TENDER NO:MGVCL/RAPDRP/SCADA/222A ITEM- A: TECHNICAL SPECIFICATION FOR OUTDOOR 11 KV RING MAIN UNIT SWITCHGEAR 1.1 GENERAL: 1.1.1 All equipment and material shall be designed accordance with the latest applicable IEC standard. 1.1.2 Equipment and material conforming to any other standard, which ensures equal or better quality, may be accepted. In such case copies of English version of the standard adopted shall be submitted. 1.1.3 The electrical installation shall meet the requirement of Indian Electricity Rules-1956 as amended up to date; relevant IS code of practice and Indian Electricity Act-1910. In addition other rules and regulations applicable to the work shall be followed. In case any discrepancy ,the most stringent and restrictive one shall be binding. 1.1.4 The high-tension switchgear offered shall in general comply with the latest issues including amendments of the following standards but not restricted to them. 1.2 SCOPE: manufactured and tested in Design, Engineering, Manufacture, assembly, Stage testing, inspection and testing before supply and delivery at site, Installation, testing & Commissioning of Ring Main units outdoor type SF6 filled , with various combinations of load break isolators & breakers. The scope includes Supply, Erection, testing and commissioning of outdoor type RMU with necessary take off terminal units for future automations contains load break isolators, breaker and associated accessories, equipments. (including earthing- Erection of earthing by using GI strip (minimum 35 mm strip) with earthing plate including cost of coal/salt to RMU).The Installation of 11KV Outdoor SF6 Insulated RMU covering erection, testing and commissioning with associated equipment excluding civil work,supply & laying of 11kv cable,cable jointing kit etc. of RMU. The permission of Electrical inspector for charging of RMUs is in utility scope. RMU fencing is not in the scope of bidder. Cable termination kits, cable laying is in utility scope. The RMUs should be provided with necessary take off terminal units for future automations and all these units should be shielded in a outdoor metal-body for making them suitable for outdoor use. The insulation/dielectric media inside the stainless steel welded tank should be SF6 gas. The RMUS should be Modular ,extensible type on both sides with provision of attaching/connecting with SNAP FIT arrangement W/o External Busbars additional load break switches and circuit breakers in future whenever required. However, RMU shall be extensible on both side however left side is occupied by metering panel and right side is free for extension on vice versa is also possible depending on site condition. Alternatively Extension shall be possible by adding trunking chambers and required accessories or by plug-in bushing type arrangement. The Package scope of work shall include survey, design, manufacture, FAT and delivery, installation and commissioning of new SCADA enabling equipments of new “SCADA-Ready” . 1|Pa ge TENDER NO:MGVCL/RAPDRP/SCADA/222A The RMU should have compatibility with MODBUS PROTOCOL SCADA system. The RMU shall provide DI/Dos for interfacing with FRTU. The protection relay shall have MODBUS protocol alongwith DOs. Ring Main Units capable of being monitored and controlled by the SCADA/DMS. Where relevant, the RMU scope of work shall be coordinated with the work to be carried out under the project’s other construction packages & associated materials to the designated destinations as per this tender specification and Bill of quantities. Includes supply of relevant 11KV cable termination kits per this tender Specification. Each RMU shall include its own power supply unit (including auxiliary power transformer, maintenance free batteries, and battery charger), which shall provide a stable power source for the RMU. The RMUs will be connected to the FRTU which will be procured, supplied and installed as a part of Part A of R-APDRP. The RMU shall be supplied with battery charger for charging of 24VDC 48 AH battery set for FRTU. FRTU, MODEM (Modem Size: 88lx60wx26mm depth), Power and I/O cable interface between FRTU and Control panel of RMU are excluded in the scope of supply and these items will be provided by DISCOM/SIA. Each new RMU shall be equipped with main-line load break switches and a fault passage indicator (FPI). Furthermore, to protect each of its lateral / transformer feeders, it shall be equipped with a corresponding set of circuit breakers and relay with auxiliary supply (24V DC) shall be provided. The RMU shall include potential-free contacts and control contacts so as to connect to SCADA/DMS via FRTUs, so as to: Monitor and control the open/closed status of the RMU circuit breakers and load break switches. Monitor the local/remote position of RMU motorised (in case if failure of motor) manually-operated switches that can be used to enable and disable remote monitoring. Monitor the health of the power supply, which will include battery failure and low voltage indications. Monitor the open/closed status of RMU earthing switches. Monitor the open/closed status of RMU enclosure doors in case of Hinge doors. Monitor for low SF6 gas pressure indication. Monitor for circuit breaker relay operations. Monitor for indication of main-circuit fault detected by the RMU’s FPI. Configurations Required:11KV RMU a) 2-Way , 11KV Gas (SF6) Insulated RMU with One 630A load break switches and One SF6 Insulated VCB of suitable rating b) 3-way , 11KV ,Gas (SF6) Insulated RMU with 2Nos 630A load break switch and 1No. SF6 insulated VCB of suitable rating c) 4-way ,11KV Gas (SF6) Insulated RMU with 2Nos 630A Load break switches and 2Nos , SF6 Insulated VCB of suitable rating – d) 5-way , 11KV ,Gas (SF6) Insulated RMU with 3Nos 630A load break switch and 2No. SF6 insulated VCB of suitable rating e) 6-way ,11KV Gas (SF6) Insulated RMU with 3Nos 630A Load break switches and 3Nos , SF6 Insulated VCB of suitable rating – 2|Pa ge TENDER NO:MGVCL/RAPDRP/SCADA/222A PLS NOTE: THE NOMINAL CURRENT RATING OF VCB SHALL BE ACCORDING TO LOAD OF THE FEEDER AND ACCORDINGLY SUITABLE RELAY SHALL BE PROVIDED AND ANY CHANGE IN COMBINATION/CONFIGURATION SHALL BE EXECUTED WITH THE APPROVAL OF CHIEF ENGINEER OF RESPECTIVE DISCOM. a. This Specification provides for design, manufacture, inspection and testing before dispatch, packing and delivery F.O.R.(Destination) of SF6 insulated RMUs with necessary take off terminal units for future automations, compatible with SCADA system other accessories and auxiliaries equipment and mandatory spares, described herein and required for their satisfactory operation. b. The objective of the RMUs is for extremely small construction width, compact, maintenance free, independent of climate, easy installation, operational reliability, Safe and easy to operate, minimum construction cost, minimum site work and minimum space requirement. c. The RMUs shall conform in all respects to high standards Of Engineering design, workmanship and latest revisions of relevant standards at the time of offer. d. The type of the 11 KV circuit breaker shall be VCB and insulating medium for load break isolators, Earth switch, 11 KV Buses and other associated equipments should be SF6 gas. 1.3 Necessary current sensors / transformers for protection and metering (wherever required). All necessary dry (potential-free) contacts for indications relevant to RMU monitoring status and control. A PT Panel including auxiliary power transformer for measurement of system voltage and for charging the batteries. Battery and battery charger, to provide stable as per motor rating, 24 VDC, power for the RMU’s motors. Capacitor voltage dividers serving live-line cable indicators. GENERAL: The Ring Main Unit shall be installed at 11 KV junction points to have continuous supply by isolating faulty sections. The RMU shall be extensible on both sides and consists of the following combinations of load break switches and Circuit breakers for a nominal voltage of 12 KV using SF6 gas as insulating and Vacuum as arc quenching medium. The RMU and combination shall be tropicalised and outdoor metal enclosed type. The RMU metal parts shall be of high thickness, high tensile steel which must be grit/short blasted, thermally sprayed with Zinc alloy, phosphate or should follow the 7 tank pre-treatment process and be subsequently painted with polyurethane/PP based powder paint. The overall paint layer thickness shall be not less than 80 microns. Relevant IE rules for clearances, safety and operation inside the enclosure shall be applicable. The enclosure shall be IP 54 and type tested for weather proof at EREDA/CPRI. All live parts except for the cable connections in the cable compartments shall be insulated with SF6 gas. The SF6 gas tank shall be made of robotic or TIG or MIG welded stainless steel, to have the best weld quality. The gas cubicle shall be metal enclosed with stainless Steel of thickness as per IEC 3|Pa ge TENDER NO:MGVCL/RAPDRP/SCADA/222A tested/ designed so as to provide safety and to avoid leakage of gas and should be provided with a pressure relief arrangement away from operator. Both the load break switches and the tee off circuit breaker must be motorized. The cable box of isolators and circuit breakers both should be of front access type as per site requirement. Any accidental over pressure inside the sealed chamber shall be limited by the opening of a pressure-limiting device in the top or rear-bottom part of the tank or enclosure. Gas will be release to the rear of the switchboard away from the operator and should be directed towards the bottom, into the trench to ensure safety of the operating personnel and the pedestrians / civilians. All the manual operations should be carried out on the front of the switchboard. GENERAL TECHNICAL REQUIREMENTS 1. Fixed type SF-6 gas insulated / Vacuum circuit breakers. It should be maintenance free, having stainless steel robotically/ TIG / MIG welded enclosure for IN DOOR / OUTDOOR RMU. However, offer with high quality of the welding which has necessary extensive leakage test with leak rate of 0.075% per annum can be accepted. The RMUs to be used are only outdoor type. 2. Low gas pressure devices- 1.2 Bar pressure. 1.2 bar pressure of SF6 gas in chamber of RMU is required. 3. Live cable indicators- High operator safety. 4. Fully Rated integral ear thing switch on each device. 5. Back up relay with auxiliary supply (24V DC) shall be provided 6. Units fully SCADA Compatible. Retrofitting at site possible at a later date. Line switches (Load break switches) as well as T- OFF circuit Breaker can be operated by remote. ( Manual operations should be possible in case of motor failure.) 7. For indoor Cable boxes should be front access and interlocked with earth switch. No rear /side access required. For outdoor RMUs cable boxes shall be on front. 8. Cable testing possible without disconnection of cables. 9. Compact in dimension. 10. Circuit Breaker with back up relay with auxiliary supply (24V DC) shall be provided. 11. Low pressure, sealed for life equipment, can operate at “0” bar pressure. 12. Cable ear thing switch on all switching device-standard, for operator safety. 13. Enclosure with IP 54 standard protection for OUTDOOR RMUs and IP2X for INDOOR RMUs 14. All live parts should be inside a stainless steel enclosure for out door type RMU & minimum 2 mm thickness of stainless steel robotically/TIG/MIG welded enclosure for Outdoor / indoor RMU. 4|Pa ge TENDER NO:MGVCL/RAPDRP/SCADA/222A TECHNICAL AND GUARANTEED PARTICULARS: The bidders shall furnish all guaranteed technical particulars as called for in Schedule “A” of this specification. Particulars which are subject to guarantee shall be clearly marked. Bids lacking information in G.T.P are liable to be rejected The Entire units or minimum three functions of RMU shall be enclosed in a single compact metal clad, outdoor enclosure suitable for all weather conditions. The switchgear/steel gas tank shall be filled with SF6 as per IEC/IS Standards relative pressure to ensure the insulation and breaking functions. The steel gas tank must be sealed for life and shall meet the “sealed pressure system” criteria in accordance with the IEC 298 standard. The RMU must be a system for which no handling of gas is required throughout the 20 years of service life. The RMU shall have a design such that in the event of an internal arc fault, the operator shall be safe. This should be in accordance with IEC 298 and relevant Test certificates shall be submitted with the Tender. The offered switchgear and control gear should be suitable for continuous operation under the basic service conditions indicated below. Installation should be in normal indoor conditions in accordance with IEC 60694. Ambient temperature – 10 degree C to + 50 degree C Relative humidity - up to 95% Altitude of installation - up to 1000m, IEC 60120 1.3.1 The RMU shall be tested for an internal arc rating of 20 kA for 1 Sec. for 11 KV RMU. Suitable temperature rise test on the RMU shall be carried out & test reports shall be submitted with tender for technical bid evaluation. Each switchboard shall be identified by an appropriately sized label, which clearly indicates the functional units and their electrical characteristics. The switchgear and switchboard shall be designed so that the position of the different devices is visible to the operator on the front of the switchboard and operations are visible as well. The entire system shall be totally encapsulated. There shall be no access to exposed conductors. In accordance with the standards in effect, the switchboards shall be designed so as to prevent access to all live parts during operation without the use of tools. The entire 11 KV RMU are insulated by inert gas (SF6) suitable for operating voltage up to 12 KV respectively. The 11 KV circuit breakers must be VCB breaker. It is necessary to fit an absorption material in the tank to absorb the moisture from the SF6 gas. The SF6 insulating medium shall be constantly monitored via a temperature compensating gas pressure indicator offering a indication at different temperature ranges, having distinctive RED and GREEN zones for safe operation. All the RMUs must be routine tested for the following at factory in India: Micro-ohm test(Contact Resistance test) for the assembly inside the tank. 5|Pa ge TENDER NO:MGVCL/RAPDRP/SCADA/222A Circuit breaker analyzer test so as to ensure the simultaneous closing of all poles for VCB. SF6 gas leak test. Partial Discharge test on the complete gas tank so as to be assure of the proper insulation level and high product life. High voltages withstand. Secondary test to ensure the proper functioning of the live line indicators, fault passage indicators and relays. 1.3.2 Sulphur Hex fluoride Gas(SF6 GAS) The SF6 gas shall comply with IEC 376,376A, and 376B and shall be suitable in all respects for use in 11 KV RMUs under the operating conditions. The SF6 shall be tested for purity, dew point air hydrolysable fluorides and water content as per IEC 376,376A and 376B and test certificate shall be furnished to the owner indicating all the tests as per IEC 376 for each Lot of SF6 Gas. DIELECTRIC MEDIUM SF6 gas/ VCB shall be used for the dielectric medium for 11KV RMUS in accordance with IEC376. It is preferable to fit an absorption material in the tank to absorb the moisture from the SF6 gas/ VCB and to regenerate the SF6 gas/ VCB following arc interruption. The SF6 gas / VCB insulating medium shall be constantly monitored via a temperature compensating gas pressure indicator offering a simple go, no-go indication. General structural and mechanical construction: The offered RMU should be of the fully arc proof metal enclosed, free standing, floor mounting, flush fronted type, consisting of modules assembled into one or more units. Each unit is made of a cubicle sealed-for life with SF6 gas / VCB and contains all high voltage components sealed off from the environment. The overall design of the indoor switchgear should be such that front access only is required. It should be possible to erect the switchboard against a substation wall, with HV and LV cables being terminated and accessible from the front. The units should be constructed from Minimum 2 mm thick stainless steel sheets. However, Offer with type test report of pressure withstand test for gas filled compartment with pressure relief device test as per cl. no. 6-103-1 of IEC 62271-200-2003 can be accepted for 2mm stainless steel tank thickness. The design of the units should be such that no permanent or harmful distortion occurs either when being lifted by eyebolts or when moved into position by rollers. For outdoor RMUs a weather proofing process shall be carried out. SHEET METAL MUST BE GRIT BLASED / THERMALLY SPRAYED AND POLYURETHANE PAINTED WITH ABOUT 80 MICRON THICKNESSES, TO ACHIVE OUTDOOR WORTHINESS AND CORROSION PROOF NESS. - RMU ENCLOSURE MUST BE SHIELDED AGAINST SOLAR IRRADIATION AND TESTED FOR A AMBIENT OF 50 DEGREE C WITHOUT DERATING OF THE EQUIPMENT. 6|Pa ge TENDER NO:MGVCL/RAPDRP/SCADA/222A The cubicle shall have a pressure relief device. In the rare case of an internal arc, the high pressure caused by the arc will release it, and the hot gases is allowed to be exhausted out at the bottom / top / rear of the cubicle. A controlled direction of flow of the hot gas should be achieved. The switchgear should have the minimum degree of protection (in accordance with IEC 60529) - IP 67 for the tank with high voltage components - IP 2X for the front covers of the mechanism - IP 3X for the cable connection covers - IP 54 for the outdoor enclosure. 1.4 STANDARDS: Unless otherwise specified elsewhere in this Specification, the RMU, Switchboard (Switchgear), Load break isolators, Instrument Transformers and other associated accessories shall conform to the latest revisions and amendments thereof to the following standards. 1. IEC 60 298/IEC 62 271-200/IS 12729:1988 - General requirement for Metal Enclosed Switchgear 2. IEC60129/IEC62271-103/IS 9921 - Alternating current disconnector (Load break isolators) and earthing switch 3. IEC 62 271-100 & 200/IEC 60 056/IS 13118:1991 - Specification for alternating current circuit breaker 4. IEC 62 271-1/IEC 60694 - Panel design, SF6/Vacuum Circuit Breakers 5. IEC 60044-1/IEC 60185/IS 2705:1992 - Current Transformer 6. IEC 60265-1/IS 9920:1988- High voltage switches. 7. IEC 376 - Filling of SF6 gas in RMU. 8. IEC 60273/IS: 2099 - Dimension of Indoor & Outdoor post insulators i. with voltage > 1000 Volts. 9. IEC 60529/IS 13947(Part-1) - Degree of protection provided by i. enclosures for low voltage switchgear and ii. Control gear. 10. Indian Safety Regulations 2010/Relevant IS Equipment meeting with the requirements of any other authoritative standards, which ensures equal or better quality than the standard mentioned above as well as latest standard shall also be acceptable. If the equipments, offered by the Bidder conform to other standards, salient points of difference between the standards adopted and the specific standards shall be clearly brought out in relevant schedule. In case of any difference between provisions of these standards and provisions of this specification, the provisions contained in this specification shall prevail. One copy of such standards with authentic English Translations shall be furnished along with the offer.(Hard copy) Applicable Standards The RMUs shall be manufactured to the highest quality consistent with best practice and workmanship and in full accord with the Supplier’s quality assurance plan. The RMUs shall conform to the Indian or IEC international standards that are applicable. These include the standards listed in Table 1 below. 7|Pa ge TENDER NO:MGVCL/RAPDRP/SCADA/222A Table 1: Applicable Standards Standard Description IS 3427 AC metal enclosed switchgear and control gear for rated voltages above 1 kV and up to and including 52 kV IS 12063 Classification of degrees of protection provided by enclosures of electrical equipment IS 9920 (Parts 1 to 4) High Voltage Switches IS 9921 (Parts 1 to 5) IS 13118 IS 10601 Specification for AC disconnectors and earthing switches for voltages above 1000 V HV AC Circuit Breakers Dimensions of terminals of HV Switchgear and Control gear IS 12729 General requirements of switchgear and control gear for voltages exceeding 1000 V IEC 1330 IEC 60694 IEC 6081 IS 2705 IS 3156 IS 8686 IEC 62271200 High voltage/Low voltage prefabricated substations Common clauses for MV switchgear standards Monitoring and control Current Transformers Voltage transformers Specification for Static Protective Relays Standards for high voltage metal clad switchgear up to 52 KV. INDIAN This is to be as per Central Electricity Authority (Safety Requirement for ELECTRCIATY Construction, Operation & Maintenance of Electrical Plants and Electric Lines) REGULATION Regulations, 2010 2010 1.5 THE STANDARDS MENTIONED ABOVE ARE AVAILABLE FROM: IEC - (INTERNATIONAL ELECTRO-TECHNICAL COMMISSION, BUREAU CENTRAL DE LA COMMISSION, ELECTRO TECHNIQUE INTERNATIONAL, 1, RUE DE VEREMBE, GENEVA, SWITZERLAND.) ISO - INTERNATIONAL STANDARD ORGANISATION 1.6 SPECIFIC REQUIREMENTS IN RMU:- 1.6.1 CLIMATE CONDITIONS The climatic conditions under which the equipment should operate satisfactory are as under: Maximum ambient air temperature :50 deg. C 8|Pa ge TENDER NO:MGVCL/RAPDRP/SCADA/222A Minimum ambient air temperature Maximum daily average ambient air temperature Maximum humidity Altitude above M.S.L. (maximum) Average annual rainfall(mm) Max. wind pressure(Kg/sq.m) Seismic level(Horizontal accn.) Iso-ceraunic level(Days per Year) Average thunder storm days per annum :10 deg.C :45 deg C :100% :1000 metres :925 :200 :0.3 g :50 :50 1.6.2 Distribution Network Electrical Parameters The main parameters of the distribution network are as follows: 1.7 Rated Voltage Nominal system voltage: Highest system voltage: Number of phases: Frequency: Variation in frequency: Type of earthing: Power frequency withstand voltage: Basic impulse withstand voltage : 12 KV 11 kV (rms) 12 kV (rms) 3 50 Hz 48.5 Hz to 51.5 Hz Solid 28 kV 95 kV RMU OUTDOOR METAL CLAD ENCLOSURE. The RMU enclosure must be a metallic, it shall follows an industrialized process of manufacturing. The RMU and combination shall be tropicalised and outdoor metal enclosed type. The RMU metal parts shall be of high thickness, high tensile steel which must be grit/short blasted, thermally sprayed with Zinc alloy, phosphate or should follow the 7 tank pre-treatment process and be subsequently painted with polyurethane based powder paint. The overall paint layer thickness shall be not less than 80 microns. The rating of enclosure shall be suitable for operation on three phase, three wire, 11 KV, 50 cycles, A.C. System with short-time current rating of 20KA for 3 seconds for 11 KV with RMU Panels. The enclosure should have two access doors one for the operation and relay monitoring and other for the cable access. Both the doors should have the locking facility to prevent the access to operating mechanism to avoid unauthorized operating of RMU and relay. RMU Design Features All design features of the proposed RMU, as described in the supplier’s bid and in the bid’s reference materials, shall be fully supported by the equipment actually delivered. The key design features include those that relate to: Maintainability, expandability, and life span Ability to operate in severe outdoor environmental conditions. Immunity to electrical stress and disturbance. Acceptable insulation properties. 9|Pa ge TENDER NO:MGVCL/RAPDRP/SCADA/222A Convenient FRTU interconnection features. INDOOR RMU 1. MODULAR DESIGN, PANEL TYPE WITH FRONT CABLE ACCESS. 2. RMU MUST BE MADE OF ROBOTICALLY / TIG / MIG WELDED STAINLESS STEEL. 3. Offered RMU must be extensible. OUT DOOR RMU 1. Stainless steel enclosure for OUT DOOR RMU application. The manufacturers shall conform the normal current ratings mentioned in GTP at 50 deg. Ambient without derating or as per IEC Standard 2. Enclosure with I.P.54 standard protection. 3. Offered RMU must be extensible. 4. Cable boxes shall be on Front sides. 5. RMU ENCLOSURE MUST BE SHIELDED AGAINST SOLAR IRRADIATION AND TESTED FOR AMBIENT OF 50 DEGREE C. The manufacturers shall conform the normal current ratings mentioned in GTP at 50 deg. Ambient without derating, however, design for higher ambient temperature than 50 degree may be admissible. 1.8 TAKE OFF TERMINAL UNITS FOR AUTOMATION: The RMU shall be provided with necessary take off terminal units for automations, located in the front recesses / LV cubical of the RMU. The connectivity to the FRTU for SCADA purpose shall be provided. Refer Annexure-1 for general arrangement of the termainals. 1.9 ISOLATORS (LOAD BREAK TYPE) The load break isolators for Incoming and Outgoing supply must be provided. These should be fully insulated by SF6 gas. The load break isolators shall consist of 630 Amp fault making/load breaking spring assisted ring switches, each with integral fault making earth switches. The switch shall be naturally interlocked to prevent the main and earth switch being switched “ON at the same time. The selection of the main and earth switch is made by a lever on the facia, which is allowed to move only if the main or earth switch is in the off position. The load break isolators should have the facility for remote operation. Each load break switch shall be of the triple pole, simultaneously operated, automatic type with quick break contacts and with integral earthing arrangement. The isolating distance between the OFF and the ON position in the isolator should be sufficient to withstand dielectric test as per IS/IEC, so as to have enough isolating distance for ensuring safety during DC injection for Cable testing. Load break switch should have the following Motor operated 12 KV, 630A Load Break switch and manually operated Earthing Switch with making capacity. “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Mechanical ON/OFF/EARTH Indication Anti-reflex operating handle 10 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A Cable Testing facility without disconnecting the cable terminations, cable joints and terminal protectors on the bushings. Cable terminations Cable boxes suitable for 1 X 3C x 300 sq mm XLPE Cable with right angle Cable Termination Protectors. 1.10 EARTHING OF ISOLATORS AND BREAKERS (EARTH SWITCH) Necessary arrangements are provided at Load break isolators Breaker for selecting Earth position. Mechanical interlocking systems shall prevent the RMU function from being operated from the “ON” to “Earth On” position without going through the “OFF” position. 1.11 DISTRIBUTION TRANSFORMER/FEEDER BREAKER (VACUUM) The VCB breaker for the controlling of DT/Feeder Breaker must be provided inside welded stainless steel SF6 gas tank with the outdoor metal clad enclosure. The VCB circuit breaker must be a spring assisted three positions with integral fault making earth switch. The selection of the main/earth switch lever on the facia, which is allowed to move only if the main or earth switches is in the off position. The manual operation of the circuit breaker shall not have an effect on the trip spring. This should only be discharged under a fault (electrical) trip; the following manual reset operation should recharge the trip spring and reset the circuit breaker mechanism in the main off position. The circuit breaker shall be fitted with a mechanical flag, which shall operate in the event of a fault (electrical) trip occurring. The “tripped” flag should be an unambiguous colour differing from any other flag or mimic. Both the circuit breaker and ring switches are operated by the same unidirectional handle. The protection on the circuit breaker shall comprise of the following components:5P10 class protection CTs, low burden trip coil and O/C & E/F relay with auxiliary supply (24V DC) shall be provided IDMT protection relays (Numeric/Micro processor based) 3 x over current and earth fault element shall be Definite Time type relay . The relay should be housed within a pilot cable box accessible. Circuit Breaker should have the following: - Motor operated 200 A / 630A SF6 insulated Vacuum circuit breaker and Ear thing Switch with making capacity 51KA - Mechanical tripped on fault indicator - Auxiliary contacts 4NO and 4NC - Anti-reflex operating handle - “Live Cable” LED Indicators through Capacitor Voltage Dividers mounted on the bushings. - O/C + E/F relay with auxiliary supply (24V DC) shall be provided. - Shunt Trip circuit for external trip signal - Mechanical ON/OFF/EARTH Indication - Cable boxes suitable for 1 X 3C x 300 sq mm XLPE Cable with right angle Cable Termination / protectors / boots 11 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A TECHNICAL DATA 1 Ring Main Unit, Electrical data Electrical data and service conditions Rated voltage KV 12 1 Power frequency withstand voltage KV 28 2 Impulse withstand voltage KVp 95 3 Rated frequency Hz 50 4 Rated current busbars A 630 5 Rated current (cable switch) A 630 6 Rated current (T-off) A 630 Breaking capacities: 7 active load A 630 8 closed loop (cable switch) A 630 9 off load cable charging (cable switch) A 135 10 earth fault (cable switch) A 200 11 earth fault cable charging (cable switch) 115 12 short circuit breaking current (T-off circuit kA breaker) 20 / 21 13 Rated making capacity kA 52 14 Rated short time current 3 sec. kA 20 / 21 Ambient temperature: 15 Maximum value °C + 50 16 Maximum value of 24 hour mean °C + 40 17 Minimum value °C 0 18 Altitude for erection above sea level4 m ...1000 19 Relative humidity Max 95% 12 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A 2 Ring Main Unit Technical data (11KV) No. General data, enclosure and dimensions 1 Standard to which Switchgear complies IEC Metal Enclosed, Panel type, Compact Module. 3 Yes 2 Type of Ring Main Unit 3 Number of phases 4 Whether RMU is type tested 5 6 Whether facility is provided with pressure relief Insulating gas Yes SF6 7 Nominal operating gas pressure 1.4 bar @ 20° C. However offer with Nominal operating gas pressure shall be as per manufacturer standard and suitable to satisfy the rated dielectric strength can be accepted 8 9 Gas leakage rate / annum Expected operating lifetime 10 Whether facilities are provided for gas monitoring 11 Material used in tank construction No. 1 2 3 4 5 6 7 8 9 Operations, degree of protection and colours Means of switch operation Means circuit breaker operation Rated operating sequence of Circuit Breaker Total opening time of Circuit Breaker Closing time of Circuit Breaker Mechanical operations of switch (co) Mechanical operations of CO earthing switch Mechanical operations of circuit breaker (co) Principle switch / earth switch Degree of protection: High Voltage live parts, SF6 / VCB tank Front cover mechanism Cable covers Outdoor Enclosure Colours: Front cover Side and cable cover 10 11 12 13 14 15 1.12 0.075% 30 years Yes, temperature compensated manometer can be delivered Stainless steel sheet, minimum 2 mm separate handle separate handle and push buttons O - 3min-CO-3min-CO approx. 45ms approx. 40ms 1000 1000 2000 3 position combined switch / earth switch IP 67 IP 2X IP 3X IP 54 BUSHINGS 13 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A The units are fitted with the standardized bushings that comply with IEC standards. All the bushings are the same height from the ground and are protected by a cable cover. 1.13 CABLE BOXES All the cable boxes shall be air insulated suitable for dry type cable terminations and should have front access. The cable boxes at each of the two ring switches should be suitable for accepting HV cables of sizes 3c x 300 sq.mm and circuit breaker cable suitable up to 3c x 300 sq.mm. The cable boxes for an isolator in its standard design should have sufficient space for connecting two cables per phase .Necessary Right angle Boot should be supplied to the cable terminations .The type of the Right angle Boot should be cold applied insulating Boot. 1.14 CABLE TESTING FACILITY It shall be possible to test the cable after opening the cable boxes. The cable boxes should open only after operation of the earth switch. Thus ensuring the earthing of the cables prior to performing the cable testing with DC injection. 1.15 VOLTAGE INDICATOR LAMPS AND PHASE COMPARATORS The RMU shall be equipped with a voltage indication to indicate whether or not there is voltage on the cable. There should be a facility to check the synchronization of phases with the use of external device. It shall be possible for the each of the function of the RMU to be equipped with a permanent voltage indication as per IEC 601958 to indicate whether or not there is voltage on the cables. 1.16 EXTENSIBLE Each combination of RMU shall have the provision for extension both sides by load break isolators / breakers in future, with suitable accessories and necessary Bus Bar. The equipment shall be well designed to provide any kind of extension / trunking chamber for connecting and housing extensible Busbars. Extensible isolators and circuit breakers shall be individually housed in separate SF6 gas enclosures. Multiple devices inside single gas tank / enclosure will not be acceptable. In case of extensible circuit breakers, the Breaker should be capable of necessary short circuit operations as per IEC at 20 KA, and the Breaker should have a rated current carrying capacity of 630 A. 1.17 WIRING & TERMINALS: The wiring should be of high standard and should be able to withstand the tropical weather conditions. All the wiring and terminals (including take off terminals for future automation, DC, Control wiring), 20% Spare terminals shall be provided by the contractor. The wiring cable must be standard single-core non-sheathed, Core marking (ferrules), stripped with non-notching tools and fitted with end sleeves, marked in accordance with the circuit diagram with printed adhesive marking strips. The wiring should be of high standard and should be able to withstand the tropical weather conditions. All wiring shall be provided with single core multi-strand copper conductor wires with P.V.C insulation. The wiring shall be carried out using multi-strand copper conductor super flexible PVC insulated wires of 1100V Grade for AC Power, DC Control and CT circuits. Suitable colored wires shall be used for phase identification and interlocking type ferrules shall be provided at both ends of the wires for wire identification. Terminal should be suitably protected to eliminate sulphating. Connections and terminal should be able to withstand vibrations. The terminal blocks should be stud type for controls and disconnecting link type terminals for CT leads with suitable spring washer and lock nuts. 14 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A Flexible wires shall be used for wiring of devices on moving parts such as swinging Panels (Switch Gear) or panel doors. Panel wiring shall be securely supported, neatly arranged readily accessible and connected to equipment terminals, terminal blocks and wiring gutters. The cables shall be uniformly bunched and tied by means of PVC belts and carried in a PVC carrying trough. The position of PVC carrying trough and wires should not give any hindrance for fixing or removing relay casing, switches etc., Wire termination shall be made with solder less crimping type of tinned copper lugs. Core identification plastic ferrules marked to correspond with panel wiring diagram shall be fitted with both ends of each wire. Ferrules shall fit tightly on the wire when disconnected. The wire number shown on the wiring shall be in accordance with the IS.375. All wires directly connected to trip circuits of breaker or devices shall be distinguished by addition of a red color unlettered ferrule. Inter-connections to adjacent Panels (Switch Gear) shall be brought out to a separate set of Terminal blocks located near the slots or holes to be provided at the top portion of the panel. Arrangements shall be made for easy connections to adjacent Panels (Switch Gear) at site and wires for this purpose shall be provided and bunched inside the panel. The bus wire shall run at the top of the panel. Terminal block with isolating links should be provided for bus wire. At least 20% of total terminals shall be provided as spare for further connections. Wiring shall be done for all the contacts available in the relay and other equipment and brought out to the terminal blocks for spare contacts. Color code for wiring is preferable in the following colours. Voltage circuits : CT circuits : DC circuits : 250V AC circuits : Earthing : Red, Yellow, Blue for phase and Black for Neutral similar to the above Grey for both positive and negative Black for both phase and neutral Green The wiring shall be in accordance to the wiring diagram for proper functioning of the connected equipment. Terminal blocks shall not be less than 1100V grade and shall be piece-molded type with insulation barriers. The terminal shall hold the wires in the tight position by bolts and nuts with lock washers. The terminal blocks shall be arranged in vertical formation at an inclined angle with sufficient space between terminal blocks for easy wiring. The terminals are to be marked with the terminal number in accordance with the circuit diagram and terminal diagram. The terminals should not have any function designation and are of the tension spring and plug-in type. Clear empty Space shall be mandatorily provided in RMU Panel for mounting FRTU Panel. Dimensions details of required space for FRTU are about 1200 mm H x 600 mm W x 300 mm D. Normal FRTU load for DCPS will be minimum 25 watts to 80 watts.230V AC Supply for charging of FRTU battery should be available. The Aux supply will be taken through the PT provided for metering in RMU. We require 24V DC. FRTU will require power up to 200 VA depending upon RMU configuration. The PT must have sufficient burden for meeting the aforesaid requirement also for battery charging. The separate transformer must have sufficient capacity for meeting the aforesaid requirement also for battery charging. 1.18 EARTHING 15 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A The RMU outdoor metal clad, Switch Gear, Load break isolators, Vacuum circuit breakers shall be equipped with an earth bus securely fixed along the base of the RMU. The size of the earth bus shall be made of IEC/IS standards with tinned copper flat for RMU and M.S.Flat for Distribution Transformer, earth spike and neutral earthing. Necessary terminal clamps and connectors shall be included in the scope of supply. All metal parts of the switchgear which do not belong to main circuit and which can collect electric charges causing dangerous effect shall be connected to the earthing conductor made of copper having CS area of minimum 75 sq.mm. Each end of conductor shall be terminated by M 10/equivalent quality and type of terminal for connection to earth system installation. Earth conductor location shall not obstruct access to cable terminations. The following items are to be connected to the main earth conductor by rigid or copper conductors having a minimum cross section of 75 mm (a) earthing switches (b) Cable sheath or screen (c) capacitors used in voltage control devices, if any. The metallic cases of the relays, instruments and other panel mounted Equipment s shall be connected to the earth bus by independent copper wires of size shall be made of IEC/IS standards. The colour code of earthing wire shall be green. Earthing wires shall be connected on the terminals with suitable clamp connectors and soldering shall not be permitted. Two no. of earthing with connecting G.I Strip (size=35mm*3mm) are to be provided as per attached Drawing(Appendix-2) with ref IS:3043-1987(2006). 1.19 ACCESSORIES & SPARES: The following spares and accessories shall be supplied along with the main equipments at free of costs. This shall not be included in the price schedule. 1. Charging lever for operating load break isolators & circuit breaker of each RMU. 2. The pressure gauges indications - 1 numbers Provision shall be made for padlocking the load break switches/ Circuit breaker, and the earthing switches in either open or closed position with lock & master key. 1.20 TESTING OF EQUIPMENT & ACCESSORIES: Provision for testing CTs,PTs, Relays, Breakers and Cables shall be made available. Procedure and schedule for Periodical & Annual testings of equipments, relays, etc. shall be provided by the supplier. 1.20.1 TYPE TEST The Tenderers should, along with the tender documents, submit copies of all Type test certificate of their make including breaker and Isolators in full shape as confirming to relevant ISS/IEC of latest issue obtained from a International/National Govt. Lab/Recognized laboratory. The above type test certificates should accompany the drawings for the materials duly signed by the institution who has type test certificate. 1.20.2 ACCEPTANCE AND ROUTINE TESTS All acceptance and routine tests as stipulated in the latest IEC- shall be carried out by the supplier in the presence of DISCOM’s representative. The supplier shall give at least 7 days advance intimation 16 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A to the DISCOM to enable them to depute their representative for witnessing the tests. The partial discharge shall be carried out as routine test on each and every completely assembled RMU gas tank and not on a sample basis. As this test checks and guarantees for the high insulation level and thus the complete life of switchgear. 1.20.3 ADDITIONAL TESTS The DISCOM reserves the right for carrying out any other tests of a reasonable nature at the works of the supplier/laboratory or at any other recognized laboratory/research institute in addition to the above mentioned type, acceptance and routine tests at the cost of the Board to satisfy that the material complies with the intent of this specification. 1.20.4 PRE-COMMISSIONING TESTS All the pre-commissioning tests will be carried out in the presence of the DISCOM’s testing engineer and necessary drawing manual and periodical test tools shall be arranged to be supplied. During the above tests the contractor representative should be present till the RMUs are put in to service. 1.21 INSPECTION: The inspection may be carried out by the DISCOM at any stage of manufacture. The supplier shall grant free access to DISCOM’s representative at a reasonable time when the work is in progress. Inspection and acceptance of any equipment under this specification by the DISCOM shall not relieve the supplier of his obligation of furnishing equipment in accordance with the specification and shall not prevent subsequent rejection if the equipment is found to be defective. The supplier shall keep the DISCOM informed in advance, about the manufacturing programme so that arrangement can be made for inspection. The DISCOM reserves the right to insist for witnessing the acceptance/routine testing of the bought out items. The DISCOM has rights to inspect the supplier’s premises for each and every consignment for type & routine test. No material shall be dispatched from its point of manufacture unless the material has been satisfactorily inspected and tested / unless the same is waived by the DISCOM in writing. QUALITY ASSURANCE PLAN: The bidder shall invariably furnish following information along with his offer / in case of event of order. I. Statement giving list of important raw materials including but not limited to a) Contact material b) Insulation c) Sealing material d) Contactor, limit switches, etc. in control cabinet. Name of sub-suppliers for the raw materials, list of standards according to which the raw materials are tested, list of test normally carried out on raw materials in presence of Bidder’s representative, copies of test certificates. II. Information and copies of test certificates as in (I) above in respect of bought out accessories & raw materials. 17 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A III. List of areas in manufacturing process, where stage inspections are to be carried out. IV. Normally carried out for quality control and details of such tests and inspections. V. Special features provided in the equipment to make it maintenance free. VI. List of testing equipment available with the Bidder for final testing of RMUs and associated combinations vis-à-vis the type, special, acceptance and routine tests specified in the relevant standards. These limitations shall be very clearly brought out in the relevant schedule i.e. schedule of deviations from specified test requirements. The supplier shall, within 15days from the date of receipt of Purchase Order submit following information to the DISCOM. a) List of raw materials as well bought out accessories and the names of sub-suppliers selected from those furnished along with offer. b) Necessary test certificates of the raw material and bought out accessories. c) Quality Assurance Plan (QAP) with hold points for DISCOM’s inspection. The quality assurance plan and hold points shall be discussed between the DISCOM and supplier before the QAP is finalized. The supplier shall submit the routine test certificates of bought out items and raw material, at the time of routine testing of the fully assembled breaker. 1.22 TRAINING: The supplier shall give rigorous training to the engineers & staff for 2 days in attending trouble shooting and maintenance. 1.23 SCADA CONNECTIVITY: Provision shall be made in all the RMUs with necessary take off terminal units for automations and connectivity with FRTU. The all RMUs shall be motorized type and compatible for SCADA operation. All the I/O signals need to be brought to the Terminal Strip on a Din Rail, also the Din Rail should have space to mount the MFT’s provided by SIA. Size of MFT is 96H X 96W X 117D mm. All the DI’s, AI’s and DO’s should be provided as potential free and control contacts. The CT/PT should provide metering grade core for connecting MFT provided with FRTU. The RMU will also supply 230VAC 200 VA for FRTU. Battery for FRTU supplied by SIA. The RMU should be provided with provision of following minimum signals available at separate SCADA terminal box. Minimum signals for SCADA/DMS - to be wired to Separate TBs CB close / open potential free contacts LBS close / open potential free contacts LBS & CB Earth Switch close /open potential free contacts Spring charge Status indication potential free contacts SF6 gas pressure low potential free contacts O/C Operated potential free contacts 18 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A E/F Operated potential free contacts Local/Remote potential free contacts Common Power Supply Healthy potential free contacts Motor MCB Healthy Status potential free contacts potential free contacts Battery charger Fail 1.24 RMU Door Open potential free contacts CB Trip Coil Healthy potential free contacts CT & PT For SCADA Metering FPI Control FPI remote resetting for SCADA CB control Control from SCADA LBS Control Control from SCADA DOCUMENTATION and DRAWINGS All drawings shall conform to relevant International Standards Organization (ISO) Specification. All drawings shall be in ink and suitable for microfilming. The tenderer shall submit along with his tender dimensional general arrangement drawings of the equipments, illustrative and descriptive literature in triplicate for various items in the RMUs which are all essentially required for future automation. I. Schematic diagram of the RMU panel II. Instruction manuals III. Catalogues of spares recommended with drawing to indicate each items of spares IV. List of spares and special tools recommended by the supplier. V. Copies of Type Test Certificates as per latest IS/IEC. VI. Drawings of equipments, relays, control wiring circuit, etc. VII. Foundation drawings of RMU so that Utility will planned and carry out civil works etc. VIII. Dimensional drawings of each material used for item VII. IX. Actual single line diagram of RMU/RMUs with or without Extra combinations shall be made displayed on the front portion of the RMU so as to carry out the operations easily. The following should be supplied to each consignee circle/town along with the initial supply of the equipments ordered. 19 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A a. Copies of printed and bound volumes of operation, maintenance and erection manuals in English along with the copies of approved drawings and type test reports etc. b. Sets of the manuals as above shall be supplied to the Chief Engineer/Distribution. A soft copy of the all Technical and Drawing furnished in a CD 1.25 NAME PLATE: Each RMU and its associated equipments shall be provided with a nameplate legible and indelibly marked with at least the following information. a. Name of manufacturer b. Type, design and serial number c. Rated voltage and current d. Rated frequency e. Rated symmetrical breaking capacity f. Rated making capacity g. Rated short time current and its duration h. Purchase Order number and date i. Month and Year of supply j. Last date of completion of Guarantee period k. Rated lightening impulse withstand voltage l. Feeder name (Incoming and Outgoing), DTs Structure name, 11000 Volts Dangers etc. j Name of DISCOM NOTE: I) II) 1.26 THE WORD RATED NEED NOT APPEAR ON THE NAME PLATE. RECOGNIZED ABBREVIATIONS MAY BE USED TO EXPRESS THE ABOVE PARTICULARS. WHETHER THE CIRCUIT BREAKER IS FITTED WITH CLOSING/TRIPPING DEVICES NECESSITATING AN AUXILIARY SUPPLY SHALL BE STATED EITHER ON THE CIRCUIT BREAKER NAME PLATE OR ANY OTHER ACCEPTABLE POSITION. FAULT PASSAGE INDICATORS (FPI): These shall facilitate quick detection of faulty section of line. The fault indication may be on the basis of monitoring fault current flow through the device. The unit should be self-contained requiring no auxiliary power supply. The FPI shall be integral part of RMU. The FPI shall have LCD/LED display, automatic reset facility. FPI Reset from SCADA will be through momentary closure of a potential free contact from FRTU. The sensors to be bushing/cable mounted. The number of FPI should be put in all the three phases of the outgoing branch of the RMUs FPI should have suitable connectivity with the FRTUs for the SCADA purpose. 20 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A The FPI inside the RMU may be non communicable and hard wired to the TB for the signals Fault Passage indicator OK Fault Passage indicator operated The conventional practice is to have (N-1) FPI where N is nos. of LBS in a particular configuration of RMU i.e. following for tendered RMUs: 2WAY 3WAY 4WAY 5WAY 6WAY 1.27 - NIL 1 1 2 2 TROPICALISATION Due regard should be given to the climatic conditions under which the equipment is to work. Ambient temperatures normally vary between 20 deg C and 40 deg C, although direct sun temperature may reach 45 deg C. The climate is humid and rapid variations occur, relative humidity between 60% and 95% being frequently recorded, but these values generally correspond to the lower ambient temperatures. The equipment should also be designed to prevent ingress of vermin, accidental contact with live parts and to minimize the ingress of dust and dirt. The use of materials which may be liable to attack by termites and other insects should be avoided. 1.28 Motorization : All the functions within the RMU i.e Isolators/Breakers should be fitted with motor mechanism and closing coil making it suitable to make it on from remote.( However, manual mechanism should be possible in case of failure/ non working of motor) Other Accessories (required with RMU) :a) Shunt Trip Coil ( Coil voltage shall be indicated later on) b) Battery & Battery Charger. c) 4NO+4NC auxiliary contacts. 1.29 Metering: Multifunction Energy meter shall be provided by DISCOMS with, of accuracy class of 0.5 at incoming isolator of all RMUs. The Metering CTs and PTs of suitable rating shall be provided and wired in SCADA terminal TBs. Metering and protection is required on Breaker only and not on Isolator. CTs may consider accordingly. 1.30 TECHNICAL SPECIFICATION FOR RMU 1.30.1 11KV Bus Bar I. II. III. IV. Current Carrying Capacity Short time rating current for 3 secs. Insulation of bus bar Bus bar connections : 630 Amps. : 20 KA for 11kv : SF6 : Anti-oxide grease 1.31 PARAMETERS FOR SWITCH GEAR OF DT AND LOAD BREAK ISOLATORS I. II. III. Type No of Phases No. of poles : Metal enclosed :3 :3 21 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A IV. Rated voltage :12 KV V. Operating voltage :11 KV(+10% to -20%) VI. Rated lightning impulse withstand voltage :95 KV VII. Rated power frequency withstand voltage :28 KV VIII. Insulating gas :SF6 IX. Rated filling level for insulation :As Per IEC. Max.permissible site altitude at the above gas pressures : 1000m (The operating pressure has to be adjusted for greater altitudes) Isolating distance between ON and OFF position in isolator :80 mm (min). Rated short time current :20 KA.for 11kv Rated short time :3s Rated peak withstand current :50 KA. No of operations in Short circuit :15Nos (minimum) Operating mechanism: Circuit breaker with spring assisted anti reflex mechanism. Rated current (Bus): :630 A Rated current (breaker) :200 A Circuit Breaker interrupter :SF6 insulated VCB Rated frequency : 50 Hz Rated operating sequence :O-3min- CO Number of mechanical/Remote operations for earthing : As per IEC & Ring switches & Number of mechanical/ Remote operations for circuit breakers 60298 1.32 PRINCIPAL FEATURES Sr. DESCRIPTION No Breaker 1 2 3 4 5 Circuit label Mimic diagram Supply voltage indication Current Transformer IDMT O/C & E/F Numerical/Microprocessor relay with auxiliary supply (24V DC) shall be provided. Yes Yes Yes Yes Yes 6 7 Anti - Reflexing Handle Interlock to defeat the operation of the line side earthing when the line side isolator is ON. Yes Yes 8 Interlock to defeat the operation of the earthing when the breaker is in service position and is ON. Yes 9 10 Breaker ON/OFF indication Spring Charge indication / Spring assisted mechanism. Yes Yes 11 12 13 Fault Tripping indication Bus bar end caps Whether the SF6 gas pressure gauge indicator and filling arrangement. Yes Yes Yes 14 Whether the spring assisted mechanism with operating handle for ON/OFF. Yes 22 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A 15 Whether the earth positions with arrangement for padlocking in each position and independent manual operation with mechanically operated indicator are provided Yes 16 RMUs are provided with necessary take off terminals for future automation. Yes 1.33 Earthing switch for 11 KV Line side Isolation and DT Rated short time current : 20 KA.for 11kv. Rated short time :3s Rated peak withstand current :50 KA Interlocking facility: 1) Between 11 KV Line side isolator “ON”&Earthing. 2) Between 11 KV DT side breaker on close condition &earthing 1.34 CT Type Current Transformers for breaker : Tape wound CT Description : The CTs of breaker shall be Suitable for sensing the minimum primary variable current in the order of 100-200 A and the secondary current for the CT is 1 A. The CT shall be housed in outside SF6 chamber for testing and Maintenance . CT Ratio for protection CT is 100-200/1-1 A, class 0.5/5p10 & PT Ratio is 6.35 KV/63.5 V, class-0.5, Burden – 10 VA Accuracy Class CT :0.5/5P10 Rated burden : 15 VA. 23 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A Guaranteed Technical Particulars for Extensible SF6 Unit(Mandatory To be submitted by Bidder) S.No. A 1 Service 2 Type 3 Number of phases 4 Voltage 5 Rated Frequency 6 Rated Current 7 Short Circuit rating Breaking (breaker) 8 Short time withstand 3S Fault making 9 Insulation Level 10 System earthing Particulars /Units insulated Ring Main To be specified by Bidder B Vacuum or SF6 Circuit Breaker 1 Type 2 Rated Voltage 3 Breaking Current 4 Making Current 5 Rupturing Capacity 6 Rated Current 7 No. of Poles 8 Operating mechanism 9 Breaker Operating Time i) Break Time msec. ii) Make Time msec. iii) No. of Operations a) At full load current b) At Fault Current C Isolators 1 Type 2 Duty cycle 3 Rated current 4 Rated breaking capacity 5 Fault making capacity 6 Rupturing Capacity 7 No. of poles 8 Operating mechanism 9 SF6 tank 10 Interlocks 24 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A 11 Operation safety D Busbars: 1 Material 2 Type 3 Rated Current 4 Short time rating for 3 Sec. E Cable Boxes Air Termination F Current Transformer 1 C.T. Ratio 2 Over current factor 3 Class of accuracy 4 Rated Burden G Configuration(Left to Right facing front of Ring Main Unit) H Protection 1 Three phase over current and Earth Fault I Size of RMUs( L X W X D )(for civil works etc –under Utility scope) 2. 3. 4. 5. 6. 2 WAY 3 WAY 4 WAY 5WAY 6 WAY SIGNATURE OF TENDERER NAME: DESIGNATION: Add more sheets if required. 25 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A ITEM-B TECHNICAL SPECIFICATIONS FOR 11kV FAULT PASSAGE INDICATOR (FPI) with DCU 1.1 SCOPE: Supply of overhead Fault Passage Indicators (FPI) for over head lines to be installed on 11 KV lines. The objective of this remote communicable FPI is to quickly identification of the faulty circuit and automatic update to the SCADA control center over remote communication. Fault Passage Indicators clipped on the overhead lines. One such device shall be clipped on each phase so that to measure current and Voltage presence in this phase and compute fault detection algorithm accordingly. A short-range radio interface shall be embedded in this Fault Passage Indicator so that to allow it communicate with the Data Concentrator interface This specification applies to a system allowing to remotely monitor appearance of faults on an Overhead High Voltage network so that to localise faulty sections and send patrols for reconfiguration of the network accordingly. The system shall be made of: - Fault detection systems with wireless communication to be installed on Medium Voltage Overhead Electric networks, as specified in this document. - ONE application software is to be installed on a PC in the control centre so that to display the information from these Fault passage indicators. This shall be referred to as Fault Monitoring software. This software with registry address & stored data shall be readable integrating with 104 SCADA. Alternatively the information through IEC-104 protocol from all FPIs to be integrated with SCADA/DMS under implementation in coordination with SIA. The network connection & modem required for communication between DCU to the control center is under the scope of SIA. 1.2 PURPOSE: To locate the exact passage of faults on overhead lines. The FPI shall indicate both transient as well as permanent faults on the O/H lines . The Fault Passage Indicators shall be designed to be clipped on the Overhead MV line. 3 Fault Passage Indicators shall be clipped on one line, one on each phase. It shall include the following functions: - Measurement of current running in the phase it is clipped on 26 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A - Detection of Voltage absence/presence on the phase it is clipped on - From the 2 previous functions, detection of phase-to-phase and phase-to-earth faults - Short-range radio communication with a Data Concentrator interface at a minimum distance of 100m at least. It shall be self-supplied from a non-rechargeable battery of a minimum life time 8 years, in the temperature conditions specified in this specification, including at least 1 short range radio communication with the Data Concentrator interface. The Fault Passage Indicators shall be suitable for outdoor use in the tropical climate condition stipulated in the relevant paragraph. The components used in the Fault Passage Indicators shall be suitably protected from direct sunlight to prevent malfunctioning due to solar radiation. The maximum operating temperature shall not be less than 70° C. The Fault Passage Indicators shall be suitable for mounting on live line conductors of a diameter ranging between 5 and 25 mm, with clamps designed so that the Fault Passage Indicator can withstand winds of 150km/h without falling from the line. The Fault Passage Indicator shall be fully self-contained type without any external connection, indicator or sensors. The Fault Passage Indicators shall be suitable for use on multiple lines supported by the same pole. Wireless communication Fault detection systems General information System parameters The Fault detection systems shall be designed to operate on a Medium Voltage overhead network with the following characteristics: - Nominal Operation Voltage 7 to 13 kV - Frequency 50 Hz - Type of MV neutral earthing: through a resistor or solidly grounded - Conductor diameter 5 to 25 mm One single product shall be proposed to cover the whole range of above characteristics: Particularly, the same product should be installed on any network from 7 to 13 kV. 1.3 OPERATION: The Fault Passage Indicator shall operate on either passing over of the absolute threshold current (user settable) or the current variation (di/dt). Upon the installation of the indicator, the FPI shall adjust itself to the network frequency and voltage of perform required function. Operational specifications Fault detection Fault detection shall be performed by the Fault Passage Indicator described above. Fault sensing shall be made from current measurement and Voltage presence detection, based on detection of the electromagnetic field and its variations. The Fault Passage Indicator shall be of the programmable type, suitable for sensing: - Short-circuit faults, Low earth leakage faults (referred to as “unbalance”) phase-to-phase faults 27 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A Phase-to-earth faults Event time-stamping Any change of state of information shall generate a time-stamped event stored in the Data Concentrator memory. The event storage capacity shall be at least 100 events. 1.4 FAULT TYPES: The FPI shall detect and indicate both earth faults as well as phase to phase faults. In addition to this, the FPI shall also detect and indicate transient and permanent faults. 1.4.1 INRUSH RESTRAINT: The FPI shall be equipped to filter out the inrush current due to transformer magnetizing currents thus avoiding the possible false indication of faults. 1.4.2 RESET: Once the fault is cleared, the FPI shall reset itself upon the power return, it shall also have a facility of resetting with settable time duration and the remote reset. 1.5 TRANSIENT FAULT EVOLUTION: If FPI is busy in flashing on transient fault and if the permanent fault occurs, the FPI shall automatically change the priority and shall start flashing differently to show the permanent fault; thus helping maintenance crew to review the priorities. Salient Technical Features of FPI Offered 11 kV Clip-on / Pole mounting, Remotely monitored ,Outdoor unit Fault Passage Indicator (FPI) should have compatibility with OPEN PROTOCOL SCADA system. 1. It should operate on either passing over of the absolute threshold current (user settable) or the current variation(di /dt) 2. It should adjust itself to the network frequency and voltage to perform required function. 3. It should detect and indicate both earth faults as well as phase to phase faults 4. It should also detect and indicate transient and permanent fault 5. It should be equipped to filter out the inrush current due to transformer magnetizing currents thus avoiding the possible false indication of faults 6. Once the fault is cleared, the FPI shall reset itself upon the power return. It shall also have a facility of resetting with settable time duration and the manual reset 7. If FPI is busy in flashing on transient fault and if the permanent fault occurs, the FPI shall automatically change the priority and shall start flashing differently to show the permanent fault; thus helping maintenance crew to review the priorities 8. The lithium battery provided inside the FPI should be trouble free of 10 years life and replaceable type, in the case of battery failures and 9. The FPI should have some self-test possibility usable when the FI is on the line (powered or not) 10. Installation of FPI should be possible on live lines using an isolated hot stick with shot gun type termination 11. It should support communication system SNMP, Master station(s) using 60870-5104protocol, protocol over 3G/GPRS , and forming IPSec VPN based security. 28 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A 12. Short range radio communication with a Data concentrator interface at a minimum distance of 100m at least. 13. Monitored information configurable as “alarming” shall include at least the following, consisting both of HV network diagnostic information and monitoring equipment internal faults for self-diagnostic purpose: - Fault detection appearance with indication of Fault Passage Indicator reporting the fault and tripping criteria tripped. - Fault detection disappearance with indication of Fault Passage Indicator reporting the fault and tripping criteria tripped clear. - Voltage absence - Voltage presence - Change of state of a digital input - Fault Passage Indicator absent (failure of the Data concentrator interface to communicate with it through short range radio) - Fault Passage Indicator battery low Configuration and maintenance Equipment configuration and diagnostic shall be performed by connection of a laptop PC to the Data Concentrator using the PC RS232 interface. Configuration shall include: a. Scanning of all Fault Passage Indicators in the short range radio range (at least 100m) and assigning of an identification (typically number) to each of them, so that to allow identification of line (when Data Concentrator is monitoring more than 3 Fault Passage Indicators) and phase on the line on which each Fault Passage Indicator is clipped-on, in order to allow identification by the control centre of line and phase where faults or voltage absence are detected. b. Configuration of fault detection thresholds and other characteristics. c. Configuration of communication: PIN code, telephone numbers (control centre and mobile for sending SMS messages), transmission speed, etc… d. Configuration of alarms, as explained above Diagnostic shall include at least display of the current value of all information monitored (Fault Passage indicators list and status, Fault indications (phase-to-phase and phase-to-earth) from Fault Passage indicators, digital inputs, measurements….) and an embedded protocol analyser showing frames received and sent. 1.6 DCU for FPI: The DCU should be a low power consumption unit to be used as a gateway to link the communicable FPI to the SCADA application. This DCU unit should be mounted on an overhead line pole close to FPI installed in the 11kV distribution network. Fault Passage Indicators clipped on the overhead lines. One such device shall be clipped on each phase so that to measure current and Voltage presence in this phase and compute fault detection algorithm accordingly. A short-range radio interface shall be embedded in this Fault Passage Indicator so that to allow it communicate with the Data Concentrator interface mentioned below. 29 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A -A Data Concentrator interface, pole-mounted, acting as a communication gateway between Fault Passage Indicators using short-range radio and the remote control centre using 3G/GPRS communication. Data Concentrator Interface Unit(DCU) The Data Concentrator interface shall be designed to be mounted on a wooden, concrete or metallic pole. It shall be able to interface up to 9 Fault Passage Indicators installed in a 100m minimum range at least, corresponding to up to 3 overhead lines. This box shall include the following functions: - Short range radio Interface to up to 9 Fault Passage Indicators in a 100m range. - External 3G/CDMA/GPRS Modem (will provided Utility/SIA) connected to Serial port/RJ 45 of the Data concentrator. - Communication protocol to the control centre shall be Modbus over TCP/IP or IEC 870-5-101 or IEC 870-5-104 - Configuration of the Data Concentrator (3G /GPRS communication, definition of alarms…) and Fault Passage Indicators (Fault detection thresholds…) by connection of a laptop running the configuration software to an RS232 interface on the communication interface. The same software shall also include full diagnostic capabilities. It should be possible to configure these parameters from remote control centre over the 3G /GPRS network. Suitably power supply with battery backup arrangement for data concentrator and 3G/GPRS MODEM shall be done by the supplier. If power supply is not integral part Data concentrator same needs to be quoted separately. The Battery shall have a warranty of atleast 3 years & replaceable. Low battery alarm shall be provided at remote location. The battery backup duration for the DCU to run without AC supply is minimum 4hrs. The DCU should enable the communication, one side with the FPI units, via a spread spectrum license-free radio frequency with low power consumption and the other side with the distant acquisition system through a long range communication medium over mobile telephone network (3G/GPRS) others via the local RS232 port. The DCU should be capable of forming IPsec VPN connectivity. 1.6.1 Basic Functions The DCU should be able to store the date and time stamping of all events from communicable FPI and send all requested events to the SCADA application. This DCU should have the facility to change the FPI setting over remote operation. This DCU should have the memory capacity to store last 100 stamped events. 1.6.2 Description The DCU should be available in a Pole-mounted enclosure, able to house a battery and a battery charger, with external AC supply . The main board includes: A short range low power spread spectrum radio for communication with the FPI For long range communication: 30 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A One communication medium with its embedded modem (3G/GPRS) or o one RS232 port for external communication. One RS232 local parameter setting port 6 digital inputs, for alarm information to SCADA application 3 digital dry contact outputs set to repeat phase faults (phase A, B, or C) from FPI or short range communication faults or battery faults for transmission by an external DCU. 1.6.3 Detail Characteristics Sr. Details No. Specific Requirement 1 2 3 4 5 6 7 Spread spectrum low power licence-free Free Band allowed in India FCC part 15.249 and AS/NZS 4268:2003 approved radio. Embedded 3G/ GPRS modem DNP3, IEC 870-5-101/104 I(min), I(max), I(mean) and I(inst) 9 phases 9 Type Frequency RF output Communication media Communication protocol Type Number of HV lines monitored per DCU mechanical Large enclosure Small box Cabinet Earth fault indication 10 Phase fault or Imax b Phase fault indication (phase A, B, or C), (beginning time, ending time) 11 Transient fault detection if enabled Voltage loss indication Transient fault indication and time stamping 8 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 Equipment monitoring Local radio communication faulty FPI battery alarm DCU U battery alarm AC supply alarm Inputs Outputs Local archive of Date and time stamped events and measures Downloading of local archive Power supply Operating temperature Storage temperature Mechanical Large enclosure Small box Cabinet Dimensions in cm Net weight in kg 100 m (phase A, B, or C), (beginning time, ending time) Voltage loss indication (phase A, B, or C) and time stamping and Voltage recovery time indication Equipment monitoring Communication with FPI Nos. XX faulty (after a number of attempts) and time stamping Battery low in FPI no.x and time stamping Battery low in DCU and time stamping AC supply alarm External AC supply off 6 digital inputs 3 relay outputs 220 Vac/1 A 100 events Remote via SCADA application In built Battery of suitable rating -25°C to +70°C -40°C to +85°C Mechanical Large enclosure Small box Cabinet 430x330x200 8 kg 31 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A 28 29 30 31 32 Protection level Standards Vibrations and shocks test EMI/EFI immunity Salt spray and humidity tests IP 54 Standards IEC 68-2-6 and 68-2-29 IEC 801-3 and FCC Part 15 IEC 68-2-11 and 68-2-30 TECHNICAL DATA for FPI No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 25 26 27 28 Nominal operation Voltage Power Frequency Conductor diameter MV neutral arrangement Fault Detection Parameters Di trigger setting Current setting trigger value Transient fault detection Flash duration (user settable) Inrush transient duration Loss of voltage condition Fault confirmation Reset (Permanent Faults) Automatic power return reset Timer reset Manual reset Fault Indication Indication Light power Visible angle Standard total flash duration Battery Environment Operating temperature Storage temperature Protection level Test 7 TO 13 kV 50 Hz 5 to 25 mm Independent / Solidly earthed Short circuit withstand Dielectric test Site Condition Ambient Temperature Relative humidity Average annual rainfall Altitude 25 KA / 170 ms 125 KV 6-12-25-60-90-120-160A-Off 100-200-500-800A On / Off facility required 2-4-8-16 hours 3 Sec U < 45% Un Voltage drop within 70s after fault detection U > 70% Un during 70S 4-16 hours By magnet Red flash light 40 Lumens 360 deg. 400-800 hours Lithium with life > 10 years 0 to +85 deg. C 0 to +85 deg. C IP 54 IK7 0-50 deg C 10-100% 750 mm 300 m Max 32 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A 29 30 31 32 33 Wind pressure Technical description Rated operating voltage Rated frequency Trip current Fault current minimum duration 195Kg/m2 upto 30m 11 kV 50 Hz 30-500A 50 ms CODES AND STANDARDS:The equipment proposed to be designed, manufactured and tested in compliance with the latest version of IEC Standards. Electro-magnetic compatibility IEC-61000-6-2 and FCC part 15 IP65 Protection level IEC-60529 Damp Heat cycle Test (Humidity & Heat cycle ) IEC-68-2-30 Salty fog IEC-68-2-11 Sinus wave vibration & Shocks IEC-68-2-6 , IEC-68-2-29 Dielectric Test IEC 60060-1 Temperature aging IEC-68-2-14 Short circuit ANSI 495 (part 4.4.8) EMI / EFI immunity IEC -801 Device Enclosure IP 65 SCADA compatibility of FPIs: The FPI should be provided with provision of necessary terminal blocks which shall be used for connecting the DCUs for automations as mentioned in below table: O/C operated Potential free contact E/F operated Potential free contact Fault passage indicator OK Potential free contact Command for reset FPI Potential free contact 1.7Additional requirements – 1.7.1 For FPIs there shall be four types of resetting facility a) Self reset after set reset time b) Self reset time after restoration of voltage c) Manual d) Remote resetting from SCADA control centre 33 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A 1.7.2 Radio Frequency connectivity shall carry the data between the FPIs and the base control unit (DCU). 1.7.3 FPI should be able to communicate to remote SCADA system using standard protocols like modbus/IEC-103 over long range communication medium (GPRS/CDMA) 1.7.4 It should be able to generate Digital Indications to be sent to remote location SCADA system. Simultaneously, it should have Digital Output facility to execute the resetting commands from SCADA/ Local point along with the timer based self resetting feature. Marking Each Fault Passage Indicator shall carry a weather and corrosion proof plate indicating the following particulars. - Manufacturer’s identification. - Model or type number (as per catalogue) - Year of manufacture in characters big enough to allow reading from the ground so that to provide indication of battery age. - Last date of completion of Guarantee period 1.8 Environmental specifications 1.8.1 Mechanical resistance to vibration and shocks 1.8.2 The equipment shall have vibration resistance in accordance with 1.8.3 IEC 60068.2.6: 10 to 500 Hz; 0.7 mm peak to peak from 10 to 59Hz and 5g from 59 to 500 Hz. 1.8.4 IEC 60068.2.27: 40g / 6 ms / 2000 positive and 2000 negative shocks in each direction, in the three directions. 1.9 Dielectric withstand IEC 61010 Insulation (50 Hz/1 min.): 2 kV EN 60-950 Impulse wave (1.2/50 µs): 5 kV/IEC Equivalent 2.0 Electromagnetic compatibility Electrostatic discharge IEC 1000-4-2 Level 3 Radiated fields IEC 1000-4-3 Level 3 Radio frequency IEC 1000-4-6 Level 3 Magnetic immunity, 50 Hz, IEC 1000-4-8 Level 4 Emissions EN 55011 Class A/IEC Equivalent 2.1 Environment Operating temperature: -25°C to +70°C Storage temperature: -40°C to +85°C Humidity: 95% at 40°C 2.2 Documentation Each device shall be supplied with a user manual for installation and commissioning on site. TRAINING: The supplier shall give rigorous training to the engineers & staff for 3 days for 8 persons in attending trouble shooting and maintenance at owners premise in the field after successful installation. Training should be at free of cost 34 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A Guaranteed Technical Particulars for OVERHEAD INDICATOR(Mandatory To be submitted by Bidder): S.No. DESCRIPTION A Application 1 Type 2 Distribution Network Voltage 3 Power Frequency 4 Short – circuit withstand 5 HV Neutral arrangement 6 Diameter 7 License Free Radio Frequency B Fault detection parameters 8 Current setting Trigger value 9 Transient faults detection 10 Minimum impulse time 11 Beacon Flash Indication Duration (user settable) 12 Inrush transient restraint C Reset (Permanent Fault) 13 Automatic Power Return 14 Timer Reset 15 Manual Reset D Fault indication 16 Indication 17 Light Power 18 Visibility Angle Degree 19 Flash Period for permanent Faults 20Flash Period for transient Faults 21Standard total flash Duration E Power Supply 22 Battery 23 Life of the Battery Years F Environment 24 Operation Temperature 25 Storage Temperature 26 Protection Level G Mechanical 27 Wind Resistance 28 Weight 29 Dimensions Units FAULT PASSAGE To be specified by Bidder KV Hz kA/ms As per the Bidder A M sec Min Sec A Min Lumens Sec Sec Hrs Deg C Deg C Kg/sq.mm. Kg Mtr H DCU 30 Event storage capacity Events 35 | P a g e TENDER NO:MGVCL/RAPDRP/SCADA/222A 31 Dimensions 32 Net Weight 33 Battery back up duration to run Without AC supply cm kg Hrs SIGNATURE OF TENDERER NAME: DESIGNATION: Add more sheets if required ANNEXURE 1 FRTU requirements with respect to RMU A. Introduction: The purpose of the document is to specify FRTU requirements with respect to RMU equipment. The requirements can be broadly specified as; 1. Space for mounting FRTU. 2. Mounting holes. 3. ‘SCADA Interface’ module. 4. 24V DC 200VA auxiliary power source with earthing point. All these are to be provided in RMU Cabinet/Panel. B. Mounting requirements: For the purpose of safety and compactness it is required that FRTU be mounted in RMU cabinet so, suitable mounting space for FRTU to be provided inside cabinet. The size of FRTU and typical arrangement of FRTU is as shown in Appendix-1. Since the FRTU will be mounted inside the panel, mounting holes are to be provided. The mounting hol es can be provided on a mounting plate or any other suitable arrangement. The details of mounting holes are shown in Appendix-1. C. Connectivity requirements: The connectivity of signals between FRTU and RMU is required to be hardwired instead of serial communication. Since connectivity of FRTU with the RMU will be hardwired signals, all the I/O signals required for SCADA are to be terminated on the ‘SCADA Interface’ module. 36 | P a g e
© Copyright 2024