EL-VARME
EL-heating
Eksplosionssikker
ribberørsovn
Explosion proof
ribbed pipe radiator
Bruges til opvarmning i eksplosionssikre områder - som f.eks. batterirum, containere, tankstationer eller tavler (f.eks. maling- og kemisk
materiale).
Bruges også på olieplatforme, raffinaderier for
at undgå kondens i kontrolskabe.
Application areas space heating and control
cabinet heating, such as battery, paint or chemical material storage rooms and gas stations.
Applied on platforms, chemical and petrochemical plants for space heating. Applied in control cabinets to prevent condensation in switchboards, control and instrument panel.
Standardregel ved beregning af varmeforbrug.
- indendørs installation 30-60W/m3
- udendørs installation 60-100W/m3
- installation under dårlig isolerede områder
100-150W/m3
Fremstilling:
Jernribberør, tryksikker konstruktion - epoxybelagt grå - som garanterer den bedste overførsel af varme fra et keramisk elvarmelegeme.
Overfladetemperaturen er begrænset til den
maximalt tilladte temperatur i grupperne 135°C
(T4) og 200°C (T3). ATEX d II C, IP65, 230V max. 440V. Kan også leveres i rustfri stål.
Standard rule by calculating the heating.
- installed indoor 30-60W/m3
- installed outdoor 60-100W/m3
- installed under extreme weather conditions
100-150W/m3
Contruction:
A steel tube is welded to the junction box. The
steel tube is provided with rolled fins of steel
which guarantees the highest efficiency in heat
transfer. A ceramic heating element has been
mounted in the tube. The effect is that the surface temperature never exceeds the maximum
admissible temperature in the groups T4 and
T3. Can also be delivered in stainless steel.
Højnæsvej 44
DK-2610 Rødovre
Tlf. +45 36 72 22 00
Fax. +45 36 41 07 41
www.elthermo.dk
[email protected]
EL-VARME
EL-heating
Eksplosionssikker ribberørsovn Explosion proof
ribbed pipe radiator
Til vægmontage 250 mm fra gulv og 250 mm
frit over ovn. Må ikke tildækkes. Skal monteres
horisontal.
Der skal være frit areal, 90 cm over ovnen.
Maximal omgivelsestemperatur 40°
For wallmounting 250 mm from floor, and 250
mm free space above radiator. Do not cover.
The heater should be installed horizontally and
must not be covered during heating. A free area
of 90 cm above heater top is needed. Maximum
surrounding temperature: 40°C.
Ribberørsovne EX, T4, standard 230V
Watt
180
420
510
650
880
1120
Volt
24-400
24-400
24-400
110-400
110-400
110-400
A-mm
550
1050
1250
1550
2050
2550
Kg
5,0
10,0
12,0
15,0
20,0
25,0
105
105
Type
80.2
80.4
80.5
80.6
80.8
80.10
70
B = A - 100 mm
Total length = A mm
30