How to commission the AC units via the Communications Adaptor? 1

SIP Panasonic-Web - Interface Range
How to commission the AC units via the Communications Adaptor? - Technical Note
How to commission the AC units via the Communications Adaptor?
1
PANASONIC (SANYO) AC SYSTEM ADDRESSING
All SIP Panasonic products rely on the units address in the AC network to be static.
Caution
1.1
Ensure the Panasonic (Sanyo) AC system will not be re-addressed if the Panasonic (CZ-CFUNZ) (or Sanyo AMY SHA-KT256EG))
Communications adapter is re-started.
ENABLE STARTUP MODE IN THE SIP PANASONIC-WEB
Before scanning for the units installed on the AC network using the Panasonic (CZ-CFUNZ) (or Sanyo AMY SHA-KT256EG)) Communications adapter.
The SIP Panasonic Web Technical Guide provides additional information about the ‘Startup mode’
Note
1.
Set the ‘Discovery’ and ‘Commissioning’ mode ‘On’ (‘’/enable).

Caution
If necessary, set the ‘Central Addressing’ option to ‘On’ (‘’/enable).
If performing a scan of the VRF system in order to update the physical architecture, the tenant information must be verified, i.e. if the
physical architecture has changed, it is very likely that a tenant is not assigned to the appropriate indoor units. This may cause incorrect
energy calculations supplied to the incorrect tenant.
1
Issue 1, Jul. 2014
© Copyright Synapsys Solutions 2012
No.1 Woodlands Court, Albert Drive, Burgess Hill, West Sussex, RH15 9TN
Tel: 0845 680 0303 - Fax: 0845 680 0304
International - Tel: +44(0)1444 246128 - Fax: +44(0)1444 239527
Sales: [email protected] Orders: [email protected]
Web: http://www.synapsys-solutions.com
We reserve the right to change or amend any design or specification in accordance with our policy of continuing development and improvement. No warranty is given, implied or otherwise.
SIP Panasonic-Web - Interface Range
How to commission the AC units via the Communications Adaptor? - Technical Note
1.2
CONTROL THE AC SYSTEM UNIT ADDRESSING IN THE COMMUNICATIONS ADAPTOR
To ensure the AC network is commissioned (via the Communications adapter) for on-going reliability.
1.
Press ‘S6 (Home)’ for longer than 2 seconds, wait for the display to show ‘no.00’ and wait again for the display
to change to ‘AdP.dt’.
2.
Press ‘S7 (Up)’ 5 times until the displays shows ‘no.05’ and wait again for the display to change to ‘FirSt’.
3.
Press ‘S9 (Set)’ for the display to show ‘1.Ano.00’. This is the status of the Communications adaptor. The green
monitor LED is lit.
The ‘00’ in the ‘1.Ano.00’ refers to the adaptor number.
Note
4.
Press ‘S7 (Up)’ or ‘S8 (Down)’ until the displays shows ‘8.SCAn.0’.
5.
Press ‘S9 (Set)’ to confirm that changes will be made to this option.

1.3
The display shows ‘8.SCAn.0’
6.
Press ‘S7 (Up)’ or ‘S8 (Down)’ until the displays shows ‘8.SCAn.3’ and press ‘S9 (Set)’ to perform a scan of the units connected to LINK1 and LINK2
when the communication adaptor power is turned on. Wait for the Communications adaptor to complete the scan process and automatically return to the
‘Home’ display.
7.
Reboot the Communications adaptor and confirm the unit addresses are correct.
8.
Repeat 1 to 4 and the scan option to ‘8.SCAn.0’ and wait or the Communications adaptor to automatically return to the ‘Home’ display.
DISABLE STARTUP MODE IN THE SIP PANASONIC-WEB
1.
Set the ‘Discovery’ and ‘Commissioning’ mode ‘Off’ (‘’/disabled).

If necessary, set the ‘Central Addressing’ option to ‘Off’ (‘’/disable).
2
Issue 1, Jul. 2014
© Copyright Synapsys Solutions 2012
No.1 Woodlands Court, Albert Drive, Burgess Hill, West Sussex, RH15 9TN
Tel: 0845 680 0303 - Fax: 0845 680 0304
International - Tel: +44(0)1444 246128 - Fax: +44(0)1444 239527
Sales: [email protected] Orders: [email protected]
Web: http://www.synapsys-solutions.com
We reserve the right to change or amend any design or specification in accordance with our policy of continuing development and improvement. No warranty is given, implied or otherwise.