v Brochure Company Presentation ()

BROCHURE COMPANY PRESENTATION
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
OUR MISSION
From the idea to its application.
To like your job is the best way to do it very well. Following this concept we have always designed
our products focusing our attention to their application, so that “from the idea to its application” is
not only a slogan but it has always been our method of job shared by management and
collaborators. The red line which has always linked together all the efforts of the company, is to turn
ideas into products concentrating on their applications. We have developed this concept in order to
build a corporate assets made of good clients and our own “Know How”. We have later increased the
number and the “quality” of our clients and we have developed our products starting from the
drawing. This has been our mission. We don’t think to have achieved it yet, because we must not
ever regard ourselves as arrived to the top and we can always improve ,but we can strongly affirm
that our company offers a range of interesting products, so that we have been able to enter in the
global international market. Since 1994 when in Florence Electrical Fair we showed the circuit
breaker MV unit with isolator below and breaker above, which has been lately adopted by all the
players of the MV market; then the first SF6 three positions switch , the CB and the new Ring Main
Unit, also available in the extendible version. At last the Internal Arc Proof Compact Station.
Following our corporate policy we have created several products completely designed by us and
realized under our direct control that starts from the components and arrives to the applications.
Today we can say that SEL can cover every necessity of the secondary MV Distribution up to 40.5 kV
with its products. As told before we haven’t reached the top yet and very soon will arrive other new
products that will hopefully let us go on working and exporting our job Our mission is to take up the
challenge of the global market using the high technological content of our job and products, in order
to be leading players also in countries where it is not possible to compete on costs of production. It
is still possible to take up the challenge of the global market thanks to the pleasure that we find in
doing our job and to the cleverness of the people who work in this company.
Good job for everybody.
Management of SEL.
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
PRESENTATION
SEL is a continuously growing , dynamic Italian company that produces ( manufactures )
switchboards, MV and LV devices and transformation stations.
Sel is specialized in designing its products ,including the components. It also can supply a complete
offer to the market: components, boards and turnkey solutions.
Some reasons of our growth are for sure the entrance in new markets by opening our branches and
the increasing of investments in research and development of new products
SEL S.p.A. - ITALY
Marketing and sales
Project planning and engineering
Research and Development
Production of MV LBS and Vacuum CB
Assembly of MV switchboards
Shipping
Service and customer support
SEL TECH – Branch in China
Marketing and sales
Assembly of MV switchboards only
for China market
Shipping
Service and customer support in the
Asian market
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
HISTORY
Founders of SEL , Alessandro and Leonardo Leporatti, could take advantage from their experience in
the family business that their father started at the beginning of the 60’s and where they realized big
electrical plants of every kind.
They started in a small workshop collocated in the countryside from the windows of that it was
possible to admire the hills where the famous genius Leonardo da Vinci was born.
SOME
MILESTONES IN
SEL’S HISTORY:
1988
Foundation of
1989-91
Specialization in the construction of MV and LV switchboards
1992
Doubling of production space
1993
Investments and staff increase
1994
SEL’s module with isolator below and SF6 circuit breaker above
revolutionizes the market by providing two times more compact solution for
medium voltage substations.
1996
SF6 isolated TPS “Three Position Switch”. TPS SF6 switch is a turning point
for SEL meaning a new era of growth and success and starting business
abroad. SEL concentrates its force on MV switchgear
2001
SEL moves to a more spacious factory. At the same time it enters into the
Chinese market
2002
SEL opens a branch in Shanghai.
2003
Ring Main Unit TPR6. SEL recruits new experts in their fields and invests
more in the research.
2004
Vacuum circuit-breaker TCB. Export increases
2005
New markets and distributors
2006
SEL becomes a private limited company and opens a new branch in Bulgaria
2007
SEL introduces its Vacuum Circuit Breaker up to 1250A 24 KV
2007
SEL introduces the New TPR6 24 KV - G. I. S.
2008
SEL presents its fully tested Compact Station according to IEC 62271-202
2008
SEL improves its production capacity with its new robotic production line
2009
SEL introduce its TPR6 36 KV. - G. I. S.
2009
SEL introduce its PLS 24 and 36 kv (Pole mounting switch disconnector)
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
HOW TO REACH US
BY PLANE
Closest airports
SEL is situated in the hearth of Tuscany between the airports of Florence and Pisa
BY CAR
On the motorway A11, exit at signpost for Montecatini Terme
Follow the signposts for Fucecchio, Empoli. Drive along SS436 and drive via the centres of
Monsummano Terme, Cintolese and Castelmartini. After you have passed the centre of Castelmartini
turn left onto the road called Via di Cerbaia. After 1600 meters turn left onto the road called Via
Amendola.
On the motorway A11, exit at signpost for San Miniato
Follow the signposts for Fucecchio, Montecatini Terme. Drive along SS436 road “Via Francesca” and
pass through the centres of Fucecchio and Stabbia. After you have passed Stabbia turn right onto
the road called Via Cerbaia. Drive along for 1600 meters and turn left onto the road called Via
Amendola.
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
QUALITY
SEL uses ISO 9001-2000- based quality control system in planning and production.
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
CERTIFICATES & APPROVALS
SEL products have been approved by Electric Distribution Companies and by Power Research &
Testing Companies in many countries.
(For information: [email protected])
CERTIFICATES
All our production is under technical control and accident prevention and it respects the main
international and national standards. Our company possess official certificates which are obtained
carrying out tests on prototypes in our test rooms. These certificates accepted by the following
authorized bureaus:
CESI: Italian Experimental Electro Technical Centre in Milan.
National Electro Technical Institute “Galileo Ferraris” in Turin.
TUV
Laboratories SINAL.
ABS
KEMA
LLOYD’S
BUREAU VERITAS
ICMET
XIAN Laboratory of
China.
RINA
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
SOFTWARE
SEL is able to provide its users such as design engineers, installers and wholesalers with all
the necessary
software needed.
The software that SEL offers for its users is divided into:
ELEMENTARY
Microsoft Excel based software for the quotation of TPS MV switchgear in Windows
environment
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
TPS-CAD
Software for designing the TPS medium voltage switchboards in the AutoCad environment
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
REFERENZE
AIRPORT & SEAPORT
Pisa airport, Italy
Brescia airport, Italy
Marseille airport, France
CaiLan Sea port, Vietnam
Puerto Guayacán, mining sea port, Chile
OS Romairport Bucharest, Romania
Port of Livorno, Italy
Constanta sea port, Romania
Freight village Americo Vespucci, Livorno,
Italy
Port Construction Command, Xian, China
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
UTILITY
EDF, France
Fortum Power and Heat, Finland
LYDEC, Marocco
Elettrica, Romania
Radeema, Marocco
Hanoi Power Company, Vietnam
CEZ, Bulgaria
Amendis, Marocco
KESH, Albanian Power Corporation
Radeef, Marocco
ENEL, Italy
CHILECTRA, Cile
Energopomiar, Poland
Bejing Power Supply, China
Gost, Russian
Evn, Macedonia
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
HOSPITAL
Clinique St. Etienne, France
US-hospital, Landstuhl, Germany
Hospital Spallanzani,
Rome, Italy
Hospital, Usez, France
Hospital, Warsaw, Poland
Clinica 1 Mai, Bucarest, Romania
Hospital, Pori, Finland
Hospital Bouqueval, France
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
POWER PLANTS
Nuclear Power Plant, Flaminville,
France
Hydroelectric power plant, Lecco, Italy
Power Plant Łagisza, Poland
Hydroelectric power plant, Arezzo, Italy
Hydroelectric Power Plant, Jalasjoki,
Finland
Phong Phu Power Plant, Vietnam
Hydroelectric Power Plant, Kokaliane,
Bulgaria
Hydroelectric Power Plant, Myczkowce,
Poland
Hydroelectric Power Plant, Katunzi,
Bulgaria
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
INDUSTRY
Renault, France
LG Electronics e LG Innotek, Poland
Coca Cola, Greece
Nestlé, Turin, Italy
Hoa Phu Industrial Park, Vietnam
Pirelli tyres, Milan, Italy
Ferrari, Maranello, Italy
Saint Gobain, Mexico
Namtrieu shipping factory, Vietnam
Cement industry, Casablanca, Marocco
Phosphate mine, Youssoufia & Ben Guerir
divisions, Marocco
Song Hau Steel Mill, Vietnam
Rolls Royce
KME Italy, Lucca, Italy
Danube-Pak, Kherson, Ukraine
Nuovo Pignone, Firenze, Italy
SKF Stab. Massa, Italy
EATON Services Ltd., Lucca, Italy
Europa Metalli SpA. Lucca, Italy
Termomeccanica, La Spezia, Italy
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
TRANSPORT & RAILWAYS
High speed train link, Rome, Italy
VR Track Ltd. Kemijarvi, Finland
Haiphong bridge company, Vietnam
New Nanjing bridge, China
Aria, logistics, Poland
Florence S.M.N central raiway station, Italy
Rome Ring Road, Italy
Hangzhou Bay Bridge, China
WIND POWER & SOLAR ENERGY
Varna Wind Power Generator, Bulgaria
Samos Island wind park, Greece
Kavarna wind farm, Bulgaria
Sardinia Island, Alta Nurra Wind Farm, Italy
Vestas wind turbine, Sicily Island,
Italy “Erga and Enel Green Power
Troyan energy, wind power generator,
Bulgaria
Sunelectrics, Bari, Italy
Yambol wind power generator, Bulgaria
Produzione
Fotovoltaiche, Viterbo, Italy
La Fabbrica del Sole, Arezzo, Italy
Alerion Energie Rinnovabili, Brindisi, Italy
SunElectrics S.r.l. - Impianto DIVELLA,
Agrinova 1, Binardo, Mascava - Puglia,Italy
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
INDUSTRY
Carrefour shopping center, France
Casino Calama, Santiago, Chile
Prisma shopping center, Finland, Rauma,
Raahe, Kuopio
Ferio Shopping Mall, Poland
Mall Plaza Sur San Bernardo, Santiago, Chile
Leclerc shopping center, France
Lakai Mart, Ho Chi Minh City, Vietnam
Leroy Merlin Mall, Poland
Shopping center Casino, France
Volga shopping mall, Voronezh, Russia
Walter Mobel, Poznan Poland
Dealu Bradului shopping center, Bucharest,
Romania
Makro Mall, Poland
Sivas Shopping Mall, Krasnodar, Russia
Leclerc shopping cemter, Slupsk, Poland
Shopping mall, Artemovsk, Ukraine
Hyundai showroom, Sofia, Bulgaria
International exhibition center, Kiev, Ukraine
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
SPORT CENTER
Athens Olympic stadium, Greece
Olympic village, Greece
Taihu International Golf Club, China
Borovets ski resort, Bulgaria
Aerial tramway and ski lifts, Abetone ski
resort, Italy
Bansko ski resort, Bulgaria
OFFICE BUILDING
Passat, Poland
IP Networks Ltd., Finland
Saigon Pearl Building, Ho Chi Minh City,
Vietnam
Pearl Plaza, Wujiang, China
Le Thanh Ton building, Ho Chi Minh City,
Vietnam
NgheAn Bank, Vietnam
Corriere della Sera Newspaper, Bologna, Italy
UNIVERSITY
Lille university, France
ASE university, Bucharest, Romania
Lyon university, France
Genoa university, Italy
Florence university, Italy
Technical High School de Troyes, France
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
OTHERS
Telecom Italia - Italian Telecomunication
Company
Fincantieri S.p.A., Venezia
Bacino galleggiante 40000T, La Spezia
S.Giorgio del Porto S.p.A. (per M/N Enrico Costa), Genova
SAIPEM (Posatubi "Castoro VIII"),
Genova
M/N RO-RO Tirrenia, La Spezia
Terme Montecatini, Pistoia
ENEL si - Cabina di trasformazione
PALAZZO VECCHIO - FIRENZE
Arsenale MARINA MILITARE, La Spezia
Ferragamo S.p.A., Firenze
Centro Nazionale delle Ricerche, Firenze
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
PRODUCT
MEDIUM VOLTAGE > LB-TPS > SF6 GAS
INSULATED LOAD BREAK SWITCH
LB-TPS is a three position rotary switch (earth connection-open-closed)
enclosed in an epoxy resin envelope. The envelope is filled with SF6 gas
at a pressure of 0.4 bar. LB-TPS is available in both load break switch
and isolator versions depending on the type of operating mechanism
used.
The equipment is sealed for life.
The main characteristics of TPS LB are reduced dimensions and resin envelope made of one single
piece. It is maintenance free due to a sealed envelope which is segregated from the external
ambient.
SOME TECHNICAL ADVANTAGES OF TPS LB ARE THE FOLLOWING:
It is equipped with a movable mimic by showing immediate position of the switch
Through a frontal window it is possible to check visually the position of switch contacts.
It is provided with a pressure relief valve on its back side in case of internal fault. With the help
of this structure in the event of overpressure the gas will go out from the opposite part where
the operator is situated. All the above mentioned things together with excellent electrical and
mechanical characteristics guarantee maximum safety, reliability and duration of the product..
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
TECHICAL DATA
The following values are correct in an ambient temperature between -5º and 40°C and in the
installations at the altitudes lower than 1000m. (For different values, please consult SEL).
RATED VOLTAGE
PHASE-PHASE
TEST VOLTAGE
FOR 1 MIN.
AT
50HZ
AND
7.2 kV
12 kV
17.5 kV
24 kV
20 kV
42 kV
38 kV
50 kV
23 kV
48 kV
45 kV
60 kV
60 kV
95 kV
95 kV
125 kV
70 kV
110 kV
110 kV
145 kV
PHASE EARTH
BETWEEN
OPEN
CONTACTS
INSULATION
LEVEL
PHASE-PHASE
AND
PHASE EARTH
IMPULSE
TEST VOLTAGE
BETWEEN
OPEN
CONTACTS
400 A
RATED CURRENT
MAKING
CAPACITY (X
SHORT- TIME
IN
1
SEC.)
WITHSTAND
CONFORMITY WITH
DEGREE PROTECTION
630 A
630 A
62.5 kV
50 kA
25 kA
20 kA*
INTERNATIONAL
IEC 60265-1
EXTERNAL
IP30
ACCREDITED LABORATORYS INAL
ACCREDITED LABORATORYS INAL
CERTIFICATIONS
CHINA NATIONAL ACCREDITATION OF LABORATORIES
THIS
VALUES ARE THE MAXIMUM APPROVED.
* On request duration of short circuit up to 4 sec.
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
MEDIUM VOLTAGE > TCB > VACUUM CIRCUIT BREAKER UP TO 24KV 630A
It is a known fact that the vacuum circuit breaker has become the dominant technology in the main world
market and its diffusion is increasing in an outstanding way.
Today it is possible to get very efficient vacuum circuit-breakers with electrical duration which is longer than
mechanical duration, with total respect of environment (SF6 circuit breakers contribute to greenhouse effect and
they need maintenance and a particular treatment at the end of their life cycle); but in particular, vacuum circuit
-breakers offer the best performances
thanks to the reduction of arc energy, very quick opening, insulation restoring after overvoltage impulse and
reduction of mechanical energy needed for operating mechanism.
It is a known fact that the vacuum circuit breaker has become the dominant technology in the main world
market and its diffusion is increasing in an outstanding way.
Today it is possible to get very efficient vacuum circuit-breakers with electrical duration which is longer than
mechanical duration, with total respect of environment (SF6 circuit breakers contribute to greenhouse effect and
they need maintenance and a particular treatment at the end of their life cycle); but in particular, vacuum circuit
-breakers offer the best performances
thanks to the reduction of arc energy, very quick opening, insulation restoring after overvoltage impulse and
reduction of mechanical energy needed for operating mechanism.
CONSTRUCTION CHARACTERISTICS
The vacuum medium voltage circuit breakers for indoor installation TCB series are “sealed for life” pressure
systems (IEC 62271-100 and CEI 71-1 Standards, EN 62271-100) and they are constructed using the separate
pole technique.
Each pole has a vacuum interrupter inside it which, thanks to a special production process, is incorporated in
the resin. This construction technique ensures protection of the vacuum interrupter against impact, dust
andcondensation phenomena and guarantees the lightning impulse withstand also on the external surface of the
vacuum interrupter. The transmission is obtained by a mechanical central bar which allows to transform the
circuit breaker in different executions very easily.
ADVANTAGES
-
Long Mechanical life
Reduced Maintenance
Respect of Ambient: No Greenhouse or Toxic Gases are emitted during Operation
Elevated Accumulated Amp Performances
Short Arcing Time damages less contacts
Short Opening Time
Quick Recovery of Insulating capacity in case of Overvoltage
SERIES
The circuit-breakers are available in three versions:
- TCB: standard for metal enclosed MV modules ICBV or ILCBV
- TCB/LD: on truck version with right lateral operating mechanism. There are two version of this, 12kV and
24kV.
- TCB/LS: on truck version with left lateral operating mechanism. There are two version of this, 12kV and 24kV.
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
TECHICAL DATA
The following values are correct in an ambient temperature between -5º and 40°C and in the
installations at the altitudes lower than 1000m. (For different values, please consult SEL).
RATED VOLTAGE
Ur
12 kV
24 kV
IMPULSE
Up
75 kV
125 kV
Ud
28 kV
50 kV
WITHSTAND VOLTAGE
DIELECTRIC WITHSTAND
VOLTAGE TO
EARTH AND BETWEEN PHASES
(50HZ 1MIN.)
RATED FREQUENCY
fr
50 Hz
RATED CURRENT
Ir
630 A **
Isc
16 - 20 kA
Ip
40 - 50 kA
Ik
16 - 20kA
Tk
3 sec.
RATED BREAKING
MAKING
CAPACITY
CAPACITY
SHORT-TIME
WITHSTAND CURRENT
SHORT-CIRCUIT TIME
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
MEDIUM VOLTAGE > PLS > Pole Mounted switch Disconnector
PLS is an outdoor SF6 insulated pole mounted switch
disconnector up to 40.5 kV. The stainless steel tank is
particularly suitable for providing protection against
the extremes of heat, snow, corrosion, moisture, salt
and other critical environmental conditions.
PLS switch disconnector can be remote controlled or
operated manually with two different operating
mechanisms. The first one is a transmitted operating
mechanism which can be operated directly from the
ground with the help of small ladders. The second
one is a switch disconnector which can be operated
from the ground by means of insulated hook stick.
Two or three position
Two or three way
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
MAIN ELECTRICAL CHARACTERISTICS
kV
ALTITUDE
IEC 62271-1
AMBIENT
AIR TEMPERATURE
RELATIVE
HUMIDITY
IEC 62271-1
7,2
12
12*
17,5
24
40,5*
(3)
m
<1000
°C
-25 ÷55
%
36
(2)
95
INSULATION RATED VOLTAGE
kV
7,2
12
12
17,5
24
36
40,5
RATED VOLTAGE
kV
7,2
12
12
17,5
24
36
40,5
LIGHTNING IMPULSE
WITHSTAND VOLTAGE BETWEEN PHASES AND TOWARDS THE GROUND
kV
60
75
95
95
125
170
185
LIGHTNING IMPULSE
WITHSTAND VOLTAGE ACROSS THE ISOLATING DISTANCE
kV
70
85
110
110
145
195
210
kV
20
28
42
38
50
70
95
kV
23
32
48
45
60
80
110
POWER
FREQUENCY WITHSTAND VOLTAGE BETWEEN THE PHASES
POWER
FREQUENCY WITHSTAND VOLTAGE ACROSS THE ISOLATING DISTANCE
RATED FREQUENCY
Hz
RATED CURRENT
A
RATED SHORT TIME WITHSTAND
RATED PEAK
WITHSTAND CURRENT
RATED DURATION
IP (MAKING
ON FRONT FACE
DEGREE OF PROTECTION
ON ELECTRICAL
ELECTRICAL
ELECTRICAL
MAINLY
CLOSE
NO
OPERATION
OPERATION
MV CIRCUITS
LINE
IEC 60265-1
EARTHING
OPERATION
SWITCH
EARTHING
ACTIVE LOAD BREAKING CURRENT
LOOP BREAKING CURRENT
CHARGING BREAKING CURRENT
FAULT BREAKING CURRENT
SWITCH
DISCONNECTOR
SWITCH
IEC 60265-1
IEC 60265-1
DISCONNECTOR
IEC 60265-1
3
3X
67
making capacity 5 / Class E2
A
630
A
630
A
16
DISCONNECTOR
IEC 60265-1
A
32
SWITCH
DISCONNECTOR
IEC 60265-1
A
32
A
57
DISCONNECTOR
IEC 60265-1
OPTIONAL
5.000 operation / class M2
MECHANICAL
ELECTRICAL
2,5 x Ik
3(1)
SWITCH
SWITCH
12.5-16-20
1.000 operations / Class M1
IEC 60271-102
DISCONNECTOR
16-20-21
100 breaks at In p.f.=0,7 / Class E3
IEC 60271-102
SWITCH
SWITCH
16-20-25
(2)
1.000 operations / Class M1
SWITCH DISCONNECTOR IEC 60265-1
CHARGING BREAKING CURRENT
EARTH
IP
DISCONNECTOR
630 - 1250
kA
IP
LOAD TRANSFORMER BREAKING CURRENT
CABLE
)
s
SWITCH
OPERATION
MECHANICAL
CAPACITY
OF SHORT CIRCUIT TK
DEGREE OF PROTECTION
MECHANICAL
kA
CURRENT
50-60
OPERATION
400 breaks at In p.f. = 0.7
OPERATION
(1) For Ik25 kA Maximum short circuit duration time 1s
(2) Rated current is referred to 40°C ambient temperature. For different values contact SEL
(3) For different values contact SEL
* For Asian market
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
MEDIUM VOLTAGE > TPS> Metal enclosed switchboards up to 24 kV 630A
TPS MV switchboards are constructed of standardized modules in metal sheets. These modules
contain SF6 insulated devices for switching and earthing. The main advantages of TPS switches are
reduced installation and maintenance time and small dimensions. All this is obtained by ensuring
CONSTRUCTION CHARACTERISTICS
The switchboard is made of a metal structure composed of galvanized steel sheets
that are assembled using rivets and bolts. This structure is built to withstand the
electrodynamic stresses during the operation. A three position earthing switch is
fixed to this structure. An envelope made of epoxy resin makes the isolation possible
between the structure and live parts.
An operating mechanism, a movable mimic and a voltage indicator are positioned in
the front of the panel. The position of the switch is given by the movable mimic
whereas the voltage signalling lamp indicates the voltages.
It is possible to inspect the inside of the switch through an inspection window
positioned above the operating mechanism. In the front of the panel there is a door
giving access to different compartments, e.g. cables, fuses and measurement. When
the door is closed it is possible to see inside the switch through the inspection window.
If the module is equipped with a low voltage auxiliary compartment it is situated in its upper part.
Safety characteristics
The personnel safety is obtained by mechanical interlocks which guarantee correct operations of
the device.
In this way involuntary mistakes which could be dangerous for the operator can be prevented.
Metal screens prevent access to electrical parts during maintenance operations. It is possible to
block the switch
in three positions with key locks.
Series
TPS is available in the following two series:
Standard series: The series guarantees the internal
arc proof on the frontal side up to 12.5kA for 1 sec.
Internal arc proof series: The series guarantees the
internal arc proof on the four sides up to 16 kA for 1 s
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
TECHICAL DATA
The following values are correct in an ambient temperature between -5º and 40°C and in the
installations at the altitudes lower than 1000m. (For different values, please consult SEL)
RATED VOLTAGE
PHASE-PHASE
TEST VOLTAGE
FOR 1 MIN
AT
50HZ
AND
PHASE EARTH
BETWEEN
OPEN
CONTACTS
7.2 kV
12 kV
17.5 kV
24 kV
20 kV
28 kV
38 kV
50 kV
23 kV
32 kV
45 kV
60 kV
60 kV
75 kV
95 kV
125 kV
70 kV
85 kV
110 kV
145 kV
INSULATION LEVEL
PHASE-PHASE
AND
PHASE EARTH
TENSIONE DI PROVA A
IMPULSE TEST VOLTAGE
BETWEEN
OPEN
CONTACTS
RATED CURRENT
630 A
BREAKING CAPACITY (X 1
25 kA
20 kA
12.5 kA
x 1 sec.
20 kA
x 1 sec. (4 sec. On request)
SHORT- TIME WITHSTAND
1: ICB, ICBR, 2ICB= 3 SEC. ON REQUEST
16 kA
x 1 sec. (4 sec. On request)
12,5 kA
x 1 sec. (4 sec. On request)
TRANSFER CURRENT FOR STRIKER IN-
FS
TERVENTION
MECHANICAL DURATION
ELECTRICAL
1800 A
SM, BSM, FS, SMM,
SMS, FIM
1400 A
2000 (CEI 17.1)
ICB, ICBR, ICBV,
ILCBV, 2ICB
10000 (CEI 17.1)
100 (CEI 17.1)
DURATION
ITALIAN
CEI 17 - 6
IN CONFORMITY WITH
INTERNATIONAL
DEGREE OF PROTECTION
IEC 298
IP30
IP20
INTERNO / INTERNAL
ACCREDITED LABORATORYS INAL
CERTIFICATIONS
ACCREDITED LABORATORYS INAL
THE
STRUCTURE
STRUCTURE IS MADE OF GALVANIZED STEEL SHEETS AND IT IS TREATED WITH AN EPOXY POWDER PAINTING IN THE OVEN.
THESE
THESE
POSSIBLE
VALUES ARE THE MAXIMUM APPROVED. SEE MODULE TAGS DATA FOR NOMINAL VALUES.
COLOUR RAL 7030
VALUES ARE THE MAXIMUM APPROVED.
SEE
MODULE TAGS DATA FOR NOMINAL VALUES.
CHANGES IN STANDARDS OR MATERIALS CAN INFLUENCE ON ELECTRICAL CHARACTERISTICS AND OVERALL DIMENSIONS SHOWN IN
THIS DOCUMENT.
FOR
THIS REASON THEY MAY BE CONSIDERED FINAL ONLY AFTER CONFIRMATION BY
SEL.
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
MEDIUM VOLTAGE > TPR6> Switchboards for Ring Main Unit up to 7,2 Kv -
TPR6 is an SF6 insulated ring main unit for the secondary distribution network. TPR6 uses the latest
developments in switchgear technology by providing an extremely compact medium voltage
switchgear solution. It can be supplied in a number of different configurations suitable for most
switching applications in 7,2 up to 40,5 kV distribution networks. TPR6 is available in a standard
configuration or a modular version making further extension possible. All this is obtained by ensuring
maximum personnel safety.
CONSTRUCTION CHARACTERISTICS
TPR6 is a completely “sealed for life” system with a stainless steel tank containing all live parts and
switching devices. A hermetically sealed steel tank from the outside
environment ensures a high level of reliability as well as personal safety.
The structure can withstand the electrodynamics stresses during the
operation. The operating mechanism, movable mimic and voltage signaling
lamps are positioned in the front panel. Switches are operated by means of
spring-operated mechanisms. Movable mimic gives the position of the
switch whereas the voltage signaling lamp indicates the voltages. Fuses
and cable compartment are easily accessible through the front door which
is interlocked with the earth switch. Should the low voltage auxiliary
compartment be present, it is situated above the ring main unit.
SAFETY CHARACTERISTICS
The personnel safety is obtained by using mechanical interlocks. These mechanical locks operate as
follows:
When the switch disconnector is closed the earth switch can not be closed simultaneously and
the access to MV cables (T, C and F modules) is prevented.
When the earth switch is closed there is a free access to MV cables (T, C and F modules) but it
is impossible to close the switch.
When the access door to MV cables and fuses is open it is impossible to close the switch (T, C
and F modules).
Metal screens prevent access to electrical parts during maintenance operations. It is possible to block
the switch in three positions with key locks.
INTERNAL ARC WITHSTAND
The robust design of the metal enclosure prevents deformations and ensures protection against
fault. TPR6 is designed to withstand an internal arc caused by a rated short-circuit current for 1
second preventing any danger to the operator. A safety valve against accidental overpressure caused
by an internal arc is located at the bottom of the metal enclosure. The gas is released to the bottom
of the TPR6 without any danger to the operator. TPR6 has been type tested and it meets all the
criteria of IAC class A FL, as defined by IEC 62271-200 standard, annex A.
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
MODULE EXTENSIBILITY
TPR6 switchboards are easily extensible on-site, without
requiring the handling of gas or any special work. One or
several modules may be simply added to the existing
switchboard by using special connectors.
MAIN ELECTRICAL CHARACTERISTICS
MECHANICAL AND ELECTRICAL CHERACTERISTICS
U.M.
KV
ALTITUDE
IEC 62271-1
7.2
12
12*
17.5
24
36
40.5*
m
<1000 (1)
°C
-25 ÷ 55 (1)
RELATIVE HUMIDITY
%
95
INSULATION RATED VOLTAGE
KV
7.2
12
12
17.5
24
36
40.5*
RATED VOLTAGE
KV
7.2
12
12
17.5
24
36
40.5*
KV
60
75
95
95
125
170
185
KV
70
85
110
110
145
195
210
KV
20
28
42
38
50
70
95
KV
23
32
48
45
60
80
110
AMBIENT AIR TEMPERATURE
IEC 62271-1
LIGHTNING IMPULSE WITHSTAND VOLTAGE BETWEEN PHASES AND
TOWARDS THE GROUND
LIGHTNING IMPULSE WITHSTAND VOLTAGE ACROSS THE ISOLATING DISTANCE
POWER FREQUENCY WITHSTAND VOLTAGE BETWEEN THE PHASES
POWER FREQUENCY WITHSTAND VOLTAGE ACROSS THE ISOLATING
DISTANCE
RATED FREQUENCY
Hz
50-60
RATED CURRENT
A
630-1250(2)
RATED SHORT TIME WITHSTAND CURRENT (L - U1 MODULE) IK
(5)
kA
16-20-25
16-20-21
12.5-16-20
RATED SHORT TIME WITHSTAND CURRENT (F MODULE) IK (5)
kA
16-20-25
16-20-21
12.5-16-20
RATED SHORT TIME WITHSTAND CURRENT (C - T - U2 MODULE)
IK (5)
kA
16-20-25
16-20-21
12.5-16-20
RATED PEAK WITHSTAND CURRENT IP (MAKING CAPACITY )
kA
2.5x lk
RATED DURATION OF SHORT CIRCUIT TK
s
DEGREE OF PROTECTION ON FRONT FACE
IP
3X
DEGREE OF PROTECTION ON ELECTRICAL MV CIRCUITS
IP
67
3(1)
3
(1) For other solution please contact SEL
(*) For asian market
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
FUNCTIONS
Connection and power supply on a open or closed ring network
Power supply and protection of transformers with circuit breaker or combined fuse- switches
up to 200A
Power supply and protection of lines by a 630A circuit breaker
Busbar coupling
MV metering
Earth switch for cable connection
The letter under each figure
identifies the function of the
module. Each function can be
supplied with options +; I or X
on the left, right or on both
sides.
(*) All the modules supplied with option “I” on the left, right or on both sides will be equipped with
350mm wide metal enclosure which has the same height and depth than the module. See examples
6,7,8,and 9.
All the singular modules and standard configurations can be extended or they can have an outgoing
cable or connection to measuring module on the left, on the right or on both sides. For the code
composition, choose the function or the configuration and the symbols +; I or X if needed. The
configuration with “0” symbols means non extensible TPR6. For example the code of LLFF with the
right extension is LLFF+. If LLFF has the right outgoing cable and the left extension the code is
+LLFFI
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
SUBSTATION MV/LV > CAB> MV/LV PREFABRICATED SUBSTATION
SEL supplies complete prefabricated MV/LV substations
made in concrete.
The most important advantages of our products are:
Maximum safety and reliability
Reduced costs
Quick realization and putting into service
Personalized and flexible design
Substations can be monoblock or panel type and this way they can meet all the requirements of a
versatile plant.
STANDARDS
The substations are in compliance with IEC 62271-202
QUALITY SYSTEM
Our production is made in accordance with quality control system EN ISO 9001:2000 certificated
by TUV.
TEST
Walk-in e NO Walk-in type C.S. passed all tests according with IEC 62271-202
WALKIN
NO WALKIN
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
SPECIAL APPLICATIONS > MT > MV AUTOMATIC CHANGE OVER DEVICE
MV swichboard with Automatic Change Over device composed by TPS
Load-Breaker Switch equipped with motor drive LT operative
mechanism.
SAFETY CHARACTERISTICS
The personnel safety is obtained by mechanical interlocks which guarantee correct operations of
the device. In this way involuntary mistakes which could be dangerous for the operator can be
prevented.
Metal screens prevent access to electrical parts during maintenance operations. It is possible to
block the switch in three positions with key locks.
SERIES
TPS is available in the following two series:
Standard series:
The series guarantees the internal arc proof on the frontal side up to 12.5kA for 0.7 sec. Internal
arc proof series:
The series guarantees the internal arc proof on the four sides up to 16 kA for 1 s.
Main electrical characteristics
See the TPS catalogs.
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
INTEGRATED DATA ACQUISITION > MONITOR 2003 > MANAGEMENT AND
AUTOMATION SYSTEM
MANAGEMENT AND AUTOMATION SYSTEM
INTEGRATED DATA ACQUISITION, MONITORING AND CONTROL SYSTEM
Monitor 2003 is an integrated data acquisition and control system.
It is used in plant and substation monitoring and in industrial
equipment control. Its easy construction technique and flexibility
allows to use it in all the situations where it is necessary to acquire
data from different machines and instruments.
The system is composed of one or more GPCs “General Purpose
Controllers” which are connected by the means of standard RS485, making reference to a personal
computer for data acquisition and process.
The GPCs allow to interface to the measuring instruments, existing PLCs or PLCs dedicated to real
time alarm management, energy meters and gas meters. By the means of local network, standard
telephones or mobile phones it is possible to connect to remote sites and control them in a
centralized way.
The core of the system is Monitor 2003 software. In PC application it is connected to GPC network
by the means of RS485, by constantly comunicating with data collection terminals, monitoring the
conditions and acquiring data.
By the means of graphical data it is possible to control and illustrate the values. Real-time visual
section is divided in two typologies;text data collection and graphic data collection.
The report section configurable by the user allows to visualize the maximum, minimum and
medium values.
Alarm system completes the switchboard allowing to send special messages by mobile phone to a
selected contact list. The flexibility of GPC configuration allows the modification of inputs. By the
means of configuration it is possible to program 4 outputs of each GPC and connect it to the alarm
functions centrally.
MINIMUM CHARACTERISTICS OF PC
Processor PIII 1000
Windows 2000 Pro
128 MB RAM
1 R S232 for GSM
1 R S232/R S485 for GPC
Free space 100 MB on hard disc for data and programs
Color printer or laser printer (optional local or network)
Monitor 15” 800x600
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
HEAD OFFICE
SEL S.p.A.
Via Amendola
51035 LAMPORECCHIO (PT)
ITALY
Tel. +39-0573-80051
Fax. +39-0573-803110
e-mail: [email protected]
OUR BRANCHES IN THE WORLD
BULGARIAN MARKET
ASIAN & CHINESE MARKETS
SEL BULGARIA S.r.l.
SEL-TECH ELECTRIC (SHANGHAI) Co. Ltd.
Sofia 1000, bul. Vasil Levski 112, et. 2, ap.10
BULGARIA
Tel. +35 - 928432540
e-mail: [email protected]
3rd Floor, Bldg no.13, No.14, Sublane No. 172,
Lane No. 1340
Jinshajiang Rd, Putuodistrict, Shanghai - China
200333
Tel. +86(0)21-52804397, 52804698
Fax +86 (0)21-52804698
(e-mail): [email protected]
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
SEL S.P.A. VIA AMENDOLA - 51035 LAMPORECCHIO (PISTOIA) - ITALY
SEL S.p.A.
Via Amendola
51035 LAMPORECCHIO (PT) ITALY
Tel. +39-0573-80051
Fax. +39-0573-803110
Web site : http://www.sel-electric.com
e-mail: [email protected]