SIRCOVER ATS Bypass Manual transfer switches from 125 to 1600 A The solution for svr_133_a Transfer switches > Industry > Healthcare buildings Strong points SIRCOVER ATS Bypass I-0-II 12+4P > > > > Function SIRCOVER ATS Bypass switches are manual four pole transfer switches with positive break indication. They are designed to isolate ATS type electrical equipment (automatic transfer switch) or UPS, with minimum interruption to the load supply. Integrating a SOCOMEC transfer switch into the installation enables source selection when in Bypass (see operating principle below). Stable positions Secured breaking On load switching A complete solution Conformity to standards > IEC 60947-3 Advantages Secured breaking Simultaneous upstream and downstream isolation and fully visualised breaking. Stable positions SIRCOVER ATS Bypass switches have 3 stable positions which are not affected by voltage drops or vibrations. A complete solution The SIRCOVER ATS Bypass is a single product offering a genuine solution incorporating both an equipment isolation function and a switching function. On load switching Thanks to its AC-22 characteristics, tested in accordance with standard IEC 60947-3, the SIRCOVER ATS Bypass enables on load switching. Operating principle T2 T1 S2 S2 SIRCOVER I2 I1 S1 atys_569_d_1_gb_cat ATS S2 I3 BY-PASS ATS II Load 30 Changeover Switching solutions - Catalogue 2015 In Bypass position: • Without SIRCOVER: The load is supplied directly by one of the two power sources (transformer T1 for example). • With a SIRCOVER: The supply source can be selected. SIRCOVER ATS Bypass Manual transfer switches from 125 to 1600 A References Rating (A) No. of poles Switch body 125 A 12 + 4 P 4100 9813 Shaft for Direct handle External handle external handle Bridging bars Auxiliary contact Terminal shrouds Terminal screens 4P 4109 4019 160 A 250 A 12 + 4 P 12 + 4 P 4100 9816 4100 9825 S3 type Black IP65 I - O - II S3 type Black IP65 I - O - II 1433 3113 400 A 12 + 4 P 1433 3113 12 + 4 P 4100 9863 800 A 12 + 4 P 4100 9880 2694 4014 (2)(3) 1401 1520 320 mm 1401 1532 400 mm 1401 1540 4100 9840 630 A 4P 200 mm 4P 1509 4012(4) 4P 4109 4025 4P 4109 4039 4P 4109 4063 4P st 1 contact NO/NC included nd 2 contact NO/NC 2694 4021(2)(3) 4P 4P 1509 4025(4) 4P 2694 4051 (2)(3) 1509 4063(4) Please consult us 1509 4080(4) 4109 0021(1) 4P 4109 4080 1000 A 12 + 4 P 4100 9881 Black IP65 I - 0 - II Black 2799 7062 1250 A 12 + 4 P 2799 7147 4100 9882 Included with the external handle 4P 4P 4109 4160 1600 A 12 + 4 P 4100 9886 (1) 2 pieces: one for position I and one for position II. (2) To fully shroud front, rear, top and bottom 8 references required. (3) To shroud front switch top and bottom 4 references required. (4) For complete front protection, order the reference twice. Accessories acces_001_a_1_x_cat Key handle interlocking system Locking in position 0 with RONIS EL11AP (lock not supplied) Rating (A) Operation Figure Reference 125 … 630 direct 1 125 … 630 external 3 4109 1006 (1) 1499 7701 800 … 1600 direct and external 2 Please consult us Fig. 1 acces_132_a_1_x_cat (1) Specific handle included. Locking in positions I, 0, II with RONIS EL11AP (lock not supplied) Rating (A) Operation Figure Reference 125 … 630 direct 1 4109 1002 (1) 800 … 1600 direct 2 Please consult us (1) Specific handle included. acces_158_a_1_x_cat Fig.2 Locking with CASTELL K type lock (lock not supplied) Rating (A) Operation 125 … 630 external 800 … 1600 external Figure 3 Reference 1499 7702 Please consult us Fig. 3 Changeover Switching solutions - Catalogue 2015 31 SIRCOVER ATS Bypass Manual changeover switches from 125 to 1600 A Characteristics according to IEC 60947-3 125 to 1600 A Thermal current Ith at 40°C Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kV) 125 A 800 8 160 A 800 8 250 A 800 8 400 A 800 8 630 A 1000 12 800 A 1000 12 1000 A 1000 12 1250 A 1000 12 1600 A 1000 12 A/B(1) 1000/1000 1000/1000 1000/1000 1000/1000 1000/1000 800/800 800/800 200/250 1000/1000 1000/1000 1000/1000 1000/1000 1000(4)/1000(4) 1000(4)/1000(4) 1000(4)/1000(4) 1000(4)/1000(4) A/B(1) 1250/1250 1250/1250 1250/1250 1250/1250 1250/1250 800/800 800/800 200/250 1250/1250 1250/1250 1250/1250 1250/1250 1250/1250 1250(4)/1250(4) 1250(4)/1250(4) 1250(4)/1250(4) A/B(1) 1600/1600 1600/1600 1600/1600 1250/1250 1600/1600 1000/1000 1000/1000 500/500 1600/1600 1250/1250 1250/1250 1250/1250 1600/1600 1250(4)/1250(4) 1250(4)/1250(4) 1250(4)/1250(4) 710/710 475/475 Rated operational currents Ie (A) Rated voltage 415 VAC 415 VAC 415 VAC 415 VAC 690 VAC(2) 690 VAC(2) 690 VAC(2) 690 VAC(2) 220 VDC 220 VDC 220 VDC 220 VDC 440 VDC 440 VDC 440 VDC 440 VDC Utilisation category AC-20 A / AC-20 B AC-21 A / AC-21 B AC-22 A / AC-22 B AC-23 A / AC-23 B AC-20 A / AC-20 B AC-21 A / AC-21 B AC-22 A / AC-22 B AC-23 A / AC-23 B DC-20 A / DC-20 B DC-21 A / DC-21 B DC-22 A / DC-22 B DC-23 A / DC-23 B DC-20 A / DC-20 B DC-21 A / DC-21 B DC-22 A / DC-22 B DC-23 A / DC-23 B A/B(1) A/B(1) A/B(1) A/B(1) A/B(1) A/B(1) 125/125 160/160 250/250 400/400 630/630 800/800 125/125 160/160 250/250 400/400 630/630 800/800 125/125 160/160 250/250 400/400 630/630 800/800 125/125 160/160 250/250 250/250 500/500 800/800 125/125 160/160 250/250 400/400 630/630 800/800 125/125 160/160 200/250 200/250 500/500 800/800 125/125 125/125 125/160 125/160 315/315 800/800 63/80 63/80 100/125 100/125 160/200 200/250 125/125 160/160 250/250 400/400 630/630 800/800 125/125 160/160 250/250 250/250 630/630 800/800 125/125 160/160 250/250 250/250 500/500 800/800 125/125 125/125 200/200 200/200 500/500 800/800 125/125 160/160 250/250 400/400 630/630 800/800 125(3)/125(3) 125(3)/125(3) 200(3)/200(3) 200(3)/200(3) 500(3)/500(3) 800(4)/800(4) 125(3)/125(3) 125(3)/125(3) 200(3)/200(3) 200(3)/200(3) 500(3)/500(3) 800(4)/800(4) 125(4)/125(4) 125(4)/125(4) 200(4)/200(4) 200(4)/200(4) 500(4)/500(4) 800(4)/800(4) Operational power in AC-23 (kW) At 400 VAC without pre-break in AC(1)(5) At 690 VAC without pre-break in AC(1)(5) 63/63 55/75 80/80 55/75 132/132 90/110 132/132 90/110 280/280 150/185 450/450 185/220 710/710 185/220 710/710 185/220 55 75 115 185 290 365 575 575 100 160 50 250 18 400 70 630 50 800 100 1000 100 1250 100 2 x 800 Reactive power (kvar) At 400 VAC (5) Fuse protected short-circuit withstand (kA rms prospective) Prospective short-circuit (kA rms)(6) Associated fuse rating (A)(6) 100 125 Circuit breaker protected short-circuit withstand with any circuit breaker that ensures tripping in less than 0.3s(7) Rated short-time withstand current 0.3s Icw (kA rms) 15 15 17 17 25 50 65 65 100 125 A 8 160 A 8 250 A 9 400 A 9 630 A 14 800 A 27 1000 A 36 1250 A 36 75 1600 A 50 75 35 50 95 185 25 9 50 25 9 95 32 20 150 32 20 2 x 150 2 x 30 x 5 240 50 20 2 x 185 2 x 40 x 5 2 x 300 63 20 2 x 60 x 5 2 x 300 63 20 2 x 60 x 5 2 x 300 63 20 2 x 80 x 5 4 x 185 100 40 10 000 8.3 10.6 10 000 8.3 10.6 10 000 10 11.7 10 000 10.3 12.4 5 000 20.7 24.8 3 000 44.3 53 3 000 45.4 54.4 3 000 46.4 55.8 3 000 54.7 67.3 Short-circuit capacity (without protection) Thermal current Ith at 40°C Rated short-time withstand current 1s Icw (kA rms) Rated short-circuit making capacity Connection Minimum Cu cable cross-section (mm2) Minimum Cu busbar cross-section (mm2) Maximum Cu cable cross-section (mm2) Maximum Cu busbar width (mm) Tightening torque min (Nm) Mechanical characteristics Durability (number of operating cycles) Weight of 3 P switch (kg) Weight of 4 P switch (kg) (1) Category with index A = frequent operation Category with index B = infrequent operation. (2) With terminal shrouds. (3) 3-pole device with 2 poles in series for the "+" and 1 pole for the "-". (4) 4-pole device with 2 poles in series per polarity. (5) The power value is given for information only, the current values vary from one manufacturer to another. (6) For a rated operational voltage Ue = 400 VAC. (7) Value for coordination with any circuit breaker that ensures tripping in less than 0.3s. For coordination with specific circuit-breaker references, higher short-circuit current values are available. Please consult us. Connection terminals SIRCOVER ATS Bypass 1250 to 1600 A ø9 32 ø 15 8.5 33 8.5 50 Changeover Switching solutions - Catalogue 2015 ø12.5 5 12.5 svr_098_a_1_x_cat 10 33 svr_077_a_1_x_cat 5 15 SIRCOVER ATS Bypass 800 to 1000 A 25 25 30 30 45 45 90 SIRCOVER ATS Bypass Manual transfer switches from 125 to 1600 A Dimensions SIRCOVER ATS Bypass 125 to 630 A Direct front operation External front operation Z1 A M ØW Z 6 Ø 8.5 Y Y A I atys_617_c_1_x_cat 19 210 210 N BA II CA AA V CA U H H 25 E min. 1 X T T T T J Rating (A) 125 160 250 400 630 T T X J1 Overall dimensions A 8p. E min 610 260±1 610 260±1 725 260±1 725 260±1 850 337±1 61 61 A. S3 type handle for external front operation: 125 to 630 A. 1. Max length with shaft extension: E min + 50 mm. Switch Switch body mounting N H J 8p. J1 8p. M 8p. 193 238 338 576 101 193 238 338 576 101 193 295 396 691 116 193 295 396 691 116 270 358 458 816 176 T 36 36 50 50 65 U 20 20 25 35 45 V 25 25 30 35 50 W 8.5 8.5 11 11 13 Connection X 8p. Y 76 3.5 76 3.5 83.5 3.5 83.5 3.5 91.5 5 Z 47 47 49 49 62 Z1 143 143 143 143 199 AA 135 135 160 170 235 BA 115 115 130 140 220 AC 10 10 10 15 20 SIRCOVER ATS Bypass 800 to 1600 A Direct front operation External front operation CA = A M 324 271.5 Z = Y Y CA atys_742_b_1_x_cat X T T T J J1 T J T T 545 380 AA BA 250 V 90 19 X 344 425 Rating (A) 800 1000 1250 1600 Overall dimensions A 8p. 1 055 1 055 1 320 1 320 Switch body J 8p. J1 8p. 510.5 189 510.5 189 643 195 643 195 Switch mounting M 8p. 1 021 1 021 1 286 1 286 T 80 80 120 120 V 60.5 60.5 44 44 E min. = 460 Connection Y Z 7 84.5 7 84.5 8 85.5 8 85.5 X 8p. 81.5 81.5 88 88 AA 321 321 288 288 110 BA 268 268 258 258 AC 26.5 26.5 15 15 Dimensions for external handles SIRCOVER ATS Bypass 125 to 630 A SIRCOVER ATS Bypass 800 to 1600 A Front operation Handle type Direction of operation Front operation Door drilling Handle type 0 90 ° S3 type Direction of operation Door drilling V type 90 20 20 ° 50 Ø78 II 4Ø7 61 50 545 4 Ø 6.5 0 ° Ø D (1) ° 90 poign_042_a_1_gb_cat 210 1414 II 90 poign_041_a_1_gb_cat I I Ø 31 Changeover Switching solutions - Catalogue 2015 33
© Copyright 2024