OM-5-2014 Published February 2014 OPERATIONAL MANUAL for the CERTIFICATION of AIR HANDLING UNITS OM-5-2014 Published February 2014 Supersedes OM-5-2012 (Dec. 2012) Editing (date): Checking (date): Approval (date): Sylvain Courtey Jean Fourcroy Compliance Committee for AHU CPPC 21 October 2013 16 October 2013 8 November 2013 25 February 2014 1 March 2014 Comes into effect from: Modifications as against last version: . No. 1 2 3 4 5 6 7 Modifications Editorial changes following the merge between Eurovent Certification Company and Certita Deadline for real units delivery is set at 6 months after selection during the qualification test campaign; Cases of force Majeure are described. Consistency check of HRS has been updated according to Decision 6 of the Compliance Committee meeting held on 22 March 2013. Insulation material (wool vs foam): density out of - 25%, conductivity out of + 15% Failure treatment for model box test is added. In case the real unit cannot reach the lowest class defined in the relevant standard (see RS 6/C/005) the participant is suspended until a re-design of the model box is done and a re-test is successfully performed. 8 The list of major and minor non-conformities is listed in 0. 9 Mandatory information to be found on printouts has been added 10 The diploma number shall be displayed on the label 11 12 Handling of several ranges Explanations on construction variations of AHU Model Boxes have been added. Section Page All document IV.6 9 IV.4 7 IV.5 8 Table 1 IV.12.b 10 12-13 IV.12.b 13 IV.15 13 31 16 0. APPENDIX A APPENDIX B.II.2 0. APPENDIX F This document is strictly reserved for use in the Eurovent Certified Performance Programmes. Reproduction or translation of any part of the document is forbidden without written permission from Eurovent Certita Certification. Published by Eurovent Certita Certification SAS 53 rue de Turbigo 75003 Paris, FRANCE Tel: + 33 1 49 96 69 80 Fax: + 33 1 49 96 45 10 E-mail: [email protected] AHU, OM-5-2014 Published February 2014 Page 2 of 36 19 31 35 TABLE OF CONTENTS I. II. III. PURPOSE _______________________________________________________________ 5 SCOPE __________________________________________________________________ 5 BASIC OUTLINE OF THE PROGRAMME ______________________________________ 5 III.1 III.2 III.3 III.4 IV. Preapplication ......................................................................................................................................5 Qualifying procedure ...........................................................................................................................5 Repetition procedure ...........................................................................................................................5 Failure treatment .................................................................................................................................6 OPERATION OF THE PROGRAMME __________________________________________ 6 IV.1 Declaration of data ..............................................................................................................................6 a. b. c. Rated performance data ................................................................................................................................... 6 Certification forms ............................................................................................................................................. 6 Modifications to the range ................................................................................................................................. 6 IV.2 IV.3 IV.4 IV.5 Preapplication procedure ....................................................................................................................7 Software ..............................................................................................................................................7 Factory visits........................................................................................................................................7 Consistency check of heat recovery ...................................................................................................8 a. b. c. Manufacturer uses Eurovent certified heat recovery systems (HRS)................................................................ 8 Manufacturer does not use Eurovent certified HRS .......................................................................................... 8 For certified and non-certified rotors ................................................................................................................. 9 IV.6 IV.7 IV.8 IV.9 IV.10 IV.11 Qualifying campaign ............................................................................................................................9 Repetition campaign ............................................................................................................................9 Ranges to be taken out of production ...............................................................................................10 Selection of units for tests .................................................................................................................10 Ranges produced in several production places ................................................................................11 Procedures at the laboratory .............................................................................................................11 a. b. c. General ........................................................................................................................................................... 11 Test conditions................................................................................................................................................ 11 Test report and tests results ........................................................................................................................... 12 IV.12 Failure treatment ...............................................................................................................................12 a. b. c. d. e. f. Component failure .......................................................................................................................................... 12 Unit failure on a real unit ................................................................................................................................. 12 No class reached during RU tests .................................................................................................................. 12 Unit failure on a Model Box ............................................................................................................................. 13 Failure in case of multiple production places .................................................................................................. 13 Irregularities in production places ................................................................................................................... 13 IV.13 Special complaint procedure .............................................................................................................13 IV.14 Brand Name ......................................................................................................................................13 IV.15 Non-respect of procedures ................................................................................................................14 V. PROMOTION OF THE PROGRAMME ________________________________________ 14 V.1 V.2 By Eurovent Certita Certification .......................................................................................................14 By the Participant ..............................................................................................................................14 a. b. On printouts .................................................................................................................................................... 14 On units .......................................................................................................................................................... 15 APPENDIX A. APPENDIX B. 18 B.I. B.II. SELECTION SOFTWARE MANDATORY REQUIREMENTS ______________ 16 EUROVENT CERTIFIED PERFORMANCE MARK AND ENERGY EFFICIENCY LABEL Eurovent Certified Performance mark ...............................................................................................18 Eurovent Certified Performance energy efficiency label ...................................................................19 B.II.1. For units (eventually on printouts)................................................................................................................... 19 B.II.2. For printouts.................................................................................................................................................... 19 APPENDIX C. C.I. C.II. CERTIFICATION SCHEDULE______________________________________ 20 Application and test schedule............................................................................................................20 Checking of software schedule .........................................................................................................22 AHU, OM-5-2014 Published February 2014 Page 3 of 36 APPENDIX D. D.I. FORMS _______________________________________________________ 23 Submittal for certification by Manufacturer ........................................................................................23 D.I.1. Form AHU-1A: Data list of certified models & sizes ........................................................................................ 23 D.I.2. Form AHU-1B: Data list of certified model boxes, or casing constructions ..................................................... 23 D.II. Submittal for certification by Brand Name .........................................................................................23 D.II.1. D.II.2. Form AHU-2A: Data list of certified models & sizes (BN) ........................................................................... 23 Form AHU-2B: Data list of certified model boxes, or casing constructions (BN) ........................................ 23 D.III. Technical forms .................................................................................................................................24 D.III.1. Form AHU-3A: Technical specification related to tested real unit ......................................................... 24 D.IV. Test result forms ................................................................................................................................28 D.IV.1. D.IV.2. D.IV.3. APPENDIX E. Form AHU-4A: Evaluation of mechanical, thermal and acoustical tests ................................................ 28 Form AHU-4B: Recalculation after Real Unit Test ................................................................................ 28 Form AHU-4C: Software Update Record Sheet .................................................................................... 30 MAJOR / MINOR NON COMPLIANCES ______________________________ 31 E.I. Handling of several ranges................................................................................................................31 E.II. Major Non-Compliances (2 Points) ...................................................................................................32 E.III. Minor Non-Compliances (0 Points) ...................................................................................................34 APPENDIX F. F.I. F.II. F.III. F.IV. CONSTRUCTION VARIATIONS OF AHU MODEL BOXES_______________ 35 Corner post (corner and frame) .........................................................................................................35 Mullion ...............................................................................................................................................35 Filter construction ..............................................................................................................................36 Panel shape.......................................................................................................................................36 AHU, OM-5-2014 Published February 2014 Page 4 of 36 I. PURPOSE The purpose of this manual is to prescribe procedures for the operation of the Eurovent Certified Performance Programme for Air Handling Units, in accordance with the Eurovent Certified Performance Certification Manual. II. SCOPE This programme applies to selected ranges of Air Handling Units. Each range shall at least present one size with a rated air volume flow below 7 m 3/s. All Real Unit sizes in the range up to the maximum stated air flow shall be declared. All Model Box configurations shall be declared. Ranges without at least one size with a rated air volume flow below 7 m 3/s (25 000 m3/h) are excluded. III. BASIC OUTLINE OF THE PROGRAMME III.1 Preapplication Before the licence agreement is signed between the company and Eurovent Certita Certification, the preapplication procedure shall be completed. The company shall first submit to Eurovent Certita Certification name of the range and complete list of names and versions of the corresponding selection tools (selection softwares) for verification by an auditor appointed by Eurovent Certita Certification. If the software fulfils all preliminary requirements, the company shall submit to Eurovent Certita Certification the complete list of factories where the range is produced for verification by an auditor appointed by Eurovent Certita Certification. If the software and the factory fulfil all the preliminary requirements, the company is entitled to sign the Licence Agreement. III.2 Qualifying procedure After signing the Licence Agreement, the Applicant shall submit to Eurovent Certita Certification the declaration list with all Real Unit (RU) sizes and Model Box (MB) configurations with all the required characteristics and performance data as required by the Rating Standard, RS 6/C/005. The following number of units per factory producing the range (except the case of “sister factories”, see IV.10) are then required for test in an independent laboratory selected by Eurovent Certita Certification: The minimum number of Model Boxes to cover all worst configurations of the mechanical, thermal and acoustical performance. If several ranges use the same construction, the corresponding unit will be tested only once. One complete Air Handing Unit, being one size from the range, for all performance. The Real Unit is selected during the factory visit by the auditor appointed by Eurovent Certita Certification. For units above the stated air flow rate of 7 m3/s, the software shall be checked for consistency. If the tests show conformity with the relevant Rating Standard and consistency is verified, certification is granted until next annual on-site checking of software. III.3 Repetition procedure For mechanical, thermal and acoustical testing, Model Boxes shall be tested every six years for ISO-certified factories, every three years otherwise. For performance testing, a Real Unit from recent regular production shall be tested, every three years for ISO-certified factories, AHU, OM-5-2014 Published February 2014 Page 5 of 36 every year otherwise. If several factories produce exactly the same range with the same components, suppliers and methods, one unit is sufficient instead of one per factory. In addition, annual onsite checking of software shall be carried out every year. When the repetition procedure is passed certification is renewed for another campaign. III.4 Failure treatment When a unit fails to comply with the requirements of the relevant Rating Standard, failure treatment shall be applied. IV. OPERATION OF THE PROGRAMME IV.1 Declaration of data Each manufacturer shall nominate one contact person who will deal with all certification matters, plus eventually one by factory. a. Rated performance data All characteristics shall be expressed in SI Units. b. Certification forms Submittal of certification of models shall be completed and sent to Eurovent Certita Certification as .xlsx files. Copies of these forms are part of this manual (see APPENDIX D). Original Equipment Manufacturer (OEM): Form AHU-1A for Real Units and Form AHU-1B for Model Boxes will be used. Brand Name: For models submitted by a company presenting on the market units, under its own brand, manufactured by a certified company, forms AHU-2A and AHU-2B will be used to identify the corresponding model number of the OEM. Technical forms: For models selected for test, Forms AHU-3A and AHU-3B have to be completed with technical description of all components along with characteristics and performance data. Evaluation of test result: For models tested, Forms AHU-4A is added to the test report and AHU-4B is sent by Eurovent Certita Certification, showing the deviations between claimed and measured data. c. Modifications to the range The Participant shall inform Eurovent Certita Certification and the auditor of any modification to the range and/or software, using Form AHU-5. A new software version without impact on performance does not have to be sent. If new components (fans, coils etc) are implemented in standard production, manufacturer shall inform Eurovent Certita Certification and provide new software to the auditor. For next test new components shall be selected. Non compliance is considered as a non-respect of procedures (see IV.14). Anytime, Eurovent Certita Certification has the right to perform extra checking of software. Eurovent Certita Certification decides whether the modification is significant for the certified performance data or not. In the case of significant modifications Eurovent Certita Certification is entitled to demand adequate tests to verify the influence on performance data. This test shall not be considered as a repetition one. AHU, OM-5-2014 Published February 2014 Page 6 of 36 IV.2 Preapplication procedure During the preapplication procedure, the auditor appointed by Eurovent Certita Certification shall first verify that the software fulfils minimum requirements (no certification shall be accepted without appropriate selection software). If yes, he shall visit the factory, verify that AHUs are really manufactured there and selected with the software, and send a report of his visit to Eurovent Certita Certification. If the report shows that rules are not followed the Licence Agreement shall not be signed. IV.3 Software An English version of the software selection is necessary. Each quotation of a certified AHU shall include the date/code/number of the software version used for the selection of the unit. From the version code-key it shall be possible to check what the latest technical software version is by splitting up the code in more characters. An example of a suitable code is given below: Version: XY / Z characters indicating a version serial number, not affecting the selection results characters to indicate the technical version serial number The participant is obliged to send the most recent technical software version to Eurovent Certita Certification. The selection software shall be operative as an entity with all unit components integrated in one software. Components in an AHU that are selected with different software or any other means of selection cannot be certified. The units of the applied range shall be built with components specified in the selection software. If some components not present in the certified software performing a certified performance item (see VI.2 of Rating Standard) are included in the technical specification of a particular order, the following statement shall be provided in the quotation: “This component is not included in the software Eurovent certified”. This statement is not required for components serving for non-certified performance items (see list on VI.2 of RS 6/C/005). At least four sections must be included: fan, filter, heating and cooling. When a heat recovery section is available, it shall be declared and included in the selected unit for test for certification. Consistency of the software shall be verified by the auditor appointed by Eurovent Certita Certification. In case inconsistency of the software is observed, failure treatment shall be applied. Anytime, Eurovent Certita Certification has the right to collect data directly from customer and perform extra checking of software. IV.4 Factory visits Before each visit the auditor appointed by Eurovent Certita Certification shall collect and study the construction details and claimed performance of the relevant AHU range in order to make a proper selection of suitable unit(s) for testing. Anytime, Eurovent Certita Certification has the right to ask an auditor to conduct a surprise visit to participants’ factory as well as to collect data directly from customer and perform extra checking of software. During selection visits, a factory tour shall be made by the auditor, accompanied by manufacturer’s technical expert. A random selection of at least one unit under construction or just built, shall be made. The selected unit shall be suitable for testing. If no unit suitable for AHU, OM-5-2014 Published February 2014 Page 7 of 36 testing is under construction or just built, a random selection from files of recently delivered units shall be made. The entire composition and technical specifications of the selected units shall then be checked onsite. Manufacturer’s technical expert shall fully inform the auditor by submitting all relevant assembly drawings, specifications and technical data sheets of the selected units. Agreement shall be reached between manufacturer and the auditor on final selection of Real Unit for testing. During annual on-site checking of software, the same procedure shall be applied, without selection of unit for testing so without the restrictions for measuring facilities. This implies that any size may be selected. The expected performance shall be recalculated based on components reselected with the software provided to Eurovent Certita Certification. The composition and technical specifications and performance from recalculation shall be the same as the one specified and announced to the customer. If in the meantime the Participant has officially launched a new software version and recalculation is made with this version, deviations should be traceable in the software update record sheet (see D.IV.2). Deviations on performance above tolerances can lead to additional test (see IV.1c). If it appears that different software had been used, this shall be considered as a non-respect of procedures (see Certification Manual). In addition, mechanical construction (all the parameters) of one production unit shall be verified by the auditor, to compare certified characteristics of production with the tested Model Box(es). If it appears that different construction had been used, additional Model Box test shall be required by the auditor. Finally, consistency of heat recovery shall be verified by the auditor. At least one unit shall be verified with the methodology detailed in the following paragraph. In case of force majeure (e.g. accidents, labour disputes, natural events, acts of war) which would not allow Eurovent Certita Certification to perform a factory visit Eurovent Certita Certification can decide to replace it by another mean of verification, to postpone it within a reasonable deadline or to cancel it. The Compliance Committee will be made informed regarding these cases. IV.5 Consistency check of heat recovery a. Manufacturer uses Eurovent certified heat recovery systems (HRS) Compare the efficiency and pressure drop data in the AHU quotation or software with results obtained from the current stand-alone certified software from the HRS supplier. AHU manufacturer can never claim higher efficiencies and/or lower pressure drops than the values received from the stand-alone software. If possible one quotation with a rotor and one quotation with a plate heat exchangers have to be checked. b. Manufacturer does not use Eurovent certified HRS Additional testing of non-certified HRS are requested in the laboratory of the regular certification campaign, of the different models, one every year. Repetition would only be necessary in case of change of the structure of the HRS. When a HRS is tested in the RU one year, this additional testing is not necessary for that year. Compare the efficiency and pressure drop data in the AHU quotation or software with results obtained from the test result. Deviation shall be equal or lower than the acceptable tolerance defined in the certification programme for the HRS. In case a RU is tested every year, this additional testing is not necessary. AHU, OM-5-2014 Published February 2014 Page 8 of 36 c. For certified and non-certified rotors Observations of rotor arrangements in the AHUs shall be made during the annual factory inspection. If it appears that (sometimes) parts of the actual heat exchanger surface of the rotor are blanked / obstructed it shall be verified in manufacturer’s software if this unfavourable assembly has been considered. The software shall predict (small) reduction in efficiency and (substantial) pressure drop increase, compared to a selection with completely open rotor surface. IV.6 Qualifying campaign For a company (“Brand name”) presenting on the market units, under its own brand, manufactured by a certified company, only on-site checking of software shall be conducted at the place (“office”) where the orders to the customers can be accessed. This place is often the factory of the certified manufacturer. For manufacturers, Real Units taken from the production line shall be selected by the auditor appointed by Eurovent Certita Certification during a factory visit, using the selection software. Models Boxes will be directly selected by Eurovent Certita Certification from the declaration list, to cover all worst configurations of the mechanical, thermal and acoustical performance (see Table 1). Selected units shall be sent to the independent laboratory within maximum 6 months. If this deadline is not fulfilled another on-site checking with selection shall be scheduled within maximum one year from the previous on-site checking. Units are then tested and the obtained performances compared with the values calculated using the software. The test on the Real Unit of a range can be carried out after the test results on the Model Box(es) is/are available. Assembly places of flat-package units shall be considered exactly the same way as manufacturing places. When a manufacturer presents several manufacturing places, each place shall be considered independently. If all the test results are within the tolerances and calculation model appears consistent, Eurovent Certita Certification shall grant the certification. If not, failure treatment shall be applied. When certified, the range is published on the Eurovent Certified Performance website with an agreement number, associated characteristics and performance, name and version of the last software verified by Eurovent Certita Certification, and production places. The participant is then entitled to use the certification mark for this range in literature and on products (see V.2). It shall be obvious for which products the certification is granted (see also APPENDIX B and Certification Manual). IV.7 Repetition campaign For a company (“Brand name”) presenting on the market units, under its own brand, manufactured by a certified company, only on-site checking of software shall be conducted annually at the place (“office”) where the orders to the customers can be accessed. For manufacturers, Participant’s quality control shall be appropriate to maintain the performance within the tolerances. A quality system according to ISO 9001 (covering the production quality systems) is acknowledged by a reduction in the frequency of repetition tests. The manufacturer shall then annually provide a valid ISO 9001 certificate to Eurovent Certita Certification. In addition, annual on-site checking shall be performed in each Participant’s factory(ies). Assembly places of flat-package units shall be considered exactly the same way as manufacturing places. AHU, OM-5-2014 Published February 2014 Page 9 of 36 For each certified range and factory, repetition tests in the independent laboratory selected by Eurovent Certita Certification shall be required: Every six years for mechanical, thermal and acoustical performance on Model Boxes for participants holding valid ISO 9001 (every three years otherwise) Every three years for performance on Real Unit for participants holding valid ISO 9001 (every year otherwise) Eurovent Certita Certification shall select the units for repetition using the same procedure as for selection of units for the qualification test. If possible, a RU size or MB configuration different from those previously tested shall be selected. If all the test results are within the tolerances and calculation model appears consistent, Eurovent Certita Certification shall maintain the certification for another period. If not, failure treatment shall be applied. IV.8 Ranges to be taken out of production Running a test on a unit from a range which is going to disappear from the market can represent a useless cost for the Participants. If a test is necessary on a unit from a range which is going to disappear from the market, the Participant may send an official letter to Eurovent Certita Certification stating that the range will disappear between the date of the scheduled test and the date + one year. The range remains then certified for maximum one year. If the Participant changes his mind or if it appears that the range is still available after that time, it is considered as a major breach of the rules, and the Participant will have to pay a penalty fee of 15 000 €. In addition, the unit will have to be tested and the following test will have to follow normal schedule. IV.9 Selection of units for tests Table 1: Table for selection of model boxes Construction variation Corner post Mullion Filter construction Panel shape Panel thickness Sheet metal thickness Insulation material (wool vs foam): - density out of - 25% - conductivity out of + 15% Way of insulation mounting (fixed vs loose) Metal sheet of panel (galvanized vs stainless steel) Casing strength x x Casing air leakage x x x the thinnest the thinnest x the thinnest x (density) Filter bypass Thermal leakage transmittance x x x x x x the thinnest the thickest - Thermal bridging x x Acoustic insulation x x x the thinnest the thickest x the thinnest the thinnest x x (conductivity) (conductivity) x x (density) x worst case: galvanized worst case: galvanized External finishing (galvanized vs coated) Hinge and /or latch Regarding Model Boxes, Eurovent Certita Certification shall select the minimum number of units to cover the construction variations available on the software and catalogue under the declared range names. All variations (marked by a X) and worst cases are mandatory to be tested according to the Table 1 above, and worst case performances can be transferred from the tested MB to other constructions. To claim better class on one performance data, another MB with the construction parameter variation has to be tested too. AHU, OM-5-2014 Published February 2014 Page 10 of 36 Selection of one Real Unit suitable for testing shall be made during selection visits as described above (see IV.4). Size of the units, air volume performance, heating and cooling capacity, shall be within the limits of the measuring facilities of the laboratory. An up-scaled or down-scaled unit can be selected if no suitable size is available. In case no unit with heat recovery or cooling/heating coils can be provided by the factory, these components and the associated performance shall be non-certified. Because it is a significant parameter for the energy efficiency classification, in case the software proposes heat recovery, then the selected unit shall include heat recovery. Unit for test shall be supplied to the laboratory within six weeks for factories in Europe and within eight weeks for factories outside Europe (see APPENDIX C). When the manufacturer does not meet the time limits for the supply of units this will be considered as a non-respect of procedures. The manufacturer shall inform the laboratory (preferably before the test) if he wants the unit to be scrapped after the test results are available. IV.10 Ranges produced in several production places When a manufacturer presents several production places, each place will be considered independently so each factory has to be visited every year by the auditor appointed by Eurovent Certita Certification (selection or annual on-site checking). Assembly places of flatpackage units shall be considered exactly the same way as manufacturing places. Regarding the selection of units to be tested, the production places for an identical product – identical software, identical components (designation) and suppliers, same casing (same drawings and materials), same assembly procedures and ISO 9001 – have to be considered as one collective production place. In that case each time a different production location will be randomly chosen for the selection of the unit to be tested. The different production places are thus called “sister production places”. During the annual on-site checking (see IV.4), if there is any suspicion that the production place cannot ensure the same performances as its sister production places, then the auditor may ask that a Real Unit and/or Model Box be tested. IV.11 Procedures at the laboratory a. General Only the independent laboratory personnel shall be permitted to handle test units. The manufacturer's installation and handling instructions shall be followed. The laboratory shall be responsible for uncrating, handling, testing and recrating the unit for shipment. The laboratory personnel shall make repairs to the test unit only in agreement with the manufacturer. No manufacturer's personnel shall be present in the test facility during the test. b. Test conditions The units shall be tested at the conditions as stated in the relevant Rating Standard. Thermal tests will be performed at 2 conditions in the heating mode and 2 conditions in the cooling mode (one condition at manufacturer’s rated design and one condition selected by Eurovent Certita Certification within the scope of the selection software). Independent laboratory shall test units at the conditions as close as possible to the selected rating conditions. Aerodynamic tests (air flow - pressure - power input) shall be performed in accordance with the test standard ISO 5801, in an operating range of +/-5% around the selected rating point. AHU, OM-5-2014 Published February 2014 Page 11 of 36 Testing for heat recovery shall be carried out with at least 20 K difference, under dry conditions (supply air temperature should not be below +5°C). c. Test report and tests results For each unit, upon completion of all the measurements, the laboratory will render a test report (pdf) to Eurovent Certita Certification with tested data compared to original selection data. If at least one performance measurement is out of the tolerances, the auditor shall conduct a “test check”, i.e. the selection software will be used to recalculate the performance at conditions used for test: test data will be compared to recalculation data. Eurovent Certita Certification will transmit a copy of the report together with results of test check (Forms AHU-4, see APPENDIX D). Manufacturer has to collect its products one month after receiving the test report. After this delay, the laboratory will destroy the units if not collected and the manufacturer will be invoiced through Eurovent Certita Certification. If the results are out of the allowable tolerance, or the calculation model appears inconsistent, failure treatment shall be applied. IV.12 Failure treatment For each test, a performance item fails when the difference between the declared value and the measurement differs by more than the allowable tolerance (see relevant Rating Standard). A test fails when one or more performance(s) fail. In case of failure, Eurovent Certita Certification shall promptly notify the Participant. a. Component failure The manufacturer shall be authorised to examine the reasons of the failure. In case of a component failure the unit may be repaired or replaced by a new one of the same model within 4 weeks, which shall be tested then, according to normal schedule of the laboratory. b. Unit failure on a real unit If the failure is established after the recalculation, the manufacturer shall rerate his data by adapting the software to the test results within 6 weeks (see APPENDIX C). If the software is then in accordance with all measurements, certification is granted or maintained with the re-rated data. After reverification (“test recheck”), if the software is still not in accordance with the test results, manufacturer will have two additional weeks for final adjustment of the software (see APPENDIX C). In case of new failure, no adjustment of software will be accepted and manufacturer has to restart the test procedure. c. No class reached during RU tests In case of failure on RU tests not reaching any Filter By-pass Leakage (FBL) class, it is considered as Component failure (immediate stop of the test) and complete retest is mandatory. In case retest is failed, manufacturer is excluded from the programme for 1 year. In case of failure on RU tests not reaching any Casing Air Leakage (CAL) class, it is considered as Component failure (immediate stop of the test) and complete retest is mandatory. In case retest is failed, manufacturer is excluded from the programme for 1 year. AHU, OM-5-2014 Published February 2014 Page 12 of 36 d. Unit failure on a Model Box Manufacturer has four weeks after notification of failure to select one of the following alternatives: Accept measured values. (Uprate is allowed.) Ask for a second test on the same unit. In this case, the Manufacturer can choose to re-test only the performances which are not accepted Ask for a second test on another unit of the same model selected by Eurovent Certita Certification. The delivery shall be done within 8 weeks from the date of the test report. In this case, all measurements are to be re-tested. e. Failure in case of multiple production places When a range is tested for different production places, if one repetition test fails, all production places will have to re-rate their data and the software shall be re-rated according to the worst test results for each performance item. f. Irregularities in production places Irregularities found in a factory can be a reason for retesting or suspension of certification of the factory or the complete range. In case several factories produce the same range, if one factory is suspended, the Participant has one year to align it. After this delay, if the factory is still not in accordance with the requirements, the complete range is suspended from certification for one year. IV.13 Special complaint procedure The general complaint procedure is described in Certification Manual. In addition, if a Participant obtains doubtful data from a competitor quotation he may present a complaint request. The Participant who complains will pay 1000 € as fee. Eurovent Certita Certification auditor will examine complaint within 6 weeks and complaint data will be also used during annual on-site checking. If checking results show that the obtained data are different – meaning that other software had been used or quotation data manipulated – this is considered as a non-respect of procedures (see Certification Manual). The 1000 € fee will then be sent back to the plaintiff and it will be invoiced to the Participant who failed. IV.14 Brand Name This covers the case of models submitted by a company presenting on the market units, under its own brand, manufactured by a certified company. When Company A doesn’t produce his own range but distributes under its own brand ranges already certified by Participant B, no additional test is required for A. Nevertheless, A has to declare to Eurovent Certita Certification a place (“office”) where the orders to the customers can be accessed to and the software can be annually verified by an Eurovent Certita Certification auditor, during the same quarter as the verification of software hold by B. A’s office is often B’s factory. If a range or a production place of B doesn’t fulfil the requirements and B’s certificate is suspended and/or expelled from the programme, A is also automatically suspended. If B quits certification, A is offered the possibility to cover test expenses for B’s products. The Brand of the A company must be shown on the output. A is fully responsible of his software and any non compliance may have a consequence on A certification, even if B is the software provider. AHU, OM-5-2014 Published February 2014 Page 13 of 36 IV.15 Non-respect of procedures The general consequences of non-respect of procedures are described in Certification Manual. In complement applied penalties can be: A certified range and/or production place is withdrawn from the Eurovent Certified Performance website for one year. Any minor non-conformity identified during an on-site checking will be escalated to major if not solved prior or during the next follow-up audit. At the end of the first penalty year and after a second checking, if failure occurs again, the certified range and/or production place is withdrawn from the Eurovent Certified Performance website for three years. The level of penalties and the list of major and minor non-conformities are listed in 0. V. PROMOTION OF THE PROGRAMME V.1 By Eurovent Certita Certification The following information shall be published for each certified range on the Eurovent Certified Performance website www.eurovent-certification.com: Name of Company Trade or brand name Agreement number (format: YY.MM.NNN) Designation(s) of the range Software name and version List of certified characteristics and performance items Designation of certified sizes of the real units Heights and widths of the real units Designation of certified model boxes The certified mechanical, thermal and acoustical performance data of the model boxes: casing strength (deflection) identified with a “(M)”, casing air leakage at -400 Pa and +700 Pa identified with a “(M)”, filter bypass leakage identified with a “(M)”, thermal transmittance, thermal bridging factor and sound level at different frequencies Production sites (city, country) V.2 By the Participant The design of the Eurovent Certified Performance mark for Air Handling Units, letter size and style are presented in APPENDIX B. Display of Eurovent Certied Performance mark on literature is detailed in Eurovent Certified Performance Certification Manual, paragraph VI.2. The design and specifications of the energy efficiency label are given in APPENDIX B. a. On printouts Participants are obliged to display the Eurovent energy efficiency class on the printouts of certified ranges by the means of class on first page (statement, small or large label). If possible the graphical energy efficiency label shall be displayed. Otherwise statement shall be: “Eurovent energy efficiency class X”. The following shall be applied: AHU, OM-5-2014 Published February 2014 Page 14 of 36 motor out only Standard plate and rotary heat exchangers, as well as standard fans and motors shall be evident in the software and label is mandatory (first column). In case of a special project and a heat recovery component is not included in the AHU software but Eurovent certified or covered by IV.5a or IV.5b Erreur ! Source du renvoi introuvable.(second column), or if the motor is out only (third column), label is mandatory. In case of special projects and if displaying the energy label is not allowed (third column), the following statement shall be written instead: “Heat recovery component and/or fan selection beyond certified software does not comply with the Eurovent Certified Performance rules for label designation.” b. On units Each Participant is entitled to display the Eurovent Certified Performance mark on units of ranges which have been certified: By using the relevant Eurovent Certified Performance mark By application of the relevant Eurovent Certified Performance mark directly on the nameplate By using the relevant Eurovent Certified Performance energy efficiency label if applicable. In case the Participant has chosen to display the Eurovent Certified Performance Energy Efficiency label on units, each unit shall be marked, even the one with class <E. AHU, OM-5-2014 Published February 2014 Page 15 of 36 APPENDIX A. SELECTION SOFTWARE MANDATORY REQUIREMENTS The auditor assigned by Eurovent Certita Certification shall receive a software program, on a CD-Rom or a website with remote access. Other access facilities are only possible in consultation with Eurovent Certita Certification and the auditor. The primary language of the software including outputs must be in English. The software must be able to calculate operating points between the upper and lower operating condition without changing any components (for example): The operating point of fan (nominal air flow = 100 %) have to calculate by +5 %, +2.5 %, -2.5 % and -5 % of nominal air flow. The fan speed must be constant. The external pressure will be variable. The software has to calculate the power input (in kW) at the electric terminal of the motor / FU-controller. The software must have the possibility to calculate the heating capacity with the selected heating coil between the upper and lower operating condition. It must be possible to change the air flow rate, the water flow rate, the air inlet temperature. The software must show and print out the results. The software must give a warning, in case that the result data run out of limits. The software must have the possibility to calculate the cooling capacity with the selected cooling coil between the upper and lower operating condition. It must be possible to change the air flow rate, the water flow rate, the air inlet temperature, the air inlet humidity. The software must show and print out the results. The software must give a warning, in case the result data run out of limits. The software must have the possibility to calculate the heat recovery capacity with the selected heat recovery system between the upper and lower operating condition. It must be possible to change the air flow rate, the supply air inlet temperature and humidity, the exhaust air inlet temperature and humidity. The software must show and print out the results. The software must give a warning, in case the result data run out of limits. The selection software must have the following Mandatory requirements including Input data & Output data. General Requirements: Printouts should be provided as a minimum pdf file. There must be only one Eurovent certified software version. All components must be described by product key or relevant information (manufacturer name and reference). Calculations must all be at a minimum in SI units. The software must show a sketch of the AHU Software able to store & restore the selection details without alterations of the calculation. General: all data which are asked for in D.IV.2 “Form AHU-4B: Recalculation after Real Unit Test” must be given from the selection software. Mandatory Input Data: Reference nomenclature of unit i.e ABC 40. Upper & lower Summer & Winter operating conditions (outdoor air temp & humidity). Air flow rate & external pressure. Heating coil water inlet temp, water flow rate or water outlet temp & supply air temp behind the heater coil. Cooling coil water inlet temp, water flow rate or water outlet temp & outlet air temp & relative humidity and supply air temp and humidity behind the cooler. Selected filter section (filter class). Selected fan section (fan type, motor type). Selected inlet & outlet sections. Selected heat recovery system with all necessary inputs (Rotary, Plate HX & Run around coils.) Mandatory information to be found on printouts: General information: On the first page: AHU, OM-5-2014 Published February 2014 Page 16 of 36 o o o o o o Project name Customer Quote/Order no. Unit range Unit designation Eurovent Energy efficiency class. Preferably the graphical energy efficiency label shall be displayed. Otherwise the statement: “Eurovent energy efficiency class X”, must be announced. o If the graphical energy efficiency label is not used the Eurovent Certified Performance mark shall be displayed o If it is not allowed to display the Eurovent Certified Performance mark or energy class/label, a statement shall be written instead, e.g. “Heat recovery component- and/or fan selection beyond certified software do not comply with Eurovent Certified performance rules for label designation”. On each page (including the first page): o Software name, version code and version date o printout date o page numbering with total number of pages (e.g. page x of y) Statement “This component is not included in the software Eurovent certified”, if a component, serving a certified performance, cannot be selected within the certified software. This statement is not required for non certified components that are not included in the software (e.g. filters, attenuators, humidifiers, etc.). Unit sketches with overall dimensions must be available on selection printouts. Technical data: The technical specification of a quoted AHU shall include all technical data required to verify the claimed energy efficiency class: General Velocity in the cross section of the filter section (or of the fan cross section if no filter) Octave bands (dB) Outlet and Inlet in-duct sound power(dBA) and Airbourne Sound Power(dBA) Air Density if set at 1.2kg/m3 then no need to be on printout, otherwise actual density must be provided on selection output. Design winter outdoor temperature for the selected unit, specified as a separate item or mentioned as design inlet temperature for the first thermal component (heat recovery component or heating coil) Mixing ratio (RCA/SUP) at design winter outdoor temperature (maximum value 85%) External static pressure for the supply and extract unit (where applicable) Basic unit construction (same as model box), it is not necessary to include leakage class & deflection on the selection / quotation output. Internal static pressure drop across the components in the AHU. This requirement shall be fulfilled in one of the following ways: o the air side pressure drop across each component is specified in the technical specification (mandatory method unless unit configuration does not permit this practice) o the sum of these pressure drops is specified as total internal static pressure drop across components (pressure drop across filters, HRS and designed (dry or wet) cooling coil shall always be specified individually); o the external static pressure, static fan pressure and fan system effect for the design duty point is specified. The useful fan static pressure increase to calculate the fan reference power can be derived from all three data sets. Fans Fan speed in rpm Absorbed electrical power from the mains for each fan in the AHU, including the power losses in any motor speed controller. If no fan speed controller is quoted, but the fan needs such a device to operate AHU, OM-5-2014 Published February 2014 Page 17 of 36 on the design fan speed, the power loss of such device shall be included in the specified absorbed power. Filters Filter type and class Pressure drops: clean, design and final conditions Heat recovery system (HRS) Dry temperature efficiency (no condensation on extract side) of the HRS for design winter operation at equal mass flows (extract flow equal to design supply flow) Air side pressure drop across the heat recovery system on the extract side and supply side for the design air flows at winter condition and standard density 1.2 kg/m3. Brine concentration in fluid of run around coil system (where applicable) Coils Statement if air side pressure drop cooling coil is for dry (“dry pressure drop”) or wet (“wet pressure drop”) condition or statement if fan has been designed for dry or wet condition. Heating coil: air side Inlet/Outlet temperatures, airside pressure drop, water flow, & waterside Inlet/Outlet temperatures & pressure drop. Cooling coil: airside Inlet/Outlet temperatures, inlet/Outlet relative humidity, airside pressure drops (designed: wet or dry, both can be provided, however dry shall be always visible in the software), waterside flow rate and Inlet/Outlet temperatures and pressure drop. APPENDIX B. EUROVENT CERTIFIED PERFORMANCE MARK AND ENERGY EFFICIENCY LABEL B.I. Eurovent Certified Performance mark See relevant specifications in Certification Manual. In addition, the mark shall also include the name of the certified range and the Agreement number provided by Eurovent Certita Certification when certification is granted. Figure 1: Eurovent Certified Performance mark specifications and Eurovent Certified Performance mark for Air handling units AHU, OM-5-2014 Published February 2014 Page 18 of 36 B.II. Eurovent Certified Performance energy efficiency label Rules for the use of Eurovent Certified Performance energy label are given in the Certification Manual. It is not mandatory to use Eurovent Certified Performance energy labels however it is highly recommended to do so. If an energy label is used by the participant it is mandatory to use the layout described on our website. High resolution files of these labels, as well as specifications for the layout are available on the website in the manufacturer’s restricted area. http://www.euroventcertification.com/en/Documentation/_ECC_mark_and_Energy_efficiency_labels.php?rub=09&srub=07&ssrub=&lg=en B.II.1. For units (eventually on printouts) Figure 2: Examples for Eurovent Certified Performance Energy Efficiency Label – for units B.II.2. For printouts The label shall be at least 40 mm wide and 40 mm high. The diploma number shall be displayed on the label. Conditions of use: can only be used in printed/web document: if the product shown is certified if no other product is shown if all certified performance of the product are displayed next to the label. Files can be found on the restricted part of the Eurovent Certified Performance website http://www.euroventcertification.com/en/Documentation/_ECC_mark_and_Energy_efficiency_labels.php?rub=09&srub=07&ssrub=&lg=e n Figure 3: Eurovent Certified Performance Energy Efficiency Label – for printouts AHU, OM-5-2014 Published February 2014 Page 19 of 36 APPENDIX C. CERTIFICATION SCHEDULE C.I. Application and test schedule The process lasts an average of about 8½ months, including the preliminary steps (see Table 2 and Figure 4). About 7 months are necessary for repetition tests (pre-checking is not included). Table 2: Minimum, maximum and average time needed for certification of a range Certification Step How many weeks does it take? min max Average week number The auditor appointed by Eurovent Certita Certification contacts the manufacturer. Manufacturer sends software to auditor. The auditor pre-checks the software. When software does not meet the certification requirements, the manufacturer has to correct it and send a new version. When the software meets the certification requirements, the manufacturer makes an appointment with the auditor to visit the factory. Waiting for the visit date. The auditor visits manufacturer’s factory, checks sale data and selects one unit for testing. The auditor sends the visit report and technical form completed for the selected unit to Eurovent Certita Certification. The manufacturer must up-date his list of products and then to send it to Eurovent Certita Certification (Forms AHU-1A and 1B). Eurovent Certita Certification has to send the manufacturer the visit report and the quotation according to the technical form of the selected real unit(s). When necessary, Eurovent Certita Certification has also to send the quotation for the model box(es). The manufacturer has to send the order/payment(s) to Eurovent Certita Certification. The unit(s) has(have) then to be delivered to the independent laboratory(ies) (2 to 6 weeks for Europe, 4 to 8 weeks for outside of Europe). Waiting for the availability of the test rig. The unit(s) is/are tested at the laboratory(ies). The auditor checks that the software is in accordance with the test results. The laboratory has to send the test report and the checking report to Eurovent Certita Certification. Eurovent Certita Certification has to send the report (comments included) to the manufacturer. If the software is in accordance with the test results, the certification is granted for the next period. In case the software is not in accordance with the test results, the manufacturer has to send the software revised according to the test results to the auditor. The auditor has to check the revised software and send Eurovent Certita Certification a new, revised report. Eurovent Certita Certification has to check this report and send it to the manufacturer. If the software is in accordance with the test results, the certification is granted for the next period. In case the software is still not in accordance with the test results, the manufacturer may correct again and send back to the auditor for rechecking. The auditor has to check the software and send a new report to Eurovent Certita Certification. If the software is in accordance with the test results, the certification is granted for the next period. In case the software is still not in accordance with the test results the selection process has to start again from the beginning and the manufacturer’s data are withdrawn from Eurovent Certified Performance Website until the certification is granted (min. one year after the first certification step). TOTAL number of weeks necessary 1 1 1 4 1 3.5 1 2 5 1 4 7.5 1 2 9 1 3 11 2 8 16 0 1 5 2 18.5 20 1 2 21.5 0 2 22.5 2 6 26.5 1 2 28 0 2 29 2 4 32 1 2 33.5 0 1 34 16 52 34 AHU, OM-5-2014 Published February 2014 Page 20 of 36 APLLICATION PROCEDURE: PRE-CHECKING Figure 4: Planning for application procedure and testing of units 1st contact Send software 1 week 1.5 weeks Software failure Checking of software Send revised software 6 weeks NO Softwar e ok ? YES 3.5 weeks Appointment Licence agreement Factory visit QUALIFYING OR REPETITION PROCEDURE: TESTING OF UNITS 4 weeks 1.5 weeks 2 weeks 5 weeks 4 weeks 0.5 week Failure treatment: 4 weeks 1 week Factory ok? YES Visit report Sign licence agreement Report of selection of real unit Up-date of lists Quotation for real unit Quotation for model box Purchase order Purchase order Delivery Delivery Testing and test report Testing and test report Checking Send revised software 3 weeks 1.5 weeks 1.5 weeks Checking report NO Softwar e ok? YES 0.5 weeks EUROVENT C. certificate ISO 9001? NO: every year YES: every 3 years AHU, OM-5-2014 Published February 2014 Page 21 of 36 C.II. Checking of software schedule The process lasts an average of about 3½ months (see Table 3 and Figure 5). Table 3: Schedule for annual onsite checking – Minimum, maximum and average time needed for certification of a new AHU range Certification Step How many weeks does it take? min max Average week number 1 1 1 1 2 2.5 1 4 5 Eurovent Certita Certification informs the manufacturer about the need for a visit of the factory. The manufacturer has to give to the auditor an appointment for visit of the factory. Waiting for the visit date. The auditor has to visit manufacturer’s factory and check sale data. The auditor sends the visit report to Eurovent Certita Certification. Eurovent Certita Certification has to send the report including its comments to the manufacturer. If the onsite software version is in accordance with the certified software version kept by the technical auditor and the last test results, the certification is granted for the next period. In case the software is not in accordance with the test results, the manufacturer has to send the revised software according to the test results to the auditor. The auditor has to finalize the recheck of the software and send back to Eurovent Certita Certification a new report. If the software is in accordance with the test results, the certification is granted for the next period. In case the software is still not in accordance with the test results it is considered as violation of rules. REPETITION PROCEDURE: CHECKING TOTAL number of weeks necessary 1.5 weeks Appointment 4 weeks Factory visit 0.5 weeks Failure treatment: 1.5 weeks 6.5 0 2 7.5 2 4 10.5 1 2 13 0 1 13.5 7 18 13.5 Send revised software Checking report Sofwar e ok? YES 2 weeks 2 Checking 3 weeks 1 week 1 NO EUROVENT C. certificate Figure 5: Planning for on-site checking of software AHU, OM-5-2014 Published February 2014 Page 22 of 36 APPENDIX D. FORMS D.I. Submittal for certification by Manufacturer Information to be provided by Manufacturer (except gray cells) D.I.1. n° PA id Form AHU-1A: Data list of certified models & sizes Trade name Range Agree ment Sub Range Model name Height Catalo Software gue Width Perf Lib Certified The “Perf Lib” column should be filled in with: “heating only”/”reversible”/”cooling only” and “with heat recovery”/”without heat recovery”. D.I.2. Form AHU-1B: Data list of certified model boxes, or casing constructions n° PA id Trade name Range Model box tests (followed by “(M)”) Casing Air Casing Air Filter Casing Leakage Leakage Bypass Strength 400 Pa 700 Pa Leakage Insertion 125 Insertion 250 Insertion 500 Panel shape Panel thickness Sheet metal thickness Agreement Casing name Real Unit tests (followed by “(R)” Casing Air Casing Air Filter Casing Leakage Leakage Bypass Thermal Bridge Thermal Transmittance Strength 400 Pa 700 Pa Leakage Insertion 1000 Insertion 2000 Insertion 4000 Insertion 8000 Corner post Mullion Insulation material Insulation material density Insulation material conductivity Way of insulation mounting Metal sheet of panel Certified Filter construction D.II. Submittal for certification by Brand Name Information to be provided by the Brand Name (except gray cells) D.II.1. Form AHU-2A: Data list of certified models & sizes (BN) OEM id n° PA Trade Name Range Brand name Sub Range Model Height Width id n° PA Trade Name Range Sub Range Model Software Catalogue D.II.2. Form AHU-2B: Data list of certified model boxes, or casing constructions (BN) OEM id n° PA Trade Name Range Brand name Casing Name id n° PA Trade Name Range Casing Name AHU, OM-5-2014 Published February 2014 Page 23 of 36 D.III. Technical forms D.III.1. Form AHU-3A: Technical specification related to tested real unit INFORMATION RELATING TO TESTED UNIT and CERTIFIED VALUES APPLICANT DESIGNATION Software version Manufacturing place PERFORMANCE Nominal applied value Meas.1 Meas.2 0 0 a - Air flow Total fan pressure External pressure Filter pressure drop Fan speed Power input 1) 1) 0 0 Pa Values transposed to 0 Pa 20°C ; 101325 Pa ; 1,2 kg/m3 0 0 0 0 0 0 0 0 2) of the clean filter kW 63 Total rpm at the terminal of the motor / frequency converter b - Octave band OUTLET in-duct sound power, supply air only Conditions: Fan speed: 0 rpm - Ext. pressure: 0 dBA (air flow measurements have to be +/-5% around nominal point) m3/h Pa 0 2) Meas.3 Meas.4 Meas.5 125 Pa - Air flow: 250 500 1000 0 m³/h at 0 °C 2000 4000 8000 Hz no value dB c - Octave band INLET in-duct sound power, supply air only Conditions: Fan speed: 0 rpm - Ext. pressure: 0 dBA 63 Total 125 Pa - Air flow: 250 500 1000 0 m³/h at 0 °C 2000 4000 8000 Hz no value dB d - Airborne sound power, supply air only Conditions: Fan speed: 0 rpm - Ext. pressure: dBA 63 125 Total 0 250 Pa - Air flow: 500 1000 0 2000 m³/h at 4000 0 8000 no value e - Capacity of cooling coil dB 1st point 2nd point m3/h kg/h Supply air flow rate : 27 / °C 7 / °C Water flow rate : 47 / dm3/h % kW m3/h kg/h Supply air flow rate : (at 1,2 kg/m³) Supply air flow rate : 0 Mass air flow rate : Air in/out : Cold water in/out : Water flow rate : Humidity in/out : f - Capacity of heating coil °C Hz Supply air flow rate : ³ (at 1,2 kg/m ) Mass air flow rate : 0 m3/h kg/h Air in/out : / °C Cold water in/out : / °C / dm3/h % kW Mass air flow rate : Humidity in/out : m3/h kg/h Mass air flow rate : Air in/out : 10 / °C Air in/out : / °C Hot water in/out : Water flow rate : 60 / °C Hot water in/out : Water flow rate : / °C dm3/h kW dm3/h kW The test w ill be perform ed at the specified w ater flow rate and the specified air flow rate. The air flow rate w ill be adjusted before the test if the claim ed available pressure for this flow is not achieved during the aerodynam ic test. g - Heat recovery : category (in accordance with EN 308) winter conditions Temp. supply-air inlet °C supply-air outlet °C exhaust-air inlet °C exhaust-air outlet °C 0,0 m3/h kg/h 0,0 m3/h kg/h ratio #DIV/0! % h - Pressure loss on water side Cooling coil kPa kPa Heating coil kPa kPa AHU, OM-5-2014 Published February 2014 Page 24 of 36 DESIGNATION xxx xxx Software version xxx APPLICANT ADDITIONAL INFORMATION FAN Type Model Diameter / Number Manufacturer Speed belt pulley diameter belt pulley type Belt type Efficiency of belt drive Supply air circuit Motor Type Model Diameter / Number Manufacturer Nominal Voltage Nominal current Start current Efficiency of motor Speed belt pulley diameter Frequency converter Frequency (in / out) Efficiency of converter Supply air circuit FILTER Brand and type Filter class Initial pressure drop (clean filters) Final pressure drop (dirty filters) Design pressure drop Type of filterframe Number and size of filters Supply air circuit Type Manufacturer Fin Spacing / number per m Fin Thickness and type length(l) x height(H) x width(L) Number of Rows deep Number of circuits Tube Nominal OD Tube Wall Thickness Tube Pattern Tube innergrooved/smooth Inlet Connection Outlet Connection Internal Volume Air pressure drop (dry) qv1 & qv2 Air pressure drop (wet) qv1 & qv2 Type code of manufacturer Exhaust air circuit ------------------- rpm mm % rpm mm % Exhaust air circuit --------------------------- V A A % rpm mm Hz % Exhaust air circuit --------------- Pa Pa Pa COOLING COIL HEATING COIL mm Nb/m mm Nb/m mm type V A A % rpm mm Hz % Pa Pa Pa mm type mm mm mm mm mm mm dm3 Pa Pa Drop eliminator of cooling coil Air pressure drop at qv1 & qv2 yes / no Pa --- Pa Pa q v1 ; q v2 : air volume flow 1; 2 HEAT RECOVERY SYSTEM PLATE Manufacturer Reference Material Fin spacing Fin thickness Dimensions Pressure drop on air side sup./ ex. Drop eliminator of HR Air pressure drop at nominal point mm mm mm Pa yes / no Pa TOTAL UNIT Net weight kg Dimensions (overall) mm Dimensional drawing of unit and the coil circuiting shall be provided AHU, OM-5-2014 Published February 2014 Page 25 of 36 HEAT RECOVERY COILS COOLING COIL Type Manufacturer Designation Diameter / depth Fin Spacing / number per m Fin Thickness and type length(l)xheight(H)xwidth(L) Number of Rows deep Number of circuits Tube Nominal OD Tube Pattern Tube innergrooved/smooth Inlet Connection Outlet Connection Internal Volume Air pressure drop at nominal point HEATING COIL mm mm Nb/m mm type Drop eliminator of cooling coil Air pressure drop at nominal point mm mm Nb/m mm type mm mm mm mm mm mm mm mm dm3 Pa mm mm dm3 Pa yes / no Pa TOTAL UNIT Net weight HEAT Dimensions (overall) ROTARY Dimensional drawing of unit and the coil circuiting shall be provided Type Manufacturer Reference of the wheel Material Fin Spacing or Density mm type Fin Thickness and type / Pressure drop on air side sup. / ext. Diameter Depth Speed Power input Nominal voltage Frequency Drop eliminator of cooling coil Air pressure drop at nominal point kg mm RECOVERY SYSTEM mm Pa mm mm rpm W V Hz yes / no Pa TOTAL UNIT Net weight Dimensions (overall) Dimensional drawing of unit and the coil circuiting shall be provided kg mm Notes for the Test House 1 2 Physical checks shall made on the additional informations and result shown before performance test. Fin spacing - the number of fins shall be counted over three separate 100 mm sections of the coil face, the average figure shall then be divided by 100 and the reciprocal shown to 2 decimal places. Dimensional drawing and circuit diagram - this shall be checked against test unit. Fan type : Axial - Centrifugal - Tangential 3 Fin type : Flat - Corrugated - Louvered - Wavy action or reaction Date : AHU, OM-5-2014 Published February 2014 Page 26 of 36 INFORMATION RELATING TESTED UNIT and Form AHU-3B: TechnicalTO specifications related to CERTIFIED tested modelVALUES box MECHANICAL CARACTERISTICS MANUFACTURER: UP DATE: Eurovent test code/ Article number Serial Number Manufacturing place name email adress Contact for technical questions: Contact for pickup of model box: MODEL BOX 1 Range names using this casing: Designation of the panel: Max.admissible pressure: Pa Cover: Painted (Painted, corrosive treatment,....) Option: (Special joint, hygienic.....) Length of model box: mm Width of model box: mm Heigth of model box: mm thickness of side panel: mm thickness of bottom panel: mm thickness of roof panel: mm thickness of access doors: mm Insulation type: ( Rock wool, PU, mineral wool.....) specific volume of insulation: coefficient of heat conductivity of insulation: kg/m³ W/mK Sheet metal material: Galvanized Thickness of sheet metal (inside): Thickness of sheet metal (outside): mm mm Profile dimentions: a - Casing strength b - Casing air leakage c - Filter bypass leakage x mm Applied classes D1 - 400 Pa + 700 Pa L2 L2 (specified in EN1886) Maximum relative deflection: 4,00 mm/m F7 Maximum leakage rate: Maximum filter bypass leakage rate: d - Thermal transmittance T3 Thermal transmittance range: e - Thermal bridging factor TB3 - 400 Pa + 700 Pa 0,44 0,63 2,00 1<U<=1,4 l.s -1m-2 % W.m-2.K-1 0,45<=kb<0,60 125 250 500 1000 2000 4000 8000 f - Acoustical insulation AHU, OM-5-2014 Published February 2014 Page 27 of 36 D.IV. Test result formsEUROVENT CERTIFICATION PROGRAMME FOR D.IV.1. AIR HANDLING UNITS REPORTING OF TEST RESULT Evaluation of mechanical, MODEL BOX Form AHU-4A: thermal and acoustical tests Participant : Real unit designation : Model box designation : Eurovent article number: Eurovent test number: Software name and version : Laboratory TÜV SÜD GmbH APPLIED: MEASURED: Class (EN 1886) a - Casing strength Values Conclusion Class (EN 1886) CERTIFIED: Class (EN 1886) Maximum relative deflection [mm/m]: - 400 Pa b - Casing air leakage c - Filter bypass leakage Maximum leakage rate [l.s -1m-2]: Maximum filter bypass leakage rate [%]: d - Thermal transmittance Thermal transmittance range [W.m -2.K-:]: + 700 Pa - 400 Pa + 700 Pa - 400 Pa + 700 Pa 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz - 400 Pa + 700 Pa - 400 Pa + 700 Pa e - Thermal bridging factor APPLIED [dB]: MEASURED [dB]: f - Acoustical insulation Tolerance Conclusion: CERTIFIED [dB]: Signature: RECALCULATION AFTER REAL UNIT TEST Sandrine MARINHAS Certification Manager Date of D.IV.2. recalculation Participant Real unit designation Software Designation Version number Laboratory 2012-08-19 Participant AHU 12 AHU Selection Software 1.0.1 TNS Date: Form AHU-4B: Recalculation after Real Unit Test CAPACITY Applied 1st point Measured Cooling kW 49,30 44,70 Heating kW 53,98 52,50 Applied 2nd point Measured -9,3% 20,80 21,00 1,0% FAILED -2,7% 23,20 22,00 -5,2% FAILED Deviation Deviation Result Tolerance -2% Water-side pressure loss in kPa Applied Measured Water flow Press. loss Water flow Press. loss 3 kPa dm /h Cooling Heating 3 kPa dm /h Deviation #1 Deviation #2 Result 1st point 1870 2,7 1911 4,80 71,0% 2,0 2nd point 3580 8,7 3633 15,70 75,7% 6,8 FAILED 1st point 560 0,5 562 0,70 39,1% 0,2 PASSED 2nd point 1010 1,4 1011 2,00 42,6% 0,6 PASSED PASSED The pressure losses are compared with the following formulas #1 and #2: Deviation#1 {[( D p / q m 1,8 ) Measured / ( D p / q m 1,8 ) Applied ] - 1} Tolerance: 10% Deviation#2 {(Dp)Measured - (Dp / qm1,8)Applied * (qm1,8)Measured} Tolerance: 2.0k Pa HEAT RECOVERY Applied Supply air Exhaust air Measured In 5,1 5,1 Out 16,0 15,7 In 25,2 25,2 Out 14,4 13,8 54,23% 52,7% Ratio Air-side pressure loss in Pa Temperatures in °C Deviation 1,5% Result PASSED Applied Measured 96 111 300 320 Deviation #1 Deviation #2 Result 15,6% 15,0 PASSED 6,7% 20,0 PASSED Deviation#1 Tolerance : 10% Deviation#2 Tolerance: 15Pa Tolerance-3%-points SOUND POWER Conditions during acoustic test Fan speed: rpm 2305 Air flow: m³/h 5000 ESP: Pa 250 Octave Band In-duct OUTLET in dB 125 82 250 87 500 87 1000 84 2000 80 4000 75 8000 71 Hz Applied Measured 68 85 91 82 77 73 68 dB Deviation -14 PASSED -2 PASSED 4 FAILED -2 PASSED -3 PASSED -2 PASSED -3 PASSED dB Result dB Octave Band In-duct INTLET in dB 125 80 250 85 500 85 1000 82 2000 78 4000 73 8000 69 Hz Measured 75 89 80 85 80 70 70 dB Deviation -5 4 -5 3 2 -3 1 dB Applied dB AHU, OM-5-2014 Published February 2014 Page 28 of 36 Supply air Exhaust air Out 16,0 15,7 In 25,2 25,2 Out Ratio 14,4 13,8 54,23% 52,7% Deviation 1,5% Result PASSED 96 111 15,6% 15,0 PASSED 300 320 6,7% 20,0 PASSED Deviation#1 Tolerance : 10% Deviation#2 Tolerance: 15Pa Tolerance-3%-points SOUND POWER Conditions during acoustic test Fan speed: rpm 2305 Air flow: m³/h 5000 ESP: Pa 250 Octave Band In-duct OUTLET in dB 125 82 250 87 500 87 1000 84 2000 80 4000 75 8000 71 Hz Applied Measured 68 85 91 82 77 73 68 dB Deviation -14 PASSED -2 PASSED 4 FAILED -2 PASSED -3 PASSED -2 PASSED -3 PASSED dB Result dB Octave Band In-duct INTLET in dB 125 80 250 85 500 85 1000 82 2000 78 4000 73 8000 69 Hz Measured 75 89 80 85 80 70 70 dB Deviation Result -5 PASSED 4 FAILED -5 PASSED 3 PASSED 2 PASSED -3 PASSED 1 PASSED dB Applied dB AIRBORNE Sound Power - Total in dB(A) Applied Measured Deviation Tolerance Result 72 74 2 3 PASSED Air flow in m3 /h dB(A) External pressure in Pa (1) Applied Measured Applied Measured 4719 4850 4973 5093 5211 4719 4850 4973 5093 5211 365 520 360 515 360 (3) Power input in kW (2) Fan speed in rpm Deviation Results Applied Measured Deviation Results Applied Measured 321 -12,2% FAILED 2,140 3,200 49,5% FAILED 1661 1661 325 -9,9% FAILED 2,160 3,200 48,1% FAILED 1659 1659 589 394 9,4% PASSED 2,170 3,100 42,9% FAILED 1662 1662 310 469 334 7,7% PASSED 2,600 3,000 15,4% FAILED 1662 1662 295 431 314 6,3% PASSED 2,800 2,850 1,8% PASSED 1661 1661 Available Values listed above are related to nominal condition r =1,2 kg/m 3 (1) Allowable deviation : -4 % or -15 Pa (2) Allowable deviation : +3 % (3) To get the available external pressure, the measured one must be lowered by the unconsidered part of the design filter pressure drop for the nominal conditions and dry cooler during the air flow test. Correction for the ESP measured during air flow test All pressure drops in Pa Corrected design pressure drop of filter 360+(-34/2) Measured pressure drop of clean filter 148 Difference to be taken in consideration @ nominal point 100% 195 Applied Available (cooler dry) limit Air flow / PowerXinput Measured Y limit Applied (1) Allowable deviation : -4 % or -15 Pa 2,17 (1) Allowable deviation : -4 % or -152,2785 Pa #VALEUR! 2,2785 #VALEUR! 2,17 (1) Allowable deviation : -4 % or -15 Pa 2,17 3,40 3,20 Power input in kW External pressure in Pa X limit Y limit Air flow / Pressure (1) Allowable deviation : -4 0% or -15 Pa (1) Allowable 700 deviation : -4 0% or -15 Pa #VALEUR! 0 #VALEUR! 0 600 (1) Allowable deviation : -4 0% or -15 Pa 500 400 300 3,00 Measured 2,80 2,60 2,40 2,20 2,00 1,80 200 100 4600 1,60 4700 4800 4900 5000 5100 5200 1,40 4600 5300 4700 4800 4900 5000 5100 5200 5300 Air flow in m³/h Air flow in m³/h Recalculation after Test Calculation External Static Pressure (ESP) - Correction of filter pressure drop Date: 19/08/2012 Air Flow Points Air Flow Rate 95,0% 97,5% 100,0% 102,5% 105,0% Δpclean filter in Pa Δpdesign filter in Pa ESP in Pa m³/h measured applied Δpclean, mea-app applied corrected Δpcorr. design - clean 4719 4850 4973 5093 5211 160 155 148 165 162 171 184 182 185 193 -11 365 360 200 520 -29 360 346 191 515 -34 360 343 195 589 -20 310 300 135 469 -31 295 280 118 431 measured available 321 325 394 334 314 AHU, OM-5-2014 Published February 2014 Page 29 of 36 D.IV.3. Form AHU-4C: Software Update Record Sheet Company Logo XXXXX Software Name Software Update Record Sheet Prepared By: _____________________________ Software Revision Date Brief Description of update AHU, OM-5-2014 Published February 2014 Page 30 of 36 APPENDIX E. MAJOR / MINOR NON COMPLIANCES Each certified range shall be allocated of 15 audit points (after first delivery of certificate). Each major non-compliance related to the range (independently of the manufacturing place), shall remove 2 points to the account of the range. If a range reaches 0 point, Participant shall be notified for immediate suspension of the range for one year. A 24-months period without major non-conformity resets the account to the initial level. E.I. Handling of several ranges Does product 1 carry the ECP mark Does product 2 carry the ECP mark NO YES NO YES “Classic range” YES “Classic range” “Classic range” “Classic range” “Classic range” Name of the range of product 1, certified Name of the range of product 2 Are energy components basically the same Is mechanical construction the same ? “Super range” “Poor range” YES “Super range” “Poor range” “Classic range” “Classic range” Compliant with certification rules ? Cause NO YES 2 different ranges, different names, it is ok. YES NO YES 2 different ranges, different names, it is ok. YES YES NO NO Not at all YES YES NO NO “Classic range” Special product YES except certified plate or rotary HE YES YES YES YES “Classic range” Special product YES except non certified plate or rotary HE YES YES YES YES Marking is mandatory for AHU printouts, all printouts for units of the certified range shall be marked. Marking is mandatory for AHU printouts. Misleads the customer about the components. Marking and labelling are mandatory Misleads the customer about the components Marking is mandatory, but labelling is forbidden Misleads the customer about the components Marking is mandatory, “Classic range” Special product YES except fan “Classic range” Special product YES except motor YES “Classic range” YES NO YES YES NO Misleads the customer about the construction “Range for Exotic market” YES YES YES NO UNCLEAR Waiting for CPPC decision YES YES YES YES but labelling “Classic range” “Classic range” “Classic range” YES YES is forbidden YES Marking and labelling are mandatory AHU, OM-5-2014 Published February 2014 Page 31 of 36 E.II. Major Non-Compliances (2 Points) Ite Major Non Compliance = Non-compliance which involves direct impact on the units finished product performance , and may mis-lead the end user m OM-5, from the software output / product and marketing advertisment, or impacts on the completion of the 3A Technical Form for ECC Real Unit test selection. No. Page No. P14 Any minor non-conformity identified during an on-site checking will be escalated to major if not resolved prior or during the next follow-up audit (IV.15 OM-5) 1 3 P9/P18 4 5 6 P6/P13 Mis-use of ECC mark in portraying products / ranges to be certified when they are not, this also applies to branded products that have not been declared to ECC or tracability of the original ECC manufacturer has been removed, either software or unit (IV.14 - OM-5) Use of ECC mark: The participant is entitled to use the certification mark for the certified range in literature and on products, however it must be obvious for which products the certification is granted. See also guidance in Certification Manual. Declaration of Certified Brand without prior knowledge / approval from ECC HQ. P6/P16 Model Size in Certified range not already declared to ECC 7 P8 8 P11 2 P9/P14/P17 P11 Declaration of Certified MB values without prior knowledge / approval from ECC HQ If it appears that different MB construction has been used during the factory audit to that supplied for the MB certification charateristics, then this is deemed a failure and additional MB test shall be required. Several production places: During the annual on-site checking (see IV.4), if there is any suspicion that the production place cannot ensure the same performances as its 'sister' production places, then the auditor can issue a major non-compliances and ask for that a Real Unit and/or Model Box be tested. Software update record sheet not available for updated perfomance to existing components i.e DLL updates P7 9 P8 Software update record sheet must provide enough traceable information should differences exist during factory software checking 10 11 P5/P10/P11 Manufacturer not providng proof of ISO 9001 continuation after existing certification has lapsed. 12 P8/P9 13 14 15 16 P8 P8 P7/P9 Consistancy checks of Heat Recovery stand-alone ECC software or Real Unit component test to unit selection: NO unit selection software performance can be higher than that of the stand-alone ECC software or outside the tolerance of the independent Heat Recovery test report. Able to re-calculate the last Real Unit before removing the compoment from selection software, otherwise re-calculation can not be completed. If moving to new software platform between the period when the Real Unit was selected & re-calculation, the same unit (all components) must be selectable. During the factory audit if it appears that different software has been used, then this shall be considered as a non-respect of procedures (see certification manual) Calculated Eurovent Certified Performance energy class is lower than the claimed energy class If it is not allowed to display the energy class classification a statement shall be written e.g "Heat Recovery component -and/or fan selection beyond certified software do not comply 17 P15/P17 with Eurovent Certita Certification rules for Energy Class classification.," Refer to Table V.2 in OM-5 for heat recovery systems & fan / electrical motors for when the energy classification can be used. General Software Requirements 18 19 20 21 22 23 24 25 P20 P16 Printouts must be provided as a minimium pdf file. P16 There must be only one active Eurovent Certified AHU software version P16 If the software is able to export to other formats, then the key output selection requirements must exist eg. Software version, Project name etc… P16 All components must be described inside the software by a product key or relevant tracable information. P16 Software data charateristics shall be expressed in SI Units as a minimuim. P7/P16 The primary language of the software including outputs must be in English. P17 ECC energy efficiency Class i.e. 'A' must be on the first page (at least on one page) P16 Unit Sketches and overal dimensions must be available from software. 26 P16 Software must be able to calculate between the upper & lower operating conditions without changing components, software should provide user warning if selection not possible. 27 P16 Software able to store & restore the selection details without alterations of the calculation. AHU, OM-5-2014 Published February 2014 Page 32 of 36 Ite Major Non Compliance = Non-compliance which involves direct impact on the units finished product performance , and may mis-lead the end user m OM-5, from the software output / product and marketing advertisment, or impacts on the completion of the 3A Technical Form for ECC Real Unit test selection. No. Page No. Input / Selection Print Output Data 28 29 30 P16 Unit reference nomenclature to be present on selection output i.e. ABC 40 The product name must be same as that of the certified product listed on the ECC website. P16 Upper & Lower Summer & Winter operating conditions (outdoor air temperature & humidity) P16 31 P16 32 33 P7/P17 Air flow rate & external pressure Heating & Cooling coil water inlet temp's, water flow rate or water outlet temp's. Supply air temp behind heating coil & outlet air temp & relative humidity for cooling coil and supply air temp and humidity behind the cooler On the First Page: Project name / Customer / Quote No./ Unit designation & Project selection date must be at a minimium on the first page. 35 36 37 38 P17 All data to calculate the Energy efficiency Class must be available from the data selection sheet. P17 Velocity in cross-section of the filter section (or of the fan cros-section if no filter) P17 Octave bands to be in (dB) and Outlet/Inlet & Airbourne Sound Power (dBA) of the unit P17 39 P17 40 41 42 P17 If software not using standard 1.2kg/m3 air density, then actual air density must be provided on selection output Design Winter outdoor air temperature and % factor of recirculation air (if applicable) must be declared on the selection printout or mentioned as design inlet temperature for the first thermal component (heat recovery or heating component) External static pressure for the supply and extract unit (where applicable) P17 Basic unit construction(same as Model Box), it is not necessary to include leakage class & deflection on the selection /quotation output P18 43 P18 44 P18 Selected filter sections with filter type & class, pressure drops for Clean, Design & Dirty conditions (Energy class based on Design) Heat recovery system (HRS): Dry temperature efficiency (no condensation on extract side) of the HRS for the design winter operation @ equal mass flows (extract flow equsl to design supply flow) Brine concentration in fluif of run around coil system (where applicable) 45 P18 Coils: statement if airside pressure drop cooling coil is dry (dry pressure drop) or wet (wet pressure drop) condition or statement if fan has been designed for dry or wet condition 46 47 48 P18 Cooling Coil: Designed wet or dry, both can be provided, however dry shall be always visible in the software P18 Fan & motor type including fan and motor data i.e. RPM, Input Power Absorbed Power, must be declared on selection output. On Each Page: Software name, version code and version date, printout date, page numbering with total no. of pages (e.g. x of y) Statement: "This componenet is not included in the software certified by Eurovent Certification", if a component, serving a certified performance, cannot be selected within the certified 34 P7/P17 software. This statement is not required for non-certified components that are not included in the software (e.g Filters, Attenuators, Humidifiers, etc) Technical Selection Print Output Data 49 50 51 P17 Inverter power absorption not included in total active power absorbed of the unit when inverter is not fitted in factory but required to run unit Total static pressure values of actual unit configuration different to that declared on printout “Total internal static pressure + external static pressure (+possible system effect) but not P18 including Dynamic pressure”. P17/P18 All data to calculate the Energy efficiency Class must be available from the data selection sheet. P18 P33 Note: If unit called same for certified & non certified with different components (unit must have different range name!) The above list is not absolute and at the auditors discretion based on the definition of "major" non-compliance this will be included in the audit assessment Notes: Some of these items may have also been listed on the 'minor' non-compliance list, however they will be considered as a 'major' non-compliance should they not be resolved during the n+1 audit AHU, OM-5-2014 Published February 2014 Page 33 of 36 E.III. Minor Non-Compliances (0 Points) Ite m OM-5, No. Page No. P7 1 P19 2 P15 3 P17 4 Minor Non Compliance = which does not involve a direct impact on the units finished product performance, and does not mislead the end user from the Software output / product and marketing advertisment, or does not impact on the audit completion. Software update record sheet not provided to ECC HQ for additional component additions or other updates within Software excluding performance changes to certified scope Incorrect design of ECC Mark used on any documentation as detailed in the certification manual (VI.2), this also includes color of mark If the participant has chosen to fit the energy efficiency class to the units even the one with class <E must be fitted. Filter pressure drop is missing on software print out, however tracable in software audit check 5 P18 6 7 8 9 10 11 P18 If selection design is based on WET fan condition and the energy class is calculated correctly based on the WET pressure drop of the internal static pressure, but NO note can be found on Fan selection output designed for WET conditions. The middle-life filter pressure drop is not the average between clean and final filter pressure drop. EN13053 §6.9.2 P17 No Page numbering on selection outputs P17 Software name / Version and printout date displayed on each page of the selection output with page numbering. P17 Project name / Customer / Quote No./ Unit designation & Project selection date must be at a minimium on the first page. P17 If Energy Efficiency class is provided on selection output but not on the first page P17 Software version number required on DWG (not created by Software) to customer that includes selection output data. Note: The above list is not absolute and at the auditors discretion based on the definition of "minor" non-compliance this will be included in the audit assessment Notes: Some of these items may have also been listed on the 'major' non-compliance list, however they will be considered on the first occasion as a 'minor' non-compliance AHU, OM-5-2014 Published February 2014 Page 34 of 36 APPENDIX F. CONSTRUCTION VARIATIONS OF AHU MODEL BOXES F.I. Corner post (corner and frame) material: steal/aluminium/plastic shape (see pictures): thickness of the material with/without thermal break F.II. Mullion material: steal/aluminium/plastic shape (see pictures): thickness of the material with/without thermal break AHU, OM-5-2014 Published February 2014 Page 35 of 36 F.III.Filter construction fixed or laterally extractable position in the unit (fixed on mullion or on panel) kind of filter gasket ( flat/profiled) material/thickness of gasket fixing of gasket (glued/clamped/foamed) fixing of filter cell (with springs/screws/...) used sealing material (gasket/silicone/...) F.IV. Panel shape with/without thermal break design (see sketch) AHU, OM-5-2014 Published February 2014 Page 36 of 36
© Copyright 2024