CHAPTER 7 Practical Aspects of Installation Design 7.1 Design Stages for Electrical Installations In the previous chapters some basic requirements of Regulations related to supply and distribution systems were explained. In this chapter practical aspects of installation design to determine cable sizes and PD ratings for all types circuits will be outlined. The order of the design follows the steps. 1. Establish details of circuits to determine levels of distribution (power, main, sub-main, load levels) in the installation (STAGE 1). 2. Determine design current in each levels starting from final circuits (STAGE 2). 3. If it is required, apply necessary corrections on design currents for temperature, grouping etc (STAGE 3). 4. Determine current ratings of PDs and cable sizes in each level according to type of overcurrent protection (STAGE 4) 5. Calculate voltage drop along the longest final circuit from intake position (STAGE 5) 6. Determine earth fault impedance to check electrical conditions Fundamentals of Electrical Installation 35 for safe operation against electrical shock (Chapter 5 and 8) 7. Check short circuit conditions for conductor temperature rise (Chapter 8) 7.2 Establish Details of Circuits to Determine Levels of Distribution (Stage 1) After deciding on divisions and subdivisions of the building and locations of distribution boards (DBs) and sub-distribution boards (SBD), it is necessary to divide installations into a number of circuits independent of its size. Dividing circuits into several levels have several advantages. (i) It provides - safe operation and easy handing of cabling and PDs during operation - easy maintanence (ii) It eliminates requirements for - voltage drop - earth fault impedance (iii) It avoids hazardous situations arising during usage of installation. Example cases for advantages achieved with leveling installations: - In small installations, it is advisable to supply lighting circuits from different PDs, such that in the case of tripping of one PD under fault conditions eliminates total blackout. Also a separate ring circuit is installed in kitchen apart from other ring circuits serving other parts of the premise. - In larger commercial or industrial installations leveling of circuits must be carefully planned to handle different types of loads such that in case of a fault, number of loads to be interrupted is minimized. In large installations such as workshops or factory halls, power and lighting need may be supplied from different DBs. Such division (Fig. 7.1) - In all installations, it is economical to distribute power considering load density. This provides considerable cable and labour cost saving other than the electrical advantages explained above. Practical Aspects of Installation Design (lighting) SDB DB Main DB Sub-main supply cable Final circuits Intake from secondary S/S (power) Supply cable (for DB) Final circuits 36 Main supply or service cable DB DB Power level Main-distribution level Sub-distribution level Load level Figure 7.1 Leveling an installation. Leveling of circuits should be based on; - type of load - power rating of equipment - distances of load or loads to the main DB. A layout of leveling of circuits is shown in Fig. 7.1. Note that a cable supplying a DB is named with the same as that of the DB, i.e., the cable supplying a SDB is named as sub-main cable and like. In a mult-floor office building design, for example, load level includes all final circuits supplying small fixed and portable loads. These loads are fed from the DB located in the DB or electrical room at every floor, and this DB together with the others are supplied from busbar trunking system via tie-off. The busbar is fed from the main distribution board at main distribution level. 7.3 Determine Design Current (Stage 2) In order to decide on the type of supply intake it is necessary to estimate the total power demand of the installation. The procedure starts with calculating design current at; Fundamentals of Electrical Installation 37 (i) load level for each final circuit to determine cable size of DB supply cable, (ii) sub-main distribution level from total power demand of all DBs to determine cable sizes of sub-main cables, (iii) main distribution level from total power demand of all sub-main DBs to determine cable size of main distribution cables, and (iv) power level from total power demand of all connected main DBs to determine cable size of service cable and power rating of secondary distribution transformer. Determining design current of is although is a straightforward procedure, sometimes it needs judgment of the designer. In domestic premises for example, as the design current of the ring circuit, diversified demand for the ring socket-outlet circuit, may be taken as half of current rating of PD, however, in some circumstances, the power ratings of equipment likely to be installed, may need to be taken as base values for the design. Power Ratings of Electrical Apparatus The power rating of an apparatus is commonly expressed as the amount of real power required to perform a certain task. This rating is given in watts or kilowatts. Associated with it usually voltage, frequency and efficiency are also specified by the manufacturers. Ratings of some domestic appliances are given in Table 7.1. Conductor sizes of cable and ratings of current-carrying components are usually expressed in table forms in terms of their current ratings. Cable sizes and ratings of current-carrying components such as PDs, switches, socket-outlets, plugs etc., must be large enough to carry the maximum current of the connected apparatus without overheating or being overstressed. Therefore, current rating of a cable and any component should be selected relatively larger than design current value in accordance with the design and protection rules. Practical Aspects of Installation Design 38 Table 7.1 Power ratings of some domestic appliances. Appliance Power rating (watts) Lamps (filament) 15, 25, 40, 60, 75, 100, 150 Lamps (fluorescent) 15, 20, 30, 40, 50, 65, 75, 85 Water heaters 3,000 - 6,000 Washing machines 2,500 - 3,000 500 - 1,500 Refigerators 5,000 - 7,500 Cookers 100 - 3,000 Vacuum cleaners 1,500 - 2,000 Irons EXAMPLE 7.1 A three-phase 22.5 kW, 415 V and 50 Hz motor load is supplied through 180 m long 3-core copper cable. The efficiency of the motor is 87 percent at PF= 0.72 lag. Calculate design current of the final circuit. Solution. Input power to the motor is 22500 Pin 25860 W 0 .87 The design current becomes Ib 25860 50 A 3 ( 415 )( 0.72 ) EXAMPLE 7.2 A three-phase DB supplies a workshop at 240 m distant. The connected motor loads are 80 kW at 0.7 PF lag and 25 kVA at 0.8 PF lag The voltage at the workshop is to be maintained at 415 V. Determine design current in each final circuit and of the main supply cable. Solution. The design current for each load is; Load 1: Load 2: I b1 I b2 P 3 VL L cos 25,000 3 (415) 80,000 3 (415)(0.7) 34.7 A 159.2 A Fundamentals of Electrical Installation 39 where, VL-L is the line-to-line voltage at motor terminals. The total design current of the supply cable to DB becomes Ib1= Ib1 /-1+ Ib1 /--2=159.2 /-45.5+ 34.7 /-37.8 = 139.3/-134.4o A 7.4 APPLY NECESSARY CORRECTIONS ON DESIGN CURRENTS AND DETERMINE CABLE SIZES (Stage 3) Determining Nominal Current Rating of Protective Devices The nominal current rating of a protective device is based upon the designed current for a given load as calculated above. The rating of the protective device should be chosen close to this value. The Regulation demands that the nominal current of the PD shall not be less than the designed current value of the circuit. That is, In Ib (7.1) The rating of PD should be chosen as close as possible to this value. Tables 41B1, 41B2, 41C and 41D given in IEE Regulation provide data for selection of standard current ratings for PDs, and are covered in Section . EXAMPLE 7.3 A distribution board feeds six separate group of lamps used for external lighting lamps. Each group consists of eight twin 85 W fluorescent lamps. Each circuit is to be protected by Type 1 to BS 3871 MCB. To account for the control gear losses the designed current should be upgraded by a factor of 1.8. Select a suitable current rating for the MCB to protect the circuit. Solution. The total load connected to each lighting circuit for 8 twin 85 W fluorescent lamp is: P=8 (2) (85) = 1360 W Including the control gear losses P becomes P = 1.8 (1360) = 2448 W Designed circuit current, Ib = 2448/240=10.2 A Practical Aspects of Installation Design 40 From IEE Table 41B2, the nearest current rating for the MCB is 15 A. Regulation requires that the effective current carrying capacity Iz of a cable conductor shall not be less than the maximum sustained current normally carried by the conductor, Ib. Thus, (7.2) Ib Iz Combining with the relation given for the nominal current rating, In, of a PD (Eq. (7.1), we have Ib In Iz (7.3) Factors Affecting Current-Carrying Capacity of Cable Conductor Regulations provide current-carrying capacities of cables based on (a) the conductor material (b) the insulation material However, the effective current-carrying capacity of a cable conductor is modified by (i) Ambient temperature, Ca (ii) Grouping, Cg (iii) Thermal insulation, Ci (iv) Disposition (method of installation) (v) Class of excess-current protection The cable rating should be modified for each of these effects as applicable. That is, when insulation conditions differ in more than one respect from those given in the appropriate table, a separate factor for each special circumstance must be applied. The correction factors upgrade the design current value, hence, appears as divisor. (i) Ambient temperature. The current ratings given in tables for cables are based on an ambient temperature of 30oC. Where the ambient air temperature exceeds this figure, such as in tropical countries or in a boiler house, the appropriate correction factor Ca should be applied to derate the cable. The necessary correction factors are given in IEE Tables 4C1 and 4C2. If the ambient temperature will not be less than 25oC, the cable rating is increased up to 1.04. In order to account temperature rise due to direct solar radiation, 20oC should be added to the ambient temperature and the appropriate correction Fundamentals of Electrical Installation 41 factor used when determining the current carrying capacity of the cable. (ii) Grouping. If a number of cables run together in close proximity to one another such as in a conduit or trunk, their current-carrying capacity is reduced. This is because the heat developed during the normal operation is trapped in the enclosure. The related correction factor Cg is applied from IEE Tables 4B1, 4B2 and 4B3. Correction factors given in dependent upon the type of installation method used. If the cables are arranged so that there is a space of one diameter between them, increased factors under the title "spaced" may be applied, and if spacing of two diameters between cables can be achieved, no grouping factor need to be used. See footnotes of Tables 4B1 and 4B2 for corrections according to cable dispositions. (iii) Thermal Insulation. If a cable run passes through thermal insulating materials, such as those used in roof spaces and wall cavities, which are fully covered or surrounded with thermal insulation, ability of the cable to radiate or shed heat is reduced. Even the cable is in contact on one side with a thermally conductive surface. As a result its temperature increases hence, it requires usage of a larger size cable. To account this increase the cable rating must be corrected by the factor Ci given in IEE Table 52A for a given length of the insulating material. For example a derating factor of 0.55 applies if a part of the cable 40 long Iis covered with a thermal insulation material. h Thermal insulating material Wall cavity Cable h Wall cavity Non-metallic sheeth Figure 7.2 Cases for which correction for thermal insulation apply. (iv) Method of Installation. Method of installation is one of the factors determining current carrying capacities of all single core (CU/PVC or CU/XLPE) and multicore (PVC/PVC/SWA/PVC or XLPE/SWA/PVC) Practical Aspects of Installation Design 42 armoured or non-armoured cables. Cables can be laid direct in the ground, in ducts, or fixed to the surface on a cable tray, or fixed to the structure by cleats. IEE Table 4A summarizes the existing methods applied in lying cables. The installation methods are basically grouped according to cable enclosures and surroundings. They are given in Table 7.2. As noticed in Tables 4D1A, 4D2A and 4D4A, the choice of installation method has a marked effect on current-carrying capacity of cables. For example, from Table 4D2A it can be estimated that current-carrying capacity of 2 2.5 mm three-core non-armoured cable installed in conduit (Method 3) is 83% of that for the same cable mounted directly on a wall (Method 1). Table 7.2 Summary of cable installation methods (IEE Table 4A) Reference Installation Procedure Method(s) Open or direct clipped 1 Embedded direct in building materials 1 Enclosed in conduit or in trunking a wall or ceiling 3 Enclosed in conduit or in trunking in a wall or ceiling but thermally insulated 4 On trays 11 or 13 Trenches 3, or 4 12 or 13 18 or 19 or 20 In air, on cleats, brackets or a ladder 12 Sometimes along the route of a cable one method of installation for part of a cable route and another method for the reminder is applied. For example, if a part is installed underground and the other part in air, the currentcarrying capacity shall be determined from the part producing higher cable cross section. (v) Class of excess-current protection. Certain thermoplastic materials (e.g. PVC) deteriorate if subjected to sustained high temperatures. Therefore, the current rating of cables insulated with PVC or synthetic rubbers are determined not only by the maximum conductor temperature allowed for continuos rating Fundamentals of Electrical Installation 43 but also by the probable duration of excess current. If a cable is protected by a semi-enclosed (rewirable) fuse to BS3036, the current ratings stated in tables must be derated by applying the factor 0.725. This is due to the longer operating time of semi-enclosed fuses. Overall Correction for Current-carrying Capacity of a Cable Conductor As can be seen from the ongoing notes on derating affects on current-carrying capacity of a cable, a number of correction factors are applied. As one factor may be applied for one condition, more of them may also be applied to the same cable. In this case, if the overloading is not allowed, the designed current value of the circuit is divided by each of these factors as (I b )c I b . 1 1 1 1 . . . C a Cg Ci 0.725 (7.4) where Ca a is correction factor for ambient temperature Cg is correction factor for grouping Ci is correction factor for thermal insulation In this case to select the appropriate cable size, the tabulated current-carrying capacity It, should be compared with (Ib)c, that is, It (Ib)c (7.3) EXAMPLE 7.4 A three-phase 25 kW, 415 V furnace load is to be protected by a semi-enclosed fuse. The connecting cables are multi-core and non-armoured and are clipped onto a perforated metal cable tray and touching with two other single-phase circuit cables on the tray. Determine fuse rating and cable size. Solution. The designed current of the load is Ib =25,000/[3 (415)] =34.7 A (a) From Table 41B1, the nominal rating of the fuse is 45 A Practical Aspects of Installation Design 44 (b) From Table 4B1, for three circuits a grouping factor of 0.81 must be applied, so the cable must be able to carry (I b ) c 34.7 / 0.81 Since protection is to be provided by a semi-enclosed fuse, applying the necessary correction, the cable must be able to carry the current I b c 34.7 59.22 A 0.81( 0.725 ) The appropriate cable size, It can be selected from Table 4D2A for the reference Method 11 using Eq. (7.5), i.e. It 59.2 A yields the tabulated current value of 60 A, which corresponds to conductor size of 10 mm2. EXAMPLE 7.5 A 5 kW, 230 V water heater is to be wired with PVC-insulated single-core cables through PVC conduit. The conduit is thermally insulated from a hot water pipe over 15 cm of its length. If the proposed isolation is for a boiler house where temperature is normally 40oC, determine the size of cable. Solution. The designed current of the circuit is, Ib =5,000/230 = 21.7 A. Correction for thermal insulation on Ib is performed taking h=15 cm and applying Ci= 0.68 (Table 52A). The ambient temperature is accounted by applying the correction factor Ca= 0.87 (Table 4C2). Therefore, the corrected designe current Ib becomes I b c 21.7 36.6 A 0.680.87 The cable size may be selected from Table 4D1A according to reference installation Method 3, hence It 36.6 A and the appropriate cable size is 6 mm2. 7. 5 DIVERSITY FACTOR (IEE Reg. 311) It is a factor usually applied to industrial loads supplied from a DB to determine size of cable conductor of supplying DB. It is also applied for large scale residential and commercial commercial loads. The size of a cable or accessory is not necessarily determined by the total power rating of all the current consuming devices connected to it. It depends Fundamentals of Electrical Installation 45 on what percentage of the connected load is likely to be operating at any one time, or the "diversity" of the loading. That is, the ratio of real power of the load used at any time to the value of the real power of the connected load. For any load it may be expressed as (7.9) P DF u Pc where Pu is average power used by the load at one time and Pc is the value of connected load For example, if n different loads are connected to a submain cable, each rated with (Pc)1 ...,( Pc)n and power used by each load at any one time is (Pu)1 ...,( Pu)n respectively, diversity factors applied to individual loads are DF1 ( Pu )1 (P ) ,..., DFn u n ( Pc )1 ( Pc ) n (7.10) and to the submain is n ( Pu ) i DF i 1 n ( Pc ) i (7.11) i 1 where (Pu)i is average power used by i-th load at one time and (Pc)i is the value of each connected i-th load In assessing the maximum current demand of circuits, allowances for economical installation design diversity is permitted, but should also be used with care for any particular installation. Its usage needs a degree of experience and knowledge about the type of installation, and should be decided by the engineer responsible for the design. Table 1B of IEE On-Site Guide gives approximate maximum current values that are expected to flow in an installation and may be increased or decreased for any given installation. - In calculating maximum current demand of radial or ring circuits Practical Aspects of Installation Design 46 supplying many socket outlets half of the nominal rating of PD or 400 W per socket can be taken as diversified load for the circuit. For example, if 8 socket outlets are connected to a ring circuit, diversified demand may be taken as 30/2= 15 A or 8 x 400 W /240 = 14 A. - For an appliance manufactures data or 80-90% of power rating of the load may be taken as diversified current demand of the load. EXAMPLE 7.6 For a flat comprising the loads indicated in the following table, calculate the maximum expected demand of the submain cable supplying the loads. Connected load Lighting Cooking appliance Total Demand (A) Diversity limit 15 - 25 10 Applied diversity factor 9.9 66 % +30% of fl in excess of 10+7.5 10 A Heating 18 10 +50% of any current excess of 10+4 +50% of any current 10+5 demand in A/C (same as heating and power) Installed ring circuit feeding 8 socket outlets 10 10 A demand in 30 (20) - Maximum expected demand (A) excess of 10 A 15(10) or 13.3 Half of the maximum demand or 400 W Total demand (A) 108(98) Diversified demand (A) 68.4 (63.4) or 66.7 When calculating voltage drop in a circuit or feeder cable to a group of circuits, the current demand can be used after diversity has been taken into account. 7.6 DETERMINATION OF THE SIZE OF CABLE ACCORDING TO TYPE OF PROTECTION (STAGE 4) Having established the design current (Ib) of the circuit, determination of the conductor size is related to cable overloading and its protection. (i) Overload protection is not required Fundamentals of Electrical Installation 47 The cable under consideration is not required to be protected against overload. In this case the design current of the circuit (Ib) is to be divided by any appropriate correction factors, the size of the cable to be wired is to be such that its tabulated current-carrying capacity (It) for the installation method concerned is not less than the value of Ib as given as It Ib. 1 1 1 . . C a C g Ci (7.6) (ii) Overload protection is required For single circuits this condition is met by dividing the nominal current of the protective device (In) by any applicable correction factor such that the size of cable to be used is to be such that its tabulated current-carrying capacity (It) is not less than the value of the nominal current of the PD adjusted as in Eq. (7.6): 1 1 1 It In. . . Ca C g Ci (7.7) If the circuit to be protected by a semi-enclosed fuse to BS 3036, the right hand side of the inequality given in Eq. (7.7) should be further divided by 0.725 to correct cable size for longer trip-off time of the fuse. If grouped cables are not simultaneously overloaded, grouping factor Cg may be expressed by the formula It In 2 2 2 1 Cg ) 0 . 48 I b ( Cg2 (7.8) EXAMPLE 7.7 A three-phase 17 kW, 415 V at 0.866 lag motor load is to be wired with a four-core PVC insulated non-armoured cable. The cable is directly clipped on a metal tray where there are Practical Aspects of Installation Design 48 two other three-phase circuits wired with similar cables. All cables are touching to each other. Determine the cable size and rating of MCB (BS3871 type 1) for cases; (i) overloading is not required and (ii) overloading is required. Solution. The design current of the circuit is 17,000 Ib 27.31 A 3 (415)(0.866) From Table 41B2 rating of the MCB can be selected as 30 A. Also from Table 4B1, the correction factor for grouping of multicore cables installed as single-layer on a metal tray and touching to each other is Cg=0.81. (i) Since overloading is not required, from Eq. (7.6), It 27.31 33.7 A 0.81 Referring to Table 4D2A with reference to installation Method 11, the current-carrying capacity of the cable is 34 A and its size is 4 mm2. (ii) Similarly if overloading is to be afforded, from Eq. (7.7) we have It 30.0 37.03 A 0.81 From Table 4D2A, this results in the cable size of 6 mm2 which corresponds to currentcarrying capacity of 43 A. 7.7 VOLTAGE DROP ALONG FINAL CIRCUITS (STAGE 5) (IEE Reg. 525.01) The resistance of a conductor increases as the length increases and/or as the csa decreases. Associated with an increase in length is a reduction in voltage at the receiving end of the cable run. This reduction is dependent on the impedance of the cable, values of which are given in mV/A/m. The Regulation requires that the voltage drop should not be so high that equipment does not function safely. The allowed voltage drop should be no more than 4% of the nominal voltage at the origin of the circuit. This means that: Fundamentals of Electrical Installation 49 1. For single-phase 240 V, the voltage drop should not exceed 4% of 240 V = 9.6 V. 2. For three-phase 415 V, the voltage drop should not exceed 4% of 415 V= 16.6 V. EXAMPLE 7.8 A 4 kW, 240 V at 0.9 lag washing machine is supplied by a 40-m long single-core cables installed through conduit. If no correction is applied to the design current, calculate the voltage drop for permissible limits. It 4,000 Solution. The design current is 18.5 A 240(0.9) This requires 20 A MCB (type 1). Since the cable is enclosed in conduit and if overloading is not required, from Table 4D1A, the size of the cable becomes 2.5 mm2. Reading from the voltage drop Table 4D1B, the voltage drop of the cable 15 mV/A/m. The voltage drop along the circuit may be calculated as Vc (mV I b L)10 3 (5 18.5 40)10 3 11.1 V This voltage drop exceeds 4% (9.6 V) and so is not satisfactory. The next largest cable size will be used instead, which is 4 mm2 with a voltage drop of 9.5 mV/A/m. Hence, repeating the calculation the voltage drop along the cable now becomes Vc = 9.5(18.5)(40) 10-3 = 7.03 V This result is within the voltage limit required. If the load has a power factor less than unity, for cables up to 16 mm2, the voltage drop figures in mV/A/m given in the regulation tables are directly used. However, for cables having sizes larger than 16 mm2, the voltage voltgae drop is approximately calculated using resistive r and reactive, x components of the cable impedance z in the formula: V (r cos x sin ) L I 10 3 volts where (r cos +x sin) is in mV/A/m and L is the length of the cable in meter. 50 Practical Aspects of Installation Design EXAMPLE 7.9 A 415-V wye-connected 105 A fan motor at PF=0.8 lag is to be fed along a 65 m long Cu/PVC/SWA/PVC armoured multi-core cable installed on cable tray. What should be the size of the cable in order to keep the voltage drop along the cable less than the limiting value? Solution. From Table 4D4A and column 5, 25 mm2 cable is sufficient to carry the load current 105 A. From the voltage drop table Table 4D4B, the resistive and reactive components of the cable impedance are r=1.5 mV/A/m and x=0.145 mV/A/m respectively. Finally, the voltage drop along the cable becomes V=[0.8(1.5)+0.6(0.145)] (65) (105) 10-3 = 8.783 V which is less than the acceptable voltage limit.
© Copyright 2024