Metal oxide arrester (ZnO)
Polymeric Housing
IEC 60099-4
Nominal discharge current: 10 kA
Line discharge class 2
High current impulse 4/10 µs: 100 kA
Energy Capability:
4.5 kJ/kV at Ur according to
IEC 60099-4
(Clause 8.4.2 table 5 & 8.5.5)
Surge Arrester Characteristics
Rated voltage:
Continuous operating voltage:
TOV Capability:
Outdoor application
Rated short circuit current:
Max. App. Cant. Load
Pull Strength:
Impulse voltage -1,2/50 µs:
Power frequency voltage- wet:
Flashover Distance:
Creepage Length:
Approx. Weight:
Maximum Residual Voltages
Lightning current impulse
8/20 µs
5 kA
30.8 kV
10 kA
33.1 kV
20 kA
36.5 kV
40 kA
41.5 kV
HSRAP12
Line Terminal
Ground Terminal
Mounting
Drawing: BOW-4-001
Ur : 12.0
Uc : 9.60
Tc : 14.2
40
2513
5000
195
61.1
249
600
1.9
kV
kV
kV for 1s
kA
N
N
kV
kV
mm
mm
kg
Steep lightning
current impulse
1/20 µs
10 kA
20 kA
35.5 kV
39.3 kV
Switching current
impulse 30/60 µs
125 A
24.4 kV
250 A
25.1 kV
500 A
25.9 kV
1000A
27.0 kV
2000 A
28.3 kV
* Residual voltage correction factor as per IEC recommendation 10kV/10kA/m
Power frequency voltage versus time with prior energy
Marking
1.25
RATIO OF WITHSTAND
VOLTAGE (Uw) /
RATED VOLTAGE (Ur)
1.15
1.10
1.05
1.00
0.95
1
TIME (s)
10
100
1000
10000
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however,
should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an
assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
Bowthorpe EMP, TE Logo and Tyco Electronics are trademarks.
Technical Information: - Contact Product Management Brighton UK (+44 (0)1273 692591)
Tyco Electronics UK Ltd.. Stevenson Road, Brighton. East Sussex. BN2 0DF England
Phone: +44-(0)1273-692591, Fax: +44-(0)1273-601741
http://energy.tycoelectronics.com
BOW-EPP-HSRAP12-03-07
ZnO - Surge - Arrester
ISC 40 kA
IN 10 kA, class 2
HSRAP12
IEC 60099-4
Manufacturing Year
Ur : 12.0 kV
Uc : 9.60 kV
1.20
HSR Range
Bowthorpe EMP Transmission Surge Arrester
Metal oxide arrester (ZnO)
Polymeric Housing
IEC 60099-4
Nominal discharge current: 10 kA
Line discharge class 2
High current impulse 4/10 µs: 100 kA
Energy Capability:
4.5 kJ/kV at Ur according to
IEC 60099-4
(Clause 8.4.2 table 5 & 8.5.5)
Surge Arrester Characteristics
Rated voltage:
Continuous operating voltage:
TOV Capability:
Outdoor application
Rated short circuit current:
Max. App. Cant. Load
Pull Strength:
Impulse voltage -1,2/50 µs:
Power frequency voltage- wet:
Flashover Distance:
Creepage Length:
Approx. Weight:
Maximum Residual Voltages
Lightning current impulse
8/20 µs
5 kA
73.9 kV
10 kA
79.4 kV
20 kA
87.6 kV
40 kA
99.6 kV
HSRCP30
Line Terminal
Ground Terminal
Mounting
Drawing: BOW-4-003
Ur : 30.0
Uc : 24.0
Tc : 35.4
40
1210
5000
267
142
482
1325
6.0
kV
kV
kV for 1s
kA
N
N
kV
kV
mm
mm
kg
Steep lightning
current impulse
1/20 µs
10 kA
20 kA
85.3 kV
94.3 kV
Switching current
impulse 30/60 µs
125 A
58.6 kV
250 A
60.2 kV
500 A
62.3 kV
1000A
64.7 kV
2000 A
67.9 kV
* Residual voltage correction factor as per IEC recommendation 10kV/10kA/m
Power frequency voltage versus time with prior energy
Marking
1.25
RATIO OF WITHSTAND
VOLTAGE (Uw) /
RATED VOLTAGE (Ur)
1.15
1.10
1.05
1.00
0.95
1
TIME (s)
10
100
1000
10000
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however,
should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an
assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
Bowthorpe EMP, TE Logo and Tyco Electronics are trademarks.
Technical Information: - Contact Product Management Brighton UK (+44 (0)1273 692591)
Tyco Electronics UK Ltd.. Stevenson Road, Brighton. East Sussex. BN2 0DF England
Phone: +44-(0)1273-692591, Fax: +44-(0)1273-601741
http://energy.tycoelectronics.com
BOW-EPP-HSRCP30-03-07
ZnO - Surge - Arrester
ISC 40 kA
IN 10 kA, class 2
HSRCP30
IEC 60099-4
Manufacturing Year
Ur : 30.0 kV
Uc : 24.0 kV