SwitchedDim - HPIDD Stand alone dimming ballasts for HID lamps

HID Outdoor
SwitchedDim - HPIDD
Designed and manufactured in the UK
HID Outdoor
Stand alone
dimming ballasts
for HID lamps
The SwitchedDim range of ballasts are a stand alone HID ballast
designed for street, road lighting and indoor applications.
It is used in conjunction with an external switching device such as a time
clock switch, motion sensor or switched wire.
Switched Supply Operation - The ballast switches on at full power and
dims to a predetermined level when the switched supply is absent, The
ballast will then quickly return to full 100% output when switched supply is
present.
Reduced Energy Consumption - A standard SwitchedDim ballast saves 30%
of power when dimmed.
Presence Detection - The lamp will quickly return to 100% when motion is
detected.
70%
Power
IWASAKI
Lamp compatability
CMH / CDM / HCI / SON/ SDW-T / ColorArc
100%
•Standard SwitchedDim ballast •Microprocessor controlled
dims to 70% power (55%
•Accepts 0.752 to 2.5mm2 solid
lumens) in standby mode*
and stranded wire
•Fast start
•Available in 120V (on request)
•Compact and lightwieght
* Other dimming ranges available. Ask sales
•Remote operation up to 25m for more info.
Technical Specification
Part Number
HPIDD60
-240-B/C-CC-SD
HPIDD90
-240-B/C-CC-SD
HPIDD140
-240-B/C-CC-SD
HPIDD70
-240-B/C-CC-SD
HPIDD100
-240-B/C-CC-SD
HPIDD150
-240-B/C-CC-SD
Power Rating
60W (42W when 90W (63W when
dimmed)
dimmed)
140W (98W
when dimmed)
70W (49W when
dimmed)
100W (70W
when dimmed)
150W (105W
when dimmed)
Cosmopolis
Lamp type
144
CMH, CDM, HCI, SON, SDW-T, ColorArc
Mains frequency range
AC45-65Hz
Power factor
Integral ‘B’
version
>0.95
Ignition voltage
2.5kV Pk
130
135
Nominal lamp operating
frequency
412Hz
160Hz
25m**
Lamp current waveform
Square Wave
91
36.7
Max. Distance from lamp
Max. ambient temperature Ta
50°C
Max. case temperature Tc
80°C
171.4
Remote ‘C’
version
-20°C to +50°C
415g
Weight
Max. number of ballasts per
Type C/D 16A circuit breaker
28
28
19
28
28
19
171.4
Safety Standard Compliance
EN61347-2-12:2005 EN61000-3-2:2000 EN61000-3-3:2001 EN61547:2000
**Harvard HID ballasts employ a unique lamp striking method which allows the lamps to be mounted further away from the ballast than with conventional gear or any other type of electronic ballast. If you ensure the cable capacitance is within the limit specified, you will be able to achieve reliable starting at
extended distances. The cable must be 2 core and earthing to the lamp head/luminaire should be routed separately to the lamp wires. Consult factory for approved cable specification
www.HarvardEng.com
Harvard Engineering plc Tyler Close
Data Sheet No.HIDO4 V1 RB
Normanton
Wakefield
Fax: +44 (0)113 383 1010
WF6 1RL
UK
91.2
Temperature range
Tel: +44 (0)113 383 1000
78
200-265V AC
73
AC voltage range limit