ELECTROLUX HOME PRODUCTS PTY LTD ABN 51 004 762 341 Issue: 3 Date: 11/10 Technical Publication Nº KSSSI90 WEB SITE ADDRESS: www.partnship.com.au KELVINATOR SPLIT SYSTEM AIR-CONDITIONER DIAGNOSTIC MANUAL MODELS: KSV53HRA KSV62HRA KSV70HRA Copyright 2010 ELECTROLUX HOME PRODUCTS PTY LTD Technical Services Indoor Unit & PCB test board Error Display. DISPLAY Not Operating E0 E1 E5 E52 E6 L2 & PA P0 P1 P2 P4 LO & P91 LED STATUS PAGE No operation by use of remote control EEPROM parameter error Indoor / outdoor units communication protection Open or short circuit of outdoor condenser pipe & compressor temperature sensors Open or short circuit of outdoor ambient temperature sensor Open or short circuit of room or evaporator temperature sensor High-temperature protection of condenser Module protection Over voltage or too low voltage protection Temperature protection of compressor top - low refrigerant charge Inverter compressor drive error Evaporator high-frequency low-temperature limit 3 to 5 6 7 to 15 16 & 17 16 & 17 18 19 & 20 21 & 22 23 24 & 25 26 & 27 28 & 29 Page 2 KSSSI90 Not Operating: # While the unit is in “stand by” mode, check if the green stand by light is flashing at 1 Hertz? # Try operating the unit by the forced operations button: By pressing the button once, the unit should activate in Auto mode. By pressing this button twice, within five seconds, the unit should activate in Cooling mode. If the unit can be operated by the forced operations button & the green stand by light was flashing on the display PCB assembly, prior to pressing forced operation button, check the remote controller. If the unit can be operated by the forced operations button & the green stand by light was off on the display PCB, replace the display PCB assembly. Stand by indicator on Display PCB assembly. Button located on top right hand side of indoor unit behind filter cover. Page 3 KSSSI90 # If the unit cannot be operated by the use of the remote control or the forced operation button, proceed as follows: # Check the wiring configuration from the indoor unit to the outdoor unit. Is it wired up correctly in accordance to the wiring diagram provided on the underside of the plastic outdoor terminal cover? # Check the supply voltage to the outdoor terminal block. # Check the supply voltage from the outdoor terminal block to the indoor terminal block. Active & Neutral wires from mains supply. Active, Neutral & Communication wires connecting from outdoor terminal block to indoor terminal block. Active, Neutral & Communication wires from outdoor terminal block. Page 4 KSSSI90 # Check the supply voltage from the indoor PCB to the transformer. If there is 240 Volts AC from this connection point on the indoor PCB, replace the transformer. If there is no supply voltage from this point, replace the indoor main PCB. Transformer AC voltage connection points. Page 5 KSSSI90 E0 error: # The E0 error indicates there is a software issue/program chip fault on the main indoor PCB assembly. # Replace the main indoor PCB assembly. If any one of the program chips fail, as highlighted by the red arrows, this could cause an E0 error. Page 6 KSSSI90 E1 error (Indoor Unit) # Disconnect the main power supply to the outdoor unit by means of the isolation switch. After approximately one minute, turn the power supply back on & attempt to operate the unit on heating or cooling mode by the use of the remote control. If E1 fault has not cleared: # Check the continuity of the (3uF) indoor fan capacitor mounted vertically inside the indoor control box assembly. # Measure the resistance of the Blue & Black wires that connect from the 3uF capacitor to the indoor fan motor. The resistance reading should be approximately “322 Ohms”, at an ambient temperature of 22ºC. 3uF indoor fan capacitor. 3uF capacitor mounted inside the indoor control box assembly. Ohms reading of indoor fan motor. Page 7 KSSSI90 E1 error (Outdoor Unit) If E1 fault has not cleared: Check the continuity of the “Bridge Rectifier” as illustrated below. Turn off the power & let the inverter electrolytic capacitors completely discharge. Identify the diodes individual ‘Plus’ and ‘Minus’ connections so as to test each diode's forward and reverse resistance values. The diagrams listed below illustrate the method of achieving this. Set the multimeter to a DC Mega Ohms setting. Place the Positive probe on the ~ pin of the rectifier & the Negative probe on the + pin of the rectifier. Place the Positive probe on the O pin of the rectifier & the Negative probe on the + pin of the rectifier. - pin of the rectifier & the Negative probe on the ~ pin of the rectifier. Place the Positive probe on the - pin of the rectifier & the Negative probe on the O pin of the rectifier. Place the Positive probe on the Note: Insure the multimeter probes are placed in their correct orientation as specified above. Note: If any of the above tests indicate a “Short Circuit” replace the main PCB assembly. All of the above tests should read several Mega Ohms. Relevant test points on the main outdoor PCB. Page 8 KSSSI90 If E1 fault has not cleared: Check the continuity of the “IGBT” as illustrated below. Turn off the power & let the inverter electrolytic capacitors completely discharge. Identify the Negative DC, U, V & W soldered points so as to test each internal IGBT resistance value. The diagrams listed below illustrate the method of achieving this. Set the multimeter to a DC Mega Ohms setting. Place the Negative probe on the Negative DC soldered point on the outdoor PCB & the Positive probe on the U soldered point on the outdoor PCB. Place the Negative probe on the Negative DC soldered point on the outdoor PCB & the Positive probe on the V soldered point on the outdoor PCB. Place the Negative probe on the Negative DC soldered point on the outdoor PCB & the Positive probe on the W soldered point on the outdoor PCB. Note: Insure the multimeter probes are placed in their correct orientation as specified above. Note: If any of the above tests indicate a “Short Circuit” replace the main PCB assembly. All of the above tests should read several Mega Ohms. Relevant IGBT test points on the main outdoor PCB. Page 9 KSSSI90 If E1 fault has not cleared: # Check the wiring connection configuration from the indoor to the outdoor units, in accordance to the wiring diagram attached to the inside of the outdoor units plastic terminal block cover. # Check the continuity on the “S” communication wire from the indoor units connection point, to the outdoor units connection point. # Check the continuity, from one point to the other, of the two “S” wiring connection points on the outdoor terminal block. # Check the continuity of the yellow “S” wire & female spade terminal located on the top section of the outdoor terminal block, to the soldered “S” wiring point on the outdoor main PCB. #Check the various Earth connection points for correct termination. Indoor terminal block “S” communication points on outdoor terminal block. “S” communication point on main outdoor PCB. Page 10 KSSSI90 If E1 fault has not cleared: # Check the continuity of the active wiring connection on the main outdoor terminal block, to the (CN4) soldered wiring point on the outdoor main PCB. “CN4” point on outdoor main PCB. Active wiring connection point on main outdoor terminal block. # Check the continuity of the neutral wiring connection on the main outdoor terminal block, to the (CN5) soldered wiring point on the outdoor main PCB. Neutral wiring connection point on main outdoor terminal block. “CN5” point on outdoor main PCB Page 11 KSSSI90 If E1 fault has not cleared: # Check the continuity of the red connection wire located on the 50uf capacitor to the “CN3” soldered wiring point on the outdoor main PCB. Caution: Discharge the 50uf capacitor prior to any service work. Red connection wire to 50uf capacitor. “CN3” connection point on main outdoor PCB. Caution: Discharge the 50uf capacitor prior to any service work. # Check the continuity of the orange connection wire located on the 50uf capacitor to the connection point on the outdoor (R1815E) reactor. Note: Check the continuity of the capacitor & reactor. If open circuit, this will also cause an E1 fault. Orange connecting wire from (R1815E) reactor. Orange connecting wire from the 50uf capacitor. Page 12 KSSSI90 Caution: Discharge the 50uf capacitor prior to any service work. If E1 fault has not cleared: # Check the continuity of the orange connection wire located on the left hand terminal of (R1815E) reactor to the “CN1” soldered wiring point on the outdoor main PCB. Note: Check the continuity of the reactor. If it’s open circuit, this will also cause an E1 fault. “CN1” soldered connection point on outdoor PCB. Orange connecting wire from (R1815E) reactor. If E1 fault has not cleared: # Check the continuity of the wire that connects to the reactor (R1502) spade terminal located closest to the front of the outdoor unit, too the “N-B” soldered connection point on the main outdoor PCB. N-B soldered connection point. Front terminal point. Reactor (R1502) Page 13 KSSSI90 If E1 fault has not cleared: # Check the continuity of the wire that connects to the reactor (R1502) spade terminal located to the rear of the outdoor unit, too the two terminal relay located under the main outdoor PCB. Note: Check the continuity of the reactor. If it’s open circuit, this will also cause an E1 fault. Rear terminal point. Reactor (R1502) Relay located under main outdoor PCB. # If there is a open circuit in any of the (R1502) reactor connection points, check the two point plug located on the harness which runs between the main outdoor PCB & the (R1502) reactor. Connection plug. Page 14 KSSSI90 #Check the outdoor LED light code configuration. During “Standby” conditions the LED’s work in this sequence: LED 1 (Yellow) is FLASHING at 1 Hz LED 5 (Red) is OFF LED 6 (Green) is ON During “Normal Operating” conditions the LED’s work in this sequence: LED 1 (Yellow) is ON LED 5 (Red) is ON LED 6 (Green) is OFF During “E1” fault the LED’s work in this sequence: LED 1 (Yellow) is FLASHING at 5 Hz LED 5 (Red) is OFF LED 6 (Green) is ON. Note: If the outdoor PCB is in the E1 fault sequence, this would indicate there is a potential fault with the indoor main PCB. If the indoor main PCB has been replaced and the E1 fault still exists or there is no LED light sequence available on the outdoor main PCB, check all the wiring connection points, as previously illustrated, on the main outdoor PCB in conjunction with the wiring diagram. If all wiring connection points are okay, this would indicate the outdoor main PCB has failed & would also need to be replaced. Page 15 KSSSI90 E5 error: # Check the “condenser coil & compressor discharge sensors” for correct connection. # Check the continuity of both sensor, if the sensor is open circuit, change it. Compressor discharge temperature sensor Condenser coil pipe temperature sensor E52 error: # Check the “condenser coil air temperature sensor” for correct connection. # Check the continuity of the sensor, if the sensor is open circuit, change it. Condenser coil air temperature sensor Page 16 KSSSI90 #Check the LED light code configuration. During normal operating conditions the LED’s work in this sequence: LED 1 (Yellow) is ON LED 5 (Red) is ON LED 6 (Green) is OFF During “E5” fault the LED’s work in this sequence: LED 1 (Yellow) is FLASHING at 5 Hz LED 5 (Red) is OFF LED 6 (Green) is ON. Note: If all the above checks relating to the sensors & wiring have been completed, yet the E5 fault still exists, this would indicate the outdoor main PCB has failed & would need to be replaced. Page 17 KSSSI90 E6 error: # Check the two indoor temperature sensors for correct connection to the indoor main PCB. # Check the continuity of the sensors, if ether of the sensors are open circuit, change them. # If E6 fault code is still displayed after replacing one or both of the indoor sensor, replace the indoor main PCB. Evaporator coil “air” temperature sensor Evaporator coil “pipe” temperature sensor Note: the outdoor LED light configuration will not be affected by this fault. Page 18 KSSSI90 L2 & PA error: If the “PA” error appears, check the following components. # Check the condenser fan for correct operation. If the fan motor is not operating check the five pin connector for correct termination. If the termination of the plug is okay check the continuity of each voltage point. Check the Resistance value of the condenser fan motor plug, from the following points. Note: The following resistance values were measured at an ambient temperature of 20ºC. Brown & Black = 0.3 Ohms. Brown & Red = 84.2 Ohms. Brown & Yellow = 132.0 Ohms. Brown & Blue = 230 Ohms. Page 19 KSSSI90 If the resistance values are okay: # Check the five soldered AC voltage points located on the main outdoor PCB. Note: The following voltage readings were measured when the unit was run in Cooling mode, with a set temperature of 17ºC. FAN-C to FAN-M = 220 Volts FAN-C to FAN-H = 200 Volts FAN-C to FAN-N = 240 Volts FAN-C to 4-WAY = 240 Volts # If there is no AC voltage at any of these points, replace the main outdoor PCB. Page 20 KSSSI90 P0 error: If the compressor is not operating, check the following components. # Check number “2” (Run) flag terminal, for correct termination. # Check number “3” (Start) flag terminal, for correct termination. # Check the continuity of the Black number “2” spade terminal wire connected to the compressor, to the “W” point soldered on the main PCB. # Check the continuity of the Blue number “3” spade terminal wire connected to the compressor, to the “U” point soldered on the main PCB. Page 21 KSSSI90 # Measure the resistance windings of the compressor. The resistance value will range between 0.45 to 0.88 ohms at an ambient temperature range of 20 to 25ºC. Note: the resistance value should be the same value across any terminal combination. #Check the LED light code configuration. During normal operating conditions the LED’s work in this sequence: LED 1 (Yellow) is ON LED 5 (Red) is ON LED 6 (Green) is OFF During “P0” fault the LED’s work in this sequence: LED 1 (Yellow) is FLASHING at 5 Hz LED 5 (Red) is OFF LED 6 (Green) is FLASHING at 5 Hz Note: If the LED’s are “NOT” On or Flashing, check the supply voltage to the board. If supply voltage is okay, this would indicate the main outdoor PCB has failed. Page 22 KSSSI90 P1 error: # Check the supply voltage to the outdoor unit. Is it within 160 to 270 Volts? Note: If the voltage is below 200 Volts, this can reduce the condenser fan speed, thus reducing the unit’s efficiency. If the voltage is within its voltage limits: # Check the AC voltage from the active spade terminal to the CN4 soldered wiring point on the outdoor main PCB. “CN4” point on outdoor main PCB. Active wiring connection point on main outdoor terminal block. # Check the AC voltage from the Neutral spade terminal to the CN5 soldered wiring point on the outdoor main PCB. Neutral wiring connection point on main outdoor terminal block. “CN5” point on outdoor main PCB Note: if the supply AC voltage is available at both the CN4 and CN5 points & P1 fault still appears, replace the main outdoor PCB assembly. Page 23 KSSSI90 P2 error: If the compressor is not operating, check the following components. # Check the three compressor flag terminals for correct termination & sequence. # Check the continuity & sequence of the three wires soldered to the main PCB (U, V & W), to the three flag terminals connected to the compressor. Correct wiring sequence from main outdoor PCB to compressor: U to Blue (Start) V to Red (Common) W to Black (Run) Page 24 KSSSI90 # Check the overload protector located next to the three compressor terminals. Note: This overload is “normally closed”. #Check the LED light code configuration. During normal operating conditions the LED’s work in this sequence: LED 1 (Yellow) is ON LED 5 (Red) is ON LED 6 (Green) is OFF During “P2” fault the LED’s work in this sequence: LED 1 (Yellow) is FLASHING at 2 Hz LED 5 (Red) is OFF LED 6 (Green) is ON. Note: If the LED’s are “NOT” On or Flashing, check the supply voltage to the board. If supply voltage is available to the board, this would indicate the outdoor PCB assembly has failed. Page 25 KSSSI90 P4 error: If the compressor is not operating, check the following components. # Check number “1” (Common) flag terminal, for correct termination. # Check the continuity of the Red number “1” spade terminal wire connected to the compressor, to the “V” point soldered on the main PCB. Page 26 KSSSI90 # Measure the resistance windings of the compressor. The resistance value will range between 0.45 to 0.88 ohms at an ambient temperature range of 20 to 25ºC. Note: the resistance value should be the same value across any terminal combination. #Check the LED light code configuration. During normal operating conditions the LED’s work in this sequence: LED 1 (Yellow) is ON LED 5 (Red) is ON LED 6 (Green) is OFF During “P4” fault the LED’s work in this sequence: LED 1 (Yellow) is FLASHING at 5 Hz LED 5 (Red) is ON LED 6 (Green) is FLASHING at 5 Hz Note: If the LED’s are “NOT” On or Flashing, check the supply voltage to the board. If supply voltage is okay, this would indicate the main outdoor PCB has failed. Page 27 KSSSI90 P91 & LO error: If the “P91 & or LO” error appears, check the following components. # Check the evaporator fan for correct operation. If the fan motor is not operating check the five pin connector for correct termination. If the termination of the plug is okay check the continuity of each voltage point. Check the Resistance value of the evaporator fan motor plug, from the following points: Note: The following resistance values were measured at an ambient temperature of 20ºC. Grey & Blue = 37.2 Ohms. Grey & Yellow = 73.7 Ohms. Grey & Red = 100.9 Ohms. Grey & White = 300 Ohms. 5 pin plug terminal points. Indoor Fan Motor plug fitting. Page 28 KSSSI90 Wire colours from left to right: Grey, Blue, Yellow, Red & White. If the resistance values are okay: # Check the five soldered AC voltage points located on the underside of the main indoor PCB. Note: The following voltage readings were measured when the unit was run in “Cooling mode, with a set temperature of 17ºC, at High fan speed. White to Grey = 315 Volts White to Blue = 287 Volts White to Yellow = 259 Volts White to Red = 238 Volts AC voltage points on rear of indoor main PCB. Side view of AC voltage points & fan motor connector plug on indoor main PCB. # If there is no AC voltage at any of these points, replace the main indoor PCB. Page 29 KSSSI90
© Copyright 2025