MODULE 2 Water-Based Suppression System Basics Based on the Ohio Building Code (OBC) National Fire Protection Association (NFPA) & Ohio Fire Code (OFC) 1 WATER-BASED SUPPRESSION SYSTEM BASICS-PART ONE This module covers: • Water supply sources • Components of fire suppression such as piping, valves, sprinkler heads, tests, foam system • Different types of automatic sprinkler systems • Standpipe systems • Foam and water mist suppression system 2 Water Supplies • The typical water supply for a water-based suppression system is a connection to a public waterworks system. However, other sources of water supply are acceptable. • Sources: • NFPA 13: 23.2 Water supply types • NFPA 13D: 6.2 Water supply sources • NFPA 13R: 9.3 Water supply sources • NFPA 20: 7.2 Water supplies 3 Water Supplies: Sources • A public waterworks system • An elevated tank • A pressure tank designed to American Society of Mechanical Engineers (ASME) standards for a pressure vessel with a reliable pressure source • A stored water source with an automatically operated pump • A well with a pump of sufficient capacity and pressure to meet the sprinkler system demand Example of a water supply source: An elevated tank 4 Fire Department Connections • NFPA states: The purpose of the Fire Department Connection is to supplement the water supply, but not necessarily provide the entire sprinkler system demand. Fire Department Connections are not intended to deliver a specific volume of water. • FDCs are required for most NFPA 13 and 13R automatic sprinkler systems and standpipe systems • NFPA 13 requires the fire department connection to be located on the street side of buildings • OBC 912.1 Installation. Fire department connections shall be installed in accordance with the NFPA standard applicable to the system design and shall comply with Section 912.2 through 912.5 5 6 Piping • In a wet pipe-sprinkler system water is constantly maintained within the piping • Dry pipe-sprinkler systems prevent the water from entering the sprinkler system piping Materials • Above ground piping material examples found in NFPA 13: 6.3 - steel, copper, and chlorinated polyvinyl chloride (CPVC). • Below ground material examples found in NFPA 13: 10.1 - ductile iron, steel, concrete, plastic, copper Location • NFPA 13: 10.6.1 Pipe shall not be run under buildings • NFPA 13: 10.6.2 Where pipe must be run under buildings, special precautions shall be taken. 7 Valves • A control valve controls the water to the sprinkler system and should be open at all times • A check valve has two-port valves, one for fluid to enter and the other for fluid to leave. • Pressure Requirements: NFPA 13: 6.7.1.1 When water exceed 175 psi, valves shall be used in accordance with their pressure rating Automatic Sprinkler Systems Handbook , Eighth Edition 8 Backflow Preventers • A device with check valves, air inlets, and/or relief valves installed on water piping designed to prevent the flow of water or other liquids, mixtures, or substances into the distributing pipes of a potable supply of water from any source or sources other than its intended source • Means of backflow prevention • air gap • atmospheric vacuum breaker (AVB) • reduced pressure valve assembly (RP) • double check valve assembly (DC) • NFPA 13: 7.2.6.5.4 A check valve or other positive backflow prevention device shall be installed in the air supply to each system to prevent airflow or water flow from one system to another. • NFPA 13: 10.10.2.5.1 The back flow prevention assembly shall be forward flow tested to ensure proper operation. • NFPA 13: 10.10.2.5.2 The minimum flow rate shall be the system demand, including hose stream demand where applicable 9 NFPA 13: Automatic Sprinkler Systems Handbook, 2013 Edition 10 SPRINKLER Definition • The component of a fire sprinkler system that discharges water after a fire has been detected • NFPA 13: 3.6.1 The following are characteristics of a sprinkler that define its ability to control or extinguish a fire: • Thermal sensitivity • Temperature rating • Specific orifice size • Installation orientation • Example: sidewall or pendent sprinklers • Water distribution characteristics • Special service conditions • Example: Corrosion-Resistant or Decorative Sprinklers Nozzle Definition • NFPA 13: 3.6.4.4 a device for use in applications requiring special water discharge patterns, directional spray, or other unusual discharge characteristics. 11 University of Toronto 12 Initiating Devices • A system component that originates transmission of a changeof-state condition • Includes smoke detectors, water flow alarm, fixed temperature detectors, rate of rise detectors, and heat detector 13 Test connections • Verify proper operation of equipment • Example: NFPA 13: 8.17.4.1 Main drain test connections shall be provided at locations that will permit flow tests of water supplies and connections • For inspection of sprinkler systems: • Alarm test connections can be located anywhere downstream of the main control valve on a wet pipe system per NFPA 13: 8.17.4.2.4 • Trip test connections must be located on the highest, most remote branch line of a dry pipe system per NFPA 13: 8.17.4.3.2 • NFPA 13: 26.1 A sprinkler system installed in accordance with this standard shall be properly inspected, tested, and maintained in accordance with NFPA 25. 14 Alarm attachments • NFPA 13: 8.17 System Attachments • NFPA 13: A.8.17.1 Central station, auxiliary, remote station, or propriety protective signaling systems are a highly desirable supplement to local alarms, especially from a safety to life standpoint. • NFPA 13: 8.17.1.1 Local Waterflow Alarms. A local waterflow alarm shall be provided on every sprinkler system having more than 20 sprinklers. 15 Automatic Sprinkler Systems: Wet Pipe • Definition NFPA 13: 3.4.10 Employs automatic sprinklers attached to a piping system containing water and connected to a water supply • NFPA 13: 7.7.1.3.2 Must be maintained at or above 40 °F (4 °C). • The water discharges immediately from sprinklers opened by heat from a fire Fire Systems, Inc 16 Automatic Sprinkler System: Dry-Pipe • Definition per NFPA 13: 3.4.5 Employs automatic sprinklers that are attached to a piping stream containing air or nitrogen under pressure • Are used when there is danger of some or all of the piping freezing. • The release of pressure permits the water pressure to open a dry pipe valve, and the water then flows into the piping system and out the opened sprinklers Fire Systems, Inc 17 Automatic Sprinkler System: Deluge • Definition per NFPA 13: 3.4.4 Employs open sprinklers that are attached to a piping system that is connected to a water supply through a valve • Valve is opened by the operation of a detection system installed in the same area • When valve opens, water flows into the piping system and discharges from all sprinklers Fire Systems, Inc 18 Automatic Sprinkler System: Pre-Action • Definition per NFPA 13: 3.4.9 A system that employs automatic sprinklers that are attached to a piping system that contains air (under or not under pressure) • Has a supplemental detection system installed in the same area as the sprinklers • Per NFPA 13: 7.3.2.1 Three basic types: single interlock, noninterlock, and double inter-lock • typically used in areas containing high value equipment or contents and spaces which are highly sensitive to the effects of accidental sprinkler water discharge. 19 Automatic Sprinkler System: Other • Anti-freeze • Circulating Closed Loop • Combined Dry Pipe-Preaction • Gridded • Looped • Multi-Cycle 20 Standpipe Systems and Classes: Automatic • A standpipe system that is attached to a water supply capable of supplying the system demand and that requires no action other than opening a hose valve to provide water at hose connections. • Standpipe systems are classified by their usage: Class I for heavy stream applications, Class II as first aid fire appliances, and Class III which has the features of both Class I and Class II • Wet: contains water at all times that is attached to a water supply capable of supplying the system demand at all times and that requires no action other than opening a hose valve to provide water at hose connections. • Dry: permanently attached to a water supply capable of supplying the system demand at all times, containing air or nitrogen under pressure, the release of which (as from opening a hose valve) opens a dry pipe valve to allow water to flow into the piping system and out of the opened hose valve. • Semi-automatic Dry: permanently attached to a water supply that is capable of supplying the system demand at all times arranged through the use of a device such as a deluge valve and that requires activation of a remote control device to provide water at hose connections. 21 Standpipe Systems and Classes: Manual • Standpipe systems are classified by their usage: Class I for heavy stream applications, Class II as first aid fire appliances, and Class III which has the features of both Class I and Class II • Wet: contains water at all times that relies exclusively on the fire department connection to supply the system demand. • Dry: has no permanently attached water supply that relies exclusively on the fire department connection to supply the system demand. 22 Foam Proportioning Systems • NFPA 11: 3.3.23 Proportioning. The continuous introduction of foam concentrate at the recommended ratio into the water stream to form foam solution. • Foam concentrate shall be introduced into the water flow by a concentrate controller utilizing balanced-pressure injection. • Types of Foam Proportioning System (NFPA 11: 3.3.23) • Balance Pressure Pump-Type Proportioning • In-Line Balanced Pressure Proportioning • Direct Injection Variable Pump Output Proportioning 23 Foam Concentrate • NPFA 11.3.3.12 Foam Concentrate. A concentrated liquid foaming agent as received from the manufacturer. • Types of Foam Concentrate (NFPA 11: 3.3.12) • Alcohol-Resistant Foam Concentrate • Aqueous Film-Forming Foam Concentrate (AFFF) • Fluoroprotein Foam Concentrate • Film-Forming Fluoroprotein Foam Concentrate (FFFP) 24 Foam Generators • Foam Generator Types (NFPA 11: 3.3.14) • Aspirator Type Jet streams of foam solutions aspirate sufficient amounts of air that is then entrained on the screens to produce foam • Blower Type Foam solution is discharged as a spray onto screens through which an airstream developed by a fan or blower is passing 25 NFPA 11 Standard for Low-, Medium-, and High-Expansion Foam 2005 Edition 26 Foam-Water Suppression Systems • Foam-water sprinkler system or foam-water spray systems are outlined in NFPA 16. • Foam-water sprinkler: • A special system that is pipe-connected to a source of foam concentrate and to a water supply. The system is equipped with appropriate discharge devices for extinguishing agent discharge and for distribution over the area to be protected. • Foam-water spray: • A special system that is pipe-connected to a source of foam concentrate and to a water supply. The system is equipped with foam-water spray nozzles for extinguishing agent discharge (foam followed by water or in reverse order) and for distribution over the area to be protected. 27 Foam-Water Suppression Systems • (NFPA 11: 5.1) Low-expansion foam to protect outdoor storage tanks, interior flammable liquid hazards, loading racks, diked areas, and non diked spill areas • (NFPA 11: 6.3) Medium and high-expansion foam shall be permuted to protect: (1) ordinary combustibles, (2) flammable and combustible liquids, combinations of (1) and (2), and liquefied natural gas (high-expansion only) 28 http://www.moody.af.mil/news/story.asp?id=123132709 29 Foam-Water Suppression Systems: Dry • Employs automatic sprinklers or nozzles that are attached to a piping system that contains air or nitrogen under pressure • The release of the pipe permits the water pressure to open a valve known as a dry pipe valve. • The water then flows into the piping system and out the opened sprinklers. 30 In Control Fire Protection 31 Foam-Water Suppression Systems: Preaction • Employs automatic sprinklers or nozzles attached to a piping system containing air that might or might not be under pressure, with a supplemental detection system installed in the same area as the sprinklers. • Actuation of the detection system opens a valve that permits water to flow into the sprinkler piping system and to be discharged from any sprinklers that have activated. 32 In Control Fire Protection 33 Foam-Water Suppression Systems: Deluge • Employs open discharge devices, which are attached to a piping system that is connected to a water supply through a valve that is opened by the operation of a detection system, which is installed in the same areas as the discharge devices. • When the valve opens, water flows into the piping system and discharges from all discharge devices attached thereto 34 In Control Fire Protection 35 Water Mist Suppression Systems • A distribution system connected to a water supply or water and atomizing media supplies • Is equipped with one or more nozzles capable of delivering water mist intended to control, suppress, or extinguish fires • NFPA 750 is the appropriate standard for the installation of water mist systems 36 Lessons Learned from Module 2 • There are many types of water supplies for water-based suppression systems, such as elevated tanks and water transported from a lake or spring. • A wet pipe automatic sprinkler system should not be installed in an area that goes below freezing and must be maintained at or about 40 degrees Fahrenheit. • Foam concentrate is a foam fire-fighting agent that must be diluted with water • There are two types of foam generators, blower and aspirator. • It is important to be familiar with the OBC, NFPA, OFC, and OPC. 37
© Copyright 2024