IP Address
Store/
Import 2
Store/
Export
Query/
Retrieve
Storage/
Commit
CX50:
Xper IM:
View Forum
Physical Location:
Store/
Import 1
Port Number:
View Forum
[ ] yes [ ] no
Time Synchronization
AE Title XtraVision:
EP Navigator
[ ] yes [ ] no
Certificate Name:
Physical Location:
AE Title for X-Ray Mod:
[ ] yes [ ] no
Encryption:
Gateway:
Port Number (3110):
Port Number:
Store/
Import 2
Store/
Export
Query/
Retrieve
Storage/
Commit
Hospital Network
M2M Server
(PRS)
Hostname:
IP Address
AE Title:
Port Number :
Audit Trail
Proxy
ePO Server
(PRS)
Scheme (https):
IP Address
(192.68.49.50):
Portnumber (443):
Use Proxy Server:
[ ] yes [ ] no
Physical Location:
Netmask:
Hostname:
Gateway:
AE Title:
Port Number:
IP Address
IP Address
Port Number:
AE Title:
User Name:
Port Number :
Password:
(13.0)
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
Drawn By: Christy Perez
Netmask:
16384 or
N2
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
]no
MPPS
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
]yes [
WLM
Email: [email protected]
IP Sec [
Basic Local RIS
Philips Contacts
Project Manager: Michael Whelchel
XtraVision
Physical Location:
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
Physical Location:
IP Sec [
Allura FD10 Ceiling
XperIM
Contact Number: (304) 625-1612
]no
N-EAS131715 C
]yes [
Project
IP Sec [
Project Details
Drawing Number
Allura
Instructions
Items Specific for the Cardio/Vascular Modality
This form is to be used by Project Manager, Contractor and Service Engineer.
Unistrut installed and level according to Philips specifications.
Information is used to develop and determine site ready date.
Floor plates installed and level according to Philips specifications.
Items listed are go/no go items for delivery unless noted as delay only items.
All cover plates have holes punched and nipples required and bushings installed.
Items identified with *** as delayed items must be completed after hours or on weekend. These items cannot be accomplished while installation is
in progress. Also, these items must be completed within two days of installation start or they may stop installation.
Emergency power requirements installed according to Philips specifications.
Building steel ground installed to ECB section of ERB.
Site Readiness Checklist
Modality:
Non-Philips provided room electrical equipment grounds installed to PCB middle section of ERB.
Conduit lengths measured according to Philips specifications. Note: Specifications is from source box to destination box
___________________________________________________________________________________________________
(not just conduit run length).
___________________________________________________________________________________________________
Site Name:
___________________________________________________________________________________________________
Location:
___________________________________________________________________________________________________
Contact Name:
___________________________________________________________________________________________________
Contact Phone Number
Routing of ductwork and conduits must be installed according to Philips specifications.
_________________________________________________________________________________________
Customer site preparation verified in general against the Philips final planning drawings.
Walls finished including painting.
Floors are tiled/covered finished. Flooring is covered with protective covering (scratch protection).
Ceiling lights installed.
Project
Cable conduit and ductwork installed and clean. Position checked. Duct covers in place but not finally closed.
HVAC environmental equipment installed and working according to Philips specifications.
X-Ray warning lights installed ***.
Dedicated phone line for modem use***.
Email: [email protected]
Lead glass installed ***.
Date Drawn: 12/19/2013
Quote: None
Order: 6600193168.010000
Pre-move survey completed - Delivery route identified.
Contact Number: (304) 625-1612
All pre-cabling identified on Philips drawings has been installed.
N-EAS131715 C
All network cabling, drops installed according to Philips specifications (including hardcopy cameras).
Philips Contacts
Project Manager: Michael Whelchel
Electrical preparation according to Philips specifications.
Project Details
Drawing Number
Ceiling installation completed.
Drawn By: Christy Perez
Cable opening are clear, without sharp edges. Pull strings in conduit. Installation per Philips specifications.
Allura FD10 Ceiling
Floor leveled according to Philips drawings and specifications.
Riverside Methodist
Columbus, OH
Room: EP 1 - R23051
Doors installed.
Room has been cleaned ***.
Cabinets and casework installed (with insulation and building steel) according Philips specifications***.
RSN survey completed and submitted
Philips RSN Champion contacted.
Approved for Delivery
Project Manager
Date
Service Engineer
Date
THIS SHEET IS PART OF THE DOCUMENT SET LISTED ON SHEET C1 AND SHOULD NOT BE SEPARATED.
CHK
3.15.13
THE INFORMATION IN THIS PACKAGE IS PROVIDED AS A CUSTOMER CONVENIENCE, AND IS NOT TO BE CONSTRUED AS ARCHITECTURAL DRAWINGS OR CONSTRUCTION DOCUMENTS.
Philips assumes no liability nor offers any warranty for the fitness or adequacy of the premises or the utilities available at the premises in which the equipment is to be installed, used, or stored.
Order: