DAP IO DNP3 Substation I/O module Substation automation I/O module

SUBSTATION AUTOMATION PRODUCT SOLUTIONS
DAP IO
DNP3 Substation I/O module
The next generation
input/output module for
substation automation and
SCADA RTU applications
Substation automation I/O module
for your Smart Grid applications
Leveraging the latest technology in microprocessors, communications and applications,
the Alstom DAP IO is the next-generation input/output (I/O) module for substation
automation and SCADA RTU applications. The DAP IO module can be deployed with
Alstom's DAPserver as a standalone RTU or integrated with IEDs to form a substation
automation system. It can also be used to replace legacy RTU I/O modules with
minimal field wiring changes. DAP IO is the most practical and cost effective solution
for substation RTU and automation upgrades and retrofits.
NEXT GENERATION I/O MODULE
The next generation of input/output modules for electrical utility automation
Substation automation
Primary equipment monitoring
CAPTION_lorem ipsum
Distribution automation
APPLICATIONS
CUSTOMER BENEFITS
Next-generation of control
I/O modules
Legacy I/O replacement
with terminal block
alignment and minimal
field wiring required
New substation RTU I/O deployment
Legacy RTU I/O expansion and replacement
I/O modules for integrated substation control systems
I/O modules for primary equipment monitoring
I/O modules for distribution automation, e.g.:
• On-Load Tap Changer (OLTC) interface
• Capacitor bank interface
• Voltage regulator interface
Upgrade legacy equipment
with added features and
increased performance
© ALSTOM 2014. All rights reserved.
Four hardware
configuration models
available for optimal
adaptation to your project
Grid-SAS-L3-DAP IO module_DNP3-3133-2014_09-EN. Information contained in this document is indicative only. No representation or warranty is given or
should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly
prohibited. Alstom contributes to the protection of the environment. This leaflet is printed on environmentally friendly paper.
FEATURES
FOUR I/O MODULE TYPES
LED indicators
Compression terminal blocks
DAP-MIO (mixed I/O module)
- Digital inputs x16
- Analog inputs x16
- Control outputs x8
Option: plug-in terminal blocks
3U rack/panel
compact profile
DAP-DI
- Digital inputs x64
DAP-AI
- Analog inputs x32
Local/Remote switch
Digital Inputs
Analog Inputs
Positive/negative polarity
20-60 Vdc (5 mA),
90-290 Vdc (2 mA)
1 ms time-stamp event
±1-20 mA current inputs (0.1%)
±5-10 Vdc voltage inputs (0.05%)
DAP-CO
- Control outputs x32
Control Outputs
Trip/close control outputs,
Form-C control outputs, with:
- V/I supervision on last two, or
- dual-polarity control outputs
SCADA / EMS / DMS
SCADA / IP NETWORK
DAPserver automation system
Standalone RTU
Substation HMI
DAPmini upgraded
legacy RTU
DAP-100
DAP-IO
modules
DAP-IO modules
Multi-vendor IEDs
SUBSTATION AUTOMATION PRODUCT SOLUTIONS
DAP IO
COMMUNICATION INTERFACE
Redundant-switched Ethernet ports
Redundant 10/100 Mbps Ethernet
switched ports (RJ-45)
Switched ports can be daisy-chained
to other I/O modules
10/100 Mbps LAN #1
LAN #1 Switched Port
DNP3 protocol support
10/100 Mbps LAN #2
LAN #2 Switched Port
POWERFUL TOOLS
DAPserver Studio - configuration,
maintenance and diagnostic tool
Local access - USB port
Remote access - Ethernet LAN
USB 2.0 port
DAISY-CHAINING I/O MODULES
DAPserver
LAN #1
LAN #2
DAP IO
DAP IO
DAP IO
DAP IO
SUBSTATION AUTOMATION PRODUCT SOLUTIONS
DAP IO
DAP IO ORDER GUIDE
1st digit "u"
Termination
2nd digit "v"
Control Output
3rd & 4th digit "ww"
Analog Input
5th digit "x" 6th digit "y" 7th digit "z"
Digital Input Power Supply Ethernet
Part Number
DAP-MIO
DAP-DI
DAP-AI
DAP-CO
IO-uvwxyz
DI-uvwxyz
AI-uvwxyz
CO-uvwxyz
DESIGNED FOR SUBSTATION
IEEE 1613 communication networking devices
IEEE C37.90 relays for electrical power apparatus
IEEE 1686 cyber security
IEEE 1588 / IEC 61588 Precision Time Protocol (PTP)
IEEE 1815 DNP3 protocol
IEC 60870 telecontrol equipment and systems
IEC TS 61000-6-5 immunity for power station & substation
IEC 60255-5 relay insulation
IEC 61010-1 safety
UL/CSA safety
CE electromagnetic compatibility & low voltage safety
For more information
please contact Alstom Grid:
RoHS/WEEE/REACH
-40°C to +85°C operating range
Alstom Grid - SAS Calgary
#8, 2121 - 29th Street NE
Calgary, Alberta, Canada T1Y 7H8
Phone (North America): +1 403 569 1680
© ALSTOM 2014. All rights reserved.
Alstom Grid Worldwide Contact Centre
www.alstom.com/grid/contactcentre/
Phone: +44 (0) 1785 250 070
Picture caption
Grid-SAS-L3-DAP IO module_DNP3-3133-2014_09-EN. Information contained in this document is indicative only. No representation or warranty is given or
should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly
prohibited. Alstom contributes to the protection of the environment. This leaflet is printed on environmentally friendly paper.
Visit us online: www.alstom.com