MODEL 4501-XX 2-Wire Series TOXIC GAS SENSOR MODULE APPLICABILITY & EFFECTIVITY Effective for all Model 4501-XX Modules manufactured after September 1, 2006. 4501-03 4501-04 4501-05 FM Approved 4501-06 4501-08 4501-10 4501-12 4501-25 4501-26 Instruction Manual Part Number T13022 Rev. C Model 4501-XX Toxic Gas Sensor Module FM PERFORMANCE APPROVAL ONLY THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS ARE FM* APPROVED Model 4501-05 Hydrogen Sulfide Gas Sensor Module Sensor Module Model 4501-05 Sensor Module - Hydrogen Sulfide Calibration Equipment Model 1250-01 Gas Sensor Calibration Kit, Type A Model 1260-05 Hydrogen Sulfide in N2, 25 ppm Gas Cylinder Model 1260-45 Hydrogen Sulfide in N2, 10 ppm Gas Cylinder Model 5358-01 Calibration Adapter Notes: 1) Apparatus must be installed in accordance with National Electrical Code. 2) FM Comments. *FM Approvals, a subsidiary of FM Global Project# 3028099 Model 4501-XX Toxic Gas Sensor Module TABLE OF CONTENTS 1. 1.1 1.2 1.3 1.4 1.5 1.6 2. 2.1 2.2 2.3 2.4 3. 3.1 3.2 3.3 3.4 3.5 3.6 4. 4.1 4.2 4.3 4.4 5. 5.1 5.2 5.3 5.4 6. PRODUCT DESCRIPTION ................................................................................................................................. 1 GENERAL ........................................................................................................................................................ 1 MOUNTING CONFIGURATION ...................................................................................................................... 1 THEORY OF OPERATION..............................................................................................................................1 MECHANICAL ................................................................................................................................................. 2 INTERCONNECT WIRING .............................................................................................................................. 2 POWER REQUIREMENTS ............................................................................................................................. 2 CAUTIONS & WARNINGS ................................................................................................................................. 4 INTRODUCTION ............................................................................................................................................. 4 GAS SENSOR MODULES - GENERAL......................................................................................................... 4 WIRING............................................................................................................................................................ 4 CALIBRATION FREQUENCY ......................................................................................................................... 4 QUICK START .................................................................................................................................................... 5 OVERVIEW...................................................................................................................................................... 5 WIRING............................................................................................................................................................ 5 MODULE INSTALLATION ............................................................................................................................... 5 TRANSMITTER INSTALLATION .................................................................................................................... 5 START-UP & OPERATION ............................................................................................................................. 5 ZERO STABILIZATION ................................................................................................................................... 5 INSTALLATION .................................................................................................................................................. 6 SENSOR MODULE LOCATIONS ................................................................................................................... 6 WIRING............................................................................................................................................................ 7 ENCLOSURE INSTALLATION ........................................................................................................................ 7 TRANSMITTER AND SENSOR INSTALLATION ........................................................................................... 8 OPERATION ....................................................................................................................................................... 9 INTRODUCTION ............................................................................................................................................. 9 DATA ENTRY KEYPAD .................................................................................................................................. 9 MAIN MENU .................................................................................................................................................. 10 SETUP SUB-MENU....................................................................................................................................... 11 CALIBRATION .................................................................................................................................................. 14 6.1 CALIBRATION FREQUENCY ....................................................................................................................... 14 6.2 CALIBRATION PREPARATION .................................................................................................................... 14 6.3 CALIBRATION GAS DELIVERY METHODS ................................................................................................. 14 CALIBRATION PROCEDURE .................................................................................................................................. 14 6.4 SENSOR EXPOSURE TO GAS .................................................................................................................... 14 6.5 CALIBRATION SUB-MENU........................................................................................................................... 15 7. 7.1 7.2 7.3 7.4 7.5 7.6 SERVICE ........................................................................................................................................................... 16 SENSOR MODULE CONFIGURATION ........................................................................................................ 16 ENCLOSURE REPLACEMENT .................................................................................................................... 16 TRANSMITTER REPLACEMENT ................................................................................................................. 17 SENSOR REPLACEMENT ............................................................................................................................ 17 INSTALLATION INSPECTION ...................................................................................................................... 17 INSPECTION AND TROUBLESHOOTING GUIDE ....................................................................................... 18 Model 4501-XX Toxic Gas Sensor Module 8. 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 APPENDICES ................................................................................................................................................... 19 APPENDIX A: SPECIFICATIONS.................................................................................................................. 19 APPENDIX B: MODEL NUMBERS & PARTS LIST ....................................................................................... 22 APPENDIX C: LIMITED WARRANTY............................................................................................................ 23 APPENDIX D: 4501-25 & 4501-26 GAS SENSOR MODULE ........................................................................ 24 APPENDIX E: US FM APPROVAL. ............................................................................................................... 28 APPENDIX F: CANADIAN FM APPROVAL ................................................................................................... 30 APPENDIX G: ATEX CERTIFICATE ............................................................................................................. 32 APPENDIX H: PIPE MOUNTING FOR 4501-XX ALUMINUM ....................................................................... 34 LIST OF FIGURES FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE 1 - 1: MODEL 4501-05 ALUMINUM HOUSING GAS SENSOR MODULE OUTLINE DIMENSIONS ....... 2 1 - 2: MODEL 4501-05 STAINLESS HOUSING GAS SENSOR MODULE OUTLINE DIMENSIONS....... 3 1 - 3: MODEL 4501-XX HYDROGEN SULFIDE GAS SENSOR MODULE, ORIENTATION OPTIONS ... 3 4 - 1: TYPICAL MOUNTING OPTIONS ...................................................................................................... 6 4 - 2: 4-20 MA CONNECTION .................................................................................................................... 7 4 - 3: CONNECTOR LOCATIONS.............................................................................................................. 8 5 - 1: FACE PLATE WITH OPERATOR KEYPAD ..................................................................................... 9 6 - 1: MODEL 5358-01 CALIBRATION ADAPTER .................................................................................. 14 7 - 1: MODULE COMPONENTS .............................................................................................................. 16 8 - 1: MODULE COMPONENTS .............................................................................................................. 24 8 - 2: SENSOR ASSEMBLY – EXPLODED VIEW ................................................................................... 26 8 - 3: MODEL 4501-25-A1 AND 4501-26-A1 OUTLINE DIMENSIONS ................................................... 27 8 - 4: MODEL 4501-25-S1 AND 4501-26-S1 OUTLINE DIMENSIONS ................................................... 27 8 - 5: MODEL 4501-XX ALUMINUM ENCLOSURE PIPE MOUNT ......................................................... 34 8 - 6: PIPE MOUNT BRACKET FOR 4501-XX ALUMINUM ENCLOSURE ............................................ 34 LIST OF TABLES TABLE TABLE TABLE TABLE TABLE TABLE 4 - 1: SPECIFIC GRAVITIES ........................................................................................................................ 6 5 - 1: MASTER MENU ............................................................................................................................................. 10 5 - 2: KEY OPERATIONAL DISPLAY ................................................................................................................... 10 5 - 3: SET-UP CONFIGURATION ......................................................................................................................... 12 5 - 4: MAINTENANCE SUB MENU ....................................................................................................................... 13 6 - 1: CALIBRATION ................................................................................................................................................ 15 Model 4501-XX Toxic Gas Sensor Module 1. PRODUCT DESCRIPTION 1.1 GENERAL The Model 4501-XX Toxic Gas Sensor Module is a 2-wire transmitter with 4-20 mA output and it offers a broad array of features including: • 2-wire loop powered • 180 day calibration interval • Selectable ranges (if appropriate for gas type) • Non-intrusive one-person calibration • Integral LCD 2-line, 20-character display • Stainless steel enclosure and sensor housing • 4-20 mA output • Long sensor life • Rotatable faceplate enables multi-directional conduit installation. The 4501-XX is designed and approved for installation and operation in hazardous locations. Members of the 4501-XX Two-Wire Toxic Gas family include: ▪ 4501-03 Oxygen Gas Sensor Module ▪ 4501-04 Carbon Monoxide Gas Sensor Module ▪ 4501-05 Hydrogen Sulfide Gas Sensor Module ▪ 4501-06 Chlorine Gas Sensor Module ▪ 4501-08 Chlorine Dioxide Gas Sensor Module ▪ 4501-10 Sulfur Dioxide Gas Sensor Module ▪ 4501-12 Nitrogen Dioxide Gas Sensor Module ▪ 4501-25 Ammonia Gas Sensor Module ▪ 4501-26 Hydrogen Fluoride Gas Sensor Module 1.2 MOUNTING CONFIGURATION Various module mounting configurations can be implemented without special fixtures. Where applicable, these options are factory configured prior to shipment. Mounting configuration can be selected by the installer or field technician and are fully described in this manual. Sensor must always be oriented downward. 1.3 THEORY OF OPERATION Electrochemical sensors are fuel cell-like devices consisting of an anode, cathode, and electrolyte. The components of the cell are selected so a subject gas, allowed to diffuse into the cell, will cause a chemical reaction and generate a current. The cells are diffusion limited so the rate the gas enters the cell is solely dependent on the gas concentration. The current generated is proportional to the rate of consumption of the subject gas in the cell. Page 1 of 35 Model 4501-XX Toxic Gas Sensor Module Sierra Monitor electrochemical sensors provide improved reliability by allowing the gas to diffuse into the sensor through a capillary port, rather than diffusing through membranes. The result is an extremely stable sensor with very low temperature and pressure coefficients and the capability to monitor gas as ppm. 1.4 MECHANICAL The sensor module is comprised of the following three primary components: 1.4.1 ENCLOSURE Explosion proof, rain-tight aluminum or stainless steel electrical housing with three ¾” FNPT conduit hubs. The enclosure cover has a viewing window. The 3 conduit hubs combined with the rotatable faceplate enable the user to mount the module in a variety of configurations. See Figure 1-2 for details. 1.4.2 TRANSMITTER ELECTRONICS Electronic Assembly consisting of one printed circuit board assembly mounted under a cover plate. Wiring connections for power and signal interface are located on the back side of the display. 1.4.3 SENSOR ASSEMBLY The sensor assembly includes a stainless steel, explosion proof, housing containing the gas sensor and a wiring harness for connection to the transmitter. The sensor assembly threads into one hub of the enclosure. The exposed end of the sensor assembly is threaded to allow connection of a rain-shield or calibration gas delivery fitting. 1.5 INTERCONNECT WIRING Not supplied with the sensor module, but necessary to the installation and operation is the two conductor wiring shielded which connects the module to its power source and controller. Before this wiring is installed it is important to read and understand the control system installation instructions to determine wiring requirements and alternatives. 1.6 POWER REQUIREMENTS The 4501-XX module operates on DC power between 14 VDC and 30 VDC. The DC power must be supplied by the loop controller. Figure 1 - 1: Model 4501-05 Aluminum Housing Gas Sensor Module Outline Dimensions Page 2 of 35 Model 4501-XX Toxic Gas Sensor Module Figure 1 - 2: Model 4501-05 Stainless Steel Housing Gas Sensor Module Outline Dimensions Figure 1 - 3: Model 4501-XX Hydrogen Sulfide Gas Sensor Module – Orientation Options Page 3 of 35 Model 4501-XX Toxic Gas Sensor Module 2. CAUTIONS & WARNINGS 2.1 INTRODUCTION Although the 4501-XX Gas Sensor Module is designed and constructed for installation and operation in industrial applications including hostile environments, caution should be taken to insure that the installation is made in compliance with this instruction manual and that certain procedures and conditions are avoided. This chapter discusses the necessary cautions. Read the entire chapter prior to installation of the equipment. 2.2 GAS SENSOR MODULES - GENERAL Avoid installing sensor modules where they will be unnecessarily exposed to wind, dust, water (i.e. direct hose down), shock, or vibration. Observe temperature range limitations. Sensors may be adversely affected by prolonged exposure to certain materials. Loss of sensitivity, or corrosion, may be gradual if such materials are present in low concentrations. These materials include: Halides (compounds containing chlorine, fluorine, bromine, iodine), acid vapors, caustic liquids or mists. Care has been taken by the manufacturer to ship modules in protective packaging to avoid contamination prior to installation. It is recommended that the modules remain protected during installation and that the covering be removed immediately prior to system start-up. During normal use the O2, CO, H2S, SO2 and NO2 sensors are protected from dirt and oil contamination by a sintered metal cover. If this cover becomes clogged, the response of the sensor will be reduced. Protect the sensor from contamination by careful placement, or by use of rain shields and dust shields. Sensor modules must not be painted. Paint may contain compounds which will contaminate the sensor. Paint will cause clogging of the sintered metal cover and will cause difficulties during attachment of the calibration head or other maintenance activity. It is recommended that the module be tagged "DO NOT PAINT". 2.3 WIRING The manufacturer recommends that extra caution be taken where the installation is near any sources of electromagnetic or radio frequency interference. Precautions include: • Avoid running sensor module cable close to high power cables, radio transmission lines, or cables subject to pulses of high current. • Avoid running cables near large electric motors or generators. • Analog devices require shielded cable. • In conduit installations and cable applications the shield should be connected to instrument ground. • All splices must be via either a termination hardware system or soldered. Improperly spliced cable can result in corrosion, resistance changes and system errors. NOTE Installation and wiring must be in accordance with the National Electrical Code. Voltage AC conductors are not to be run in the same conduit as voltage DC conductors. 2.4 CALIBRATION FREQUENCY The 4501-XX calibration frequency is six months (180 days). However, prudent gas detector maintenance practices normally suggest a simple recalibration following incidences of exposure to high levels of gas that would lead to alarm activation within any system utilizing the output of the gas sensor module. Page 4 of 35 Model 4501-XX Toxic Gas Sensor Module 3. QUICK START 3.1 OVERVIEW The gas sensor module has been supplied factory calibrated and ready for immediate installation and operation. An installer familiar with installation and operation of gas detection products can use this section to begin immediate use of the module. 3.2 WIRING Provide two conductor twisted shielded wiring from the power supply/control device to the sensor module location. Use wire that is 18 AWG or larger. 3.3 MODULE INSTALLATION The 4501-XX can be mounted in a variety of configurations supported by the conduit. See figure 1-2 to determine which configuration is best for your specific application. The default configuration enables the modules to be put in line with other modules with the sensor element below the transmitter. To change the configuration simply remove the transmitter and rotate to the appropriate configuration and remount the standoffs and transmitter. The module is designed to be installed on a ¾” conduit. Two important warnings: • The installation must meet any hazardous environment codes for electrical equipment. • The sensor module enclosure mounting must be spaced far enough from any vertical surface to allow removal and replacement of the sensor assembly which is threaded into one ¾” conduit entry. • Sensor housing must be oriented vertically pointing downward. 3.4 TRANSMITTER INSTALLATION To install the transmitter printed circuit assembly into the housing, carefully turn the faceplate so that the printing is in the correct horizontal position for the mounting configuration and slide the assembly over the two stand-offs in the enclosure. Hand tighten the two captive panel thumb screws into the stand-offs. Replace the enclosure cover prior to providing power to the transmitter. • If the transmitter is installed in a classified hazardous area, replace the threaded cover prior to providing power. 3.5 START-UP & OPERATION To begin operation of the sensor module activate the instrument loop with 14-30 VDC. Each time the sensor module is powered up it will perform a warm-up for approximately 1.0 minutes (60 seconds). During this time the display will read “Starting”. The loop output will be held at 4 mA. NOTE: If the sensor is uncalibrated, the startup display will state “UNCALIB” instead of “STARTING” NOTE: The 4501-06, 4501-08, 4501-25 and 4501-26 require 300 seconds warm-up period After the warm-up period has expired, the display will indicate the gas concentration. Also, the instrument loop will be released to output current in the range of 4 to 20 mA. The actual current is linear with the gas concentration and depends on the selected range. For instance, when the range of 0 to 50 PPM has been selected, a current of 4 mA corresponds to 0 PPM and a current of 20 mA corresponds to 50 PPM. 3.6 ZERO STABILIZATION All electrochemical sensors require at least 30 minutes on power prior to calibration. This allows the electrode potentials to equilibrate, resulting in a stable zero signal level. Page 5 of 35 Model 4501-XX Toxic Gas Sensor Module 4. INSTALLATION 4.1 SENSOR MODULE LOCATIONS The gas sensor module utilizes a diffusion type sensor which should be located close to either the expected source or destination of the gas hazard. If the gas is heavier than air, the sensor module should be installed within 24 inches of the ground or floor. If it is lighter than air, move it above 6’. After optimum locations are determined based on the above recommendations, consideration should be given to placing the sensor modules in locations which are accessible for calibration service. Slight adjustments to the location of the sensor module may have little impact on effectiveness but major effect on accessibility. • Modules should be placed in areas accessible for calibration. • The cover should face out from the wall for easy access. • Sensors should be pointed down and the conduit should include an inverse trap to reduce moisture (condensation) from accumulating in the electronics enclosure. Model Gas Specific Gravity N/A Air 1.00 4501-04 CO 0.97 4501-05 H2S 1.19 4501-06 Cl2 2.49 4501-08 ClO2 3.09 4501-10 SO2 2.26 4501-12 NO2 1.59 4501-25 NH3 0.60 4501-26 HF 1.86 Table 4 - 1: Specific Gravities Figure 4 - 1: Typical Mounting Options Page 6 of 35 Model 4501-XX Toxic Gas Sensor Module 4.2 WIRING • Wire should be 18 AWG minimum at a maximum distance is 5,000 feet. Install conduit as required by local code or construction specifications. • See figure 4-2 for typical 2 terminal and 4 terminal connections. Figure 4 - 2: 4-20 mA Connection 4.3 ENCLOSURE INSTALLATION To protect the transmitter and sensor assembly they should be removed from the enclosure and preserved until final installation and wiring termination. Prior to installation and wiring: 1. Remove the transmitter from the module housing by: • Unscrew the two captive panel screws on the faceplate. • Lift the transmitter out of the enclosure. • Unplug the sensor cable from transmitter connector J1. • Remove the sensor assembly from the enclosure hub. 2. Install the module enclosure onto the end of the supply conduit and/or bolt into position as required. NOTE When enclosure earth grounding is required for the installation a grounding lug is located in the base of the enclosure. Install the earth ground under the green ground screw. Page 7 of 35 Model 4501-XX Toxic Gas Sensor Module 4.4 TRANSMITTER AND SENSOR INSTALLATION When all pre-wiring is complete: 1. Install sensor assembly in the open hub on the module enclosure. The sensor assembly thread must be fully seated into the hub and tightened to maintain explosion proof assembly. 2. Connect the sensor assembly cable to transmitter connector J1. (Figure 4-3) 3. Connect the loop wires (Loop + and Loop -) to transmitter connector P1 4-20 mA + and – (Figure 4-3). NOTE Conductor P1 is removable 4. Carefully return the transmitter to the enclosure installing it over the two standoffs. Finger tighten the retaining screws into the standoffs. Loop Power Sensor Connector Figure 4 - 3: Connector Locations Page 8 of 35 Model 4501-XX Toxic Gas Sensor Module 5. OPERATION 5.1 INTRODUCTION The 4501-XX Toxic Gas Sensor Module utilizes a visual menu system operated by means of a magnet with the cover in place. A magnet stick is supplied for this purpose. Access the menu system to calibrate the sensor module, and for maintenance and diagnostic procedures. The following adjustments can be made to the sensor module: Range adjustments (see section 5.4) 4mA and 20mA calibration adjustments (see section 5.4) Span adjustment (see section 6.3) 5.2 DATA ENTRY KEYPAD The module menu system is operated by means of directing the magnet stick toward each of four independent hall-effect magnetic switches. Each switch functions as if it is a manually activated panel key. The keys are located under the faceplate above and below the LCD and are labeled M , E , and as shown in Figure 5-1. • Key : MODE • Key ENTER • Key : UP (+) • Key : DOWN (-) Figure 5 - 1: Face Plate with Operator Keypad Page 9 of 35 Model 4501-XX Toxic Gas Sensor Module 5.3 MAIN MENU Key Function M E M E M E M E M E M E M E M E Display Description Mode Switch [M] Enter Switch [E] Up Switch [▲] Previous Menu Down Mode Down Down Down Reference Switch [▼] Next Menu 4501-XX CAL 180 4501-XX Version 4501-XX Starting H2S XXX.PPM H2S CALIB: H2S SETUP: H2S MAINT: H2S Exit-? First screen at power-up, Model and days to calibration Second screen at start-up, Version (e.g. V300aA) Third screen at start-up, will remain for 60 seconds (4501-05) Default Display (example 4501-05) Mode Function: Calibration (example 4501-05) Table 6-1 Mode Function: Setup (example 4501-05) Table 5-3 Mode Function: Maintenance (example 4501-05) Table 5-4 Exit Mode (example 4501-05) Table 5 - 1: Master Menu Table 5-2 defines the key operational displays on the operator interface. Display - H2S STARTING SENSOR FAIL NO SENSOR Description Warm-up at start-up (example 4501-05) Sensor failure Sensor not found or plugged in C.## PPM Calibration Mode F.## PPM Failure detected, sensor is attempting recovery XXX DONE Finished with step Table 5 - 2: Key Operational Display Page 10 of 35 Model 4501-XX Toxic Gas Sensor Module 5.4 SETUP SUB-MENU The sensor module set-points menu is used to initially set-up the range and 4-20 mA calibration. • Range: Once the Set-up menu is selected, press key [▼] twice and press [E] to activate the Range Setup menu. Use the [▲] or [▼] keys to select Range menu and press [E]. When “Range” is selected menu provides any choices of ranges available for the gas type selected. Use the [▲] or [▼] keys to select the desired range. If the “User” range is selected, use the [▲] or [▼] keys to adjust the high end of the range desired. See specifications below for optional ranges. Model 4501-03 4501-04 4501-05 4501-06 4501-08 4501-10 4501-12 4501-25 4501-26 Factory Range Set-up Range Other Available 5-25% 0-25% 0-500 PPM Variable 0-100 PPM Variable 0-10 PPM None 0-3 PPM None 0-100 PPM Variable 0-20 PPM None 0-100 PPM Variable 0-10 PPM None • 4-20mA: Once the Set-up menu is selected, press key [▼] three times and press [E] to activate the 420mA Set-up menu. Use the [▲] or [▼] keys to select Calib menu and press [E]. The “Calib” section of the menu allows the user to calibrate the 4 mA and 20 mA outputs. To calibrate the 4 mA and 20 mA outputs it is necessary to have an amp meter connected to the 4501-XX and upon selecting the 4 mA output calibration then the [▲] or [▼] keys can be used to adjust the 4 mA reading on the amp meter until it reads 4 mA. Similar steps can then be performed for the 20 mA output. Page 11 of 35 Model 4501-XX Toxic Gas Sensor Module Key Function Display M M H2S XX PPM H2S CALIB: H2S SETUP: E E Mode Down Description Default Display (example 4501-05) Gas Range Adjustment Example M E M E M M M E E E Enter Range Enter H2S *100 PPM Down Down Enter H2S 10 PPM H2S USER H2S 100 PPM S.P. Function - Range Adjust Select [E] to select or or to select another and press [E] Press [E] if selecting 0-10 PPM range Press [E] if selecting User adjustable range Select [E] to select or or to select another and press [E] 4-20 mA Adjustment Example M M M M M E E E E E Down Enter Enter Enter Enter H2S 4-20mA H2S Calib H2S Out: 4mA H2S 4mA H2S ACK S.P Function 4-20 mA Calibrator S.P. Function - Calib Adjust Use or keys to select 4 mA or 20mA Selects 4 mA Momentary Acknowledge of new Set Point Table 5 - 3: Set-up Configuration Page 12 of 35 Reference Model 4501-XX Toxic Gas Sensor Module MAINTENANCE SUB-MENU The maintenance menu enables the operator to view sensor and software versions. Sierra Monitor technical support has access to other values as needed. The maintenance menu operation is described in Table 5-4. Key M E M E M E M E M E M E Function Mode Enter Down Down Enter Enter Description Display H2S XXX PPM H2S CALIB H2S SETUP: H2S MAINT: H2S VX.XX H2S: CCC001 Default Display(example 4501-05) Go to previous maintenance menu item Version number of firmware Configuration Version Table 5 - 4: Maintenance Sub Menu Page 13 of 35 Reference Model 4501-XX Toxic Gas Sensor Module 6. CALIBRATION 6.1 CALIBRATION FREQUENCY The sensor module must be calibrated every 180 days at a minimum. Periodic functional tests are advisable for critical applications and hostile environments. The sensor module microprocessor software includes high-level self checking algorithms which provide continuous sensor diagnostic and self adjustment. 6.2 CALIBRATION PREPARATION Calibration of the sensor is accomplished by simple menu based steps and application of span gas. NOTE If an error is made during any stage of the calibration process, hold the magnet stick at the [M] for 10 seconds. A scrolling display will indicate “calibration aborted” and the sensor module will exit the calibration activity and return to normal operating mode. The calibration procedure can then be restarted. Calibration must be performed only when the area is known to be clear of the gas of interest. When in doubt, use a portable instrument to confirm that there is no background. For compliance with Factory Mutual (FM) Approvals, the Sierra Monitor Model 1250-01, 1260 -05 and 1260-45 are the FM Approved calibration gas delivery devices. Use the Model 5358-01 Calibration Adapter delivery fitting. NOTE: Refer to Appendix D for information on use of permeation tube for 4501-25 calibration. 6.3 CALIBRATION GAS DELIVERY METHODS Calibration gas can be delivered to the sensors via the Model 5358-01: Calibration Adapter (Figure 6-1) - used with portable calibrators. CALIBRATION PROCEDURE The Calibration Menu is described on Table 6-1: The procedure requires that the menu “keys” be activated using the magnet stick. Each key press steps through the process of setting the zero value for clean air and then setting the span value. Sample Gas In At each of these steps, apply calibration gas of the value corresponding to the setting accepted on the sensor module display. 6.4 SENSOR EXPOSURE TO GAS Calibration gas must be delivered to the sensor using the flow rate and duration listed in below: Model 4501-03 4501-04 4501-05 4501-06 4501-08* 4501-10 4501-12 4501-25 4501-26** Calibration Gas Air Carbon Monoxide Hydrogen Sulfide Chlorine Chlorine Sulfur Dioxide Nitrogen Dioxide Ammonia Chlorine Figure 6 - 1: Model 5358-01 Calibration Adapter Flow Period 300 cc of Zero Air or exposure to Ambient Air (3 minutes) 300 cc/min Until Stable (minimum 3 minutes) 300 cc/min Until Stable (minimum 3 minutes) 300 cc/min Until Stable (minimum 3 minutes) 300 cc/min Until Stable (minimum 3 minutes) 300 cc/min Until Stable (minimum 3 minutes) 300 cc/min Until Stable (minimum 3 minutes) See Appendix D 500 cc/min Until Stable (minimum 6 minutes) * Note: Use 10 PPM Cl2 to calibrate, equivalent reading = 3.0 PPM ClO2 ** Note: Use 5 PPM Cl2 to calibrate equivalent reading = 8.0 PPM HF Page 14 of 35 Model 4501-XX Toxic Gas Sensor Module 6.5 CALIBRATION SUB-MENU Key Function Display XXXPPM M M E E M E M E M E Mode Enter H2S CALIB:-H2S Cal Zero Description Reference Default Display Mode Function - Calibrate Banner: Apply zero gas, enter <E> when done Operation: Confirm area clear of gas, or apply zero air to sensor. Enter Enter Enter H2S ACK H2S 10PPM-SP H2S CXXX PPM H2S CXXX PPM H2S CXXXPPM H2S CAL-OK H2S WAIT-300 Zero gas setting acknowledged Banner: Select span, enter <E> when done* Sub A Banner: Apply span gas, then enter <E> to calibrate gas sensor Sub B Operation: Apply calbration gas. Operation: As gas is applied the reading will increase - wait 3 minutes Calibration Passed - now remove gas Operation: Five minute time out before sensor is returned to service. Sub-Routines M M M M E E E E Down Down Enter Enter M E Enter M E Mode H2S 10PPM-SP H2S 25PPM-SP H2S Adj-SPAN H2S 25PPM-SP H2S C 25PPM H2S C 25PPM H2S CAL-FAIL H2S WAIT-300 (Any) Banner: Select span, enter <E> when done Sub A Operation: Change Span Gas Value to 25PPM Operation: User adjustable value Operation: Ready for user adjustment Banner: Apply 25PPM gas, then enter <E> to calibrate gas sensor Sub B Operation: Apply calbration gas. Operation: No calibration gas applied, or sensor did not respond correctly. Operation: Five minute time out before sensor is returned to service. Operation: Hold magnet over Mode Switch for ten senconds to abort calibration Sub C Banner: Calibration Aborted H2S XXXPPM Default Display Table 6 - 1: Calibration * 4501-03 – Oxygen Calibration: If area is known to be safe with adequate air flow, you may use the surrounding air as the calibration gas. If Oxygen levels are unknown, it is recommended to use a Zero Air gas standard. When calibrating an Oxygen module, there is no zero gas process in the calibration procedure. Only span adjustments can be made. Normal ambient Air = 20.9% Oxygen. Begin calibration procedure using the magnet on the Mode key until CALIB is displayed. Enter to begin procedure. Select cal gas value (20.9), Enter to confirm. Apply span gas for 3 minutes or use surrounding air if acceptable. Select Enter when done, and procedure is complete. NOTE The Analog output values to be transmitted during the calibration procedure are selected in the maintenance configuration. Normal 20.9% value provides 17.3 mA. Page 15 of 35 Model 4501-XX Toxic Gas Sensor Module 7. SERVICE 7.1 SENSOR MODULE CONFIGURATION The gas sensor module is comprised of the following sub-assemblies (Figure 7-1): 4501-XX Gas Sensor Module SPL27077 Stainless Steel Enclosure (SPL 27085 for Aluminum Enclosure) SPM27071 Transmitter Assembly XXXXXXX Sensor Assembly (see Appendix B) XXXXXXX Sensor (see Appendix B) There are no field serviceable components below the sub assembly level. NOTE Area must be determined to be non-hazardous before opening enclosure. 7.2 ENCLOSURE REPLACEMENT The enclosure should be replaced if the cover threads or conduit threads have been damaged, or if the enclosure has been damaged sufficiently that it no longer meets the required NEMA classification. To replace the enclosure follow the transmitter and sensor assembly removal instructions, remove the damaged enclosure from its conduit, install a new enclosure and continue the transmitter and sensor assembly replacement instructions. Figure 7 - 1: Module Components Page 16 of 35 Model 4501-XX Toxic Gas Sensor Module 7.3 TRANSMITTER REPLACEMENT The transmitter assembly should be replaced when it is determined that it is unreliable, noisy or cannot be adjusted for calibration. This may occur due to age, corrosion or failed components. To replace the transmitter assembly: a. Remove the cover of the main enclosure. b. Unscrew the two thumb screws in the top of the cover plate, lift the assembly and rotate 90o to relieve the wiring service loop. c. Remove the two wires from P1 terminals (see figure 4-3). d. Unplug the sensor connector from the transmitter. e. Reverse the preceding steps to install the new transmitter. f. Restore power and allow a minimum of 30 minutes for stabilization before re-calibration. 7.4 SENSOR REPLACEMENT NOTE: Refer to Appendix D for information on sensor electrolyte replacement for 4501-25. The gas sensor which is located inside the sensor assembly housing can be replaced without replacement of the housing. The gas sensor needs replacement when: It is no longer possible to obtain correct Zero and Span values. The “LOW SENS” message appears after calibration. The sensor output signal is noisy, causing erroneous gas level readings. To replace the sensor: a. Confirm that system power has been removed. b. Remove the gas sensor module enclosure cover. c. Unscrew the two thumb screws in the top of the faceplate, lift the transmitter assembly and rotate 90o to relieve the wiring service loop. d. Unplug the sensor connector from the transmitter. e. Unscrew the old sensor assembly from the enclosure conduit hub. Remove the sensor assembly with its harness. f. Unscrew sensor housing cover from the sensor. g. Carefully pull the old sensor straight up from the socket. h. Press the new sensor into the socket. i. Reverse the preceding steps to install the sensor assembly. j. Allow the new sensor to stabilize for a minimum of 30 minutes and then calibrate using the procedure in Section 6. 7.5 INSTALLATION INSPECTION Prior to system start-up or trouble shooting, the entire system should be visually inspected. The following are guidelines for that inspection: 7.5.1 CONTROLLER INSTALLATION • Controller installed in conformance to manufacturer’s instruction manual recommendations. 7.5.2 CABLING INSTALLATION • All splices are soldered or via terminal block. • Cabling is away from sources of electrical noise or RFI where possible. 7.5.3 SENSOR MODULE INSTALLATION • Module installation in conformance with this manual. • Modules accessible for calibration. • Wiring terminations clean and correct. Page 17 of 35 Model 4501-XX Toxic Gas Sensor Module 7.5.4 MOISTURE TRAPS AND RAINSHIELDS • Conduit seals and drains installed to avoid moisture build up in electronics enclosure. Water accumulation in sensor module enclosures is a major cause of damage and system failures - take precautions to seal electrical conduits and provide moisture traps and drains to avoid water damage. • Rain-shields installed where applicable. 7.5.5 STANDARD VOLTAGES • Loop voltage to be applied to the sensor module must be between 14 VDC and 30 VDC. 7.6 INSPECTION AND TROUBLESHOOTING GUIDE The inspection and troubleshooting guide can be used to step through the system start-up and to determine the corrective action if a fault occurs. 7.6.1 IF MODULE DOES NOT RESPOND TO GAS 1. 2. 3. 4. Repeat calibration procedure. Remove the gas and wait for the timer to completely count down. Apply calibration gas and verify that the sensor sees calibration gas after calibration. If the sensor still does not see gas, power cycle the unit and repeat calibration. 7.6.2 IF THE MODULE DISPLAYS “STARTING” FOR MORE THAN 1 HOUR 1. Make sure the sensor is place in an ambient room temperature environment. 2. Power cycle the sensor. 3. Ensure that the sensor is not exposed to the gas of interest during warm-up. 7.6.3 IF THE MODULE DOES NOT DISPLAY THE CORRECT PPM 1. Power cycle the unit. 2. Recalibrate the sensor. 7.6.4 IF THE DISPLAY SHOWS ‘F’ OR “NO SENSOR” 1. 2. 3. 4. 5. 6. Power down the unit. Open the enclosure and unplug the sensor assembly from the transmitter board. Plug the sensor back into the transmitter board carefully and ensure a secure fit. Check all wire connections. Power up the unit. If the system still shows ‘F’, apply magnet to ‘M’ key, then ‘E’ key. The module will start scrolling an error message. Please write that message down and contact Sierra Monitor for assistance. 7.6.5 IF THE DISPLAY SHOWS ‘C’ 1. Complete calibration and exit to operating mode. Page 18 of 35 Model 4501-XX Toxic Gas Sensor Module 8. APPENDICES 8.1 APPENDIX A: SPECIFICATIONS Sensor: Type: Electrochemical Max Range (1) Zero Drift Repeatability Linearity Resolution Response Time (2) Sensor Life (3) 4501-03 O2 0-25% Vol. +/- 0.5 Vol. +/- 0.1 % +/- 0.1 % 0.2% Vol. <10 seconds 20 months 4501-04 CO 0-1200 PPM +/- 1 PPM +/- 1 PPM +/- 1 PPM 0.5 PPM <25 seconds 2 years 4501-05 H2S 0-100 PPM +/- 0.5 PPM +/- 1 PPM +/- 1 PPM 0.1 PPM <30 seconds 2 years 4501-06 Cl2 0-10 PPM +/- 0.5 PPM +/- 0.5 PPM +/- 0.5 PPM 0.1 PPM <60 seconds 2 years 4501-08 ClO2 0-3 PPM +/- 0.5 PPM +/- 0.5 PPM +/- 0.5 PPM 0.1 PPM <60 seconds 2 years 4501-10 SO2 0-100 PPM +/- 0.5 PPM +/- 1 PPM +/- 1 PPM 0.5 PPM <20 seconds 2 years 4501-12 NO2 0-20 PPM +/- 0.5 PPM +/- 0.5 PPM +/- 0.5 PPM 0.2 PPM <35 seconds 2 years 4501-25 NH3 0-100 PPM +/- 1.0 PPM +/- 1.0 PPM +/- 1.0 PPM +/- 1 PPM <30 seconds (4) 4501-26 HF 0-10 PPM +/- 0.5 PPM +/- 0.5 PPM +/- 0.5 PPM +/- 0.5 PPM <90 seconds (4) (1) (2) (3) (4) Optional ranges available Response time to 90% full signal value for applied concentration Sensor life typical for use at standard temperature and pressure with occasional exposure to gas of interest Sensor electrolyte needs to be recharged every six months Output: Display: Signal Output: Loop Resistance LCD, 2-line, 16-characters 2-wire sensor powered analog 4-20 mA (Trouble: 3.6 mA) 800 ohm Power consumption: Connection type: Input voltage: RFI/EMI Protection: 0.2 watts 2 wire loop-powered 24 VDC nominal: 14-30VDC EN50081-2, EN50082-2 Electrical Data: Operating Range: 4501-03 O2 Sensor and 4-20 mA will continue to operate to -40o F (-40o C) but the LCD display will decay over time if exposed to temperatures below -4o (-20o C) for o o significant time (not Ambient Temp ( F) Ambient Temp ( C) Relative Humidity applicable to 4501o o -4 to 122 F -20 to 50 C 15 – 90% 25) 4501-04 CO -4 to 122 F Extended Range Operation: 4501-05 H2S 4501-06 Cl2 4501-08 ClO2 4501-10 SO2 4501-12 NO2 4501-25 NH3 4501-26 HF Storage Temperature: o o -4 to 122 F o -4 to 122 F o -4 to 122 F o -4 to 122 F o -4 to 122 F o +14 to 113 F o +14 to 113 F o 15 – 90% o 15 – 90% o 15 – 90% o 15 – 90% o 15 – 90% o 15 – 90% o 20 – 90% o 20 – 90% -20 to 50 C -20 to 50 C -20 to 50 C -20 to 50 C -20 to 50 C -20 to 50 C -10 to 45 C -10 to 45 C -4o to 122o F(-20o to 50o C) Page 19 of 35 Model 4501-XX Toxic Gas Sensor Module Enclosure: Dimensions: Weight: Material of Construction: Housing: 7.0 x 3.6 x 4.0 inches (H x W x D) (17.8 x 9.1 x 11.2 cm) 2.2 lb. (1.0Kg) Al 4.6 lb. (2.1 Kg) SS 316 Stainless Steel, Aluminum NEMA 4X, NEMA 7 Electrical Approvals: Factory Mutual (FM): Hazardous Locations: (All Models) CSA UL ATEX: FM Standards 3600, 3615, 3810 Class 1 Div I, Groups B, C, D Class II, Div I, Groups E, F, G NEMA 4X1 Class I, Div I, Groups B, C, D Class II, Div I, Groups E, F, G NEMA 4X UL Standard 508A II 2 G Ex d IIB+H2 T6 Gb Ta = -20oC to +50oC Performance Approvals: FM Performance Approval: (4501-05 only) Approval Standards: ISA-92.0.01, Part I-1998 and FM 3600 Limited Warranty: 2 years Warranty: Specifications subject to change without notice Page 20 of 35 Model 4501-XX Toxic Gas Sensor Module Cross Sensitivity Data: 4501-04 Carbon Monoxide Gas Conc. H2S 15 PPM SO2 5 PPM NO 35 PPM NO2 5 PPM H2 100 PPM C2H4 100 PPM HCN 10 PPM HCl 5 PPM Response ~38 PPM ~3 PPM ~10 PPM ~-3 PPM <60 PPM <100 PPM ~5 PPM 0 PPM 4501-05 Hydrogen Sulfide Gas Conc. CO 400 PPM SO2 20 PPM NO 50 PPM NO2 10 PPM Cl2 10 PPM H2 400 PPM C2H4 400 PPM NH3 20 PPM Response <.1 PPM <10 PPM <3 PPM <-30 PPM <-25 PPM 1 PPM <0.1 PPM <0.1 PPM 4501-06 Chlorine Gas Conc. CO 300 PPM H2S 15 PPM SO2 5 PPM NO 35 PPM NO2 5 PPM H2 100 PPM C2H4 100 PPM HCN 10 PPM HCl 5 PPM Response 0 PPM 0 to -3.38 PPM -0.05 PPM 0 PPM ~5 PPM 0 PPM 0 PPM 0 PPM 0 PPM 4501-08 Chlorine Dioxide Gas Conc. Cl2 3.1 PPM Response 10 PPM Page 21 of 35 4501-10 Sulfur Dioxide Gas Conc. H2S 15 PPM NO 35 PPM NO2 5 PPM Cl2 5 PPM NO2 5 PPM H2 100 PPM HCN 10 PPM HCl 5 PPM C2H4 100 PPM Response 0 PPM -7 to 0 PPM -5 PPM -1.5 to 0 PPM ~5 PPM 0 PPM <5 PPM 0 PPM 0 PPM 4501-12 Nitrogen Dioxide Gas Conc. CO 300 PPM H2S 15 PPM SO2 5 PPM NO 35 PPM Cl2 1 PPM H2 100 PPM HCN 10 PPM HCl 5 PPM C2H4 100 PPM Response 0 PPM -1.5 to 0 PPM -0.05 to 0 PPM 0 PPM ~1 PPM 0 PPM 0 PPM 0 PPM 0 PPM 4501-25 Ammonia Gas Conc. CO 1000 PPM SO2 15 PPM NO 100 PPM NO2 60 PPM H2 4% CH4 4% HCN 10 PPM H2S 3 PPM Response 0 PPM >40 PPM 0 PPM 0 PPM 0 PPM 0 PPM 75 PPM 75 PPM 4501-26 Hydrogen Fluoride Gas Conc. Cl2 5 PPM HCl 5 PPM NH3 75 PPM SiH4 15 PPM CO 1000 PPM SO2 5 PPM NO 100 PPM NO2 15 PPM H2 4% H2S 30 PPM Response 8 PPM 9 PPM 0 PPM 0 PPM 0 PPM 9 PPM 0 PPM 2 PPM 0 PPM 0 PPM Model 4501-XX Toxic Gas Sensor Module 8.2 APPENDIX B: MODEL NUMBERS & PARTS LIST Sensor Module Model 4501 Gas - XX 4501 Series - 03 = O2 - 04 = CO - 05 = H2S - 06 = Cl2 - 08 = ClO2 - 10 = SO2 - 12 = NO2 - 25 = NH3 - 26 = HF Options 5311-00 5311-02 Enclosure - XX Sensor Protection -X ATEX -X - A1 = AL ¾” NPT - A2 = AL M20 x 1.5 - S1 = SS ¾” NPT - S2 = SS M20 x 1.5 - 0 = Standard - 1 = Conformal Sensor - 0 = Standard - C = ATEX/IECEx (4501-05 only) Rainshield Rainshield, with calibration port Calibration Items Gas Sensor Calibration Kit, Type A (CO, H2S) 1250-01 Gas Sensor Calibration Kit, Type B (SO2, NO2) 1250-03 Gas Sensor Calibration Kit, Type C (Cl2) 1260-00 Gas Cylinder, Air, (Type A), 105 liters 1260-04 Gas Cylinder, CO 100 PPM, (Type A) 57 liters 1260-05 Gas Cylinder, H2S in N2, 25 PPM, (Type A) 57 liters 1260-06 Gas Cylinder, Cl2, 5 PPM, (Type C) 104 liters 1260-10 Gas Cylinder, SO2, 50 PPM, (Type B) 74 liters 1260-12 Gas Cylinder, NO2, 10 PPM, (Type B) 74 liters 1260-13 Gas Cylinder, CO, 1000 PPM, (Type A), 105 liters 5360-00 Calibrator Head Standard 1256-01 Regulator Type A Calibrator 1256-02 Regulator Type B Calibrator 1265-03 Regulator Type C Calibrator 5358-01 Calibration Adapter - Direct, Standard 5358-51 Calibration/Configuration Magnetic Tool, 4501-XX 9210-00 Calibrator, Permeation Tube 9211-09 Permeation Tube, Ammonia, NH3 SPX27057 Kit, Sensor Recharge, for 4501-25 SPX27061 Kit, Sensor Recharge, for 4501-26 Spare Parts SPM21834 SPM21832 SPM21830 SPM21833 SPM21844 SPM21845 SPM21840 SPM21878 SPM27071 SPM27082 SPM27083 SPM27074 SPM27084 SPM27087 SPM27088 SPM33044 SPM33030 SPM33041 SPM33050 SPM33052 SPM33054 SPL27085 SPL27077 Sensor Assy, Aluminum, 4501-03 Sensor Assy, Aluminum, 4501-04 Sensor Assy, Aluminum, 4501-05 Sensor Assy, Aluminum, 4501-06/4501-08 Sensor Assy, Aluminum, 4501-10 Sensor Assy, Aluminum, 4501-12 Sensor Assy, Plastic, 4501-25 Sensor Assy, Plastic, 4501-26 Transmitter for 4501-XX Sensor Assy, 316SS, 4501-03 Sensor Assy, 316SS, 4501-04 Sensor Assy, 316SS, 4501-05 Sensor Assy, 316SS, 4501-06/4501-08 Sensor Assy, 316SS, 4501-10 Sensor Assy, 316SS, 4501-12 Sensor for 4501-03 Sensor for 4501-04 Sensor for 4501-05 Sensor for 4501-06 & 4501-08 Sensor for 4501-10 Sensor for 4501-12 Module Enclosure AL Module Enclosure SS Page 22 of 35 Model 4501-XX Toxic Gas Sensor Module 8.3 APPENDIX C: LIMITED WARRANTY SIERRA MONITOR CORPORATION warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment. SMC will repair or replace without charge any equipment found to be defective during the warranty period. Final determination of the nature and responsibility for defective or damaged equipment will be made by SMC personnel. All warranties hereunder are contingent upon proper use in the application for which the product was intended and do not cover products which have been modified or repaired without SMC approval or which have been subjected to accident, improper maintenance, installation or application, or on which original identification marks have been removed or altered. This Limited Warranty also will not apply to interconnecting cables or wires, consumables (i.e. calibration gases, batteries, sensors), nor to any damage resulting from battery leakage. In all cases SMC’s responsibility and liability under this warranty shall be limited to the cost of the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compliance with such instruction shall be a condition of this warranty. Except for the express warranty stated above, SMC disclaims all warranties with regard to the products sold hereunder including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of SMC for damages including, but not limited to, consequential damages arising out of/or in connection with the use or performance of the product. Page 23 of 35 Model 4501-XX Toxic Gas Sensor Module 8.4 APPENDIX D: 4501-25 & 4501-26 GAS SENSOR MODULE 1. Calibration of 4501-26 (Follow instructions in Section 6) 2. Calibration of 4501-25 (See below) 3. Equipment Required The following tools and equipment will be required for calibration: - Permeation Device Calibrator (Model 9210-00), with Ammonia Permeation Tube (Model 9211-09). - Calibration Adapter (Model 5358-01). 4. Permeation Device Calibrator Operation The calibrator is a portable device with a pump that operates from a 1.5 V alkaline size D battery. A fresh battery should allow 8 hours of continuous operation. The permeation device will probably be shipped separately, usually in a pipe with screw cap ends, one of which will be marked for opening. The permeation device should come fitted with a scrubber, but, as a precaution, open the pipe and remove the permeation device in a well ventilated area. 1. Remove the scrubber from the permeation device and attach the device to the stainless steel “Tee” assembly inside the calibrator box. Tighten the connection with a wrench, with the device resting inside one of the openings in the rack. Figure 8 - 1: Module Components 2. Close the door of the calibrator and turn on the pump switch. 3. Set the flow rate for the desired ppm of ammonia. The desired flow rate for calibration of the Model 4501-25 is 300-500 cc/min. and the concentration range should be set between the high alarm point and 100 ppm full scale. The carrier gas flow rate can be calculated from the formula: P = (CxF)/K Where P = the permeation rate in nanograms/min., and C = ppm of span gas, F = carrier gas flow rate in ml./min. and K = 1.437 for ammonia. The permeation rate for the temperature read on the front of the calibrator can be obtained from permeation rate vs. temperature chart. 4. Run the gas calibrator for 30 min. before attaching the output hose to the ammonia sensor. 5. When the use of the calibrator is completed, do not turn off the pump unit until the permeation device has been removed from the “Tee” and the gas scrubber reattached. Failure to remove the permeation device when the pump has been turned off will contaminate the system with high amounts of the permeating gas and result in erroneous concentrations. The device, with scrubber, can be stored in the storage rack overnight, but should not stay in the gas calibrator for longer storage periods. 5. Calibration Procedure Follow procedures outlined in Section 6.0 Page 24 of 35 Model 4501-XX Toxic Gas Sensor Module Electrolyte/Membrane Replacement (See Fig. 8-2) – Models 4501-25 and 4501-26 The electrolyte needs to be replaced at least every six months, or if there is evidence of low sensor output. The membrane and O-Ring should be replaced at the same time that the electrolyte is replaced. 1. Equipment Required - Electrolyte Recharge Kit (SPX27057 for Model 4501-25 NH3 and SPX27061 for Model 4501-26 HF) consisting of the electrolyte, package of 5 membranes, one (1) 0-Ring and alcohol wipes to clean the electrode. - Tweezers to aid in removing and replacing the membrane. 2. Preparation a. Transfer the necessary electrolyte into a plastic wash bottle. b. Confirm that system power has been removed. c. Remove the transmitter electronics board from the main housing and unplug the sensor harness from the transmitter electronics. d. Unscrew the sensor assembly from the bottom of the enclosure. e. Remove the assembly cover from the sensor assembly. CAUTION: Only remove the sensor cover from the assembly, DO NOT attempt to unscrew the sensor from the mounting assembly or you could damage the wiring. 3. Electrolyte Replacement (See Fig. 8-1) a. Invert the sensor assembly so that the membrane is upward. b. Insert the sensor assembly in a clamp, if available, and unscrew the box nut counterclockwise, and take out the hold-down ring, membrane and O-Ring. Then pour out the old electrolyte into a beaker for disposal. CAUTION: Avoid contact of the electrolyte with skin, eyes and clothing. immediately - rubber gloves and safety glasses are recommended. In case of contact wash c. Clean the electrode with the alcohol wipes included in the electrolyte replacement kit. All oxidation residue must be removed before re-assembly. When dirt is found inside the sensor assembly, wash the dirt off with electrolyte. d. Hold the sensor assembly with the sensing electrode up. Close the pressure compensation port with a tissue. Pour approximately 10cc of fresh electrolyte from the wash bottle into the sensor, and rinse the inside of the sensor. Empty the electrolyte into the beaker. e. Place the O-ring on top of the washer. Then transfer one drop of electrolyte from the plastic wash bottle to the exposed electrode surface. f. Place a new membrane into the hold-down ring and carefully place the plastic hold-down ring on top of the sensor body with the ring ears in the slots of the sensor body. Then fasten the sensor cover over the assembly. CAUTION: Never touch the membrane with your hands. Use rubber gloves or tweezers. g. Invert the sensor so that the membrane is down. If this is the first time that electrolyte has been replace, there should be a round Mili Seal covering the pressure compensation screw. This Mili-Seal prevented loss of electrolyte during shipment. Remove and discard the round Mili Seal and remove the screw to expose the electrolyte supply port. h. Transfer electrolyte from the plastic wash bottle into the electrolyte supply port (see Fig. 8-1) until the level is at the maximum level line on the side of the sensor body. Page 25 of 35 Model 4501-XX Toxic Gas Sensor Module i. Replace the pressure compensation screw into the electrolyte supply port. j. Replace the sensor housing cover. k. Install the sensor assembly into the enclosure hub and tighten firmly. l. Reconnect the sensor harness to the transmitter, carefully install the transmitter into the housing and restore system power. m. Recalibrate the transmitter following the instructions in Section 6. (WHITE) Figure 8 - 2: Sensor Assembly – Exploded View Page 26 of 35 Model 4501-XX Toxic Gas Sensor Module Figure 8 - 3: Model 4501-25-A1 and 4501-26-A1 Outline Dimensions Figure 8 - 4: Model 4501-25-S1 and 4501-26-S1 Outline Dimensions Page 27 of 35 Model 4501-XX Toxic Gas Sensor Module 8.5 APPENDIX E: US FM APPROVAL. . Page 28 of 35 Model 4501-XX Toxic Gas Sensor Module 8.6 Page 29 of 35 Model 4501-XX Toxic Gas Sensor Module APPENDIX F: CANADIAN FM APPROVAL . Page 30 of 35 Model 4501-XX Toxic Gas Sensor Module Page 31 of 35 Model 4501-XX Toxic Gas Sensor Module 8.7 APPENDIX G: ATEX CERTIFICATE Page 32 of 35 Model 4501-XX Toxic Gas Sensor Module Special Conditions for Safe Use: Contact the original manufacturer for information on the dimensions of the flameproof joints. Page 33 of 35 Model 4501-XX Toxic Gas Sensor Module 8.8 APPENDIX H: PIPE MOUNTING FOR 4501-XX ALUMINUM Figure 8 - 5: Model 4501-XX Aluminum Enclosure Pipe Mount Figure 8 - 6: Pipe Mount Bracket for 4501-XX Aluminum Enclosure Page 34 of 35 Model 4501-XX Toxic Gas Sensor Module INDEX 4-20MA ...............................................................1, 11 RANGE .................................................................. 11 AMMONIA............................................................... 24 SENSOR .................................. 2, 4, 6, 14, 16, 17, 22 APPROVALS .......................................................... 20 SET-UP .............................................................. 5, 11 CALIBRATION ............................. 1, 4, 14, 15, 22, 24 SPARE PARTS ...................................................... 22 DATA ENTRY KEYPAD ........................................... 9 SPECIFICATIONS ................................................. 19 ENCLOSURE ...........................................2, 7, 16, 20 THEORY OF OPERATION...................................... 1 FM .................................................................1, 28, 30 TRANSMITTER ......................................... 2, 5, 8, 17 INSTALLATION ..........................................5, 7, 8, 17 TROUBLESHOOTING........................................... 18 MAINTENANCE...................................................... 13 WARRANTY .................................................... 20, 23 MOUNTING .............................................................. 1 WIRING.................................................... 1, 2, 4, 5, 7 POWER .................................................................... 2 Page 35 of 35
© Copyright 2024