ENGINEERING REPORT

ENGINEERING REPORT
XYZ Corporation
100 Anyplace Drive
Chicago, Illinois 60613
PERFORMED BY:
MIDWEST ELECTRICAL CONSULTANTS, INC
18055 UPLAND DRIVE
TINLEY PARK, ILLINOIS 60487
(708) 444-0001 fax: 444-0003
www.midwestelectrical.com.
POWER QUALITY TESTING & INSPECTIONS OF TRANE AIR
CONDITIONING COMPRESSOR(S) ELECTRICAL SERVICE
PROJECT: C822
1
D.J. Sweeney Electric
6813 Hopson Valley Drive
Woodridge, Illinois 60517
May 5, 2008
Re: Power quality testing & inspections of Trane compressor(s) electrical service
Attention: Mr. Timothy Sweeney,
Enclosed is the engineering report detailing the project that we recently completed
at the XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613. MEC is a full
service independent testing company and appreciates the opportunity to provide
your system review, inspection, power quality testing and engineering support
services.
Our mission is to provide an independent technical service to enhance the safety,
reliability and efficiency of electrical systems.
Thank you for the opportunity to provide this service. Please contact us if you
have any questions or wish to know more about our services.
Respectfully Submitted,
Douglas Christianson
Electrical Engineer
Cc: Mr. William W. Baird - XYZ Corporation
Cc: Mr. Robert Rogers - Advantage Electric
Cc: Mr. Timothy Fashing - Roberts Mechanical
2
ENGINEERING REPORT
XYZ Corporation
100 Anyplace Drive
Chicago, Illinois 60613
Power Quality Testing & Inspections of Trane Compressor(s) Electrical Service
SECTION 1
SCOPE; PURPOSE; PROCEDURE;
APPRAISAL AND RECOMMENDATIONS
SECTION 2
POWER QUALITY MONITORING DATA
(separate file)
SECTION 3
ADDITIONAL TESTING SUPPORT DATA
(separate file)
3
ENGINEERING REPORT
XYZ Corporation
Chicago, IL
Power Quality Testing & Inspections of Trane Compressor(s) Electrical Service
SECTION I
SCOPE:
On April 29, 2008, Midwest Electrical Consultants, Inc. (MEC) provided power
quality testing and inspections at the XYZ Corporation 100 Anyplace Drive
Chicago, Illinois 60613 twin Trane Heli Rotor RTWA070AY001C3DOWN air
conditioning compressor(s) electrical service. All testing and inspections were
performed according to the manufacturer and International Electrical Testing
Association (NETA) recommendations.
Detailed inspection notes and observations documented during the execution of
this project are contained in the additional support test data (separate file) test data
section (separate file) and recommendation section of this engineering report. This
summary contains data for the completed inspections.
PURPOSE:
The purpose of this inspection and subsequent report is to provide information
relative to the operation of the Trane air conditioning compressor(s) electrical
service and equipment located in the XYZ Corporation building. This report is
intended to assist you in planning for upgrades or changes to the electrical system,
increase the safety of the electrical system through inspections and provide
recommendations for future equipment usage at the facility. It is not intended to
imply that other equipment issues or recommendations not covered in this scope
may or may not exist at the time of the inspection.
PROCEDURE:
All inspections and recommendations are performed in accordance with MEC’s
standard procedures including, but not limited to, selected specifications from the
following: International Electrical Testing Association (NETA), National Electrical
Code (NEC), National Fire Protection Association 70B-Electrical Equipment
Maintenance (NFPA 70B), Institute of Electrical and Electronic Engineers (IEEE),
American Society for Testing and Materials (ASTM), National Electrical
Manufacturer's Association (NEMA), Occupational Safety and Health
Administration (OSHA), unless otherwise noted.
INSPECTIONS: The electrical distribution equipment associated with the Trane air
conditioning compressor(s) electrical service was inspected for installation
according to standard NEC practices, appropriate sizing and cleanliness.
Equipment inspections included the grounding system and ground system
bonding.
4
ENGINEERING REPORT
XYZ Corporation
100 Anyplace Drive
Chicago, Illinois 60613
Power Quality Testing & Inspections of Trane Compressor(s) Electrical service
APPRAISAL AND RECOMMENDATIONS: The Trane Heli Rotor air
conditioning compressor(s) system was found to be installed according to
manufacture and electrical standard practices. A digital power recorder was
installed at the local compressor(s) disconnect and allowed to monitor
during multiple starts of the unit.
Compressor(s) disconnect location (240 volt compressor)
1) Utility/system voltage levels were found to be imbalanced during the
monitoring period (approximately 4.7%). Average voltage levels were
found to be 236 volts on A-B, 247 volts on B-C, 245 volts on C-A.
Voltage magnitudes were consistent during compressor(s) starts,
indicating the system is not overloaded. MEC recommends review of
the electrical service voltage levels with the utility to determine if the
voltage imbalance is caused by service entrance equipment
(transformer(s), cabling, connectors, etc.) or utility distribution (grid)
system voltage deviation caused perhaps by loading or other issues.
2) Compressor(s) motor currents (amps) were found to be severely
imbalanced at the main disconnect panel. Average current for each
phase was 28.6 amps- Phase ‘A’, 46.3 amps - Phase ‘B’, and 54.7
amps - Phase ‘C’ per motor. Load imbalances greater than 4% (91%
during the monitoring period) would typically indicate an internal
motor problem. Further investigation indicates a different problem
exists at this location. Motor leads were moved to accommodate
proper rotation at the compressor(s) control board. Upon restart of
the compressor(s) with exchanged phasing, the voltage and current
imbalances followed the same phases to different motor windings
(See two attached files, section 2 power quality monitoring data, and
section 3 additional testing support data). Investigation of the
electrical service voltage levels is recommended.
3) Overhead transformers providing service for the facility were
inspected for proper installation and operation. Inspection of the
transformers indicate that transformer bank ‘A’ (East) is currently or
was previously overloaded. Localized discoloration and corrosion of
transformer tank components (secondary bushings) generally
indicates an overloaded condition. MEC recommends investigation
of the electrical transformers by utility personnel.
5
4) Voltage magnitudes at the utility transformer secondary locations
were found to be identical to the voltage levels measured at the
compressor(s) disconnect location. Due to similar voltage readings,
we recommend a review of the utility distribution system.
5) We recommend that an adequately sized dedicated power source
(e.g. diesel or natural gas generator) be used to support the
compressor(s) load to confirm the existing utility source issue, and
run the equipment until the problem is corrected.
APPRAISAL AND RECOMMENDATIONS: General
1) MEC recommends REGULAR ELECTRICAL INSPECTIONS, CLEANING
AND TESTING of electrical equipment to assist in identifying deteriorated
insulation, abnormal operating temperatures and malfunctioning protective
devices prior to equipment failure.
2) All electrical protective equipment including ground fault relays, circuit
breakers and fused disconnects should be tested, exercised and lubricated
on a regular basis. Mechanical equipment may not operate properly when
called upon if regular maintenance is neglected.
3) New OSHA requirements have been issued regarding Arc Flash
recommendations and personnel safety. New Arc Flash requirements will
require all facilities (industrial, commercial, institutional) to display
information about the arc flash availability at each panel, switch or breaker
where the equipment is accessible by maintenance/site personnel. The arc
flash information on the panel fronts will indicate the level of clothing and
level of training required to open and maintain the equipment within the
panel or switchboard. See note #2 above; protective equipment which does
not operate within specified tolerances (tripping time or magnitudes) will
invalidate any Arc flash study results.
4) Transient voltage surge suppressor (tvss) units were not evident on any of
the electrical distribution equipment we inspected or tested at. We
recommend the installation of a properly sized high quality tvss unit on the
main electrical switchboard. The main tvss unit will mitigate or remove any
and all transient voltage spike and surge disturbances caused externally to
the building (lightning, electrical storms, downed power lines, utility
company switching, high winds, tree branches, ice/snow on utility lines and
distribution equipment, other utility customers in close proximity, etc.) Also
secondary sub panel or final point of protection tvss units should be installed
on or at ALL critical equipment especially electronic loads (fire alarm,
security, telephone, roof hvac, elevators, etc.) to address or clamp internally
generated switching transient/surge events created by all electrical and
electronic equipment being turned off and on or duty cycled within the
building. The secondary level of protection would also act as back up
protection should the primary tvss unit become damaged or sacrificial.
6
All plug in or corded electronic equipment (pc’s, monitors, printers, modems,
Fax, etc.) should be plugged into a quality corded power strip tvss unit. I
would direct your attention to the documentation I left with you for a more
detailed explanation on this subject. We would be happy to provide any
engineering assistance in the selection or installation of any of the transient
voltage surge suppressors outlined in this report.
7
Power Analysis Collected Data Summary Section 2
Introduction
This is a summary of the power conditions at the XYZ Coporation 100 Anyplace Drive
Chicago, Illinois 60613 as recorded at location delta setup#2 Trane Heli Rotor air
conditioning compressor(s) service disconnect. Data at this location was collected from
04/29/08 11:16:18 through 04/29/08 11:31:18.
This summary is composed of:
• The Voltage Current and Frequency, (VIF), section. This section contains summaries
for each of these parameters during the monitor interval.
• The Harmonics section. This contains the voltage and current harmonic, and
harmonic distortion summaries acquired during the monitor interval.
• The Power section. This contains the VA, VARS., Watts, and Power factor acquired
during the monitor interval. For multiphase locations, voltage and current imbalance
are also included.
Site and Location Information
Site Information
Name
Account Number
Date and Time
Phone Number
Contact
Memo
Problem Description
Date First noticed
Problem Frequency
How problem exhibits itself
Problem Cost
Location Information
Name
Power Type
Feed Phase
Phone
Date and Time
Nominal Voltage
Nominal Frequency
XYZ Coporation
04/29/08 09:24:20
04/29/08
Unknown
Unknown
delta setup #2 Trane compressor(s) service disconnect
Three phase delta
Unknown
04/29/08 11:06:38
240 Volts
60 Hz
1
Report Parameters
This report was prepared on 4/29/2008 by Midwest Electrical Consultants, Inc. 18055
Upland Drive Tinley Park, Illinois 60487 (708) 444-0001 fax: 444-0003
www.midwestelectrical.com The following limits were used in analyzing the results.
Maximum Phase Voltage.
Minimum Phase Voltage.
Maximum Impulse Voltage.
Maximum. Waveshape Voltage.
Maximum Frequency Deviation.
Minimum Power Factor.
Maximum Voltage T.H.D.
Maximum Current T.H.D
Maximum Voltage Imbalance.
Maximum Current Imbalance.
254 volts
208 volts
500 volts
10 volts
.02 Hz
.85
5%
20 %
2%
5%
Any values outside these limits are noted in the report. Values within the limits are
considered to be within a safe operating range. These limits have been programmed by
Midwest Electrical Consultants, Inc.
2
Voltage, Current and Frequency Summaries
Voltage, Current and Frequency measurements for XYZ Coporation:delta setup#2 from
04/29/08 11:16:18 through 04/29/08 11:31:18.
RMS. Voltages
Value
Date and Time
Phase A minimum
Phase A average
Phase A maximum
Phase B minimum
Phase B average
Phase B maximum
Phase C minimum
Phase C average
Phase C maximum
229.2V
235.8V
240.4V
240.3V
247.2V
255.3V
239.5V
245.1V
252.2V
Apr 29 2008 11:21:22
RMS. Currents
Value
Date and Time
Phase A minimum
Phase A average
Phase A maximum
Phase B minimum
Phase B average
Phase B maximum
549.3mA
11.93A
380.3A
3.662A
20.53A
487.2A
Apr 29 2008 11:21:41
Phase C minimum
Phase C average
Phase C maximum
1.098A
23.14A
343.5A
Apr 29 2008 11:18:23
Frequency
Value
Date and Time
Phase A minimum
Phase A average
Phase A maximum
Phase B minimum
Phase B average
Phase B maximum
Phase C minimum
Phase C average
Phase C maximum
42.12Hz
43.61Hz
44.69Hz
42.12Hz
43.61Hz
44.69Hz
42.12Hz
43.61Hz
44.69Hz
Apr 29 2008 11:21:22
Apr 29 2008 11:21:22
Apr 29 2008 11:21:22
Apr 29 2008 11:21:22
Apr 29 2008 11:19:48
Apr 29 2008 11:21:22
Apr 29 2008 11:19:49
Apr 29 2008 11:21:52
Apr 29 2008 11:22:18
Apr 29 2008 11:22:18
Apr 29 2008 11:16:42
Apr 29 2008 11:21:22
Apr 29 2008 11:16:42
Apr 29 2008 11:21:22
Apr 29 2008 11:16:42
3
RMS. Voltage Summaries for XYZ Coporation:delta setup#2.
Phase A Voltage Summary.
Min.
Avg.
Max.
229.2V
235.8V
240.4V
Apr 29 2008 11:21:22
Apr 29 2008 11:21:22
4
Phase B Voltage Summary.
Min.
Avg.
Max.
240.3V
247.2V
255.3V
Apr 29 2008 11:21:22
Apr 29 2008 11:21:22
5
Phase C Voltage Summary.
Min.
Avg.
Max.
239.5V
245.1V
252.2V
Apr 29 2008 11:19:48
Apr 29 2008 11:21:22
6
RMS. Current Summaries for XYZ Coporation:delta setup#2.
Phase A Current Summary.
Min.
Avg.
Max.
549.3mA
11.93A
380.3A
Apr 29 2008 11:21:41
Apr 29 2008 11:19:49
7
Phase B Current Summary.
Min.
Avg.
Max.
3.662A
20.53A
487.2A
Apr 29 2008 11:21:52
Apr 29 2008 11:22:18
8
Phase C Current Summary.
Min.
Avg.
Max.
1.098A
23.14A
343.5A
Apr 29 2008 11:18:23
Apr 29 2008 11:22:18
9
Voltage and Current Distortion Summaries
Voltage and Current harmonic distortion measurements for XYZ Coporation:delta
setup#2 from 04/29/08 11:16:18 through 04/29/08 11:31:18.
Voltage Distortion
Value
Date and Time
Phase A minimum
Phase A average
Phase A maximum
Phase B minimum
Phase B average
Phase B maximum
Phase C minimum
Phase C average
Phase C maximum
2.83%
3.388%
5.68%
2.55%
3.039%
4.83%
2.95%
3.523%
5.38%
Apr 29 2008 11:23:55
Current Distortion
Value
Date and Time
Phase A minimum
Phase A average
Phase A maximum
4.81%
34.15%
67.92%
Apr 29 2008 11:19:48
Phase B minimum
Phase B average
Phase B maximum
Phase C minimum
Phase C average
Phase C maximum
4.06%
121.5%
308.2%
3.8%
30.55%
143.9%
Apr 29 2008 11:19:48
Voltage Flicker
Value
Date and Time
Phase A minimum
Phase A average
Phase A maximum
Phase B minimum
Phase B average
Phase B maximum
Phase C minimum
Phase C average
Phase C maximum
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Apr 29 2008 11:21:22
Apr 29 2008 11:21:00
Apr 29 2008 11:21:22
Apr 29 2008 11:19:15
Apr 29 2008 11:21:22
Apr 29 2008 11:17:47
Apr 29 2008 11:17:42
Apr 29 2008 11:19:48
Apr 29 2008 11:16:43
10
Voltage T.H.D. Summaries for XYZ Coporation:delta setup#2 .
Phase A Voltage Distortion.
Min.
Avg.
Max.
2.83%
3.388%
5.68%
Apr 29 2008 11:23:55
Apr 29 2008 11:21:22
11
Phase B Voltage Distortion.
Min.
Avg.
Max.
2.55%
3.039%
4.83%
Apr 29 2008 11:21:00
Apr 29 2008 11:21:22
12
Phase C Voltage Distortion.
Min.
Avg.
Max.
2.95%
3.523%
5.38%
Apr 29 2008 11:19:15
Apr 29 2008 11:21:22
13
Current T.H.D. Summaries for XYZ Coporation:delta setup#2.
Phase A Current Distortion.
Min.
Avg.
Max.
4.81%
34.15%
67.92%
Apr 29 2008 11:19:48
Apr 29 2008 11:17:47
14
Phase B Current Distortion.
Min.
Avg.
Max.
4.06%
121.5%
308.2%
Apr 29 2008 11:19:48
Apr 29 2008 11:17:42
15
Phase C Current Distortion.
Min.
Avg.
Max.
3.8%
30.55%
143.9%
Apr 29 2008 11:19:48
Apr 29 2008 11:16:43
16
Power Summaries
Power measurements for XYZ Coporation:delta setup#2 from 04/29/08 11:16:18 through
04/29/08 11:31:18.
Imbalance
Value
Date and Time
Minimum Voltage Imbalance
Average Voltage Imbalance
Maximum Voltage Imbalance
Minimum Current Imbalance
Average Current Imbalance
Maximum Current Imbalance
2.68%
2.840%
3.37%
2.17%
48.58%
154.8%
Apr 29 2008 11:23:30
VA Power
Value
Date and Time
Phase A minimum
Phase A average
Phase A maximum
Phase B minimum
Phase B average
Phase B maximum
Phase C minimum
Phase C average
Phase C maximum
Total minimum
Total average
Total maximum
97.69VA
1.660kVA
51.31kVA
512.7VA
2.868kVA
65.88kVA
179.5VA
3.346kVA
48.39kVA
925.0VA
7.874kVA
77.57kVA
Apr 29 2008 11:21:41
VARS Power
Value
Date and Time
Phase A minimum
Phase A average
Phase A maximum
-3.482kVAR
1.457kVAR
49.95kVAR
Apr 29 2008 11:19:49
Phase B minimum
Phase B average
Phase B maximum
Phase C minimum
Phase C average
Phase C maximum
-4.439kVAR
1.475kVAR
26.88kVAR
-13.10kVAR
2.845kVAR
46.66kVAR
Apr 29 2008 11:22:18
Total minimum
Total average
Total maximum
-3.962kVAR
5.777kVAR
68.11kVAR
Apr 29 2008 11:16:43
Apr 29 2008 11:21:22
Apr 29 2008 11:22:17
Apr 29 2008 11:16:43
Apr 29 2008 11:19:49
Apr 29 2008 11:21:52
Apr 29 2008 11:22:18
Apr 29 2008 11:21:48
Apr 29 2008 11:22:18
Apr 29 2008 11:21:48
Apr 29 2008 11:19:48
Apr 29 2008 11:22:18
Apr 29 2008 11:22:17
Apr 29 2008 11:16:43
Apr 29 2008 11:22:18
Apr 29 2008 11:19:48
17
Watts Power
Value
Date and Time
Phase A minimum
Phase A average
Phase A maximum
Phase B minimum
Phase B average
Phase B maximum
Phase C minimum
Phase C average
Phase C maximum
Total minimum
Total average
Total maximum
-11.75kW
737.8W
15.35kW
-97.99W
2.118kW
19.78kW
-3.091kW
1.706kW
20.38kW
-98.06W
4.563kW
36.85kW
Apr 29 2008 11:19:49
Demand Power
Value
Date and Time
Phase A minimum
Phase A average
Phase A maximum
Phase B minimum
Phase B average
Phase B maximum
Phase C minimum
Phase C average
Phase C maximum
645.8W
707.4W
788.7W
1.806kW
1.982kW
2.214kW
1.434kW
1.570kW
1.750kW
Apr 29 2008 11:16:42
Total minimum
Total average
Total maximum
3.887kW
4.260kW
4.753kW
Apr 29 2008 11:16:42
Power Factor
Value
Date and Time
Phase A minimum
Phase A average
Phase A maximum
Phase B minimum
Phase B average
Phase B maximum
Phase C minimum
Phase C average
Phase C maximum
Total minimum
Total average
Total maximum
0.968 Lead
0.271 Lag
0.000 Lag
0.000 Lead
0.608 Lag
0.004 Lag
0.003 Lead
0.344 Lag
0.000 Lag
0.861
0.270
0
Apr 29 2008 11:19:49
Apr 29 2008 11:22:18
Apr 29 2008 11:21:22
Apr 29 2008 11:22:18
Apr 29 2008 11:21:22
Apr 29 2008 11:19:49
Apr 29 2008 11:21:22
Apr 29 2008 11:19:48
Apr 29 2008 11:21:18
Apr 29 2008 11:16:42
Apr 29 2008 11:21:18
Apr 29 2008 11:16:42
Apr 29 2008 11:21:18
Apr 29 2008 11:21:18
Apr 29 2008 11:21:22
Apr 29 2008 11:21:22
Apr 29 2008 11:17:46
Apr 29 2008 11:16:43
Apr 29 2008 11:16:43
Apr 29 2008 11:22:18
Apr 29 2008 11:21:23
18
Voltage and Current Imbalance Summaries for XYZ Coporation:delta setup#2.
Minimum Voltage Imbalance
Average Voltage Imbalance
Maximum Voltage Imbalance
2.68%
2.840%
3.37%
Apr 29 2008 11:23:30
Apr 29 2008 11:21:22
19
Minimum Current Imbalance
Average Current Imbalance
Maximum Current Imbalance
2.17%
48.58%
154.8%
Apr 29 2008 11:22:17
Apr 29 2008 11:16:43
20
VA Power Summaries for XYZ Coporation:delta setup#2.
Phase A VA Summary.
Min.
Avg.
Max.
97.69VA
1.660kVA
51.31kVA
Apr 29 2008 11:21:41
Apr 29 2008 11:19:49
21
Phase B VA Summary.
Min.
Avg.
Max.
512.7VA
2.868kVA
65.88kVA
Apr 29 2008 11:21:52
Apr 29 2008 11:22:18
22
Phase C VA Summary.
Min.
Avg.
Max.
179.5VA
3.346kVA
48.39kVA
Apr 29 2008 11:21:48
Apr 29 2008 11:22:18
23
Total VA Summary.
Min.
Avg.
Max.
925.0VA
7.874kVA
77.57kVA
Apr 29 2008 11:21:48
Apr 29 2008 11:19:48
24
VARS Power Summaries for XYZ Coporation:delta setup#2.
Phase A VARS Summary.
Min.
Avg.
Max.
-3.482kVAR Apr 29 2008 11:19:49
1.457kVAR
49.95kVAR Apr 29 2008 11:22:18
25
Phase B VARS. Summary.
Min.
Avg.
Max.
-4.439kVAR Apr 29 2008 11:22:18
1.475kVAR
26.88kVAR Apr 29 2008 11:22:17
26
Phase C VARS. Summary.
Min.
Avg.
Max.
-13.10kVAR Apr 29 2008 11:16:43
2.845kVAR
46.66kVAR Apr 29 2008 11:22:18
27
Total VARS Summary.
Min.
Avg.
Max.
-3.962kVAR Apr 29 2008 11:16:43
5.777kVAR
68.11kVAR Apr 29 2008 11:19:48
28
WATTS Power Summaries for XYZ Coporation:delta setup#2.
Phase A Watts Summary.
Min.
-11.75kW
Max. 15.35kW
Apr 29 2008 11:19:49Avg.
737.8W
Apr 29 2008 11:22:18
29
Phase B Watts. Summary.
Min.
Avg.
Max.
-97.99W
2.118kW
19.78kW
Apr 29 2008 11:21:22
Apr 29 2008 11:22:18
30
Phase C Watts. Summary.
Min.
Avg.
Max.
-3.091kW
1.706kW
20.38kW
Apr 29 2008 11:21:22
Apr 29 2008 11:19:49
31
Total Watts Summary.
Min.
Avg.
Max.
-98.06W
4.563kW
36.85kW
Apr 29 2008 11:21:22
Apr 29 2008 11:19:48
32
Power Factor Summaries for XYZ Coporation:delta setup#2.
Phase A Power Factor Summary.
Min.
Avg.
Max.
0.968 Lead Apr 29 2008 11:19:49
0.271 Lag
0.000 Lag Apr 29 2008 11:21:22
33
Phase B Power Factor. Summary.
Min.
Avg.
Max.
0.000 Lead Apr 29 2008 11:21:22
0.608 Lag
0.004 Lag Apr 29 2008 11:17:46
34
Phase C Power Factor. Summary.
Min.
Avg.
Max.
0.003 Lead Apr 29 2008 11:16:43
0.344 Lag
0.000 Lag Apr 29 2008 11:16:43
35
Total Power Factor Summary.
Min.
Avg.
Max.
0.861
0.270
0
Apr 29 2008 11:22:18
Apr 29 2008 11:21:23
36
MIDWEST ELECTRICAL CONSULTANTS, INC.
18055 UPLAND DRIVE
TINLEY PARK, ILLINOIS 60487
(708) 444-0001 fax: 444-0003
www.midwestelectrical.com
SECTION 3
Trane Heli Rotor compressor motor power supply testing :
Tests performed during the monitoring period at the XYZ Coporation 100 Anyplace
Drive Chicago, Illinois 60613, consisted of rotation of the phases to test the
compressor(s) equipment for problems. Amperage readings are taken on each
phase, then the phases are rotated and a second set of amperage readings are taken.
Comparing the two sets of readings indicates if the problem is located in the motor
or power supply system. The following example in figures 1 and 2 illustrates the
procedure per motor:
Step 1:
Measure all three legs
A phase - 28.6 amps
B phase - 46.3 amps
C phase - 54.7 amps
Figure 1
Page 2
Figure 2
Step 3:
Measure amperages again
C phase - 54.7 amps
A phase - 28.6 amps
B phase - 46.3 amps
Notice that the amperages rotated with the wires. This indicates
the problem lies within the utility electrical supply to the facility,
had the amperages remained with the motor windings when the
wires were rotated, the problem would have been in the motor
windings.
Page 2