Document 259859

ELECTRICAL DRAWING INDEX
GENERAL NOTES
1.
CONTROL/ELEMENTARY
ELECTRICAL PLAN SYMBOLS
SYMBOLS
NORMALLY OPEN CONTACT
S
NORMALLY CLOSED CONTACT
S3
LIMIT SWITCH, NORMALLY OPEN
LIMIT SWITCH, NORMALLY CLOSED
SV
PRESSURE SWITCH, NORMALLY OPEN
PRESSURE SWITCH, NORMALLY CLOSED
SM
FLOAT SWITCH, NORMALLY OPEN
FLOAT SWITCH, NORMALLY CLOSED
SP
FLOW SWITCH, NORMALLY OPEN
FLOW SWITCH, NORMALLY CLOSED
S WP
TEMPERATURE SWITCH, NORMALLY OPEN
TEMPERATURE SWITCH, NORMALLY CLOSED
NORMALLY OPEN, TIMED TO CLOSE CONTACT
NORMALLY OPEN, TIMED TO OPEN CONTACT
AR
ALARM RELAY
AT
ALARM TIMER
CR
CONTROL RELAY
F/T
FIT
FSH
FSL
FLOW SWITCH HIGH/LOW
LS
LIMIT SWITCH OR LEVEL SWITCH
M
MOTOR STARTER
PRESSURE GAUGE
PFT
PROCESS FLOW TIMER
POWER FACTOR METER
KILOWATT METER
AMMETER
THREE PHASE VOLT SWITCH
WALL OUTLET BOX AND 20 AMP SWITCH WITH PILOT
LIGHT.
AS
THREE PHASE AMP SWITCH
WALL OUTLET BOX AND 20 AMP SWITCH WITH WEATHERPROOF COVER
OR ENCLOSURE.
AT
CURRENT TRANSMITTER
WALL OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE 18" TO
KW
KILOWATT TRANSMITTER
WALL OUTLET BOX AND 20 AMP DUPLEX RECEPT MOUNTED 48"AFF OR ABOVE
PFT
POWER FACTOR TRANSMITTER
WALL OUTLET BOX AND 20 AMP GFCI DUPLEX RECEPTACLE AT 18" TO
CP
LOCAL CONTROL PANEL
WALL OUTLET BOX AND 20 AMP GFCI RECEPTACLE MOUNTED 48"AFF OR ABOVE
COUNTER, OR AS NOTED.
GFI
GROUND FAULT INTERRUPTER
W
PHASE CONDUCTOR OR SWITCH LEG, LONG INDICATE NEUTRAL CONDUCTOR.
GREEN GROUND CONDUCTOR NOT SHOWN; ALL CONDUITS REQUIRE COPPER
GROUND CONDUCTOR. TWO CONDUCTORS PLUS GROUND REQUIRED, MINIMUM.
CONDUCTORS SHALL NOT BE SPLICED WITHOUT WRITTEN PERMISSION FROM
THE ENGINEER.
BRANCH CIRCUIT PANELBOARD
PRESSURE SWITCH
TS
TAMPER SWITCH
TR
TIMING RELAY
S/S
SURGE SUPPRESSION DEVICE
SV
SOLENOID VALVE
SCHEDULES
ALL DISCONNECTS, J-BOXES, TERMINAL CABINETS, ETC. & MOUNTING
5.
ALL CONDUITS (POWER, CONTROL, INSTRUMENTATION, ETC.) SHALL HAVE
45
WATT HOUR METER
ELECTRIC A.C. MOTOR, NO. INDICATES HORSEPOWER.
NO
ELECTRIC D.C. MOTOR, NO. INDICATES HORSEPOWER.
FOR ALL MOTOR LOADS SERVED THROUGH
NON-FUSIBLE DISCONNECT SWITCH, 30A,3P UNLESS
9.
PROVIDE A #2 BOND FROM ALL FIELD INSTRUMENTS, MOTORS, CONTROL
10.
PROVIDE 2' MINIMUM DISTANCE BETWEEN PARALLEL RUNS OF LOW VOLTAGE
AS REQUIRED BY ELEMENTARY DIAGRAMS OR SPECS.
VARIABLE FREQUENCY DRIVES;
12.
13.
14.
TORQUE SWITCH
HP
ZERO SPEED SWITCH
15.
ALARM INDICATING LIGHT
RUN INDICATING LIGHT
LIGHTING PANELBOARD
HP
AIR HANDLING UNIT CONNECTION; PROVIDE FUSED DISCONNECT AS REQUIRED
BY EQUIPMENT NAMEPLATE; MAKE CONNECTIONS.
ELECTRIC DUCT HEATER CONNECTION; PROVIDE FUSED DISCONNECT AS
REQUIRED BY EQUIPMENT NAMEPLATE; MAKE CONNECTIONS.
MOMENTARY CONTACT PUSHBUTTON
MOMENTARY BREAK PUSHBUTTON OR RESET
KEYED SWITCH
MANUAL TRANSFER SWITCH OR REVERSING SWITCH
K
K:\CCUD IQ Telemetry\Priority 2\E1.dwg Plotted: Nov 14, 2011 - 9:54am by tracy
ADDITIONAL CONDUIT FOR CONDUCTORS AS SHOWN ON RISER, ONE-LINE
DIAGRAMS, DETAILS AND NOTES.
ALL CIRCUITS SHALL BE IDENTIFIED IN JUNCTION BOXES, PULL BOXES,
CONTROL PANELS, PANELBOARDS, LIGHTING POLES, CONTROLLERS AND
SERVICE POINTS. IDENTIFICATION SHALL MATCH PANELBOARD SCHEDULES,
MCC SECTION, I&C SHOP DRAWINGS & SCHEDULES & TAG LISTS, ETC.
CURRENT TRANSFORMERS
POTENTIAL TRANSFORMERS
ALL EXCAVATIONS FOR CONDUITS, HANDHOLES, MANHOLES AND PULLBOXES
NEAR EXISTING PIPING, CONDUIT AND EQUIPMENT SHALL BE HAND
18.
GROUNDING CONNECTIONS BELOW GRADE SHALL BE EXOTHERMIC UNLESS
SPECIFICALLY INDICATED OTHERWISE.
19.
ALL ENCLOSURES, TERMINAL CABINETS, WIREWAYS, PULL BOXES ETC. SHALL
20.
CONTRACTOR SHALL CORE DRILL EXISTING CONCRETE WALLS, FLOORS,
MANHOLES, HANDHOLES AND PULL BOXES FOR CONDUIT PENETRATIONS.
LIGHTNING PROTECTION AIR TERMINAL;
21.
STREAMER RETARDING AIR TERMINAL
MOUNTED TO LIGHT POLE TOP.
MAIN ROOF CONDUCTOR TYPICAL
ALL CONDUITS PENETRATING RATED FIRE WALLS OR RATED FIRE FLOORS
SHALL BE INSTALLED WITH U.L. APPROVED DEVICES TO MAINTAIN THE FIRE
RATING OF THE WALL OR FLOOR PENETRATED.
22.
PROVIDE CONDUIT DUCT SEAL AT ALL CONDUIT ENDS.
#2 TINNED BARE COPPER
23.
FLEXIBLE CONDUITS SHALL BE USED TO TERMINATE ALL MOTORS AND OTHER
#2 TINNED BARE COPPER
24.
PROVIDE TYPEWRITTEN PANEL SCHEDULES IN PANELBOARD & TYPEWRITTEN
STREAMER RETARDING TYPE.
HOA
HAND OFF AUTO CONTROL STATION
G
COUNTERPOISE LOOP GROUND
COUNTERPOISE LOOP GROUND
TWISTED SHIELDED PAIRS
25.
RKS
Electrical, Instrumentation & Control Design
HOLE MONTES
15400 Shamrock Dr. Fort Myers, Fl. 33912
TRACY PROKOPETZ
PE #62427
P.E.
Certificate of Authorization #8212
NO.
DATE
REVISIONS
BY
ENGINEERS PLANNERS SURVEYORS
LANDSCAPE ARCHITECTS
CONTROL PANEL DETAILS
VETERANS PARK CONTROL PANEL DETAILS
ELECTRICAL DETAILS
RTU ANTENNA & ELECTRICAL DETAILS
EQUIPMENT RACK LOCATIONS SHOWN ON PLANS ARE
APPROXIMATE PREFERRED LOCATIONS ONLY.
COORDINATE LOCATION OF EQUIPMENT RACK WITH
LOCATION OF REUSE PIPING. DO NOT MOUNT RACK
DIRECTLY ABOVE PIPING. MOUNT RACK TO ALLOW
MAINTENANCE.
3.
CONTRACTOR IS REQUIRED TO HAVE SITES
PROPERTY LINES SURVEYED AND STAKED PRIOR TO
PLACEMENT OF EQUIPMENT RACK. COORDINATE
EQUIPMENT RACK LOCATION WITH PROPERTY LINES AS
REQUIRED.
4.
WORK IN THE RIGHT OF WAY REQUIRES RIGHT OF WAY
PERMIT. COORDINATE EQUIPMENT RACK LOCATION
WITH PIPING AND RIGHT OF WAY LIMITS.
5.
COORDINATE FINAL LOCATION OF RACK WITH COUNTY,
DOCUMENT COORDINATION TO ENGINEER.
VIBRATING EQUIPMENT AND SHALL BE BETWEEN 18" AND 2' IN LENGTH.
TERMINAL BLOCK SCHEDULES IN TERMINAL CABINETS; PROPOSED &
MODIFIED.
SERVICE OR EQUIPMENT GROUND.
Consulting
Engineers
TARPON COVE, CALUSA BAY & VINEYARDS ELEMENTARY
SEAL PENETRTATIONS WITH NON-SHRINK GROUT OR APPROPRIATE FIRE
RATED DEVICES WHERE APPLICABLE.
CONTROL POWER TRANSFORMER
HAND OFF REMOTE CONTROL STATION
PLAN
CONTAIN A GROUNDING BUS BAR. CONNECT ALL RACEWAY BONDS TO BUS
BAR VIA GROUNDING BUSHING AND EXTEND BONDING JUMPER FROM BUS
BAR TO ENCLOSURE.
SYSTEMS CABINET AS NOTED OR MARKED.
HOR
VINEYARDS ELEMENTARY POWER, INSTRUMENTATION &
CONTROLS, LIGHTNING PROTECTION BONDING & GROUNDING
FINISHED GRADE DIRECTLY ABOVE ALL UNDERGROUND YARD CONDUITS.
MOLDED CASE CIRCUIT BREAKER
LP
LIGHTNING PROTECTION BONDING & GROUNDING PLAN
GRADE SHALL BE 30" UNLESS OTHERWISE NOTED.
SYSTEMS BACKBOARD AS NOTED
COPPERWELD GRD. ROD
CALUSA BAY POWER, INSTRUMENTATION & CONTROLS,
FOR EXCAVATION OF PIPING AS REQUIRED FOR
PERPENDICULAR TO WALLS, STRUCTURAL MEMBERS OR INTERSECTIONS OF
VERTICAL PLANES AND CEILINGS, WITH RIGHT ANGLE TURNS CONSISTING OF
PROVIDE COLORED WARNING TAPE 6" WIDE SHALL BE INSTALLED 12" BELOW
MANUAL OR AUTOMATIC TRANSFER SWITCH
2.
EXPOSED RUNS OF CONDUITS SHALL BE INSTALLED WITH RUNS PARALLEL OR
FUSE
REMOTE TERMINAL BLOCK POINT
TSP
PLAN DRAWINGS DO NOT SHOW ALL CONDUITS REQUIRED. PROVIDE
17.
KIRK KEY INTERLOCK
SYSTEM SYMBOL LEGEND
MAINTAINED CONTACT
LIGHTNING PROTECTION BONDING & GROUNDING PLAN
EQUIPMENT RACK LOCATION NOTES:
1.
MINIMUM DEPTH FROM TOP OF DUCTBANKS OR CONDUITS TO FINISHED
MAINTAINED CONTACT ON-OFF SWITCH
START/STOP (S/S) CONTROL SWITCH
RECOMMENDATION. CONTRACTOR SHALL INSTALL PULL BOXES TO MEET
16.
POWER PANELBOARD
MOTOR OPERATED VALVE CONNECTION
CONDUCTOR PULLING TENSIONS SHALL NOT EXCEED MANUFACTURER'S
EXCAVATED AND COORDINATED WITH ENGINEER.
COMBINATION MAGNETIC MOTOR STARTER PROVIDED BY ELECTRICAL U.N.O.
MOTOR CONNECTION
MOV
E7
E8
E9
VETERANS PARK POWER, INSTRUMENTATION & CONTROLS,
480V/120V POWER CONDUITS AND I&C CONDUITS. POWER CONDUIT SHALL
SYMMETRICAL BENDS OR PULL BOXES AS INDICATED ON THE DRAWINGS.
BENDS AND OFFSETS SHALL BE AVOIDED WHERE POSSIBLE.
PROVIDE SURGE SUPPRESSION DEVICE EQUAL TO SQ.-D. SP3650 OR EQUAL
VIBRATION SWITCH
E6
LIGHTNING PROTECTION BONDING & GROUNDING PLAN
PANELS, TERMINATION CABINETS, ETC TO THE GROUND GRID.
MANUFACTURER'S REQUIREMENTS.
NON-FUSIBLE DISCONNECT SWITCH, 30A,3P UNLESS
OTHERWISE INDICATED, WITH REMOTE CONTROL STATION
AT DISCONNECT.
REMOVE CONDUCTORS BACK TO
PANEL/MCC. REMOVE CONDUIT BACK TO FIRST MANHOLE, HANDHOLE OR
DRAWINGS DO NOT SHOW EXACT ROUTING OF CONDUIT. COORDINATE
CONDUIT LOCATIONS WITH OTHER TRADES SO THAT CONFLICTS ARE AVOIDED.
SERVICE OR EQUIPMENT GROUND.
SERVING MOTOR LOADS OF 10HP OR GREATER AND
DO NOT ABANDON ELECTRICAL IN PLACE.
8.
OTHERWISE INDICATED.
FOR DISCONNECTS
EQUIPMENT GROUNDING CONDUCTOR SIZED PER TABLE 250.122 OF THE N.E.C.
ALL CONTROL PANELS SHALL BE CONSTRUCTED BY A UL508A APPROVED
PANEL VENDOR AND SHALL BEAR A UL508A LABEL ON THE PANEL. THE
PANEL SHALL ALSO BE RATED AND LABELED FOR A 10KAIC MINIMUM SCC.
11.
NO
DISCONNECT SWITCH SIZE PER EQUIPMENT NAME PLATE OR AS NOTED:
E5
GENERAL NOTES
CROSS INSTRUMENTATION CONDUIT PERPENDICULARLY AT RIGHT ANGLES
WITH 6" SEPARATION FOR 480V/120V.
TYPICAL STARTER CONTROL. SEE SWITCHGEAR
CONTROL DIAGRAMS FOR EXACT TYPE.
TRANSFORMER, SIZE AS INDICATED
E4
HARDWARE SHALL BE NEMA 4X STAINLESS STEEL UNLESS NOTED OTHERWISE.
7.
MOLDED CASE CIRCUIT BREAKER
AS NOTED; SEE PANEL
TARPON COVE POWER, INSTRUMENTATION & CONTROLS,
E3
4.
CONDUIT AND WIRE CONCEALED IN FLOOR SLAB OR UNDERGROUND.
PS
ELECTRICAL SYMBOLS LEGEND, DRAWING INDEX &
E2
REUSE FOR NEW WORK. REMOVE COMPLETE DUCT BANK AND MANHOLES IF
NOT BEING REUSED.
SLASH MARKS INDICATE NUMBER OF
CONDUCTORS; (MARKS SHOWN TO AID CONTRACTOR IN BIDDING, THE
3.
CAPACITOR
BRANCH CIRCUIT CONDUIT AND WIRE GENERALLY SURFACE MOUNTED,
CONCEALED ABOVE CEILINGS
PROVIDE SCHEDULE 80 PVC CONDUIT BELOW GRADE.
FUSE
FLUSH MOUNTED JUNCTION BOX ( SURFACE IN MECH/ELEC SPACES OR ABOVE
CEILINGS).
ALL WORK SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE, NATIONAL
ELECTRICAL SAFETY CODE, UTILITY REQUIRMENTS AND LOCAL CODES.
2.
6.
DRAW-OUT CIRCUIT BREAKER
CONTRACT SUM WHETHER OR NOT SHOWN). SHORT SLASHES INDICATE
P/G
VOLTMETER
VS
CONTRACTOR SHALL PROVIDE THE REQUIRED CONDUCTORS UNDER THE
MOTOR SWITCH MANUAL
K
MANUAL MOTOR STARTING SWITCH WITH OVERLOADS AND PILOT LIGHT.
NEMA 4X TYPICAL
PHOTOCELL ON ROOF
J
LEVEL INDICATOR TRANSMITTER
MS
R
KW
A
CENTERLINE. WP INDICATES WEATHERPROOF COVER PLATE.
FLOW INDICATOR TRANSMITTER (TOTALIZER)
LIT
A
CONNECTIONS.
PF
WALL OUTLET BOX AND SPECIAL PURPOSE RECEPTACLE AS NOTED OR COORDINATE.
L/T
ZS
WALL OUTLET BOX AND EXHAUST FAN SPEED CONTROLLER/SWITCH
V
CENTERLINE
FS LIQUID LEVEL SWITCH
VS
48" TO CTR LINE.
WALL OUTLET BOX AND DOUBLE 20 AMP DUPLEX RECEPTACLES 18" TO
LLS
YSH
WALL OUTLET BOX AND 20 AMP 3-WAY SWITCH (`a' INDICATES SWITCHES)
COUNTER OR AS NOTED.
NORMALLY CLOSED, TIMED TO CLOSE CONTACT
ANALYZER INDICATOR TRANSMITTER
48" TO CENTERLINE.
CENTERLINE
NORMALLY CLOSED, TIMED TO OPEN CONTACT
AIT
WALL OUTLET BOX AND 20 AMP SINGLE POLE SWITCH (`a' INDICATES SWITCHES)
SINGLE LINE DIAGRAM SYMBOLS
E1
950 Encore Way
Naples, FL. 34110
Phone: (239) 254-2000
Florida Certificate of
Authorization No.1772
DESIGN BY:
T.M.P.
DRAWN BY:
T.M.P.
CHECKED BY:
T.M.P.
CAD FILE:
E1.dwg
BRANCH CIRCUITS EXCEEDING 75 FT IN LENGTH SHALL BE WIRED WITH
MINIMUM #10 AWG WIRES.
COUNTY WATER-SEWER DISTRICT
COLLIER COUNTY, FLORIDA
ELECTRICAL SYMBOLS LEGEND, DRAWING INDEX &
GENERAL NOTES
PROJECT NO. :
2011.027
DATE :
11/11
SHEET NO. :
E1
OHW
2'
0
1/4"=1'-0"
OHP
X
X
X
X
X
X
X
X
X
X
*
1'
OHP
2'
X
X
SV SV
MOV
VALVE CONTROL PANEL (VCP).
5.
FIBER INTERFACE BOX PROVIDED BY COLLIER
COUNTY I.T. MAKE CONNECTIONS. COORDINATE
WITH COUNTY PM & IT.
X
X
X
X
X
X
X
X
X
X
X
X
X
G
G
G
X
X
X
X
G
M
15
11
X
11.
#2 TINNED SOLID COPPER TO EQUIPMENT/
12.
#2/0 STRANDED TINNED BARE COPPER
13.
#2/0 STRANDED TINEND BARE COPPER BOND
14.
(3) #14 IN 0.75"C.
15.
FLAT ROOF MOUNTED AIR TERMINAL WITH DOWN
CONDUCTOR TO COUNTERPOISE.
16.
FLOW CONTROL VALVE COORDINATE EXACT
TEST WELL (SEE DETAIL). TYPICAL.
CABINETS ETC. TYPICAL.
COUNTERPOISE LOOP GROUND. TYPICAL.
TO FENCE.
1
INTERCONNECTING WIRE REQUIREMENTS WITH
BOX AND PLC, AND PLC AND VALVE DEVICES.
17.
X
G
M
TARPON COVE SITE PLAN
APPROXIMATE SCALE: 1"=10'-0"
INTERCONNECTING WIRING BETWEEN JUNCTION
G
12
2 PAIR #16 TSP INSTRUMENT CABLE IN 1"C.
NEMA 4X SS
240V/120
MOV
70A, 240V,2P,
FPL APPROVED
DIRECT READING
UTILITY METER &
METER CAN
1∅ SERVICE
G
PIT
PROPOSED
X
G
20' DRIVEN GROUND ROD WITH INSPECTION
PROVIDE JUNCTION BOX AND ALL REQUIRED
X
G
12
FIT
10.
2
VALVE MANUFACTURES SUBMITTALS PRIOR TO
ROUGH-IN. ELECTRICAL CONTRACTOR TO
G
JB
SV SV
15 CONDUCTOR #14 CONTROL CABLE IN 1.25"C.
X
G
X
15
9.
OHP
X
X
CAT 6 ETHERNET CABLE IN 1"C.
OHP
G
G
X
8.
IN 0.75"C.
OHP
X
CAT 6 ETHERNET CABLE IN 1"C AND (3) #12
OHP
X
7.
1" CONDUIT.
OHP
13
5 CONDUCTOR, #14 CONTROL CABLE IN
X
TARPON COVE ELECTRICAL PLAN
X
6
M
OHP
X
10
SE RATED
ENCLOSED
BREAKER
VALVE
CONTROL
PANEL
G
X
4.
ENTRANCE RATED ENCLOSED BREAKER.
OHP
16
11
10
G
G
G
X
X
X
X
G
G
X
G
X
12
G
X
G
X
13
G
X
X
X
K:\CCUD IQ Telemetry\Priority 2\E2.dwg Plotted: Nov 13, 2011 - 2:01pm by tracy
60A, 240/120V, SINGLE PHASE SERVICE
PIT
X
X
M
FIT
3.
X
X
7
14
PROPOSED UNDERGROUND SERVICE LATERAL.
CONTRACTOR TO FIELD VERIFY EXACT LENGTH.
OHP
JB
2.
*
17
9
14
AERIAL
TRANSFORMER WITH POLE BASE HANDHOLE.
CONTRACTOR TO COORDINATE AND SCHEDULE
SERVICE CONNECTION WITH FPL.
OHP
4
6
KEYNOTES
PROPOSED FPL 240V/120V, 1ø
OHW
1.
M
#
5
*
3
X
X
M
OHP
X
8
X
PROPOSED FPL
POLE BASE
HANDHOLE
X
(3)#6 IN
SS
1"C.
#2
TARPON COVE GROUNDING & BONDING PLAN
(3) #6 & #6G
(3) #6 IN 1"C.
IN 1"C.
ELECTRICAL RISER DRAWING
N.T.S.
RKS
Consulting
Engineers
Electrical, Instrumentation & Control Design
HOLE MONTES
15400 Shamrock Dr. Fort Myers, Fl. 33912
TRACY PROKOPETZ
PE #62427
P.E.
Certificate of Authorization #8212
NO.
DATE
REVISIONS
BY
ENGINEERS PLANNERS SURVEYORS
LANDSCAPE ARCHITECTS
950 Encore Way
Naples, FL. 34110
Phone: (239) 254-2000
Florida Certificate of
Authorization No.1772
DESIGN BY:
T.M.P.
DRAWN BY:
T.M.P.
CHECKED BY:
T.M.P.
CAD FILE:
E2.dwg
COUNTY WATER-SEWER DISTRICT
COLLIER COUNTY, FLORIDA
TARPON COVE
POWER, INSTRUMENATION & CONTROLS, LIGHTNING
PROTECTION BONDING & GROUNDING PLAN
PROJECT NO. :
2011.027
DATE :
11/11
SHEET NO. :
E2
X
4'
2'
0
X
X
X
X
X
4'
1/8"=1'-0"
X
X
X
X
X
PIT
M
15
MOV
9
3
5
8
7
FIT
X
14
SV
16
SV
JB
14
X
X
X
X
X
6
#
1.
4
X
VETERANS PARK SITE ELECTRICAL PLAN
X
X
X
TO FENCE
X
X
X
13
IN EXISTING PANELBOARD FOR SERVICE TO
REUSE CONNECTION. FIELD COORDINATE
LOCATION OF PANELBOARD AND MATCH
EXISTING MANUFACTURER AND BREAKER
TYPE.
(3) #3 IN 1"C.
3.
EXISTING PARK BOOSTER PUMP AND CONTROL
PANEL TO REMAIN.
4.
VALVE CONTROL PANEL (VCP).
5.
RTU ANTENNA TOWER.
6.
5 CONDUCTOR, #14 CONTROL CABLE IN
7.
CAT 6 ETHERNET CABLE IN 1"C AND (3) #12
8.
COAX RADIO CABLE IN 1"C.
9.
15 CONDUCTOR #14 CONTROL CABLE IN 1.25"C.
10.
20' DRIVEN GROUND ROD WITH INSPECTION
11.
#2 TINNED SOLID COPPER TO EQUIPMENT/
12.
#2/0 STRANDED TINNED BARE COPPER
13.
#2/0 STRANDED TINNED BARE COPPER BOND
14.
(3) #14 IN 0.75"C.
15.
2 PAIR #16 TSP INSTRUMENT CABLE IN 1"C.
16.
FLOW CONTROL VALVE COORDINATE EXACT
G
G
G
G
1" CONDUIT.
IN 0.75"C.
TEST WELL (SEE DETAIL). TYPICAL.
CABINETS ETC. TYPICAL.
COUNTERPOISE LOOP GROUND. TYPICAL.
1
G
G
G
2
SEE DETAIL.
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
MOV
PROVIDE 120V, 30A, SINGLE POLE BREAKER
2.
G
PIT
M
KEYNOTES
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
TO FENCE.
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
11
12
G
G
G
G
G
G
G
FIT
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
SV
G
G
G
G
G
G
G
G
G
G
G
G
G
G
SV
G
G
G
G
G
G
G
SV
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
VALVE MANUFACTURES SUBMITTALS PRIOR TO
ROUGH-IN. ELECTRICAL CONTRACTOR TO
G
G
G
G
G
PROVIDE JUNCTION BOX AND ALL REQUIRED
G
G
G
G
G
K:\CCUD IQ Telemetry\Priority 2\E3.dwg Plotted: Nov 14, 2011 - 11:54am by tracy
INTERCONNECTING WIRING BETWEEN JUNCTION
G
10
G
G
G
G
G
G
G
G
G
G
G
G
INTERCONNECTING WIRE REQUIREMENTSW WITH
G
BOX AND PLC, AND PLC AND VALVE DEVICES.
VETERANS PARK SITE PLAN
APPROXIMATE SCALE: 1"=20'-0"
X
X
X
X
X
X
VETERANS PARK SITE GROUNDING & BONDING PLAN
RKS
Consulting
Engineers
Electrical, Instrumentation & Control Design
HOLE MONTES
15400 Shamrock Dr. Fort Myers, Fl. 33912
TRACY PROKOPETZ
PE #62427
P.E.
Certificate of Authorization #8212
NO.
DATE
REVISIONS
BY
ENGINEERS PLANNERS SURVEYORS
LANDSCAPE ARCHITECTS
950 Encore Way
Naples, FL. 34110
Phone: (239) 254-2000
Florida Certificate of
Authorization No.1772
DESIGN BY:
T.M.P.
DRAWN BY:
T.M.P.
CHECKED BY:
T.M.P.
CAD FILE:
E3.dwg
COUNTY WATER-SEWER DISTRICT
COLLIER COUNTY, FLORIDA
VETERANS PARK
POWER, INSTRUMENATION & CONTROLS, LIGHTNING
PROTECTION BONDING & GROUNDING PLAN
PROJECT NO. :
2011.027
DATE :
11/11
SHEET NO. :
E3
NOTICE OF SPECIAL REQUIREMENTS:
6
JB
14
TYPICAL INSTALLATION METHODS AS REQUIRED TO
M
9
7
14
PIT
M
4
MEET THE 14' HEIGHT RESTRICTION.
#
MOV
1.
16
KEYNOTES
G
G
G
G
10
M
PIT
M
3.
60A, 240/120V, SINGLE PHASE SERVICE
4.
VALVE CONTROL PANEL (VCP).
5.
FIBER INTERFACE BOX PROVIDED BY COLLIER
COUNTY I.T. MAKE CONNECTIONS. COORDINATE
WITH COUNTY PM & IT.
FIT
MOV
6.
5 CONDUCTOR, #14 CONTROL CABLE IN
7.
CAT 6 ETHERNET CABLE IN 1"C AND (3) #12
8.
CAT 6 ETHERNET CABLE IN 1"C.
9.
15 CONDUCTOR #14 CONTROL CABLE IN 1.25"C
10.
20' DRIVEN GROUND ROD WITH INSPECTION
11.
#2 TINNED SOLID COPPER TO EQUIPMENT/
12.
#2/0 STRANDED TINNED BARE COPPER
13.
24x24x18 FLUSH ON GRADE HEAVY DUTY
11
11
G
G
10
PROPOSED UNDERGROUND SERVICE LATERAL.
CONTRACTOR TO FIELD VERIFY EXACT LENGTH.
DIRECTIONAL DRILL ENTIRE SERVICE LATERAL.
G
G
JB
SV SV
12
G
G
G
12
LEAVE 7' EXCESS LOOP
2.
15
15
G
MOUNT TRANSFORMER.
OF CONDUCTORS AT TRANSFORMER LOCATION
FOR SERVICE CONNECTION. CONTRACTOR TO
COORDINATE AND SCHEDULE SERVICE
CONNECTION WITH FPL.
CALUSA BAY ELECTRICAL PLAN
G
APPROXIMATE LOCATION OF EXISTING FPL PAD
12
G
CALUSA BAY GROUNDING & BONDING PLAN
X
FIT
SV SV
17
3
5
M
M
RESTRICTIONS REQUIRE ALL STRUCTURES,
CONSTRUCTION EQUIPMENT, MACHINERY ETC TO BE
UNDER 14' IN HEIGHT. CONTRACTOR TO MODIFY
8
ANK ROA
D
1/8"=1'-0"
TTE - FR
THEREFORE ASSOCIATED CONSTRUCTION LIES WITHIN
AN FPL TRANSMISSION COORIDOR. FPL
4'
0
GOODLE
2'
ENTRANCE RATED ENCLOSED BREAKER.
EAST RIGHT
-OF-WAY LIN
E
4'
LOCATION OF IQ SERVICE CONNECTION AND
X
100' FLOR
IDA
POWER &
LIGHT CO
MPANY
EASEMENT
1" CONDUIT.
IN 0.75"C.
TEST WELL (SEE DETAIL). TYPICAL.
2
CABINETS ETC. TYPICAL.
COUNTERPOISE LOOP GROUND. TYPICAL.
QUAZITE OPEN BOTTOM PULL BOX WITH BOLT
ON TRAFFIC RATED COVER.
14.
(3) #14 IN 0.75"C.
15.
FLAT ROOF MOUNTED AIT TERMINAL WITH DOWN
CONDUCTOR.
16.
FLOW CONTROL VALVE COORDINATE EXACT
INTERCONNECTING WIRE REQUIREMENTS WITH
VALVE MANUFACTURES SUBMITTALS PRIOR TO
ROUGH-IN. ELECTRICAL CONTRACTOR TO
PROVIDE JUNCTION BOX AND ALL REQUIRED
INTERCONNECTING WIRING BETWEEN JUNCTION
K:\CCUD IQ Telemetry\Priority 2\E4.dwg Plotted: Nov 13, 2011 - 2:03pm by tracy
BOX AND PLC, AND PLC AND VALVE DEVICES.
NEMA 4X SS
FPL APPROVED
DIRECT
READING UTILITY
METER & METER CAN
EXISTING FPL
PAD MOUNT
240V/120V
SINGLE PHASE
TRANSFORMER
17.
70A, 240V,2P,
SE RATED
ENCLOSED
BREAKER
2 PAIR #16 TSP INSTRUMENT CABLE IN 1"C.
2
SS
(3)#1 IN
1.5"C.
COIL 7' OF
1
#2
(3) #6 & #6G
EXCESS
CONDUCTORS
FOR FPL
CONNECTION.
(3) #1 IN 1.5"C.
IN 1"C.
ELECTRICAL RISER DRAWING
N.T.S.
CALUSA BAY SITE PLAN
APPROXIMATE SCALE: 1"=40'-0"
RKS
Consulting
Engineers
Electrical, Instrumentation & Control Design
HOLE MONTES
15400 Shamrock Dr. Fort Myers, Fl. 33912
TRACY PROKOPETZ
PE #62427
13
VALVE
CONTROL
PANEL
P.E.
Certificate of Authorization #8212
NO.
DATE
REVISIONS
BY
ENGINEERS PLANNERS SURVEYORS
LANDSCAPE ARCHITECTS
950 Encore Way
Naples, FL. 34110
Phone: (239) 254-2000
Florida Certificate of
Authorization No.1772
DESIGN BY:
T.M.P.
DRAWN BY:
T.M.P.
CHECKED BY:
T.M.P.
CAD FILE:
E4.dwg
COUNTY WATER-SEWER DISTRICT
COLLIER COUNTY, FLORIDA
CALUSA BAY
POWER, INSTRUMENATION & CONTROLS, LIGHTNING
PROTECTION BONDING & GROUNDING PLAN
PROJECT NO. :
2011.027
DATE :
11/11
SHEET NO. :
E4
N
240
VOLTS
PLUS
NEUTRAL
FROM
UTILITY
N
120V
N
NEMA 3R STAINLESS STEEL HINGED 3 POINT LATCH
CABINET PAINTED WHITE
CONTINUOUS STAINLESS
STEEL HINGE
PROVIDE WITH SUNSHIELD WITH WHITE POWDER COAT
FINISH
AR1
20A-1P
L1
2A-1P
TO
MOV
5A-1P
L2
TO
FLOWMETER
G
24VDC
POWER SUPPLY
FUSE
4-20mA LOOP
for HART PROT.
SPD
R6
DOOR
INTRUSION
SWITCH
20A-1P
VALVE CONTROL PANEL
LOUVER
EDCO HSP-121
20A-1P
INTERNAL LIGHT KIT WITH TERMINAL BLOCKS AND
INTEGRAL CONVENIENCE RECEPTACLE CONTROLLED
AUTOMATICALLY VIA DOOR SWITCH
36" X 48" X 12" MIN SIZE.
PANEL INT LT & RECEPT.
R1
R2
MOV
OPEN
MOV
CLOSE
MOV FAULT OR
NOT IN AUTO
BACKPRESSURE VALVE
OPEN COMMAND
A
B
CLOSE COMMAND
BACKPRESSURE
SUSTAINING
VALVE NOT IN AUTO
W
A
CLOSE
OPEN
UTIL. POWER
AUTO
G
UTILITY POWER
A
G
MOV FAULT OR
NOT IN AUTO
MOV
R7
MOV CLOSED
MOV
NOTE: ELEVATION SHOWN WITH
EXTERIOR DOOR REMOVED
R9
CORD & PLUG
650VA UPS
MINIMUM
UPS RECEPT.
24V
PS
CLOSE
AUTO
OPEN
BACKPRESSURE VALVE
OPEN SOLENOID
R3
0OX
SV
B
OPEN COMMAND
R4
SV
0X0
W
CLOSE COMMAND
UTILITY OR MOV POWER FAILURE(AR1)
DOOR INTRUSION ALARM(R6)
MOV FAULT OR NOT IN AUTO(R7)
MOV CLOSED(R8)
MOV OPENED(R9)
BACKPRESSURE VALVE NOT IN AUTO(R10)
DIGITAL OUT
1)
2)
3)
4)
MOV OPEN(R1)
MOVE CLOSE(R2)
OPEN BACK PRESSURE SUSTAINING VALVE(R3)
CLOSE BACK PRESSURE SUSTAINING VALVE(R4)
ANALOG+HART IN
PRESSURE(ON HART)
CALIBRATION DEVIATION WARNING(ON HART)
CONFIGURE PER COUNTY DIRECTION(ON HART)
CONFIGURE PER COUNTYS DIRECTIONON HART)
A
R10
PLC
10A-1P
AB COMPACTLOGIX L23
120VAC SURGE SUPPRESSOR, EDCO HSP121
4.
DATA SIGNAL LINE SURGE SUPPRESSOR, EDCO
5.
24VDC POWER SUPPLY, ALLEN BRADLEY
6.
24VDC UNMANAGED 4 PORT INDUSTRIAL SWITCH.
7.
PLC
8.
ETHERNET DATA CIRCUIT PROTECTOR. EDCO
LCDP WITH RJ 45 JACKS. PROVIDE INDUSTRIAL
GRADE RJ45 CONNECTORS.
9.
DUPLEX GFI RECEPTACLE.
10.
110VAC CONTROL RELAY.
R6-R10.
11.
24VDC CONTROL RELAY. TYPICAL UNLESS
NOTED OTHERWISE. RELAYS R1-R5.
12.
120V, 1 POLE SQUARE D POWER BREAKER.
PC642 SERIES
1606 SERIES
11
2.
S
P
A
C
E
PLC 7
EDCO
13
NETWORK
SWITCH
RKS
Electrical, Instrumentation & Control Design
HOLE MONTES
15400 Shamrock Dr. Fort Myers, Fl. 33912
P.E.
Certificate of Authorization #8212
NO.
DATE
REVISIONS
FLOWMETER I/O IS NOT SHOWN ON THIS
REFERENCE SPECIFICATION FOR
DETAILED VIRTUAL I/O LIST.
PROVIDE INDUSTRIAL GRADE ETHERNET
CONNECTORS THROUGHOUT PANEL AND AT
FIELD INSTRUMENT.
PROVIDE ALL COMPONENTS NECESSARY AND
REQUIRED BY MANUFACTURER FOR A FULLY
FUNCTIONAL ETHERNET AND HART
INSTRUMENT NETWORK WHETHER
SPECIFICALLY SHOWN ON THIS DRAWING OR
NOT.
NEUT.
GROUND
15 AMPS MAX
EDCO
L
I
N
E
L
O
A
D
AC
NEUT.
GROUND
HSP121BT-1RU
3
BACK PLATE LAYOUT
Consulting
Engineers
PE #62427
LABELED FOR A MINIMUM 10kA SCC.
PROVIDE 250 OHM TERMINATING RESISTOR
ON HART NETWORK FIELD INSTRUMENT END.
NETWORKED PRESSURE TRANSMITTER AND
12
AC
UPS
RECEPT
PANEL IS REQUIRED TO BE RATED AND
DRAWING.
4.
2
10
GND.
VALVE CONTROL PANEL ELEMENTARY
TRACY PROKOPETZ
3.
5.
120 VAC
UPS
S
P
A
C
E
WIREWAY
8
RELAYS AR1 AND
1.
I/O
EDCO
MODULE, DUAL COMMUNICATION PORT PROCESSOR,
DATA ACCESS TOOL, MEMORY MODULE WITH REAL TIME
CLOCK, ETHERNET ADAPTER, BATTERY BACK-UP.
NOT IN AUTO
POWER MINIATURE BREAKER.
3.
ALLEN BRADLEY COMPACTLOGIX 1769-L23QB1B WITH 4
POINT SPECTRUM 1769sc-IF4IH ANALOG+HART INPUT
120V, 1 POLE PHOENIX PUSH BUTTON CONTROL
6
GENERAL NOTES:
TERMINAL BLOCKS
NOT IN AUTO
XX0
WIREWAY
TERMINAL BLOCKS
1)
2)
3)
4)
2.
DOOR CONTACT INTRUSION ALARM.
PLUNGER TYPE
CR CR CR CR CR CR
BACKPRESSURE VALVE
CLOSE SOLENOID
1)
2)
3)
4)
5)
6)
# KEYNOTES
1.
CR CR CR CR
X00
DIGITAL IN
1
9
WIREWAY
CONTROL VALVE
5
WIREWAY
FLOW CONTROL IQ SERVICE
CONNECTION I/O POINT LIST
WIREWAY
10A-1P
K:\CCUD IQ Telemetry\Priority 2\E6.dwg Plotted: Nov 14, 2011 - 9:55am by tracy
SIDE
FRONT
WIREWAY
10A-1P
EQUIPMENT
BACK PLATE
MOV OPENED
MOV
INTERNAL
LOUVER
R8
BY
ENGINEERS PLANNERS SURVEYORS
LANDSCAPE ARCHITECTS
950 Encore Way
Naples, FL. 34110
Phone: (239) 254-2000
Florida Certificate of
Authorization No.1772
DESIGN BY:
T.M.P.
DRAWN BY:
T.M.P.
CHECKED BY:
T.M.P.
CAD FILE:
E6.dwg
COUNTY WATER-SEWER DISTRICT
COLLIER COUNTY, FLORIDA
TARPON COVE, CALUSA BAY & VINEYARDS
ELEMENTARY VALVE CONTROL PANEL
DETAILS AND ELEMENTARY
PROJECT NO. :
2011.027
DATE :
11/11
SHEET NO. :
E6
120 VOLTS FROM PANELBOARD
L1
G
N
20A-1P
N
10A-1P
AR1
30A-1P
120V
AB COMPACTLOGIX L23
COMM
RESET
R6
TO
MOV
5A-1P
EDCO HSP-121
20A-1P
TO
FLOWMETER
NETWORK
SWITCH
SPD
2A-1P
20A-1P
CABINET PAINTED WHITE
36" X 48" X 12" MIN SIZE.
PROVIDE WITH SUNSHIELD WITH WHITE POWDER COAT
FINISH
24VDC
POWER SUPPLY
R7
DOOR
INTRUSION
SWITCH
NEMA 3R STAINLESS STEEL HINGED 3 POINT LATCH
CONTINUOUS STAINLESS
STEEL HINGE
FUSE
INTERNAL LIGHT KIT WITH
TERMINAL BLOCKS AND
INTEGRALCONVENIENCE
RECEPTACLE CONTROLLED
AUTOMATICALLY VIA
DOOR SWITCH
VALVE CONTROL PANEL
PANEL INT LT & RECEPT.
LOUVER
4-20mA LOOP
for HART PROT.
UTIL. POWER
5A-1P
12VDC
POWER SUPPLY
G
FUSE
OPEN COMMAND
COMM. FLT
DATA RADIO
A
A
MOV FAULT OR
NOT IN AUTO
R1
R2
MOV
OPEN
MOV
CLOSE
CLOSE COMMAND
BACKPRESSURE
SUSTAINING
VALVE NOT IN AUTO
W
A
CLOSE
OPEN
R8
AUTO
UTILITY POWER
COMMUNICATION FAULT
A
G
MOV CLOSED
MOV
A
B
R5
MOV
MOV FAULT OR
NOT IN AUTO
BACKPRESSURE VALVE
R9
RESET COMMUNICATION
MOV OPENED
MOV
R10
INTERNAL
LOUVER
10A-1P
650VA UPS
MINIMUM
CORD & PLUG
13
12V
PS
24V
PS
5
BACK PLATE
1
14
9
NOTE: ELEVATION SHOWN WITH
EXTERIOR DOOR REMOVED
UPS RECEPT.
10A-1P
0OX
X00
WIREWAY
SV
B
OPEN COMMAND
SV
0X0
EDCO
R11
13
EDCO
NOT IN AUTO
NOT IN AUTO
ANALOG+HART IN
RKS
Electrical, Instrumentation & Control Design
P.E.
Certificate of Authorization #8212
NO.
DATE
REVISIONS
BY
ENGINEERS PLANNERS SURVEYORS
LANDSCAPE ARCHITECTS
PRESSURE(ON HART)
CALIBRATION DEVIATION WARNING(ON HART)
CONFIGURE PER COUNTY DIRECTION(ON HART)
CONFIGURE PER COUNTYS DIRECTIONON HART)
ALLEN BRADLEY COMPACTLOGIX 1769-L23QB1B WITH 4
POINT SPECTRUM 1769sc-IF4IH ANALOG+HART INPUT
UPS
RECEPT
HOLE MONTES
15400 Shamrock Dr. Fort Myers, Fl. 33912
PE #62427
1)
2)
3)
4)
12
AC
Consulting
Engineers
MOV OPEN(R1)
MOVE CLOSE(R2)
OPEN BACK PRESSURE SUSTAINING VALVE(R3)
CLOSE BACK PRESSURE SUSTAINING VALVE(R4)
COMMUNICATION FAULT(R5)
COMMUNICATION FAULT RESET(R6)
NEUT.
GROUND
MODULE, DUAL COMMUNICATION PORT PROCESSOR,
DATA ACCESS TOOL, MEMORY MODULE WITH REAL TIME
CLOCK, ETHERNET ADAPTER, BATTERY BACK-UP.
15 AMPS MAX
EDCO
L
I
N
E
L
O
A
D
AC
NEUT.
GROUND
HSP121BT-1RU
3
950 Encore Way
Naples, FL. 34110
Phone: (239) 254-2000
Florida Certificate of
Authorization No.1772
DESIGN BY:
T.M.P.
DRAWN BY:
T.M.P.
CHECKED BY:
T.M.P.
CAD FILE:
E7.dwg
GENERAL NOTES:
DOOR CONTACT INTRUSION ALARM.
PLUNGER TYPE
1.
2.
2.
120V, 1 POLE PHOENIX PUSH BUTTON CONTROL
3.
120VAC SURGE SUPPRESSOR, EDCO HSP121
4.
DATA SIGNAL LINE SURGE SUPPRESSOR, EDCO
4.
5.
24VDC POWER SUPPLY, ALLEN BRADLEY
5.
6.
24VDC UNMANAGED 4 PORT INDUSTRIAL SWITCH.
7.
PLC
8.
ETHERNET DATA CIRCUIT PROTECTOR. EDCO
LCDP WITH RJ 45 JACKS. PROVIDE INDUSTRIAL
GRADE RJ45 CONNECTORS.
9.
DUPLEX GFI RECEPTACLE.
10.
110VAC CONTROL RELAY.
R7-R11.
11.
24VDC CONTROL RELAY. TYPICAL UNLESS
NOTED OTHERWISE. RELAYS R1-R6.
12.
120V, 1 POLE SQUARE D POWER BREAKER.
13.
12VDC POWER SUPPLY, ALLEN BRADLEY
14.
DATA RADIO, INTEGRA-TR
DIGITAL OUT
BACK PLATE LAYOUT
VALVE CONTROL PANEL ELEMENTARY
UTILITY OR MOV POWER FAILURE(AR1)
DOOR INTRUSION ALARM(R7)
MOV FAULT OR NOT IN AUTO(R8)
MOV CLOSED(R9)
MOV OPENED(R10)
BACKPRESSURE VALVE NOT IN AUTO(R11)
# KEYNOTES
1.
PLC
GND.
TRACY PROKOPETZ
1)
2)
3)
4)
5)
6)
1)
2)
3)
4)
5)
6)
120 VAC
UPS
DIGITAL IN
2
10
TERMINAL BLOCKS
A
XX0
WIREWAY
W
FLOW CONTROL IQ SERVICE
CONNECTION I/O POINT LIST
S
P
A
C
E
WIREWAY
8
CLOSE COMMAND
S
P
A
C
E
PLC 7
TERMINAL BLOCKS
K:\CCUD IQ Telemetry\Priority 2\E7.dwg Plotted: Nov 14, 2011 - 11:55am by tracy
BACKPRESSURE VALVE
CLOSE SOLENOID
I/O
CR CR CR CR CR CR
R4
11
6
WIREWAY
BACKPRESSURE VALVE
OPEN SOLENOID
R3
WIREWAY
CLOSE
AUTO
CR CR CR CR CR CR
OPEN
SIDE
FRONT
WIREWAY
CONTROL VALVE
EQUIPMENT
POWER MINIATURE BREAKER.
PC642 SERIES
1606 SERIES
3.
PANEL IS REQUIRED TO BE RATED AND
LABELED FOR A MINIMUM 10kA SCC.
PROVIDE 250 OHM TERMINATING RESISTOR
ON HART NETWORK FIELD INSTRUMENT END.
NETWORKED PRESSURE TRANSMITTER AND
FLOWMETER I/O IS NOT SHOWN ON THIS
DRAWING.
REFERENCE SPECIFICATION FOR
DETAILED VIRTUAL I/O LIST.
PROVIDE INDUSTRIAL GRADE ETHERNET
CONNECTORS THROUGHOUT PANEL AND AT
FIELD INSTRUMENT.
PROVIDE ALL COMPONENTS NECESSARY AND
REQUIRED BY MANUFACTURER FOR A FULLY
FUNCTIONAL ETHERNET AND HART
INSTRUMENT NETWORK WHETHER
SPECIFICALLY SHOWN ON THIS DRAWING OR
NOT.
RELAYS AR1 AND
1606 SERIES
COUNTY WATER-SEWER DISTRICT
COLLIER COUNTY, FLORIDA
VETERANS PARK
VALVE CONTROL PANEL
DETAILS AND ELEMENTARY
PROJECT NO. :
2011.027
DATE :
11/11
SHEET NO. :
E7
GREEN
INSULATED WIRE
AWG 18
CONTINUOUS STAINLESS
STEEL HINGE
OUTER JACKET
NEMA 4X ST.STEEL CABINET PANINTED WHITE FOR EXTERIOR LOCATIONS.
NEMA 1 STEEL CABINET FOR INTERIOR LOCATIONS.
AS REQUIRED
WRAPPED SHIELD
CRIMPED SPLICE
CONNECTOR
12"
AS REQUIRED
OUTER JACKET
SHIELD
OUTER JACKET
INTERNAL EQUIPMENT
BACK PLATE
INTEGRAL FLOW METER
TRANSMITTER (REQUIRED
SUNSHIELD NOT SHOWN)
RING (TYP.)
3/8" ALUMINUM
PLATE WITH 3/8"
U-BOLTS SIZED
FOR EQUIP.
FLOW
TERMINATION OF SHIELDED
INSTRUMENT
& CONTROL CABLE
N.T.S.
MOUNTING
SIDE
FRONT
FIELD SURGE
SUPPRESSION,
DISCONNECT,
CONTROL
AC
NEUT.
GROUND
L
O
A
D
REQUIRED
CAST IRON
TRAFFIC COVER
18"
9.5"
TYPE "TA" CADWELD
CONNECTION
GROUND
FIELD WIRING
PROVIDED BY
ELECTRICAL
CONTRACTOR.
ETHERNET ETHERNET
TO
TO
PLC INSTRUMENT
UNDERGROUND
CONDUIT INSTALLATION
N.T.S.
NOTE:
ALL MOUNTING HARDWARE TO BE
STAINLESS STEEL. USE WASHERS
AND SPLIT LOCK-WASHERS
UNDER ALL NUTS.
ETHERNET
INSTRUMENT SURGE SUPRESSION
N.T.S.
PLC CABINET
COPPER
GROUND
CABLE
13.5"
22"
OLD CASTLE
CONCRETE
BOX SERIES MB37
GROUND CABLE CONNECTION
N.T.S.
2-WIRE FIELD TRANSMITTERS
2 CU. FT.
CRUSHED ROCK
SCH 40
ALUM.
CONCRETE SUPPORT
PAD TYPICAL
STEEL GRD. ROD, THREE SECTION
ROD CADWELDED TOGETHER.
SCH 80
PVC
20'-0" LONG
TYPICAL GROUND ROD
INSTALLATION
DETAIL
N.T.S.
RKS
Consulting
Engineers
Electrical, Instrumentation & Control Design
HOLE MONTES
15400 Shamrock Dr. Fort Myers, Fl. 33912
P.E.
NO.
DATE
MOV WITH INTEGRAL CONTROL
INSTALLATION DETAIL
(TYPICAL ALL GROUND RODS)
TYPICAL
GROUNDROD CONNECTION
N.T.S.
Certificate of Authorization #8212
DRAWING SYMBOL
REVISIONS
BY
ENGINEERS PLANNERS SURVEYORS
LANDSCAPE ARCHITECTS
N.T.S.
950 Encore Way
Naples, FL. 34110
Phone: (239) 254-2000
Florida Certificate of
Authorization No.1772
DESIGN BY:
T.M.P.
DRAWN BY:
T.M.P.
CHECKED BY:
T.M.P.
CAD FILE:
E8.dwg
120 V.
POWER DISTRIBUTION
STAINLESS STEEL
CHANNEL
24" X 24" X 10"
5/8" DIA X 20' COPPER ENCASED
(5/8"x10') EACH.
FROM INSTRUMENT CASE TO
GROUND ROD & NEAREST
GROUND GRID. TYPICAL.
WIRE TO GROUND ROD &
GROUND GRID. TYPICAL
COUNTERPOISE
NO. 605 COPPER
COUNTERPOISE
NO. 94-10S SECTIONAL
COPPER CLAD GROUND
ANALOG
FIELD
INSTRUMENTS
#2 SOLID TINNED GROUND WIRE
#2 SOLID TINNED GROUND
2' MAXIMUM.
4-20 MA
#2/0 TINNED COPPER
6"
NO. 203-G5 GROUND
ROD COUPLING
INSTRUMENT CABLE.
TWISTED SHIELDED 4-20 MA
SEAL TIGHT CONDUIT
CADWELD TO TOP OF
ROD.
18"
CADWELD MOLD GTC-168C
WITH CARTRIDGE #150
LIGHTNING/SURGE SUPPRESSOR
4-20MA SUPPRESSOR
LOCATED NEXT TO THE
INSTRUMENT
TO
PLC
M.O.V.
36X36X12"D REINFORCED
TYPICAL DEVICE MOUNTING DETAIL
N.T.S.
12"
NOTE: PROVIDE
CONCRETE SLAB IN
AREAS WITHOUT SUITABLE
STRUCTURE FOR
MOUNTING PEDESTAL.
120V
120V
TO
TO
INSTRUMENT CP
GROUND CABLE
SHIELD AT THIS
END ONLY
K:\CCUD IQ Telemetry\Priority 2\E8.dwg Plotted: Nov 14, 2011 - 9:55am by tracy
BASE PLATE
AS DETAILED
FLOOR OR
PLATFORM
GND.
ALLEN BRADLEY
RJ45 TO M12
BULKHEAD ADAPTER
MARKED "GROUND"
SAND BACKFILL
PE #62427
AND FLOOR FLANGE
6" MIN
SCHEDULE 80 PVC
TRACY PROKOPETZ
48" FOR CONTROL STATIONS
GROUNDING OF MAGNETIC FLOW ELEMENT WITH
INTEGRAL
TRANSMITTER.
N.T.S.
SIZE AS
HSP121BT-1RU
LCDP
ALLEN BRADLEY
PATCHCORD
WITH INDUSTRIAL
GRADE RJ45
CONNECTORS
INTERNAL WIRING
PROVIDED BY
PANEL SUPPLIER
#2 CU SOLID TINNED
TO COUNTERPOISE
30" MIN;
36"FOR SERVICE CONDUCTORS
15 AMPS MAX
EDCO
L
I
N
E
12" MIN
EQUIPMENT.
EDCO
CONNECTION TO
BE MADE BY
EXOTHERMIC
WELD.
2" ALUMINUM PIPE
CL
DEVICE OR
ELECTRICAL
#2 CU SOLID
TINNED
METALLIZED WARNING TAPE
ENTIRE LENGTH OF CONDUIT.
PANEL, WIRING
GROUND
RING
#2 CU SOLID
TINNED
FINISHED GRADE
BASE
PLATE DETAIL
N.T.S.
AC
GROUND LEAD
NOTE: SHIELD
GROUNDED AT
TERMINATION
12"
NEUT.
SHRINK TUBING
PROVIDE ETHERNET
SURGE SUPPRESSION
AS DETAILED ON
INSTRUMENT SURGE
SUPRESSION DETAIL.
GROUND
CEMENT GROUT (TYP)
PLAN
120 VAC
SIGNAL LEADS
LUG. TYPICAL
1/2" CINCH ANCHOR
BOLTS AND NUTS
SHIELD
SHRINK TUBING
ALUMINUM BASE PLATE
1 1/2"
(TYP)
COVER THIS
PORTION WITH
SHRINK
TUBING
2" ALUMINUM PIPE
OR 6" CHANNEL
1/2" PLATE
60" FOR TRANSMITTERS, ETC.
COVER THIS
PORTION WITH
SHRINK
TUBING
AC POWER AND
ETHERNET SURGE
SUPPRESSORS
(LOCATED NEXT TO
THE INSTRUMENT)
120 V.A.C.
ETHERNET
FIELD
INSTRUMENTS
PLC CABINET
TO
PLC
INSTRUMENT CABLE. CAT 5e
M12 TWISTED UNSHIELDED.
SURGE SUPPRESSOR
#2 SOLID TINNED GROUND WIRE
CAT 5e M12 PATCHCORD
FROM INSTRUMENT CASE TO
GROUND ROD & NEAREST GROUND
GRID. TYPICAL.
ETHERNET FIELD TRANSMITTERS
INSTRUMENTATION
GROUNDING & SURGE PROTECTION
N.T.S.
COUNTY WATER-SEWER DISTRICT
COLLIER COUNTY, FLORIDA
ELECTRICAL DETAILS
PROJECT NO. :
2011.027
DATE :
11/11
SHEET NO. :
E8
VARIES
PROPOSED VALVE
CONTROL PANEL
PROPOSED VALVE
CONTROL PANEL
2" SCH40 GALVANIZED
STEEL PIPE END CAP
PCTEL MAXRAD UNITY
GAIN OMNI MODEL 4500
NEMA 4X SS SERVICE
ENTRANCE RATED
ENCLOSED BREAKER
OR EQUAL.
6" X 6" X 10' MINIMUM
NEMA 4X SS SERVICE
ENTRANCE RATED
ENCLOSED BREAKER
PRECAST CONCRETE POST
M
STAINLESS STEEL U-STRUT
CHANNEL SUPPORT.
INSTALL WITH STAINLESS
STEEL HARDWIRE LENGTH
IT
6' MIN.
AS REQUIRED BY
EQUIPMENT
BAND-IT S.S. TIE
SS
WRAPS 18" O.C.
MAIN SERVICE
SURGE SUPPRESS.
PVC SLEEVE
AROUND CONDUIT
FOR PROTECTION
SQUARE D XR
SERIES, 80KA.
2" SCH40
STEEL PIPE
(TYPICAL)
#2 SOLID
TINNED.
FINISH GRADE
HEAVY DUTY PC TEL
MMK12 MOUNTING BRACKET
FPL APPROVED
METER SOCKET
COAX CABLE
LMR-400-DB
FINISH GRADE
COAX CABLE
SERVICE LOOP
10'-0"
FPL APPROVED
METER SOCKET
CONTRACTOR TO MOUNT FIBER INTERFACE BOX
PROVIDED BY COLLIER COUNTY IT. COORDINATE
BOX LOCATION AND FIBER CONDUIT ROUTING
WITH COUNTY PM AND IT TO AVOID CONFLICT
WITH THIS PROJECT. FIBER OPTIC CONDUTI AND
CABLE INSTALLATION BY OTHERS.
CONTRACTOR TO MOUNT FIBER
INTERFACE BOX PROVIDED BY
COLLIER COUNTY IT. COORDINATE
BOX LOCATION AND FIBER CONDUIT
ROUTING WITH COUNTY PM AND IT TO
AVOID CONFLICT WITH THIS PROJECT.
FIBER OPTIC CONDUIT AND CABLE
INSTALLATION BY OTHERS.
HEATSHRINK COAX
CONNECTION HERE
4' MIN.
CONCRETE
3000 PSI
UNDISTURBED SOIL
G
SIDE
VIEW
N.T.S.
TYPICAL SCH .80 PVC
CONDUIT TO CONTROL
PANEL
5/8"DIA. X 20'
COPPERWELD GND. ROD
PIPING ASSEMBLY
COUNTERPOISE
SYSTEM.
CONTRACTOR TO MOUNT FIBER
INTERFACE BOX PROVIDED BY
COLLIER COUNTY IT. COORDINATE BOX
LOCATION AND FIBER CONDUIT ROUTING
WITH COUNTY PM AND IT TO AVOID
CONFLICT WITH THIS PROJECT. FIBER
OPTIC CONDUIT AND CABLE INSTALLATION
BY OTHERS.
FRONT
VIEW
N.T.S.
2' SQ. CONCRETE BASE
BACK
VIEW
N.T.S.
MINIMUM PROVIDE AS
DESIGNED FOR WIND
LOADING DETAILED
BELOW
GROUND LEVEL
SERVICE ENTRANCE
RATED ENCLOSED
CIRCUIT BREAKER
DETAIL
#2 TOWER TOP DETAIL
N.T.S.
20' X 5/8" COPPER
GROUND ROD IN
HANDHOLE. SEE
GROUNDING PLAN.
6"
FPL APPROVED
METER SOCKET
VALVE CONTROL PANEL
TO CONTROL PANEL
M
3'0"
1" PVC CONDUIT
STREAMER RETARDING
AIR TERMINAL
STREAMER RETARDING
AIR TERMINAL
PLAN
VIEW
N.T.S.
6"
TYPICAL EQUIPMENT RACK DETAIL
HEAVY DUTY 2-BOLT
LOCKABLE COVER WITH
FINISHED GRADE
"ELECTRIC" ENGRAVED
LETTERS
WITH 1" STRAIN
RELIEF ON TOP
OF STUBBED
CONDUIT FOR
COAX CABLE
GROUND CLAMP
#2/0 STRANDED
TINNED COPPER
GROUND WIRE
10"
REFER TO INDIVIUAL SITES
FOR REQUIRED EQUIPMENT
N.T.S.
1" CONDUIT
MOUNTED IN
FRONT OF
TOWER LEG
AS SHOWN IN
CONDUIT DETAIL
TOP OF
CONCRETE
TOWER
HEIGHT-
SITE
AFG
VETERANS PARK
10'
CAD WELD
BELOW GRADE
TO NEAREST
GROUND ROD
ANTENNA
UNITY GAIN OMNI
GROUND ROD REF.
BONDED TO CONTROL
PANEL GROUND GRID
NOTE: PROVIDE
36X36X12"D REINFORCED
CONCRETE SLAB IN
AREAS WITHOUT SUITABLE
STRUCTURE FOR
MOUNTING PEDESTAL.
PULLBOX SHALL BE
RTU
ANTENNA DETAIL
N.T.S.
QUAZITE COMPOSOLITE
NON-CONCRETE OR
APPROVED EQUAL
PROVIDE 6" DEPTH OF
2" ALUMINUM PIPE
48"
SEPARATE SIGNAL
AND POWER CONDUIT
TO INSTRUMENT TRANSMITTER
K:\CCUD IQ Telemetry\Priority 2\E9.dwg Plotted: Nov 14, 2011 - 3:16pm by tracy
SHOWN ON DRAWINGS;
MINIMUM SIZE 20"L X 14"W
X 12"D
PEA GRAVEL FOR
DRAINAGE.
POWER AND SIGNAL SURGE
SUPPRESSION. AS DETAILED
RUBBER GASKET AROUND NIPPLES
EXISTING SLAC UNIT ENCLOSURE
DETAIL
#1 GROUNDING DETAIL
N.T.S.
COMPOSOLITE PULLBOX WITH
OPEN BOTTOM SIZE AS
SURGE SUPPRESSOR EQUAL
TO EDCO TYPE SS-65
SERIES CLOSE NIPPLE
DIRECT TO TRANSMITTER.
1000
HANDHOLE/PULLBOX DETAIL
12"X12"X1/4" ALUMINUM
PRESSURE INDICATING
TRANSMITTER
N.T.S.
PLATE U-BOLT TO PIPE
FLEX CONDUIT TYPICAL
1/2" FLUID FILLED FLOW THROUGH
S.S. U-STRUT SUPPORTS TYP.
PRESSURE SEAL, 100% CIRCUMFERENTIAL
120V POWER CONDUIT
SENSING WITH PORT DIAMETER EQUAL TO
CONCRETE
FOUNDATION
REF.
ETHERNET SIGNAL CONDUIT
#6 INSULATED BOND WIRE
PRESSURE TRANSMITTER CONNECTION,
RED VALVE TYPE 42 PRESSURE SENSOR,
316 SS, BUNA-N SLEEVE.
1/2" SS
WHERE EXPOSED; BARE IF
EMBEDDED; FROM/TO ALL
UNION
CONTROL PANELS AND
INSTRUMENTS AND TO 20'
TOWER
REF.
GROUND RODS OR PERIMETER
GROUND SYSTEM.
24"MIN.
CONCRETE FLOOR
1/2" SS QUARTER
TURN BALL VALVE.
FROM PIPE
SADDLE
N.O.
LIGHTNING MASTER MODEL
1/2" SS QUARTER
PP-32M OR EQUAL STREAMER
RETARDING TERMINAL
1.5"
TURN BALL VALVE
WITH THD PLUG
FOR FLUSHING
AND CALIBRATION.
N.C.
5/8"X 20' DRIVEN
COPPERCLAD ROD
WEST ELEVATION
1" PVC CONDUIT OFFSET
NORTH ELEVATION
FROM FRONT OF TOWER
INSTRUMENT ELECTRICAL INSTALLATION DETAIL
N.T.S.
FLAT ROOF AIR TERMINAL
N.T.S.
RKS
Consulting
Engineers
Electrical, Instrumentation & Control Design
HOLE MONTES
15400 Shamrock Dr. Fort Myers, Fl. 33912
TRACY PROKOPETZ
PE #62427
P.E.
Certificate of Authorization #8212
NO.
DATE
REVISIONS
BY
ENGINEERS PLANNERS SURVEYORS
LANDSCAPE ARCHITECTS
950 Encore Way
Naples, FL. 34110
Phone: (239) 254-2000
Florida Certificate of
Authorization No.1772
CONDUIT
DETAIL TOP VIEW
N.T.S.
DESIGN BY:
T.M.P.
DRAWN BY:
T.M.P.
CHECKED BY:
T.M.P.
CAD FILE:
E9.dwg
PRESSURE TRANSMITTER INSTALLATION
DETAIL (TYP.)
COUNTY WATER-SEWER DISTRICT
COLLIER COUNTY, FLORIDA
RTU ANTENNA &
ELECTRICAL DETAILS
PROJECT NO. :
2011.027
DATE :
11/11
SHEET NO. :
E9