FDU FDUM

Micro Inverter [ INDOOR UNIT ]
FDU
DUCT CONNECTED -High Static pressureR410A
Point
1 Quiet operation:45dB(A)
Thanks to use of DC fan motor, fan steps increase from
two to four and quiet operation is achieved.
(Sound pressure level 45dB(A) in the Lo mode).
NEW
2 Improvement of the serviceability
Point
Fan unit (impeller and motor) can be
pulled out from the right side of the
unit. Maintenance can be available
from the right side or the bottom side.
(Common for FDU100VF1~140VF &
FDUM100VF1~140VF)
FDU 200/250
Pipe
Fan unit
3 High efficiency
Point
Remote control (Option)
Wired
Energy efficiency is improved by use of DC fan motor & high
efficient heat exchanger.
Wireless
8HP
(in case of 50Hz)
4
3
RC-EX1A
RC-E5
RCH-E3
RCN-KIT3-E
3.03
Models FDU200,250VG
2.52
3.01
10HP
4
2
1
1
Current
New
Current
EER
New
3.68
3.72
Current
New
3
2
COP
Dimensions (Unit:mm)
3.09
COP
(in case of 50Hz)
3.29
Current
EER
3.75
New
SPECIFICATIONS
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
220/230/240 V
Max. running current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Heating (Hi/Me/Lo)
Air flow
Outdoor Cooling/Heating
External static pressure*2
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter
Remote control (option)
kW
kW
kW
A
dB(A)
m3/min
Pa
mm
kg
ømm
m
m
°C
FDU200VSAVG
FDU250VSAVG
FDU200VG
FDU250VG
FDC200VSA
FDC250VSA
3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
19.0 ( 5.2 ~ 22.4 )
24.0 ( 6.9 ~ 28.0)
22.4 ( 3.3 ~ 25.0 )
27.0 ( 5.5 ~ 31.5 )
6.15 / 6.03
7.98/7.20
3.09 / 3.71
3.01/3.75
5
5
25
27
75 / 75
75 / 75
72 / 74
73 / 75
50 / 47 / 45
50 / 47 / 45
57 / 59
59 / 62
72 / 64 / 56
72 / 64 / 56
135
143 / 151
Standard:72 Max:200
379 x 1,600 x 893
1,300 x 970 x 370
1,505 x 970 x 370
89
115
143
9.52(3/8") / 22.22(7/8") 12.7(1/2") / 25.4(1")
Max.70
Max.30 / Max.15
-15~50*3
-15~20
Procure locally
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
External static pressure is 72Pa.
Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: External
static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level
* become 5dB(A)
higher at external static pressure of 200Pa.
a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
*3 : Ifwind.
If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 200/250VG: 52dB
Air flow: 200/250VG: 80m3/min