How To: Programme Master/Follower using extended cascade controller for FC202 (Based on 4 pump system with 0-10 bar transmitter as feedback) Display settings Master Drive Analogue input settings Master Drive Set analogue input 2 (terminal 54) to current using the dip switch behind the keypad Analogue input 2 default setting for current is 4-20mA Display settings Follower Drives Basic settings for both Master and Follower drives Settings for Follower drives only Set Term. 29 High Ref value 5-53 50 Hz Settings for Master drive only Use the closed loop wizard under ‘Quick Menu – Function Setup’ to set the feedback & PID settings Setpoint 1 (quick menu – function setup – closed loop settings) Table 1 20-21 4 bar (example)
© Copyright 2024