Level instruments 5

© Siemens AG 2009
Level instruments
Continuous level measurement - Ultrasonic controllers
MultiRanger 100/200
■ Overview
■ Application
MultiRanger can be used on different materials, including fuel
oil, municipal waste, acids, woodchips or on materials with high
angles of repose. MultiRanger offers true dual point monitoring,
digital communications with built-in Modbus® RTU via RS-485,
as well as compatibility with SIMATIC PDM, allowing PC configuration and setup. MultiRanger features Sonic Intelligence® advanced echo-processing software for increased reading reliability.
MultiRanger 100 offers cost-effective level alarming, as well as
on/off and alternating pump control. MultiRanger 200 will monitor
open channel flow and features more advanced relay alarming
and pump control functions as well as volume conversion.
It is compatible with chemical-resistant Echomax® transducers
that can be used in hostile environments at temperatures as high
as +145 °C (+293 °F).
• Key Applications: wet wells, flumes/weirs, bar screen control,
hoppers, chemical storage, liquid storage, crusher bins, dry
solids storage
5
MultiRanger is a versatile short to medium-range ultrasonic
single and multi-vessel level monitor/controller for virtually any
application in a wide range of industries.
The MultiRanger is available in wall or panel mounting options.
■ Benefits
• Digital input for back-up level overide from point level device
• Communication using built-in Modbus RTU via RS-485
• Compatible with SmartLinx system and SIMATIC PDM configuration software
• Single or dual point level monitoring
• Auto False-Echo Suppression for fixed obstruction avoidance
• Differential amplifier transceiver for common mode noise
reduction and improved signal-to-noise ratio
• MultiRanger 100: level measurements, simple pump control
and level alarm functions
• MultiRanger 200: level, volume and flow measurements in
open channels, differential control, extended pump control
and alarm functions
• Wall and panel mounting options
5/138
■ Design
Siemens FI 01 · 2010
© Siemens AG 2009
Level instruments
Continuous level measurement - Ultrasonic controllers
MultiRanger 100/200
■ Technical specifications
Mode of Operation
Design
Measuring principle
Ultrasonic level measurement
Measuring range
0.3 to 15 m (1 to 50 ft)
• Weight
- Wall mount
1.37 kg (3.02 lbs)
Measuring points
1 or 2
- Panel mount
1.50 kg (3.31 lbs)
• Material (enclosure)
Input
• Analog (MultiRanger 200 only)
0 to 20 mA or 4 to 20 mA, from
alternate device, scaleable
• Discrete
10 to 50 V DC switching level
Logical 0 =< 0.5 V DC
Logical 1 = 10 to 50 V DC
Max. 3 mA
Output
Polycarbonate
• Degree of protection (enclosure)
- Wall mount
IP65/Type 4X/NEMA 4X
- Panel mount
IP54/Type 3/NEMA 3
Electrical connection
• Transducer and mA output signal
2-core copper conductor, twisted,
shielded, 0.5 to 0.75 mm² (22 to
18 AWG), Belden® 8760 or equivalent is acceptable
• Echomax® transducer
44 kHz
• Ultrasonic transducer
Compatible transducers: ST-H
and Echomax series XPS-10/10F,
XPS 15/15F, XCT-8, XCT-12 and
XRS-5
• Max. separation between transducer and transceiver
365 m (1200 ft)
Displays and controls
• Relays
Rating 5 A at 250 V AC,
non-inductive
100 x 40 mm (4 x 1.5") multi-block
LCD with backlighting
• Programming
Programming using hand-held
programmer, SIMATIC PDM or via
PC with Dolphin Plus software
- Version with 1 relay
(MultiRanger 100 only)
1 SPST Form A
- Version with 3 relays
2 SPST Form A/1 SPDT Form C
Power supply
- Version with 6 relays
4 SPST Form A/2 SPDT Form C
• AC version
100 to 230 V AC ± 15 %,
50/60 Hz, 36 VA (17 W)
• DC version
12 to 30 V DC (20 W)
Certificates and approvals
• CE, C-TICK2)
• Lloyd’s Register of Shipping
• ABS Type Approval
• FM, CSAUS/C, UL listed
• CSA Class I, Div. 2, Groups A, B,
C and D, Class II, Div.2, Groups
F and G, Class III (wall mount
only), ATEX II 3D
Communication
• RS-232 with Modbus RTU or
ASCII via RJ-11 connector
• RS-485 with Modbus RTU or
ASCII via terminal strips
• Optional: SmartLinx® cards for
- PROFIBUS DP
- DeviceNetTM
- Allen-Bradley® Remote I/O
• mA output
0 to 20 mA or 4 to 20 mA
- Max. load
750 Ω, isolated
- Resolution
0.1% of range
Accuracy
• Error in measurement
0.25% of range or 6 mm (0.24"),
whichever is greater
• Resolution
0.1 % of measuring range1)
or 2 mm (0.08"), whichever is
greater
• Temperature compensation
• -50 to +150 °C (-58 to +302 °F)
• Integral temperature sensor
• External TS-3 temperature sensor (optional)
• Programmable fixed temperature values
Rated operating conditions
Installation conditions
• Location
1)
Indoor/outdoor
• Installation category
II
• Pollution degree
4
2)
Program range is defined as the empty distance to the face of the transducer plus any range extension
EMC performance available on request
Ambient conditions
• Ambient temperature (housing)
-20 to +50 °C (-4 to +122 °F)
Siemens FI 01 · 2010
5/139
5
© Siemens AG 2009
Level instruments
Continuous level measurement - Ultrasonic controllers
MultiRanger 100/200
Selection and Ordering data
Order No.
L) 7 M L 5 0 3 3 MultiRanger 100/200
Versatile short to medium-range ultrasonic single
7 7 7 77 - 77
and multi-vessel level monitor/controller for virtually
any application in a wide range of industries
Versions
MultiRanger 100, level measurement only
MultiRanger 200, level, volume, flow and differential
measurements
Instruction manual
English
French
Spanish
C) 7ML1998-5FB06
C) 7ML1998-5FB13
C) 7ML1998-5FB23
German
C) 7ML1998-5FB34
Mounting, enclosure design
Wall mount, standard enclosure
Wall mount, 4 entries, 4 M20 cable glands included
Panel mount (CE, CSAUS/C, FM, UL)
Power supply
100 to 230 V AC
12 to 30 V DC
1
2
A
B
C
C) 7ML1998-5QD83
Quick Start guide, multi-language
Note: The instruction manual should be ordered as
a separate line on the order.
This device is shipped with the Siemens Milltronics
manual CD containing the complete ATEX Quick
Start and instruction manual library.
A
B
Number of measurement points
Single point version
Dual point version
5
Selection and Ordering data
Order No.
L) 7 M L 5 0 3 3 MultiRanger 100/200
Versatile short to medium-range ultrasonic single
7 7 7 77 - 77
and multi-vessel level monitor/controller for virtually
any application in a wide range of industries
Other instruction manuals
SmartLinx Allen-Bradley Remote I/O, English
SmartLinx PROFIBUS DP, English
SmartLinx PROFIBUS DP, German
0
1
Communication (SmartLinx)
Without module
SmartLinx® Allen-Bradley® Remote I/O module
SmartLinx PROFIBUS DP module
C) 7ML1998-1AQ12
SmartLinx PROFIBUS DP, French
C) 7ML1998-1BH02
SmartLinx DeviceNet, English
Note: The appropriate SmartLinx instruction manual
should be ordered as a separate line on the order.
0
1
2
SmartLinx DeviceNetTM module
See SmartLinx product page 5/301 for more information.
3
Output relays
3 relays (2 Form A, 1 Form C), 250 V AC
6 relays (4 Form A, 2 Form C), 250 V AC
1 relay (1 Form A), 250 V AC (available on
MultiRanger 100 model only)
A
B
C
Order code
Please add "-Z" to Order No. and specify Order
code(s).
Stainless steel tag [69 x 50 mm (2.71 x 1.97")]:
Measuring-point number/identification
(max. 16 characters) specify in plain text
Accessories
Handheld programmer
Tag, stainless steel, 12 x 45 mm (0.47 x 1.77"),
one text line, suitable for enclosure
1
2
3
Approvals
General Purpose CE, FM, CSAUS/C, UL listed,
C-TICK
CSA Class I, Div. 2, Groups A, B, C and D; Class II,
Div 2, Groups F and G; Class III1)
ATEX II 3D2)
Further designs
7ML1830-2AK
7ML1930-1AC
TS-3 Temperature Sensor - see TS-3 on page 5/186
SITRANS RD100 Remote display see RD100 on page 5/304
SITRANS RD200 Remote display see RD200 on page 5/306
Spare parts
Power Supply Board (100 to 230 V AC)
Power Supply Board (12 to 30 V DC)
Display Board
C) 7ML1830-1MD
C) 7ML1830-1ME
C) 7ML1830-1MF
See SmartLinx product page 5/301 for more information.
1)
Y15
C) 7ML1998-1AP03
C) 7ML1998-1AQ03
C) 7ML1998-1AQ33
2)
For wall mount applications only
For standard enclosure wall mount, option A only
C) Subject to export regulations AL: N, ECCN: EAR99
L) Subject to export regulations AL: N, ECCN: 3A991X
®Modbus is a registered trademark of Schneider Electric.
®Belden is a registered trademark of Belden Wire and Cable Company.
®
Allen-Bradley is a registered trademark of Rockwell Automation.
TMDeviceNet is a trademark of Open DeviceNet Vendor Association (ODVA)
5/140
Siemens FI 01 · 2010
© Siemens AG 2009
Level instruments
Continuous level measurement - Ultrasonic controllers
MultiRanger 100/200
■ Dimensional drawings
■ Schematics
See note 1
DC version
DISCRETE
INPUTS
Relays shown in released state
5
Notes
1. Use 2-core copper wire, twisted, with shield, for expansion up to 365 m (1200 ft.).
Route cable in grounded metal conduit, separate from other cables.
2. Verify that all system components are installed in accordance with instructions.
3. Connect all cable shields to the MultiRanger Shield Connections. Avoid differential
ground potentials by not connecting cable shields to ground (earth) anywhere else.
4. Keep exposed conductors on shielded cables as short as possible to reduce noise
on the line caused by stray transmissions and noise pickup.
MultiRanger connections
MultiRanger dimensions
Siemens FI 01 · 2010
5/141
© Siemens AG 2009
Level instruments
Continuous level measurement - Ultrasonic controllers
HydroRanger Plus
■ Overview
Output
• Ultrasonic transducer
44 kHz
• Relays
5 alarm/control relays, 1 SPDT
Form C per relay, rated 5 A at
250 V AC, resistive load
• mA output
0/4 to 20 mA, optically isolated
- Max. load
1 kΩ
- Resolution
0.1 % of 20 mA
Accuracy
5
HydroRanger Plus is an ultrasonic level controller for control of
wet wells and reservoir pump operations, differential control and
open channel flow monitoring, using energy-saving algorithms.
• Error in measurement
0.25% of range or 6 mm (0.24"),
whichever is greater
• Resolution
0.1% of measuring range or
2 mm (0.08"), whichever is greater1)
• Temperature compensation
-50 to +150 °C (-58 to +302 °F)
• Integral temperature sensor
• External TS-3 temperature
sensor (optional)
• Programmable fixed
temperature
Rated operating conditions
Ambient conditions
■ Benefits
• Ambient temperature for enclosure
• Outputs for alarms, chart recorders, controllers and integration of existing systems
• Monitors wet wells, weirs and flumes
• Energy-saving function with built-in real-time clock
• Special control mode to reduce grease rings and other deposits
• Integral temperature compensation
• Pump performance monitoring
• System monitoring and network analysis
■ Application
The system is effective in wet wells, weirs, and flumes where
foam and turbulence are typical operating conditions. It can be
customized to meet your specific application needs – from measuring flow rate in a narrow flume to volume in a ferric chloride
storage bank.
The system consists of the electronics housed in a wall-mounted enclosure and a hermetically sealed, corrosion-resistant Echomax®
transducer. These components can be separated by up to 365 m
(1200 ft).
Optional submergence shields ensure consistent operation in
wet wells where the transducer may be submerged during flooding from rainfall or a power outage. Siemens patented detection
software can differentiate between a submerged condition and
a high level.
• Key Applications: wet wells, weirs, flumes
• Rack mount
DIN 3 HU/14 pitch, 4 rail plug-in
unit suitable for standard 84 pitch
(19") rack
• Panel mount
Suitable for standard panel cutout
DIN 43700, 72 x 144 mm, 100 mm
center height
• Degree of protection (wall mount)
IP65/NEMA 4X/Type 4X
• Weight (rack and panel mount)
0.87 kg (1.9 lbs)
• Weight (wall mount)
1.5 kg (3.3 lbs)
• Material (enclosure)
Polyester/polycarbonate alloy
Electrical connection
Commercially available copper
conductor according to local
requirements, rated 250 V/5 A
• Ultrasonic transducer cable exten- RG 62-A/U coaxial cable with low
capacitance
sion
• mA output signal
2-core copper conductor, twisted,
shielded, 0.5 to 0.75 mm² (22 to
18 AWG), Belden® 8760 or equivalent is acceptable
Power supply
100/115/200/230 V AC, ± 15%,
50/60 Hz, 15 VA and/or
9 to 30 V DC, 8 W
• Ultrasonic transducer
Compatible transducers: ST-H
and Echomax series XPS-10/10F,
XPS 15/15F, XCT-8, XCT-12 and
XRS-5
Displays and controls
■ Technical specifications
Mode of operation
Measuring principle
Ultrasonic level measurement
Measuring range
0.3 to 15 m (1 to 50 ft)
Measuring points
1 or 2
Rack and panel mount
75 x 20 mm (3 x 0.8") LCD
(selectable backlighting)
Wall mount
100 x 40 mm (4 x 1.5")
multifield LCD, backlit
Programming
Removable programmer or
optional Dolphin Plus
Memory
EEPROM (non-volatile),
no backup battery required
Certificates and approvals
CE2), FM, CSAUS/C, C-TICK
1)
2)
®
5/142
Siemens FI 01 · 2010
-20 to +50 °C (-4 to +122 °F)
Design
The measuring range corresponds to the distance from the zero point to the
sensor face, plus any range extension.
EMC certificate available on request
Belden is a registered trademark of Belden Wire and Cable Company.
© Siemens AG 2009
Level instruments
Continuous level measurement - Ultrasonic controllers
HydroRanger Plus
Selection and Ordering data
Order No.
Selection and Ordering data
Order No.
L) 7 M L 1 0 2 5 HydroRanger Plus, rack and panel mount
Non-contacting ultrasonic echo ranging technology
777 0 1
monitor that comes standard with a backlit display
Measuring range: 0.3 m to 15 m (1 to 50 ft)
L) 7 M L 1 0 2 8 HydroRanger Plus, wall mount
Non-contacting ultrasonic echo ranging technology
7A77 0
monitor that comes standard with a backlit display
Measuring range: 0.3 m to 15 m (1 to 50 ft)
Mounting/device version
Version for 19" rack
(requires terminal block; see accessories)
Version for panel
Input voltage
100 V AC, 9 to 30 V DC
115 V AC, 9 to 30 V DC
1
2
200 V AC, 9 to 30 V DC
230 V AC, 9 to 30 V DC
3
4
1
2
Approvals
CE (EN 61326), CSAUS/C, FM, C-TICK
C
Input voltage
100 V AC, 9 to 30 V DC
115 V AC, 9 to 30 V DC
A
B
200 V AC, 9 to 30 V DC
230 V AC, 9 to 30 V DC
C
D
Order code
Further designs
Stainless steel tag [69 x 50 mm (2.71 x 1.97")]:
Measuring-point number/identification
(max. 16 characters) specify in plain text
Y15
Instruction manual
C)
English
C)
French
C)
German
Note: The instruction manual should be ordered as
a separate line item on the order.
Order No.
7ML1998-1AC02
7ML1998-1AC12
7ML1998-1AC32
This device is shipped with the Siemens Milltronics
manual CD containing the complete Quick Start
and instruction manual library.
Spare parts
Card, Analog HydroRanger Plus Rack/Panel
Card, daughter
Card, display, backlit
C
Mounting/enclosure version
Standard enclosure (NEMA 4X)
Standard enclosure prepared for five M20 cable
glands
1
3
Order code
Further designs
Please add "-Z" to Order No. and specify Order
code(s).
Accessories
Handheld programmer
Tag, stainless steel, 12 x 45 mm (0.47 x 1.77"), one
text line suitable for enclosures
Terminal block for rack mount
TS-3 Temperature Sensor - see TS-3 on page 5/186
SITRANS RD100 Remote display see RD100 on page 5/304
SITRANS RD200 Remote display see RD200 on page 5/306
Approvals
CE; FM General Purpose; CSA Class I, Div. 2,
C-TICK
Please add "-Z" to Order No. and specify Order
code(s).
Stainless steel tag [69 x 50 mm (2.71 x 1.97")]:
Measuring-point number/identification (max. 16
characters) specify in plain text
Y15
Instruction manual
C)
English
C)
French
C)
German
Note: The instruction manual should be ordered as
a separate line item on the order.
Order No.
7ML1998-1AC02
7ML1998-1AC12
7ML1998-1AC32
5
This device is shipped with the Siemens Milltronics
manual CD containing the complete Quick Start
and instruction manual library.
7ML1830-2AC
7ML1930-1AC
7ML1830-1JL
C) 7ML1830-1LR
C) 7ML1830-1LS
C) 7ML1830-1LX
Accessories
Handheld programmer
Tag, stainless steel, 12 x 45 mm (0.47 x 1.77"), one
text line suitable for enclosures
M20 cable gland kit (6 M20 cable glands,
6 M20 nuts, 3 stop plugs)
7ML1830-2AC
7ML1930-1AC
7ML1830-1GM
TS-3 Temperature Sensor - see TS-3 on page 5/186
SITRANS RD100 Remote display see RD100 on page 5/304
SITRANS RD200 Remote display see RD200 on page 5/306
Spare parts
Card, mother main
Card, daughter
Card, display
C) 7ML1830-1LV
C) 7ML1830-1LW
C) 7ML1830-1LU
C) Subject to export regulations AL: N, ECCN: EAR99
L) Subject to export regulations AL: N, ECCN: 3A991X
Siemens FI 01 · 2010
5/143
© Siemens AG 2009
Level instruments
Continuous level measurement - Ultrasonic controllers
HydroRanger Plus
■ Dimensional drawings
■ Schematics
5
HydroRanger Plus dimensions
5/144
Siemens FI 01 · 2010
HydroRanger Plus connections, rack and panel mount
© Siemens AG 2009
Level instruments
Continuous level measurement - Ultrasonic controllers
HydroRanger Plus
HydroRanger Plus connections, wall mount
5
Siemens FI 01 · 2010
5/145