XGB-INV IG5A (RS-485 Modbus RTU) Sample program The communication between IG5A and built-in XGB Cnet through ch2 (RS-485). Reception ( D100, 1word ) XGB Sample Program Transmission ( M000, M001 2 words ) IG5A Setting : DRV=3(RS-485), FRQ=7(RS-485), I59=0(Modbus RTU), I60=1(station no.), I61=4(19,200bps), I65=0(Parity:None, Stop Bit:1) Eg) XGB (D1000 or M000 1 Word data) -> address no. 5 of iG5A inverter (Frequency reference ) XGB (M001 1 Word data) -> address no. 6 of iG5A inverter (Run command ) 1/ 2 XGB-INV IG5A (RS-485 Modbus RTU) Sample program XG-PD Parameter setting ① Please set “Channel 2 of Active mode” to “Use P2P settings” in using XG-PD of XG5000. ② You have to set P2P Channel to “Modbus RTU client. ③ P2P Block setting 2/ 2