CONTROL/ELEMENTARY
SYMBOLS
NORMALLY OPEN CONTACT
NORMALLY CLOSED CONTACT
LIMIT SWITCH, NORMALLY OPEN
LIMIT SWITCH, NORMALLY CLOSED
PRESSURE SWITCH, NORMALLY OPEN
PRESSURE SWITCH, NORMALLY CLOSED
FLOAT SWITCH, NORMALLY OPEN
FLOAT SWITCH, NORMALLY CLOSED
ELECTRICAL PLAN SYMBOLS
SYSTEMS BACKBOARD AS NOTED
S
WALL OUTLET BOX AND 20 AMP SINGLE POLE SWITCH (`a' INDICATES SWITCHES) 48" TO CETERLINE
S3
WALL OUTLET BOX AND 20 AMP 3-WAY SWITCH (`a' INDICATES SWITCHES) 48" TO CTR LINE.
SV
WALL OUTLET BOX AND EXHAUST FAN SPEED CONTROLLER/SWITCH CONNECTIONS.
SM
MANUAL MOTOR STARTING SWITCH WITH OVERLOADS AND PILOT LIGHT. NEMA 4X TYPICAL
WALL OUTLET BOX AND 20 AMP SWITCH WITH PILOT LIGHT.
S WP
WALL OUTLET BOX AND 20 AMP SWITCH WITH WEATHERPROOF COVER OR ENCLOSURE.
WALL OUTLET BOX AND 20 AMP DUPLEX RECEPT MOUNTED 48"AFF
TEMPERATURE SWITCH, NORMALLY OPEN
OR AS NOTED.
KILOWATT METER
WALL OUTLET BOX AND DOUBLE 20 AMP DUPLEX RECEPTACLES 18" TO CENTERLINE
A
AMMETER
WALL OUTLET BOX AND SPECIAL PURPOSE RECEPTACLE AS NOTED OR COORDINATE.
VS
THREE PHASE VOLT SWITCH
AS
THREE PHASE AMP SWITCH
AT
CURRENT TRANSMITTER
SLASH MARKS INDICATE NUMBER OF CONDUCTORS; (MARKS SHOWN TO AID CONTRACTOR IN BIDDING,
KW
KILOWATT TRANSMITTER
OR NOT SHOWN). SHORT SLASHES INDICATE PHASE CONDUCTOR OR SWITCH LEG, LONG INDICATE
PFT
POWER FACTOR TRANSMITTER
AR
ALARM RELAY
AT
ALARM TIMER
CR
CONTROL RELAY
BRANCH CIRCUIT CONDUIT AND WIRE GENERALLY SURFACE MOUNTED, CONCEALED ABOVE CEILINGS
THE CONTRACTOR SHALL PROVIDE THE REQUIRED CONDUCTORS UNDER THE CONTRACT SUM WHETHER
PHOTOCELL ON ROOF
J
FLUSH MOUNTED JUNCTION BOX ( SURFACE IN MECH/ELEC SPACES OR ABOVE CEILINGS).
F/T
FIT
FLOW INDICATOR TRANSMITTER (TOTALIZER)
FSH
FSL
FLOW SWITCH HIGH/LOW
LLS
FS
LIQUID LEVEL SWITCH
NEUTRAL CONDUCTOR. GREEN GROUND CONDUCTOR NOT SHOWN; ALL CONDUITS REQUIRE COPPER
GROUND CONDUCTOR. TWO CONDUCTORS PLUS GROUND REQUIRED, MINIMUM.
L/T
LIT
LEVEL INDICATOR TRANSMITTER
CONDUIT AND WIRE CONCEALED IN FLOOR SLAB OR UNDERGROUND.
LS
LIMIT SWITCH OR LEVEL SWITCH
BRANCH CIRCUIT PANELBOARD
M
MOTOR SWITCH MANUAL
45
MOTOR STARTER
PRESSURE GAUGE
PFT
PROCESS FLOW TIMER
PS
PRESSURE SWITCH
TS
TEMPERATURE SWITCH
TR
TIMING RELAY
SURGE SUPPRESSION DEVICE
SV
SOLENOID VALVE
VS
VIBRATION SWITCH
AS NOTED; SEE PANEL SCHEDULES
GFI
GROUND FAULT INTERRUPTER
W
TRANSFORMER, SIZE AS INDICATED
ALARM INDICATING LIGHT
R
RUN INDICATING LIGHT
FUSE
SERVING MOTOR LOADS OF 10HP OR GREATER AND FOR ALL MOTOR LOADS SERVED THROUGH
CAPACITOR
DRAW-OUT CIRCUIT BREAKER
COMBINATION MAGNETIC MOTOR STARTER PROVIDED BY ELECTRICAL U.N.O.
MOULDED CASE CIRCUIT BREAKER
HP
MOTOR CONNECTION
TYPICAL STARTER CONTROL. SEE SWITCHGEAR
CONTROL DIAGRAMS FOR EXACT TYPE.
MOV
MOTOR OPERATED VALVE CONNECTION
NO
ELECTRIC A.C. MOTOR, NO. INDICATES HORSEPOWER.
HP
AIR HANDLING UNIT CONNECTION; PROVIDE FUSED DISCONNECT AS REQUIRED BY EQUIPMENT
NAMEPLATE; MAKE CONNECTIONS.
NO
ELECTRIC D.C. MOTOR, NO. INDICATES HORSEPOWER.
NON-FUSIBLE DISCONNECT SWITCH, 30A,3P UNLESS
OTHERWISE INDICATED.
LIGHTING FIXURES SYMBOLS
MOMENTARY BREAK PUSHBUTTON OR RESET
MAINTAINED CONTACT ON-OFF SWITCH
FLUORESCENT TROFFER FIXTURE AND CEILING OUTLET BOX
START/STOP (S/S) CONTROL SWITCH
FLUORESCENT WALL MOUNTED FIXTURE AND OUTLET BOX
FUSE
FLUORESCENT TROFFER FIXTURE WITH INTEGRAL NICAD EMERGENCY BATTERY PACK.
MAINTAINED CONTACT
CURRENT TRANSFORMERS
EMERGENCY LIGHTING BATTERY PACK FIXTURE; PROVIDE
POTENTIAL TRANSFORMERS
EXIT LIGHT FIXTURE AND WALL OR CEILING OUTLET BOX
(3) COPPERWELD GRD. RODS
HID FIXTURE
COPPERWELD GRD. ROD
POLE MOUNTED SEE DETAIL
STAND MOUNTED ARTICULATING ARM DOCK LIGHT
RKS
Consulting
Engineers
Electrical, Instrumentation & Control Design
HOLE MONTES
15400 Shamrock Dr. Fort Myers, Fl. 33912
P.E.
DATE
MANUAL OR AUTOMATIC TRANSFER SWITCH
(SHADED QUADRANT INDICTES FACE(S) OF FIXTURE)
DELTA GROUND ROD LAYOUT
KIRK KEY INTERLOCK
HID OR INCANDESCENT WALL MOUNTED FIXTURE AND OUTLET BOX
UNSWITCHED CIRCUIT TO BATTERY CHARGER.
COPPERWELD GRD. ROD
MOTOR STRIP HEATER
K
HID OR INCANDESCENT FIXTURE AND CEILING OUTLET BOX
REMOTE TERMINAL BLOCK POINT
SHR
LIGHTING PANELBOARD
FLUORESCENT WALL MOUNTED FIXTURE WITH INTEGRAL NICAD EMERGENCY BATTERY PACK
CONTROL POWER TRANSFORMER
HAND OFF AUTO CONTROL STATION
AS REQUIRED BY ELEMENTARY DIAGRAMS OR SPECS.
POWER PANELBOARD
MOLDED CASE CIRCUIT BREAKER
HAND OFF REMOTE CONTROL STATION
NON-FUSIBLE DISCONNECT SWITCH, 30A,3P UNLESS
OTHERWISE INDICATED, WITH REMOTE CONTROL STATION
FLUORESCENT STRIP FIXTURE AND CEILING OUTLET BOX
KEYED SWITCH
HOR
SERVICE OR EQUIPMENT GROUND.
MANUAL TRANSFER SWITCH OR REVERSING SWITCH
MOMENTARY CONTACT PUSHBUTTON
HOA
WATT HOUR METER
DISCONNECT SWITCH SIZE PER EQUIPMENT NAME PLATE OR AS NOTED: FOR DISCONNECTS
ELECTRIC DUCT HEATER CONNECTION; PROVIDE FUSED DISCONNECT AS REQUIRED BY
EQUIPMENT NAMEPLATE; MAKE CONNECTIONS.
A
NO.
LOCAL CONTROL PANEL
VARIABLE FREQUENCY DRIVES; PROVIDE SURGE SUPPRESSION DEVICE EQUAL TO SQ.-D. SP3650
ZERO SPEED SWITCH
Certificate of Authorization #8212
CP
OR EQUAL AT DISCONNECT.
TORQUE SWITCH
K
POWER FACTOR METER
NORMALLY CLOSED, TIMED TO CLOSE CONTACT
ANALYZER INDICATOR TRANSMITTER
ZS
PF
KW
AIT
YSH
VOLTMETER
WALL OUTLET BOX AND 20 AMP GFCI RECEPTACLE MOUNTED 48"AFF OR AS NOTED.
NORMALLY OPEN, TIMED TO OPEN CONTACT
S/S
V
NORMALLY CLOSED, TIMED TO OPEN CONTACT
P/G
ELECTRICAL SYMBOLS LEGEND & DRAWING INDEX
ELECTRICAL GENERAL NOTES SCHEDULE
SLUDGE CONVEYOR SYSTEM RELOCATION POWER PLAN
ELECTRICAL DETAILS
INDICATES WEATHERPROOF COVER PLATE.
NORMALLY OPEN, TIMED TO CLOSE CONTACT
MS
E1
E2
E3
ED1
SINGLE LINE
DIAGRAM SYMBOLS
WALL OUTLET BOX AND 20 AMP GFCI DUPLEX RECEPTACLE AT 18" TO CENTERLINE. WP
TEMPERATURE SWITCH, NORMALLY CLOSED
K:\CCUD NCWRF Operational Readiness Projects\Operational Readiness\Conveyor Mods\E1.dwg Plotted: May 19, 2011 - 12:58pm by tracy
LIGHTNING PROTECTION AIR TERMINAL
STREAMER RETARDING TYPE.
WALL OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE 18" TO CENTERLINE
FLOW SWITCH, NORMALLY CLOSED
PE #62427
SYSTEMS CABINET AS NOTED OR MARKED.
DRAWING INDEX
STREAMER RETARDING AIR TERMINAL
MOUNTED TO LIGHT POLE.
SP
FLOW SWITCH, NORMALLY OPEN
TRACY PROKOPETZ
SYSTEM SYMBOL LEGEND
REVISIONS
BY
ENGINEERS PLANNERS SURVEYORS
LANDSCAPE ARCHITECTS
950 Encore Way
Naples, FL. 34110
Phone: (239) 254-2000
Florida Certificate of
Authorization No.1772
DESIGN BY:
T.M.P.
DRAWN BY:
T.M.P.
CHECKED BY:
T.M.P.
CAD FILE:
E1.dwg
NORTH COUNTY WATER RECLAMATION FACILITY
OPERATIONAL READINESS PROJECT
PROJECT NO. :
2010.075
DATE :
ELECTRICAL SYMBOLS LEGEND & DRAWING INDEX
05/11
SHEET NO. :
E1
ELECTRICAL GENERAL NOTES
1.
DO NOT SCALE THE ELECTRICAL DRAWINGS.
REFER TO THE MECHANICAL AND
STRUCTURAL DRAWINGS AND APPROVED MANUFACTURER'S SHOP DRAWINGS FOR THE
EXACT LOCATION OF ALL EQUIPMENT.
LOCATIONS OF EXISTING FACILITIES.
23.
REFER TO SITE SURVEY DRAWINGS FOR EXACT
2.
ALL WORK SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL
SAFETY CODE, UTILITY REQUIRMENTS AND LOCAL CODES.
3.
PROVIDE SCHEDULE 40 PVC CONDUIT BELOW GRADE IN CONCRETE ENCASED DUCT BANKS.
PROVIDE SCHEDULE 80 PVC CONDUIT BELOW GRADE IN NON-ENCASED DUCT BANKS.
CONTROLLERS AND SERVICE POINTS. IDENTIFICATION SHALL
MATCH PANELBOARD SCHEDULES, MCC SECTION, I&C SHOP
DRAWINGS & SCHEDULES & TAG LISTS, ETC.
24.
4.
CONDUCTORS SHALL NOT BE SPLICED WITHOUT WRITTEN PERMISSION FROM
ENGINEER.
5.
FURNISH AND INSTALL A #2 TINNED BARE COPPER COUNTERPOISE WIRE ABOVE ALL
6.
ALL DISCONNECTS, J-BOXES, TERMINAL CABINETS, ETC. & MOUNTING HARDWARE SHALL
7.
ALL CONDUITS (POWER, CONTROL, INSTRUMENTATION, ETC.) SHALL HAVE EQUIPMENT
8.
PROVIDE CONCRETE REINFORCED ENCASEMENT OF ALL DUCT BANKS INCLUDING
9.
DO NOT ABANDON ELECTRICAL IN PLACE. REMOVE CONDUCTORS BACK TO PANEL/MCC.
25.
FROM THE DESIGNED FACILITIES, THE CONTRACTOR SHALL
REDESIGN THE FACILITIES AND SUBMIT THE REVISED DESIGN FOR
THE ENGINEER'S APPROVAL AT NO ADDITIONAL COST TO THE
OWNER. PRIOR TO ELECTRICAL SUBMITTAL THE CONTRACTOR
SHALL VERIFY ALL SUPPLIED BREAKER SIZES, STARTER SIZES,
OVERLOAD SIZES, ETC. FOR ALL SYSTEMS SUCH AS HVAC,
EXHAUST FANS, CHEMICAL PUMPS ETC. AND MODIFY BREAKERS,
OVERLOADS, ETC. IN CONTRACTOR SUPPLIED EQUIPMENT
BE NEMA 4X STAINLESS STEEL UNLESS NOTED OTHERWISE.
GROUNDING CONDUCTOR SIZED PER TABLE 250.122 OF THE N.E.C.
ACCORDINGLY.
26.
DUCTBANKS UNDER STRUCTURES; TYPICAL.
27.
THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL INSTRUMENT/CONTROL EQUIPMENT
28.
LOCATIONS WITH THE MECHANICAL DRAWINGS AND THE CONTROLS CONTRACTOR PRIOR TO
ROUGH-IN. LOCATIONS SHOWN ON DRAWING ARE APPROXIMATE ONLY. THE ELECTRICAL
11.
DOCUMENT COORDINATION TO THE GENERAL
ALL WIRE INTO AND OUT OF CONTROL CABINETS SHALL BE TYPE TC CONTROL
CABLE WITH MULTIPLE CONDUCTORS, #14 STRANDED WIRE AS SPECIFIED; TYPICAL
29.
30.
THROUGHOUT.
12.
ALL WIRE INTO AND OUT OF INSTRUMENTATION CABINETS SHALL BE TYPE TC
TWISTED SHIELDED INSTRUMENT CABLE WITH MULTIPLE CONDUCTOR PAIRS OF #16
STRANDED WIRE AS SPECIFIED; TYPICAL THROUGHOUT
K:\CCUD NCWRF Operational Readiness Projects\Operational Readiness\Conveyor Mods\E2.dwg Plotted: May 19, 2011 - 12:57pm by tracy
13.
DURING CONSTRUCTION.
REQUIREMENTS.
SEE MECHANICAL DRAWINGS FOR EXACT ROUTING AND ELEVATIONS OF DUCTBANKS.
15.
ALL CONDUCTORS SHALL BE ROUTED IN AND OUT OF MANHOLES TAKING THE
DISTANCE TO ALLOW FOR SLACK CABLE.
LONGEST
16.
ALL CONTROL PANELS SHALL BE CONSTRUCTED BY A UL508A APPROVED PANEL VENDOR
AND SHALL BEAR A UL508A LABEL ON THE PANEL.
17.
DRAWINGS DO NOT SHOW EXACT ROUTING OF CONDUIT. COORDINATE CONDUIT LOCATIONS
WITH OTHER TRADES SO THAT CONFLICTS ARE AVOIDED.
18.
LOCATIONS OF MANHOLES, HANDHOLES AND PULL BOXES ARE APPROXIMATE.
19.
PROVIDE A #2 BOND FROM ALL FIELD INSTRUMENTS, MOTORS, CONTROL PANELS,
20.
PROVIDE 2' MINIMUM DISTANCE BETWEEN PARALLEL RUNS OF LOW VOLTAGE 480V &
CONTRACTOR SHALL COORDINATE EXACT LOCATION WITH EXISTING AND PROPOSED PIPING
AND OTHER INTERFERENCES.
TERMINATION CABINETS, ETC TO THE GROUND GRID.
120V POWER CONDUITS AND I&C CONDUITS. POWER CONDUIT SHALL CROSS
INSTRUMENTATION CONDUIT PERPENDICULARLY AT RIGHT ANGLES WITH 6" MINIMUM
SEPARATION FOR 480V & 120V. VFD MOTOR LEAD CONDUIT SHALL HAVE 24"
NON-DESTRUCTIVE IMAGING METHODS (RADAR,
XRAY) TO LOCATE EMBEDDED CONDUIT IN CONCRETE
PRIOR TO DEMOLITION, SAW CUTTING AND CORE
COORDINATE WITH G.C. THE REQUIRED TEMPORARY
14.
IT IS THE CONTRACTOR'S RESPONSIBILITIES TO USE
DRILLING. RELOCATE AND RECONSTRUCT AFFECTED
CONDUIT AND WIRE PER ELECTRICAL SPECIFICATIONS.
31.
SEPARATION TO INSTRUMENTATION & CONTROL CONDUITS.
21.
CONDUCTOR PULLING TENSIONS SHALL NOT EXCEED MANUFACTURER'S RECOMMENDATION.
22.
PLAN DRAWINGS DO NOT SHOW ALL CONDUITS REQUIRED. PROVIDE ADDITIONAL CONDUIT
CONTRACTOR SHALL INSTALL PULL BOXES TO MEET MANUFACTURER'S REQUIREMENTS.
FOR CONDUCTORS AS SHOWN ON RISER, ONE-LINE DIAGRAMS, DETAILS AND NOTES.
RKS
Electrical, Instrumentation & Control Design
HOLE MONTES
15400 Shamrock Dr. Fort Myers, Fl. 33912
TRACY PROKOPETZ
PE #62427
P.E.
Certificate of Authorization #8212
NO.
DATE
REVISIONS
BY
ENGINEERS PLANNERS SURVEYORS
LANDSCAPE ARCHITECTS
950 Encore Way
Naples, FL. 34110
Phone: (239) 254-2000
Florida Certificate of
Authorization No.1772
DESIGN BY:
T.M.P.
DRAWN BY:
T.M.P.
CHECKED BY:
T.M.P.
CAD FILE:
E2.dwg
GROUNDING CONNECTIONS BELOW GRADE SHALL BE EXOTHERMIC
UNLESS SPECIFICALLY INDICATED OTHERWISE.
ALL ENCLOSURES, TERMINAL CABINETS, WIREWAYS, PULL BOXES
ETC. SHALL CONTAIN A GROUNDING BUS BAR. CONNECT ALL
RACEWAY BONDS TO BUS BAR VIA GROUNDING BUSHING AND
EXTEND BONDING JUMPER FROM BUS BAR TO ENCLOSURE.
CONTRACTOR SHALL CORE DRILL EXISTING CONCRETE WALLS,
FLOORS, MANHOLES, HANDHOLES AND PULL BOXES FOR CONDUIT
32.
ALL CONDUITS PENETRATING RATED FIRE WALLS OR RATED FIRE
FLOORS SHALL BE INSTALLED WITH U.L. APPROVED DEVICES TO
MAINTAIN THE FIRE RATING OF THE WALL OR FLOOR
PENETRATED.
33.
PROVIDE CONDUIT DUCT SEAL AT ALL CONDUIT ENDS.
34.
ALL SPARE CONDUITS SHALL BE SEALED WITH A CAP AT BOTH
ENDS AND A PULL STRING INSTALLED WITH IDENTIFICATION ON
BOTH ENDS.
35.
FLEXIBLE CONDUITS SHALL BE USED TO TERMINATE ALL MOTORS
AND OTHER VIBRATING EQUIPMENT & SHALL BE A MAXIMUM OF
24" IN LENGTH.
36.
PROVIDE TYPEWRITTEN PANEL SCHEDULES IN PANELBOARD &
TYPEWRITTEN TERMINAL BLOCK SCHEDULES IN TERMINAL
CABINETS; PROPOSED & MODIFIED.
37.
38.
39.
40.
41.
42.
Consulting
Engineers
PROVIDE COLORED WARNING TAPE 6" WIDE SHALL BE INSTALLED
12" BELOW FINISHED GRADE DIRECTLY ABOVE ALL UNDERGROUND
PENETRATIONS. SEAL PENETRATIONS WITH NON GROUT OR
APPROPRIATE FIRE RATED DEVICES WHERE APPLICABLE.
THE SEQUENCE OF CONSTRUCTION WILL REQUIRE TEMPORARY ELECTRICAL SERVICES
BE PROVIDED TO ALL AFFECTED FACILITIES TO MAINTAIN CONTINUOUS OPERATION
MINIMUM DEPTH FROM TOP OF DUCTBANKS OR CONDUITS TO
FINISHED GRADE SHALL BE 30" UNLESS OTHERWISE NOTED.
YARD CONDUITS.
CONTRACTOR SHALL VERIFY ALL CONTROL CABLING REQUIRED WITH THE CONTROLS
CONTRACTOR PRIOR TO ROUGH-IN.
CONTRACTOR PRIOR TO ROUGH-IN.
ALL EXCAVATIONS FOR CONDUITS, HANDHOLES, MANHOLES AND
PULLBOXES NEAR EXISTING PIPING, CONDUIT AND EQUIPMENT
SHALL BE HAND EXCAVATED AND COORDINATED WITH ENGINEER.
REMOVE CONDUIT BACK TO FIRST MANHOLE, HANDHOLE OR REUSE FOR NEW WORK.
IF NOT BEING REUSED.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONDUIT
AND WIRING INSTALLATION FOR ALL VENDOR PROVIDED
EQUIPMENT (PACKAGE SYSTEMS). IF THE SHOP DRAWINGS DIFFER
CONDUITS IN DUCT BANKS, BONDED TO BUILDING COUNTERPOISE AT BOTH ENDS.
REMOVE COMPLETE DUCT BANK AND MANHOLES
10.
THE
EXPOSED RUNS OF CONDUITS SHALL BE INSTALLED WITH RUNS
PARALLEL OR PERPENDICULAR TO WALLS, STRUCTURAL MEMBERS
OR INTERSECTIONS OF VERTICAL PLANES AND CEILINGS, WITH
RIGHT ANGLE TURNS CONSISTING OF SYMMETRICAL BENDS OR
PULL BOXES AS INDICATED ON THE DRAWINGS. BENDS AND
OFFSETS SHALL BE AVOIDED WHERE POSSIBLE.
MAJOR DUCT BANKS AS INDICATED, MINOR DUCT BANKS AS DIRECTED BY ENGINEER IN
FIELD. PROVIDE BELL END CONDUIT IN MANHOLES AND AT STUBUP LOCATIONS. ALL U.G.
PROCESS RELATED CONDUIT SHALL BE PROTECTED IN CONCRETE ENCASEMENT.
ALL CIRCUITS SHALL BE IDENTIFIED IN JUNCTION BOXES, PULL
BOXES, CONTROL PANELS, PANELBOARDS, LIGHTING POLES,
PROVIDE 1/2"=1' SCALE ELECTRICAL ROOM/AREA LAYOUT
DRAWING SUBMITTAL, SHOWING ALL ELECTRICAL EQUIPMENT.
20AMP LIGHTING AND RECEPTACLE BRANCH CIRCUITS EXCEEDING
75 FT IN LENGTH SHALL BE A MINIMUM #10 AWG WIRE.
ALL EXTERIOR DISCONNECTS, J-BOXES, TERMINAL CABINETS, ETC.
& MOUNTING HARDWARE SHALL BE NEMA 4X STAINLESS STEEL
UNLESS NOTED OTHERWISE.
PROVIDE CONCRETE REINFORCED ENCASEMENT OF ALL DUCT
BANKS.
COMPLY WITH NEC REQUIREMENTS FOR HAZARDOUS AREAS AS
DEFINED BY NFPA-820 STANDARDS FOR FIRE PROTECTION IN
WASTEWATER TREATMENT AND COLLECTION FACILITIES CURRENT
EDITION.
COMPLY WITH THE NEC REQUIREMENTS FOR HAZARDOUS AREAS
AS DEFINED BY NFPA-820 STANDARDS FOR FIRE PROTECTION
IN WASTEWATER TREATMENT AND COLLECTION FACILITIES
CURRENT EDITION.
NORTH COUNTY WATER RECLAMATION FACILITY
OPERATIONAL READINESS PROJECT
PROJECT NO. :
2010.075
DATE :
GENERAL ELECTRICAL NOTES
05/11
SHEET NO. :
E2
6'
UP TO
PANEL
EDCCP
6'
0
3/32"=1'-0"
7
KEYNOTES
#
1.
5
J
TO BE REMOVED
6
EXISTING EAST CONVEYOR TO BE ROTATED 180
DEGREES. ALL ASSOCIATED ELECTRICAL AND
10
15
INSTRUMENT CONNECTIONS REQUIRED TO BE
RELOCATED WHETHER SPECIFICALLY SHOWN OR
NOT.
2.
EXISTING EAST CONVEYOR LOCAL DISCONNECT TO
REMAIN.
EXISTING ZERO SPEED SWITCH TO BE
RELOCATED.
4.
EXISTING SURVEILLANCE CAMERA TO BE
RELOCATED.
5.
EXISTING SURVEILLANCE CAMERA JUNCTION BOX
TO REMAIN.
6.
REROUTE EXISTING CONDUIT AND WIRE TO
13
K:\CCUD NCWRF Operational Readiness Projects\Operational Readiness\Conveyor Mods\E3.dwg Plotted: May 19, 2011 - 2:35pm by tracy
EXISTING H2S ANALYZER ELEMENT TO BE
RELOCATED.
12.
PROPOSED AUTO LUBRICATION STATION.
CONNECTION
6"-DRN
MCC-7A
3
LP7C
-
MCC 8A/B
C
-
MCC 7B
LOWER LEVEL PLAN
PULL IN NEW WIRE FROM EXISTING DISCONNECT
TO RELOCATED MOTOR. MATCH EXISTING WIRE
TYPE AND SIZE.
11.
2
LP7B
CONDUIT TO PROPOSED EQUIPMENT LOCATION.
EXISTING CONDUIT WIRE AND EQUIPMENT TO
4
FD
RELOCATED.
10.
9
8
4
8
LP7D
PULL IN COAX VIDEO CABLE FROM EXISTING
JUNCTION BOX TO RELOCATED CAMERA. MATCH
EXISTING CABLE TYPE.
INTERCEPT EXISTING CONDUIT AND PROVIDE NEW
ZS
6
FD
CONDUIT TO PROPOSED EQUIPMENT LOCATION.
9.
7.5
TO BE ROTATED 180 DEGREES
AIT
INTERCEPT EXISTING CONDUIT AND PROVIDE NEW
PROPOSED LOCATION OF EXISTING EQUIPMENT
1
3
8
DRILL REQUIRED.
REMOVE
8.
AE
UP TO UPPER
LEVEL CORE
UNUSED CONDUIT SUPPORTS FROM STRUCTURE.
PATCH AND PAINT.
7.
ZS
11
AE
8
3.
PROPOSED EQUIPMENT LOCATION.
16
8
7.5
6
EXISTING EAST
DISTRIBUTION
CONVEYOR CONTROL
REMAIN.
PANEL (EDCCP)
COORDINATE EXACT CONNECTION REQUIREMENTS
WITH SUBMITTAL PRIOR TO ROUGH-IN.
13.
14.
15.
PROVIDE 20A, 1P BREAKER IN EXISTING
M
PANEL. MATCH EXISTING MANUFACTURER AND
BREAKER TYPE FOR SERVICE TO AUTO
LUBRICATION UNIT.
FHP
SUSPEND PROPOSED CONDUIT FROM EXISTING
STRUCTURE WITH STAINLESS STEEL ALL-THREAD
AND UNISTRUT. AVOID STAIRS WHEN COMING
DOWN TO MAKE CONNECTION TO AUTO LUBE
SYSTEM.
12
14
INTERCEPT EXISTING CONDUIT AND PROVIDE NEW
CONDUIT TO PROPOSED EQUIPMENT LOCATION.
PULL IN NEW CABLE FROM EXISTING EAST
DISTRIBUTION CONVEYOR CONTROL PANEL(EDCCP)
TO RELOCATED ZERO SPEED SWITCH.
EXISTING CABLE TYPE.
16.
MATCH
INTERCEPT EXISTING CONDUIT AND PROVIDE NEW
DN TO
PNL
LP7D
CONDUIT TO PROPOSED EQUIPMENT LOCATION.
PULL IN NEW INSTRUMENT CABLE FROM EXISTING
ANALYZER TRANSMITTER TO RELOCATED
ANALYZER ELEMENT. MATCH EXISTING CABLE
TYPE.
GENERAL NOTES:
EXTEND, REROUTE, RECONNECT, REPAIR EXISTING
1.
EQUIPMENT BONDS TO PROPOSED EQUIPMENT
LOCATIONS.
= DEMO COMPLETE
UPPER LEVEL PLAN
RKS
Consulting
Engineers
Electrical, Instrumentation & Control Design
HOLE MONTES
15400 Shamrock Dr. Fort Myers, Fl. 33912
TRACY PROKOPETZ
PE #62427
P.E.
Certificate of Authorization #8212
NO.
DATE
REVISIONS
BY
ENGINEERS PLANNERS SURVEYORS
LANDSCAPE ARCHITECTS
950 Encore Way
Naples, FL. 34110
Phone: (239) 254-2000
Florida Certificate of
Authorization No.1772
DESIGN BY:
T.M.P.
DRAWN BY:
T.M.P.
CHECKED BY:
T.M.P.
CAD FILE:
E3.dwg
NORTH COUNTY WATER RECLAMATION FACILITY
OPERATIONAL READINESS PROJECT
PROJECT NO. :
2010.075
DATE :
SLUDGE CONVEYOR SYSTEM RELOCATION
POWER PLAN
05/11
SHEET NO. :
E3
STEEL OR CONCRETE
CONDUIT
COVER THIS
PORTION WITH
SHRINK
TUBING
5" MIN.
12" MAX.
SIZE AS REQUIRED
WRAPPED SHIELD
GREEN
INSULATED WIRE
AWG 18
CRIMPED SPLICE
CONNECTOR
COVER THIS
PORTION WITH
SHRINK
TUBING
AS REQUIRED
SINGLE RACK
SHIELD
SHRINK TUBING
5" MIN.
12" MAX.
SIGNAL LEADS
LUG. TYPICAL
GROUND LEAD
CONDUIT
SIZE AS REQUIRED
OUTER JACKET
SHRINK TUBING
NOTE: SHIELD
GROUNDED AT
TERMINATION
CONDUIT
SIZE AS
STAINLESS STEEL
HARDWARE TYP
OUTER JACKET
SHIELD
CONCRETE OR STEEL
5" MIN.
12" MAX.
OUTER JACKET
REQUIRED
TERMINATION OF SHIELDED
INSTRUMENT
& CONTROL CABLE
N.T.S.
DOUBLE RACK
CONDUIT RACKING SYSTEMS
FEEDER OR BRANCH CONDUCTOR
BRASS OR STAINLESS DISK
N.T.S.
BUILDING WALL
W/STAMPED IDENTIFICATION
LB CONDULETS
1/8" DIA. 50-50
SOLDER WIRE OR
NYLON TIE
STRAP
FINISH GRADE
U.G. CABLE TAG DETAIL
2'-0"
K:\CCUD NCWRF Operational Readiness Projects\Operational Readiness\Conveyor Mods\ED1.dwg Plotted: May 19, 2011 - 12:54pm by tracy
MIN.
N.T.S.
CONDUIT ENTRANCE TO
EXISTING
FACILITY
N.T.S.
CONDUIT SHALL BE GROUNDED WITH
INSULATED GROUNDING BUSHINGS
SIZE AND NUMBER AS REQUIRED
STEEL CONDUIT
GROUND WIRE
CONDUIT GROUNDING DETAIL
N.T.S.
RKS
Consulting
Engineers
Electrical, Instrumentation & Control Design
HOLE MONTES
15400 Shamrock Dr. Fort Myers, Fl. 33912
TRACY PROKOPETZ
PE #62427
P.E.
Certificate of Authorization #8212
NO.
DATE
REVISIONS
BY
ENGINEERS PLANNERS SURVEYORS
LANDSCAPE ARCHITECTS
950 Encore Way
Naples, FL. 34110
Phone: (239) 254-2000
Florida Certificate of
Authorization No.1772
DESIGN BY:
T.M.P.
DRAWN BY:
T.M.P.
CHECKED BY:
T.M.P.
CAD FILE:
ED1.dwg
NORTH COUNTY WATER RECLAMATION FACILITY
OPERATIONAL READINESS PROJECT
PROJECT NO. :
2010.075
DATE :
ELECTRICAL DETAILS
05/11
SHEET NO. :
ED1